Intesis DK-RC-KNX-1i DK RC interface, 4 binary inputs

DK RC interface, 4 binary inputs DK-RC-KNX-1i

Intesis · Order number DK-RC-KNX-1i · Communication › Interfaces › Daikin Air Conditioning Interfaces

Download .knxprod DKRCKNX1i T25V22 2.2 · 187 KB

Product

ManufacturerIntesis
Product nameDK RC interface, 4 binary inputs
Order numberDK-RC-KNX-1i
HardwareDK RC Interface
MediumTwisted Pair
Bus current (mA)8
Rail mountedNo
RegistrationCertified · 2019-01-21
Languageses-ES, en-US
Catalog entryM-0077_H-DK.2DRC.2DKNX.2D1i-32_HP-0025-22-4C5B_CI-DK.2DRC.2DKNX.2D1i-2
Fingerprint4C5B
SHA-256106808f85d657fad24e2f33e244c5dbc425ccd3ec4bc4850feadc8cbad92be4d
First seen2026-11-25
Markets69 markets

Application program: DKRCKNX1i T25V22 2.2

Application number$0025
Version2.2
Mask versionMV-0025 (2.5)
KNX Data SecureNo
Minimum ETS version3.0d
Parameters360
Group objects153
Group objects (153)
NoNameFunctionSizeDPTFlags
0Control_ On/Off [DPT_1.001]0-Off;1-On1 Bit1.1 switchCWT
1Control_ Mode [DPT_20.105]0-Aut;1-Hea;3-Coo;9-Fan;14-Dry1 Byte20.105 HVAC control modeCWT
1Control_ Mode [DPT_20.105]1-Hea;3-Coo;9-Fan;14-Dry1 Byte20.105 HVAC control modeCWT
2Control_ Mode Cool/Heat [DPT_1.100]0-Cool;1-Heat1 Bit1.100 cooling/heatingCWT
3Control_ Mode Cool & On [DPT_5.001]0%-Off;0.1%-100%-On+Cool1 Byte5.1 percentage (0..100%)CWT
4Control_ Mode Heat & On [DPT_5.001]0%-Off;0.1%-100%-On+Heat1 Byte5.1 percentage (0..100%)CWT
5Control_ Mode Auto [DPT_1.002]1-Set AUTO mode1 Bit1.2 booleanCWT
6Control_ Mode Heat [DPT_1.002]1-Set HEAT mode1 Bit1.2 booleanCWT
7Control_ Mode Cool [DPT_1.002]1-Set COOL mode1 Bit1.2 booleanCWT
8Control_ Mode Fan [DPT_1.002]1-Set FAN mode1 Bit1.2 booleanCWT
9Control_ Mode Dry [DPT_1.002]1-Set DRY mode1 Bit1.2 booleanCWT
10Control_ Mode -/+ [DPT_1.007]0-Decrease;1-Increase1 Bit1.7 stepCW
10Control_ Mode +/- [DPT_1.008]0-Up;1-Down1 Bit1.8 up/downCW
11Control_ Fan Speed / 3 Speeds [DPT_5.001]Thresholds: 50% and 83%1 Byte5.1 percentage (0..100%)CWT
11Control_ Fan Speed / 3 Speeds [DPT_5.010]Speed values: 1,2,31 Byte5.10 counter pulses (0..255)CWT
11Control_ Fan Speed / 2 Speeds [DPT_5.001]Threshold: 75%1 Byte5.1 percentage (0..100%)CWT
11Control_ Fan Speed / 2 Speeds [DPT_5.010]Speed values: 1,21 Byte5.10 counter pulses (0..255)CWT
12Control_ Fan Speed Auto [DPT_1.002]1-Set Fan Speed Auto1 Bit1.2 booleanCWT
13Control_ Fan Speed 1 [DPT_1.002]1-Set Fan Speed 11 Bit1.2 booleanCWT
14Control_ Fan Speed 2 [DPT_1.002]1-Set Fan Speed 21 Bit1.2 booleanCWT
15Control_ Fan Speed 3 [DPT_1.002]1-Set Fan Speed 31 Bit1.2 booleanCWT
16Control_ Fan Speed -/+ [DPT_1.007]0-Decrease;1-Increase1 Bit1.7 stepCW
16Control_ Fan Speed +/- [DPT_1.008]0-Up;1-Down1 Bit1.8 up/downCW
17Control_ Vanes U-D / 5 Pos [DPT_5.001]Thresholds: 30, 50, 70 and 90%1 Byte5.1 percentage (0..100%)CWT
17Control_ Vanes U-D / 5 Pos [DPT_5.010]Position values: 1,2,3,4,51 Byte5.10 counter pulses (0..255)CWT
18Control_ Vanes U-D Pos 1 [DPT_1.002]1-Set Position 11 Bit1.2 booleanCWT
19Control_ Vanes U-D Pos 2 [DPT_1.002]1-Set Position 21 Bit1.2 booleanCWT
20Control_ Vanes U-D Pos 3 [DPT_1.002]1-Set Position 31 Bit1.2 booleanCWT
21Control_ Vanes U-D Pos 4 [DPT_1.002]1-Set Position 41 Bit1.2 booleanCWT
22Control_ Vanes U-D Pos 5 [DPT_1.002]1-Set Position 51 Bit1.2 booleanCWT
