| 0 | Control_ On/Off [DPT_1.001] | 0-Off;1-On | 1 Bit | 1.1 switch | CWTU |
| 1 | Control_ Mode [DPT_20.105] | 0-Aut;1-Hea;3-Coo;9-Fan;14-Dry | 1 Byte | 20.105 HVAC control mode | CWTU |
| 2 | Control_ Mode Cool/Heat [DPT_1.100] | 0-Cool;1-Heat | 1 Bit | 1.100 heating/cooling | CWTU |
| 3 | Control_ Mode Cool & On [DPT_5.001] | 0%-Off;0.1%-100%-On+Cool | 1 Byte | 5.1 percentage (0..100%) | CWTU |
| 4 | Control_ Mode Heat & On [DPT_5.001] | 0%-Off;0.1%-100%-On+Heat | 1 Byte | 5.1 percentage (0..100%) | CWTU |
| 5 | Control_ Mode Auto [DPT_1.002] | 1-Set AUTO mode | 1 Bit | 1.2 boolean | CWTU |
| 6 | Control_ Mode Heat [DPT_1.002] | 1-Set HEAT mode | 1 Bit | 1.2 boolean | CWTU |
| 7 | Control_ Mode Cool [DPT_1.002] | 1-Set COOL mode | 1 Bit | 1.2 boolean | CWTU |
| 8 | Control_ Mode Fan [DPT_1.002] | 1-Set FAN mode | 1 Bit | 1.2 boolean | CWTU |
| 9 | Control_ Mode Dry [DPT_1.002] | 1-Set DRY mode | 1 Bit | 1.2 boolean | CWTU |
| 10 | Control_ Mode -/+ [DPT_1.007] | 0-Decrease;1-Increase | 1 Bit | 1.7 step | CW |
| 11 | Control_ Mode +/- [DPT_1.008] | 0-Up;1-Down | 1 Bit | 1.8 up/down | CW |
| 12 | Control_ Fan Speed / N Speeds [DPT_5.001] | Thresholds: 100*(n+0'5)/N % | 1 Byte | 5.1 percentage (0..100%) | CWTU |
| 13 | Control_ Fan Speed / N Speeds [DPT_5.010] | Speed values: 1...N | 1 Byte | 5.10 counter pulses (0..255) | CWTU |
| 14 | Control_ Fan Speed Man/Auto [DPT_1.002] | 0-Fanspeed 1;1-Auto | 1 Bit | 1.2 boolean | CWTU |
| 15 | Control_ Fan Speed 1 [DPT_1.002] | 1-Set Fanspeed 1 | 1 Bit | 1.2 boolean | CWTU |
| 16 | Control_ Fan Speed 2 [DPT_1.002] | 1-Set Fanspeed 2 | 1 Bit | 1.2 boolean | CWTU |
| 17 | Control_ Fan Speed 3 [DPT_1.002] | 1-Set Fanspeed 3 | 1 Bit | 1.2 boolean | CWTU |
| 18 | Control_ Fan Speed 4 [DPT_1.002] | 1-Set Fanspeed 4 | 1 Bit | 1.2 boolean | CWTU |
| 19 | Control_ Fan Speed 5 [DPT_1.002] | 1-Set Fanspeed 5 | 1 Bit | 1.2 boolean | CWTU |
| 20 | Control_ Fan Speed -/+ [DPT_1.007] | 0-Decrease;1-Increase | 1 Bit | 1.7 step | CW |
| 21 | Control_ Fan Speed +/- [DPT_1.008] | 0-Up;1-Down | 1 Bit | 1.8 up/down | CW |
| 22 | Control_ Louver / 5 Pos [DPT_5.001] | Thresholds: 30, 50, 70 and 90% | 1 Byte | 5.1 percentage (0..100%) | CWTU |
| 23 | Control_ Louver / 5 Pos [DPT_5.010] | Position values: 1,2,3,4,5 | 1 Byte | 5.10 counter pulses (0..255) | CWTU |
| 24 | Control_ Louver Stop [DPT_1.002] | 1-Stop | 1 Bit | 1.2 boolean | CWTU |
| 25 | Control_ Louver Pos 1 [DPT_1.002] | 1-Set Position 1 | 1 Bit | 1.2 boolean | CWTU |