23Control_ Vanes U-D Swing [DPT_1.002]0-Off;1-Swing1 Bit1.2 booleanCWT
24Control_ Vanes U-D +/- [DPT_1.008]0-Up;1-Down1 Bit1.8 up/downCWT
24Control_ Vanes U-D -/+ [DPT_1.007]0-Decrease;1-Increase1 Bit1.7 stepCWT
25Control_ Setpoint Temperature [DPT_9.001]ºC2 Bytes9.1 temperature (°C)CWT
26Control_ Setpoint Temperature -/+ [DPT_1.007]0-Decrease;1-Increase1 Bit1.7 stepCW
26Control_ Setpoint Temperature +/- [DPT_1.008]0-Up;1-Down1 Bit1.8 up/downCW
27Control_ Ambient Temperature [DPT_9.001]ºC2 Bytes9.1 temperature (°C)CWT
28Control_ Switch Off Timeout [DPT_1.010]0-Stop;1-Start1 Bit1.10 start/stopCWT
28Control_ Window Contact Status [DPT_1.009]0-Open;1-Closed1 Bit1.9 open/closeCWT
29Control_ Occupancy [DPT_1.018]0-Not Occupied;1-Occupied1 Bit1.18 occupancyCWT
30Control_ Sleep Timeout [DPT_1.010]0-Stop;1-Start1 Bit1.10 start/stopCWT
31Control_ Lock Remote Control [DPT_1.002]0-Unlock;1-Lock1 Bit1.2 booleanCWT
32Control_ Lock Control Objects [DPT_1.002]0-Unlock;1-Lock1 Bit1.2 booleanCWT
33Control_ Power Mode [DPT_1.010]0-Stop;1-Start1 Bit1.10 start/stopCWT
34Control_ Econo Mode [DPT_1.010]0-Stop;1-Start1 Bit1.10 start/stopCWT
35Control_ Additional Heat [DPT_1.010]0-Stop;1-Start1 Bit1.10 start/stopCWT
36Control_ Additional Cool [DPT_1.010]0-Stop;1-Start1 Bit1.10 start/stopCWT
37Control_ Execute Scene [DPT_17.001]0..4-Exec1-51 Byte17.1 scene numberCWT
37Control_ Save/Exec Scene [DPT_18.001]0..4-Exec1-5;128..132-Save1-51 Byte17.1 scene numberCWT
38Control_ Store Scene 1 [DPT_1.002]1-Store Scene 11 Bit1.2 booleanCW
39Control_ Store Scene 2 [DPT_1.002]1-Store Scene 21 Bit1.2 booleanCW
40Control_ Store Scene 3 [DPT_1.002]1-Store Scene 31 Bit1.2 booleanCW
41Control_ Store Scene 4 [DPT_1.002]1-Store Scene 41 Bit1.2 booleanCW
42Control_ Store Scene 5 [DPT_1.002]1-Store Scene 51 Bit1.2 booleanCW
43Control_ Execute Scene 1 [DPT_1.002]1-Execute Scene 11 Bit1.2 booleanCWT
44Control_ Execute Scene 2 [DPT_1.002]1-Execute Scene 21 Bit1.2 booleanCWT
45Control_ Execute Scene 3 [DPT_1.002]1-Execute Scene 31 Bit1.2 booleanCWT
46Control_ Execute Scene 4 [DPT_1.002]1-Execute Scene 41 Bit1.2 booleanCWT
47Control_ Execute Scene 5 [DPT_1.002]1-Execute Scene 51 Bit1.2 booleanCWT
48Control_ Disable Input 1 [DPT_1.003]0-Disable;1-Enable1 Bit1.3 enableCWT
48Control_ Disable Input 1 [DPT_1.002]0-False;1-True1 Bit1.2 booleanCWT
49Control_ Disable Input 2 [DPT_1.003]0-Disable;1-Enable1 Bit1.3 enableCWT
49Control_ Disable Input 2 [DPT_1.002]0-False;1-True1 Bit1.2 booleanCWT
50Control_ Disable Input 3 [DPT_1.002]0-False;1-True1 Bit1.2 booleanCWT
50Control_ Disable Input 3 [DPT_1.003]0-Disable;1-Enable1 Bit1.3 enableCWT
51Control_ Disable Input 4 [DPT_1.002]0-False;1-True1 Bit1.2 booleanCWT
51Control_ Disable Input 4 [DPT_1.003]0-Disable;1-Enable1 Bit1.3 enableCWT
52Control_ Back to Factory Settings [DPT_1.015]0-Enable;1-Disable1 Bit1.15 resetCWT
53Status_ On/Off [DPT_1.001]0-Off;1-On1 Bit1.1 switchCRT
54Status_ Mode [DPT_20.105]0-Aut;1-Hea;3-Coo;9-Fan;14-Dry1 Byte20.105 HVAC control modeCRT
54Status_ Mode [DPT_20.105]1-Hea;3-Coo;9-Fan;14-Dry1 Byte20.105 HVAC control modeCRT
55Status_ Mode Cool/Heat [DPT_1.100]0-Cool;1-Heat1 Bit1.100 cooling/heatingCRT
56Status_ Mode Auto [DPT_1.002]1-AUTO mode is active1 Bit1.2 booleanCRT