| 26 | Control_ Louver Pos 2 [DPT_1.002] | 1-Set Position 2 | 1 Bit | 1.2 boolean | CWTU |
| 27 | Control_ Louver Pos 3 [DPT_1.002] | 1-Set Position 3 | 1 Bit | 1.2 boolean | CWTU |
| 28 | Control_ Louver Pos 4 [DPT_1.002] | 1-Set Position 4 | 1 Bit | 1.2 boolean | CWTU |
| 29 | Control_ Louver Pos 5 [DPT_1.002] | 1-Set Position 5 | 1 Bit | 1.2 boolean | CWTU |
| 30 | Control_ Louver Swing [DPT_1.002] | 1-Swing | 1 Bit | 1.2 boolean | CWTU |
| 31 | Control_ Louver -/+ [DPT_1.007] | 0-Decrease;1-Increase | 1 Bit | 1.7 step | CW |
| 32 | Control_ Louver +/- [DPT_1.008] | 0-Up;1-Down | 1 Bit | 1.8 up/down | CW |
| 33 | Control_ Louver 4-way-1 / 5 Pos [DPT_5.001] | Thresholds: 30, 50, 70 and 90% | 1 Byte | 5.1 percentage (0..100%) | CWTU |
| 34 | Control_ Louver 4-way-1 / 5 Pos [DPT_5.010] | Position values: 1,2,3,4,5 | 1 Byte | 5.10 counter pulses (0..255) | CWTU |
| 35 | Control_ Louver 4-way-1 Stop [DPT_1.002] | 1-Stop | 1 Bit | 1.2 boolean | CWTU |
| 36 | Control_ Louver 4-way-1 Swing [DPT_1.002] | 1-Swing | 1 Bit | 1.2 boolean | CWTU |
| 37 | Control_ Louver 4-way-1 -/+ [DPT_1.007] | 0-Decrease;1-Increase | 1 Bit | 1.7 step | CW |
| 38 | Control_ Louver 4-way-1 +/- [DPT_1.008] | 0-Up;1-Down | 1 Bit | 1.8 up/down | CW |
| 39 | Control_ Louver 4-way-2 / 5 Pos [DPT_5.001] | Thresholds: 30, 50, 70 and 90% | 1 Byte | 5.1 percentage (0..100%) | CWTU |
| 40 | Control_ Louver 4-way-2 / 5 Pos [DPT_5.010] | Position values: 1,2,3,4,5 | 1 Byte | 5.10 counter pulses (0..255) | CWTU |
| 41 | Control_ Louver 4-way-2 Stop [DPT_1.002] | 1-Stop | 1 Bit | 1.2 boolean | CWTU |
| 42 | Control_ Louver 4-way-2 Swing [DPT_1.002] | 1-Swing | 1 Bit | 1.2 boolean | CWTU |
| 43 | Control_ Louver 4-way-2 -/+ [DPT_1.007] | 0-Decrease;1-Increase | 1 Bit | 1.7 step | CW |
| 44 | Control_ Louver 4-way-2 +/- [DPT_1.008] | 0-Up;1-Down | 1 Bit | 1.8 up/down | CW |
| 45 | Control_ Louver 4-way-3 / 5 Pos [DPT_5.001] | Thresholds: 30, 50, 70 and 90% | 1 Byte | 5.1 percentage (0..100%) | CWTU |
| 46 | Control_ Louver 4-way-3 / 5 Pos [DPT_5.010] | Position values: 1,2,3,4,5 | 1 Byte | 5.10 counter pulses (0..255) | CWTU |
| 47 | Control_ Louver 4-way-3 Stop [DPT_1.002] | 1-Stop | 1 Bit | 1.2 boolean | CWTU |
| 48 | Control_ Louver 4-way-3 Swing [DPT_1.002] | 1-Swing | 1 Bit | 1.2 boolean | CWTU |
| 49 | Control_ Louver 4-way-3 -/+ [DPT_1.007] | 0-Decrease;1-Increase | 1 Bit | 1.7 step | CW |