57Status_ Mode Heat [DPT_1.002]1-HEAT mode is active1 Bit1.2 booleanCRT
58Status_ Mode Cool [DPT_1.002]1-COOL mode is active1 Bit1.2 booleanCRT
59Status_ Mode Fan [DPT_1.002]1-FAN mode is active1 Bit1.2 booleanCRT
60Status_ Mode Dry [DPT_1.002]1-DRY mode is active1 Bit1.2 booleanCRT
61Status_ Mode Text [DPT_16.001]ASCII String14 Bytes16.1 Character String (ISO 8859-1)CRT
62Status_ Fan Speed / 3 Speeds [DPT_5.001]33%, 66% and 100%1 Byte5.1 percentage (0..100%)CRT
62Status_ Fan Speed / 3 Speeds [DPT_5.010]Speed Values: 1,2,31 Byte5.10 counter pulses (0..255)CRT
62Status_ Fan Speed / 2 Speeds [DPT_5.001]50% and 100%1 Byte5.1 percentage (0..100%)CRT
62Status_ Fan Speed / 2 Speeds [DPT_5.010]Speed Values: 1,21 Byte5.10 counter pulses (0..255)CRT
63Status_ Fan Speed Auto [DPT_1.002]1-Fan in Speed Auto1 Bit1.2 booleanCRT
64Status_ Fan Speed 1 [DPT_1.002]1-Fan in Speed 11 Bit1.2 booleanCRT
65Status_ Fan Speed 2 [DPT_1.002]1-Fan in Speed 21 Bit1.2 booleanCRT
66Status_ Fan Speed 3 [DPT_1.002]1-Fan in Speed 31 Bit1.2 booleanCRT
67Status_ Fan Speed Text [DPT_16.001]ASCII String14 Bytes16.1 Character String (ISO 8859-1)CRT
68Status_ Vanes U-D / 5 Pos [DPT_5.001]20%, 40%, 60%, 80% and 100%1 Byte5.1 percentage (0..100%)CRT
68Status_ Vanes U-D / 5 Pos [DPT_5.010]Position values: 1,2,3,4,51 Byte5.10 counter pulses (0..255)CRT
69Status_ Vanes U-D Pos 1 [DPT_1.002]1-Vanes in Position 11 Bit1.2 booleanCRT
70Status_ Vanes U-D Pos 2 [DPT_1.002]1-Vanes in Position 21 Bit1.2 booleanCRT
71Status_ Vanes U-D Pos 3 [DPT_1.002]1-Vanes in Position 31 Bit1.2 booleanCRT
72Status_ Vanes U-D Pos 4 [DPT_1.002]1-Vanes in Position 41 Bit1.2 booleanCRT
73Status_ Vanes U-D Pos 5 [DPT_1.002]1-Vanes in Position 51 Bit1.2 booleanCRT
74Status_ Vanes U-D Swing [DPT_1.002]0-Off;1-Swing1 Bit1.2 booleanCRT
75Status_ Vanes U-D Text [DPT_16.001]ASCII String14 Bytes16.1 Character String (ISO 8859-1)CRT
76Status_ AC Setpoint Temperature [DPT_9.001]ºC2 Bytes9.1 temperature (°C)CRT
77Status_ AC Reference Temperature [DPT_9.001]ºC2 Bytes9.1 temperature (°C)CRT
78Status_ Error/Alarm [DPT_1.005]0-No alarm;1-Alarm1 Bit1.5 alarmCRT
79Status_ Error Code [2byte]Error Code2 BytesCRT
80Status_ Error Text [DPT_16.001]Error Text14 Bytes16.1 Character String (ISO 8859-1)CRT
81Status_ Lock Remote Control [DPT_1.002]0-Unlocked;1-Locked1 Bit1.2 booleanCRT
82Status_ Lock Control Objects [DPT_1.002]0-Unlocked;1-Locked1 Bit1.2 booleanCRT
83Status_ Power Mode [DPT_1.001]0-Off;1-On1 Bit1.1 switchCRT
84Status_ Econo Mode [DPT_1.001]0-Off;1-On1 Bit1.1 switchCRT
85Status_ Additional Heat [DPT_1.001]0-Off;1-On1 Bit1.1 switchCRT
86Status_ Additional Cool [DPT_1.001]0-Off;1-On1 Bit1.1 switchCRT
87Status_ Operation Hour Counter [DPT_7.001]Number of operating hours2 Bytes7.1 pulsesCRT
88Status_ Operation Second Counter [DPT_13.100]Number of operating seconds4 Bytes13.1 counter pulses (signed)CRT
89Status_ Current Scene [DPT_17.001]0..4-Scene X+1;63-No Scene1 Byte17.1 scene numberCRT
90Legacy_ Mode [Enumerated]0-Aut;1-Hea;2-Dry;3-Fan;4-Coo1 ByteCRWT
91Legacy_ Fan Speed [Enumerated]0-Speed1..2-Speed3,3-Auto1 ByteCRWT
92Legacy_ Vanes Up-Down [Enumerated]0-Pos1..4-Pos5,5-Swing1 ByteCRWT
93Status_ In1 - Switching [DPT_1.001]0-Off;1-On1 Bit1.1 switchCRT
93Status_ In1 - Dimming - On/Off [DPT_1.001]0-Off;1-On1 Bit1.1 switchCRT
93Status_ In1 - Shut/Blind - Step [DPT_1.007]0-Step Up;1-Step Down1 Bit1.1 switchCRT
94Status_ In1 - Dimming - Step(%) [DPT_3.007]Dimming step4 Bit3.7 dimming controlCRT
94Status_ In1 - Shut/Blind - Move [DPT_1.008]0-Move Up;1-Move Down1 Bit1.8 up/downCRT
94Status_ In1 - Value [DPT_12.001]4-byte unsigned value4 Bytes12.1 counter pulses (unsigned)CRT
94Status_ In1 - Value [DPT_5.010]1-byte unsigned value1 Byte5.10 counter pulses (0..255)CRT
94Status_ In1 - Value [DPT_8.001]2-byte signed value2 Bytes8.1 pulses differenceCRT
94Status_ In1 - Value [DPT_9.001]Temperature (ºC)2 Bytes9.1 temperature (°C)CRT
94Status_ In1 - Value [DPT_7.001]2-byte unsigned value2 Bytes7.1 pulsesCRT
95Status_ In2 - Switching [DPT_1.001]0-Off;1-On1 Bit1.1 switchCRT
95Status_ In2 - Dimming - On/Off [DPT_1.001]0-Off;1-On1 Bit1.1 switchCRT
95Status_ In2 - Shut/Blind - Step [DPT_1.007]0-Step Up;1-Step Down1 Bit1.1 switchCRT
96Status_ In2 - Dimming - Step(%) [DPT_3.007]Dimming step4 Bit3.7 dimming controlCRT
96Status_ In2 - Value [DPT_7.001]2-byte unsigned value2 Bytes7.1 pulsesCRT
96Status_ In2 - Value [DPT_12.001]4-byte unsigned value4 Bytes12.1 counter pulses (unsigned)CRT
96Status_ In2 - Value [DPT_9.001]Temperature (ºC)2 Bytes9.1 temperature (°C)CRT
96Status_ In2 - Value [DPT_8.001]2-byte signed value2 Bytes8.1 pulses differenceCRT
96Status_ In2 - Value [DPT_5.010]1-byte unsigned value1 Byte5.10 counter pulses (0..255)CRT
96Status_ In2 - Shut/Blind - Move [DPT_1.008]0-Move Up;1-Move Down1 Bit1.8 up/downCRT
97Status_ In3 - Switching [DPT_1.001]0-Off;1-On1 Bit1.1 switchCRT
97Status_ In3 - Dimming - On/Off [DPT_1.001]0-Off;1-On1 Bit1.1 switchCRT
97Status_ In3 - Shut/Blind - Step [DPT_1.007]0-Step Up;1-Step Down1 Bit1.1 switchCRT
98Status_ In3 - Dimming - Step(%) [DPT_3.007]Dimming step4 Bit3.7 dimming controlCRT
98Status_ In3 - Value [DPT_12.001]4-byte unsigned value4 Bytes12.1 counter pulses (unsigned)CRT
98Status_ In3 - Value [DPT_9.001]Temperature (ºC)2 Bytes9.1 temperature (°C)CRT
98Status_ In3 - Value [DPT_8.001]2-byte signed value2 Bytes8.1 pulses differenceCRT
98Status_ In3 - Value [DPT_7.001]2-byte unsigned value2 Bytes7.1 pulsesCRT
98Status_ In3 - Value [DPT_5.010]1-byte unsigned value1 Byte5.10 counter pulses (0..255)CRT
98Status_ In3 - Shut/Blind - Move [DPT_1.008]0-Move Up;1-Move Down1 Bit1.8 up/downCRT
99Status_ In4 - Switching [DPT_1.001]0-Off;1-On1 Bit1.1 switchCRT
99Status_ In4 - Dimming - On/Off [DPT_1.001]0-Off;1-On1 Bit1.1 switchCRT
99Status_ In4 - Shut/Blind - Step [DPT_1.007]0-Step Up;1-Step Down1 Bit1.1 switchCRT
100Status_ In4 - Dimming - Step(%) [DPT_3.007]Dimming step4 Bit3.7 dimming controlCRT
100Status_ In4 - Value [DPT_12.001]4-byte unsigned value4 Bytes12.1 counter pulses (unsigned)CRT
100Status_ In4 - Value [DPT_9.001]Temperature (ºC)2 Bytes9.1 temperature (°C)CRT
100Status_ In4 - Value [DPT_8.001]2-byte signed value2 Bytes8.1 pulses differenceCRT
100Status_ In4 - Value [DPT_7.001]2-byte unsigned value2 Bytes7.1 pulsesCRT
100Status_ In4 - Value [DPT_5.010]1-byte unsigned value1 Byte5.10 counter pulses (0..255)CRT
100Status_ In4 - Shut/Blind - Move [DPT_1.008]0-Move Up;1-Move Down1 Bit1.8 up/downCRT
Parameters (233)
ParameterTypeDefault
Download latest database entry for this product and its User Manual from:texthttp://www.intesisbox.com