| 50 | Control_ Louver 4-way-3 +/- [DPT_1.008] | 0-Up;1-Down | 1 Bit | 1.8 up/down | CW |
| 51 | Control_ Louver 4-way-4 / 5 Pos [DPT_5.001] | Thresholds: 30, 50, 70 and 90% | 1 Byte | 5.1 percentage (0..100%) | CWTU |
| 52 | Control_ Louver 4-way-4 / 5 Pos [DPT_5.010] | Position values: 1,2,3,4,5 | 1 Byte | 5.10 counter pulses (0..255) | CWTU |
| 53 | Control_ Louver 4-way-4 Stop [DPT_1.002] | 1-Stop | 1 Bit | 1.2 boolean | CWTU |
| 54 | Control_ Louver 4-way-4 Swing [DPT_1.002] | 1-Swing | 1 Bit | 1.2 boolean | CWTU |
| 55 | Control_ Louver 4-way-4 -/+ [DPT_1.007] | 0-Decrease;1-Increase | 1 Bit | 1.7 step | CW |
| 56 | Control_ Louver 4-way-4 +/- [DPT_1.008] | 0-Up;1-Down | 1 Bit | 1.8 up/down | CW |
| 57 | Control_ Temperature Setting [DPT_9.001] | ºC | 2 Bytes | 9.1 temperature (°C) | CWTU |
| 58 | Control_ Temperature Setting -/+ [DPT_1.007] | 0-Decrease;1-Increase | 1 Bit | 1.7 step | CW |
| 59 | Control_ Temperature Setting +/- [DPT_1.008] | 0-Up;1-Down | 1 Bit | 1.8 up/down | CW |
| 60 | Control_ AutoCooling Temperature Setting [9.001] | ºC | 2 Bytes | 9.1 temperature (°C) | CWTU |
| 61 | Control_ AutoCooling Temperature Setting -/+ [DPT_1.007] | 0-Decrease;1-Increase | 1 Bit | 1.7 step | CW |
| 62 | Control_ AutoCooling Temperature Setting +/- [DPT_1.008] | 0-Up;1-Down | 1 Bit | 1.8 up/down | CW |
| 63 | Control_ AutoHeatingTemperature Setting [9.001] | ºC | 2 Bytes | 9.1 temperature (°C) | CWTU |
| 64 | Control_ AutoHeating Temperature Setting -/+ [DPT_1.007] | 0-Decrease;1-Increase | 1 Bit | 1.7 step | CW |
| 65 | Control_ AutoHeating Temperature Setting +/- [DPT_1.008] | 0-Up;1-Down | 1 Bit | 1.8 up/down | CW |
| 66 | Control_ Permit/Prohibit control of Remote Controller ALL [DPT_1.002] | 0-Permit; 1-Prohibit | 1 Bit | 1.2 boolean | CWTU |
| 67 | Control_ Permit/Prohibit control of Remote Controller On/Off [DPT_1.002] | 0-Permit; 1-Prohibit | 1 Bit | 1.2 boolean | CWTU |
| 68 | Control_ Permit/Prohibit control of Remote Controller Mode [DPT_1.002] | 0-Permit; 1-Prohibit | 1 Bit | 1.2 boolean | CWTU |
| 69 | Control_ Permit/Prohibit control of Remote Controller Temperature Setting [DPT_1.002] | 0-Permit; 1-Prohibit | 1 Bit | 1.2 boolean | CWTU |
| 70 | Control_ Permit/Prohibit control of Remote Controller FAN speed [DPT_1.002] | 0-Permit; 1-Prohibit | 1 Bit | 1.2 boolean | CWTU |
| 71 | Control_ Permit/Prohibit control of Remote Controller Louver [DPT_1.002] | 0-Permit; 1-Prohibit | 1 Bit | 1.2 boolean | CWTU |