DK-RC-KNX-1 is master in P1/P2 bus (If set to "yes", BRC must be SLAVE)listNo
> If VRV system, indoor unit is slave of Operating ModelistNo
Send READs for Control_ objects on bus recovery (T & U flags must be active)listNo
> Delay before sending READs (sec)unsignedInt 0…3010
Scene to load on bus recovery / startup (needs to define vals for that scene)list(none)
Disallow control from remote controllerlistNo
> Enable "Lock Remote" objectslistNo
Enable func "Lock Control Obj"listNo
Enable func "Operating Hours Counter"listNo
Enable use of objects for Filter (for Control and Status)listNo
Enable "Error Code" objectlistNo
Enable "Error Text" objectlistYes
Show special objectslistNo
Indoor unit has AUTO mode (see docum. for your indoor unit)listYes
Indoor unit has HEAT mode (see docum. for your indoor unit)listYes
Indoor unit has FAN mode (see docum. for your indoor unit)listYes
Indoor unit has DRY mode (see docum. for your indoor unit)listYes
When mode is AUTO Status_ objs report actual operating status (HEAT/COOL/..)listNo
Enable "Mode Cool/Heat" objects (for Control and Status)listNo
Enable PID-Compat. Scaling Mode objects (for Control)listNo
Enable use of +/- object for ModelistNo
> DPT type for +/- Mode Objectlist0-Decrease / 1-Increase [DPT_1.007]
Enable use of bit-type Mode objects (for Control)listNo
Enable use of bit-type Mode objects (for Status)listNo
Enable use of Text object for ModelistNo
ASCII strings shown in comm object "Status_ Mode Text"text<< 14-byte string values >>
> String when mode is AUTOtextAUTO
> String when mode is HEATtextHEAT
> String when mode is COOLtextCOOL
> String when mode is FANtextFAN
> String when mode is DRYtextDRY
Enable use of Legacy_ object for Mode (compatible with old vers of XXACKNX1)listNo
Enable use of "POWERFUL" mode (AC feature)listNo
Enable use of "QUIET" mode (AC feature)listNo
Enable use of POWER modelistNo
> Action time for this mode (minutes)unsignedInt 1…18030
> Setpoint delta increase (HEAT) or decrease (COOL) (ºC)list2.0 ºC
> Fan Speed for this modelistFAN SPEED 3 (if available)
Enable use of ECONOMY modelistNo
> Setpoint delta decrease (HEAT) or increase (COOL) (ºC)list2.0 ºC
> Fan Speed for this modelistFAN SPEED 1
Enable use of ADDITIONAL HEATING modelistNo
> Setpoint temp for this mode (ºC)list30.0 ºC
Enable use of ADDITIONAL COOLING modelistNo
> Setpoint temp for this mode (ºC)list20.0 ºC
Available fanspeeds in Indoor Unit (see docum. for your indoor unit)list2
Indoor unit has AUTO fan speed (see docum. for your indoor unit)listNo
DPT object type for fanspeedlistScaling [DPT_5.001]
Enable use of +/- object for Fan SpeedlistNo
> DPT type for +/- Fan Speed objectlist0-Decrease / 1-Increase [DPT_1.007]
> Does +/- sequence include fan speed AUTO?listNo
> Rollover Speed at upper/lower limit (when controlling with +/- obj)listYes
Enable "Fan Speed Man/Auto" objects (for Control and Status)listYes
Enable use of bit-type Fan Speed objects (for Control)listNo
Enable use of bit-type Fan Speed objects (for Status)listNo
Enable use of Text object for Fan SpeedlistNo
ASCII strings shown in comm object "Status_ Fan Speed Text"text<< 14-byte string values >>
> String when fan speed is AUTOtextAUTO
> String when fan speed is 1textSPEED 1
> String when fan speed is 2textSPEED 2
> String when fan speed is 3textSPEED 3
> String when fan speed is 4textSPEED 4
> String when fan speed is 5textSPEED 5
Enable use of Legacy_ obj for Fan Speed (compatible with old ver of XXACKNX1)listNo
Indoor unit has U-D Vanes (see docum. for your indoor unit)listNo
Available positions in Indoor Unit (see docum. for your indoor unit)unsignedInt 4…44
Available AUTOs in Indoor Unit (see docum. for your indoor unit)list0
Indoor unit has SWING Vanes U-D (see docum. for your indoor unit)listYes
DPT object type for Vanes Up-DownlistScaling [DPT_5.001]
Enable use of +/- object for Vanes U-DlistNo
> DPT type for +/- Vanes U-D objectlist0-Decrease / 1-Increase [DPT_1.007]
> Does +/- sequence include AUTO vanes Up-Down?listNo
> Does +/- sequence include SWING vanes Up-Down?listNo
> Rollover Vanes at upper/lower limit (when controlling with +/- obj)listYes
Enable "Vanes U-D Man/Auto" objects (for Control and Status)listNo
Enable use of bit-type Vanes U-D objects (for Control)listNo
Enable use of bit-type Vanes U-D objects (for Status)listNo
Enable "Vanes U-D Swing" objects (for Control and Status)listNo
Enable use of Text object for Vanes U-DlistNo
ASCII strings shown in comm object "Status_ Vanes U-D Text"text<< 14-byte string values >>
> String when vanes U-D in AUTOtextU-D AUTO
> String when vanes U-D in POS 1textU-D POS 1
> String when vanes U-D in POS 2textU-D POS 2
> String when vanes U-D in POS 3textU-D POS 3
> String when vanes U-D in POS 4textU-D POS 4
> String when vanes U-D in POS 5textU-D POS 5
> String when vanes U-D in SWINGtextU-D SWING
Enable use of Legacy_ object for Vanes (compatible with old vers of XXACKNX1)listNo
Indoor unit has L-R Vanes (see docum. for your indoor unit)listNo
Available positions in Indoor Unit (see docum. for your indoor unit)unsignedInt 3…55
Indoor unit has AUTO Vanes L-R (see docum. for your indoor unit)listNo
Indoor unit has SWING Vanes L-R (see docum. for your indoor unit)listNo
DPT object type for Vanes Left-RightlistScaling [DPT_5.001]
Enable use of +/- object for Vanes L-RlistNo
> DPT type for +/- Vanes L-R objectlist0-Decrease / 1-Increase [DPT_1.007]
> Does +/- sequence include vanes Left-Right AUTO?listNo
Enable use of bit-type Vanes L-R objects (for Control)listNo
Enable use of bit-type Vanes L-R objects (for Status)listNo
Enable use of Text object for Vanes L-RlistNo
ASCII strings shown in comm object "Status_ Vanes L-R Text"text<< 14-byte string values >>
> String when vanes L-R in AUTOtextL-R AUTO
> String when vanes L-R in POS 1textL-R POS 1
> String when vanes L-R in POS 2textL-R POS 2
> String when vanes L-R in POS 3textL-R POS 3
> String when vanes L-R in POS 4textL-R POS 4
> String when vanes L-R in POS 5textL-R POS 5
AC unit has Humidifier (see docum. for your indoor unit)listNo
Available intensities in Indoor Unit (see docum. for your indoor unit)listYes
DPT object type for HumidifyinglistScaling [DPT_5.001]
Enable use of +/- object for HumidifyinglistNo
> DPT type for +/- Humidifying objectlist0-Decrease / 1-Increase [DPT_1.007]
> Rollover Humi. at upper/lower limit (when controlling with +/- obj)listNo
Enable use of bit-type Humidif. objects (for Control)listNo
Enable use of bit-type Humidif. objects (for Status)listNo