| 72 | Control_ Reset Filter [DPT_1.015] | 1-Reset filter | 1 Bit | 1.15 reset | CWTU |
| 73 | Control_ Save Operation Normal Operation [DPT_1.002] | 1-Activate no save | 1 Bit | 1.2 boolean | CWTU |
| 74 | Control_ Save Operation 100-50% Operation [DPT_1.002] | 1-Activate 1..49% save | 1 Bit | 1.2 boolean | CWTU |
| 75 | Control_ Save Operation 50% Operation [DPT_1.002] | 1-Activate 50% save | 1 Bit | 1.2 boolean | CWTU |
| 76 | Control_ Save Operation Thermo Off [DPT_1.002] | 1-Activate 100% save | 1 Bit | 1.2 boolean | CWTU |
| 77 | Control_ Ventilation On/Off [DPT_1.001] | 0-Off; 1-On | 1 Bit | 1.1 switch | CWTU |
| 78 | Control_ Ventilation Mode Heat Exchange [DPT_1.002] | 1-Activate Ventilation Heat Exchange Mode | 1 Bit | 1.2 boolean | CWTU |
| 79 | Control_ Ventilation Mode Bypass [DPT_1.002] | 1-Activate Ventilation Bypass Mode | 1 Bit | 1.2 boolean | CWTU |
| 80 | Control_ Ventilation Mode Automatic [DPT_1.002] | 1-Activate Ventilation Automatic Mode | 1 Bit | 1.2 boolean | CWTU |
| 81 | Control_ Ventilation Mode -/+ [DPT_1.007] | 0-Decrease;1-Increase | 1 Bit | 1.7 step | CW |
| 82 | Control_ Ventilation Mode +/- [DPT_1.008] | 0-Up;1-Down | 1 Bit | 1.8 up/down | CW |
| 83 | Control_ Ventilation Air Volume Stop [DPT_1.002] | 1-Activate Ventilation air volume stop | 1 Bit | 1.2 boolean | CWTU |
| 84 | Control_ Ventilation Air Volume H [DPT_1.002] | 1-Activate Ventilation air volume H | 1 Bit | 1.2 boolean | CWTU |
| 85 | Control_ Ventilation Air Volume L [DPT_1.002] | 1-Activate Ventilation air volume L | 1 Bit | 1.2 boolean | CWTU |
| 86 | Control_ Ventilation Air Volume Imbalance [DPT_1.002] | 1-Activate Ventilation air volume imbalance | 1 Bit | 1.2 boolean | CWTU |
| 87 | Control_ Ventilation Air Volume -/+ [DPT_1.007] | 0-Decrease;1-Increase | 1 Bit | 1.7 step | CW |
| 88 | Control_ Ventilation Air Volume +/- [DPT_1.008] | 0-Up;1-Down | 1 Bit | 1.8 up/down | CW |
| 89 | Control_ Soft Cooling [DPT_1.001] | 0 - Off; 1-On | 1 Bit | 1.1 switch | CWTU |
| 90 | Status_ On/Off [DPT_1.001] | 0-Off;1-On | 1 Bit | 1.1 switch | CRT |
| 91 | Status_ Mode [DPT_20.105] | 0-Aut;1-Hea;3-Coo;9-Fan;14-Dry | 1 Byte | 20.105 HVAC control mode | CRT |
| 92 | Status_ Mode Cool/Heat [DPT_1.100] | 0-Cool;1-Heat | 1 Bit | 1.100 heating/cooling | CRT |
| 93 | Status_ Mode Auto [DPT_1.002] | 1-AUTO mode is active | 1 Bit | 1.2 boolean | CRT |
| 94 | Status_ Mode Heat [DPT_1.002] | 1-HEAT mode is active | 1 Bit | 1.2 boolean | CRT |