Enable use of Text obj for HumidifyinglistNo
ASCII strings shown in comm object "Status_ Humidifying Text"text<< 14-byte string values >>
> String when Humidifying is OFFtextHUMI OFF
> String when Humidifying is LOWtextHUMI LOW
> String when Humidifying is MIDtextHUMI MID
> String when Humidifying is HIGHtextHUMI HIGH
> String when Humidifying is CONT.textHUMI CONT
Enable use of Legacy_ object for Humi. (compatible with old vers of XXACKNX1)listNo
Status_ AC Return Temp shows temperature from sensor in...listIndoor Unit
Periodic sending of "Status_ AC Setp" (in seconds;0=No periodic sending)unsignedInt 0…2550
Transmission of "Status_ AC Refer. Temp"listOnly on change
> "Status_ AC Refer. Temp" periodic sending time (in sec)unsignedInt 1…255180
Enable use of +/- obj for Setpoint TemplistNo
> DPT type for +/- Setp Temp objectlist0-Decrease / 1-Increase [DPT_1.007]
> [+/-] step sizelist1.0 ºC
Enable limits on Control_ Setpoint objlistNo
> Lower limit (ºC)list18.0 ºC
> Upper limit (ºC)list30.0 ºC
Ambient temp. ref. is provided from KNX (carefully read User Guide if enabled)listNo
Enable use of sceneslistNo
Scenes can be stored from KNX buslistNo
> Enable use of bit objects for storing scenes (from bus)listNo
Enable use of bit objects for scene executionlistNo
Scene 1 presetlistNo
> Scene 1 / Value for On-Offlist(unchanged)
> Scene 1 / Value for Modelist(unchanged)
> Scene 1 / Value for Fan Speedlist(unchanged)
> Scene 1 / Value for Vanes U-D (if available)list(unchanged)
> Scene 1 / Value for Vanes L-R (if available)list(unchanged)
> Scene 1 / Value for Setpoint Templist(unchanged)
> Scene 1 / Value for Remote Locklist(unchanged)
> Scene 1 / Value for Humidifying (if available)list(unchanged)
Scene 2 presetlistNo
> Scene 2 / Value for On-Offlist(unchanged)
> Scene 2 / Value for Modelist(unchanged)
> Scene 2 / Value for Fan Speedlist(unchanged)
> Scene 2 / Value for Vanes U-D (if available)list(unchanged)
> Scene 2 / Value for Vanes L-R (if available)list(unchanged)
> Scene 2 / Value for Setpoint Templist(unchanged)
> Scene 2 / Value for Remote Locklist(unchanged)
> Scene 2 / Value for Humidifying (if available)list(unchanged)
Scene 3 presetlistNo
> Scene 3 / Value for On-Offlist(unchanged)
> Scene 3 / Value for Modelist(unchanged)
> Scene 3 / Value for Fan Speedlist(unchanged)
> Scene 3 / Value for Vanes U-D (if available)list(unchanged)
> Scene 3 / Value for Vanes L-R (if available)list(unchanged)
> Scene 3 / Value for Setpoint Templist(unchanged)
> Scene 3 / Value for Remote Locklist(unchanged)
> Scene 3 / Value for Humidifying (if available)list(unchanged)
Scene 4 presetlistNo
> Scene 4 / Value for On-Offlist(unchanged)
> Scene 4 / Value for Modelist(unchanged)
> Scene 4 / Value for Fan Speedlist(unchanged)
> Scene 4 / Value for Vanes U-D (if available)list(unchanged)
> Scene 4 / Value for Vanes L-R (if available)list(unchanged)
> Scene 4 / Value for Setpoint Templist(unchanged)
> Scene 4 / Value for Remote Locklist(unchanged)
> Scene 4 / Value for Humidifying (if available)list(unchanged)
Scene 5 presetlistNo
> Scene 5 / Value for On-Offlist(unchanged)
> Scene 5 / Value for Modelist(unchanged)
> Scene 5 / Value for Fan Speedlist(unchanged)
> Scene 5 / Value for Vanes U-D (if available)list(unchanged)