| 95 | Status_ Mode Cool [DPT_1.002] | 1-COOL mode is active | 1 Bit | 1.2 boolean | CRT |
| 96 | Status_ Mode Fan [DPT_1.002] | 1-FAN mode is active | 1 Bit | 1.2 boolean | CRT |
| 97 | Status_ Mode Dry [DPT_1.002] | 1-DRY mode is active | 1 Bit | 1.2 boolean | CRT |
| 98 | Status_ Mode AutoHeat [DPT_1.002] | 1-AUTOHEAT mode is active | 1 Bit | 1.2 boolean | CRT |
| 99 | Status_ Mode AutoCool [DPT_1.002] | 1-AUTOCOOL mode is active | 1 Bit | 1.2 boolean | CRT |
| 100 | Status_ Mode Text [DPT_16.001] | ASCII String | 14 Bytes | 16.0 Character String (ASCII) | CRT |
| 101 | Status_ Fan Speed / N Speeds [DPT_5.001] | 100*n/N % | 1 Byte | 5.1 percentage (0..100%) | CRT |
| 102 | Status_ Fan Speed / N Speeds [DPT_5.010] | Speed values: 1...N | 1 Byte | 5.10 counter pulses (0..255) | CRT |
| 103 | Status_ Fan Speed Man/Auto [DPT_1.002] | 0-Manual;1-Auto | 1 Bit | 1.2 boolean | CRT |
| 104 | Status_ Fan Speed Stop [DPT_1.002] | 1-Fan Stop | 1 Bit | 1.2 boolean | CRT |
| 105 | Status_ Fan Speed LL [DPT_1.002] | 1-Fan Extra Low | 1 Bit | 1.2 boolean | CRT |
| 106 | Status_ Fan Speed 1 [DPT_1.002] | 1-Fan in speed 1 | 1 Bit | 1.2 boolean | CRT |
| 107 | Status_ Fan Speed 2 [DPT_1.002] | 1-Fan in speed 2 | 1 Bit | 1.2 boolean | CRT |
| 108 | Status_ Fan Speed 3 [DPT_1.002] | 1-Fan in speed 3 | 1 Bit | 1.2 boolean | CRT |
| 109 | Status_ Fan Speed 4 [DPT_1.002] | 1-Fan in speed 4 | 1 Bit | 1.2 boolean | CRT |
| 110 | Status_ Fan Speed 5 [DPT_1.002] | 1-Fan in speed 5 | 1 Bit | 1.2 boolean | CRT |
| 111 | Status_ Fan Speed Text [DPT_16.001] | ASCII String | 14 Bytes | 16.0 Character String (ASCII) | CRT |
| 112 | Status_ Louver / 5 Pos [DPT_5.001] | 20%, 40%, 60%, 80% and 100% | 1 Byte | 5.1 percentage (0..100%) | CRT |
| 113 | Status_ Louver / 5 Pos [DPT_5.010] | Position values: 1,2,3,4,5 | 1 Byte | 5.10 counter pulses (0..255) | CRT |
| 114 | Status_ Louver Stop [DPT_1.002] | 1-Louver Stop | 1 Bit | 1.2 boolean | CRT |
| 115 | Status_ Louver Pos 1 [DPT_1.002] | 1-Louver in Position 1 | 1 Bit | 1.2 boolean | CRT |
| 116 | Status_ Louver Pos 2 [DPT_1.002] | 1-Louver in Position 2 | 1 Bit | 1.2 boolean | CRT |
| 117 | Status_ Louver Pos 3 [DPT_1.002] | 1-Louver in Position 3 | 1 Bit | 1.2 boolean | CRT |
| 118 | Status_ Louver Pos 4 [DPT_1.002] | 1-Louver in Position 4 | 1 Bit | 1.2 boolean | CRT |
| 119 | Status_ Louver Pos 5 [DPT_1.002] | 1-Louver in Position 5 | 1 Bit | 1.2 boolean | CRT |