> Scene 5 / Value for Vanes L-R (if available)list(unchanged)
> Scene 5 / Value for Setpoint Templist(unchanged)
> Scene 5 / Value for Remote Locklist(unchanged)
> Scene 5 / Value for Humidifying (if available)list(unchanged)
Enable use of Open Window / Switch off timeout functionlistNo
> AC switch-off timeout (min)unsignedInt 0…3010
> DPT for Window / Switch-off timeoutlist0-Stop / 1-Start Timeout [DPT_1.010]
> Disallow On/Off operation while window is OpenlistNo
> Disallow On/Off operation while timeout is elapsedlistNo
> Reload last On/Off val once timeout is stoppedlistNo
> Reload last On/Off val once window is ClosedlistNo
Enable use of Occupancy functionlistNo
> Timeout to apply action (minutes)unsignedInt 0…18020
> Action after timeout elapsedlistSwitch-Off AC
> Temp delta decrease (HEAT) or increase (COOL) (ºC)list2.0 ºC
> Enable secondary timeoutlistNo
> Timeout to apply action (min)unsignedInt 1…18020
> Action after timeout elapsedlistSwitch-Off AC
> Temp delta dec (HEAT) or inc (COOL) (ºC)list3.0 ºC
> Disallow On/Off operation while not OccupiedlistNo
> Reload last On/Off value when OccupiedlistNo
Enable use of Sleep functionlistNo
> Sleep function switch-off timeout (minutes)unsignedInt 0…18060
Enable use of Input 1listNo
> Contact typelistNO: Normally Open
> Debounce timelist50 ms
> Disabling functionlistNo
> Reset Input when enablinglistNo
> FunctionlistSwitching
> Send telegram after bus recoverylistNo action
> Sending delay after bus recovery (seconds)unsignedInt 0…25510
> Value on raising edge (contact activated)listNo action
> Scene when contact is activated (needs to be defined)listScene 1
> Mode for short (long) operationlistToggle: On/Off (increase/decrease)
> OperationlistToggle (Up/Down)
> DPT to be sentlistDPT 5.010 (1byte)
> Value on falling edge (contact deactivated)listNo action
> Increasing steplist+ 25 %
> MethodlistStep-Move-Step
> Cyclical sendinglistNever
> Decreasing steplist- 25 %
> Short/long operation limit (x100ms)unsignedInt 1…25510
> Period for cyclical sending (seconds)unsignedInt 1…6553510
> Vanes adjustment time (x100ms)unsignedInt 1…25510
> Value on raising edge (when contact activated)unsignedInt 0…2550
> Value on raising edge (when contact activated)unsignedInt 0…655350
> Value on raising edge (when contact activated)signedInt -32768…327670
> Value on rais. edge (x0.1ºC) (when contact activated)signedInt -2730…3276250
> Value on raising edge (when contact activated)unsignedInt 0…42949672950
> Cycl. send. period in long oper. (x100ms)(0-No cyclical send.)unsignedInt 0…2550
Enable use of Input 2listNo
Enable use of Input 3listNo
Enable use of Input 4listNo
Hide items?!listYes

Version history

ApplicationApp noFingerprintFirst seenSizeFile
DKRCKNX1i T25V22 2.2 latest$00254C5B2026-11-25187 KBDownload

About this file

This is the official ETS product database for the Intesis DK RC interface, 4 binary inputs (DK-RC-KNX-1i), published by the manufacturer in the KNX online catalog. To use it, open ETS, go to Catalogs → Import and choose the downloaded .knxprod file. The device then appears in your catalog and can be added to a project. Older versions are kept so existing projects can be matched to the application program they were commissioned with.