| 120 | Status_ Louver Swing [DPT_1.002] | 1-Louver Swing | 1 Bit | 1.2 boolean | CRT |
| 121 | Status_ Louver Text [DPT_16.001] | ASCII String | 14 Bytes | 16.0 Character String (ASCII) | CRT |
| 122 | Status_ Louver 4-way-1 / 5 Pos [DPT_5.001] | 20%, 40%, 60%, 80% and 100% | 1 Byte | 5.1 percentage (0..100%) | CRT |
| 123 | Status_ Louver 4-way-1 / 5 Pos [DPT_5.010] | Position values: 1,2,3,4,5 | 1 Byte | 5.10 counter pulses (0..255) | CRT |
| 124 | Status_ Louver 4-way-1 Stop [DPT_1.002] | 1-Louver Stop | 1 Bit | 1.2 boolean | CRT |
| 125 | Status_ Louver 4-way-1 Swing [DPT_1.002] | 1-Louver Swing | 1 Bit | 1.2 boolean | CRT |
| 126 | Status_ Louver 4-way-1 Text [DPT_16.001] | ASCII String | 14 Bytes | 16.0 Character String (ASCII) | CRT |
| 127 | Status_ Louver 4-way-2 / 5 Pos [DPT_5.001] | 20%, 40%, 60%, 80% and 100% | 1 Byte | 5.1 percentage (0..100%) | CRT |
| 128 | Status_ Louver 4-way-2 / 5 Pos [DPT_5.010] | Position values: 1,2,3,4,5 | 1 Byte | 5.10 counter pulses (0..255) | CRT |
| 129 | Status_ Louver 4-way-2 Stop [DPT_1.002] | 1-Louver Stop | 1 Bit | 1.2 boolean | CRT |
| 130 | Status_ Louver 4-way-2 Swing [DPT_1.002] | 1-Louver Swing | 1 Bit | 1.2 boolean | CRT |
| 131 | Status_ Louver 4-way-2 Text [DPT_16.001] | ASCII String | 14 Bytes | 16.0 Character String (ASCII) | CRT |
| 132 | Status_ Louver 4-way-3 / 5 Pos [DPT_5.001] | 20%, 40%, 60%, 80% and 100% | 1 Byte | 5.1 percentage (0..100%) | CRT |
| 133 | Status_ Louver 4-way-3 / 5 Pos [DPT_5.010] | Position values: 1,2,3,4,5 | 1 Byte | 5.10 counter pulses (0..255) | CRT |
| 134 | Status_ Louver 4-way-3 Stop [DPT_1.002] | 1-Louver Stop | 1 Bit | 1.2 boolean | CRT |
| 135 | Status_ Louver 4-way-3 Swing [DPT_1.002] | 1-Louver Swing | 1 Bit | 1.2 boolean | CRT |
| 136 | Status_ Louver 4-way-3 Text [DPT_16.001] | ASCII String | 14 Bytes | 16.0 Character String (ASCII) | CRT |
| 137 | Status_ Louver 4-way-4 / 5 Pos [DPT_5.001] | 20%, 40%, 60%, 80% and 100% | 1 Byte | 5.1 percentage (0..100%) | CRT |
| 138 | Status_ Louver 4-way-4 / 5 Pos [DPT_5.010] | Position values: 1,2,3,4,5 | 1 Byte | 5.10 counter pulses (0..255) | CRT |
| 139 | Status_ Louver 4-way-4 Stop [DPT_1.002] | 1-Louver Stop | 1 Bit | 1.2 boolean | CRT |
| 140 | Status_ Louver 4-way-4 Swing [DPT_1.002] | 1-Louver Swing | 1 Bit | 1.2 boolean | CRT |
| 141 | Status_ Louver 4-way-4 Text [DPT_16.001] | ASCII String | 14 Bytes | 16.0 Character String (ASCII) | CRT |
| 142 | Status_ Temperature Setting [DPT_9.001] | ºC | 2 Bytes | 9.1 temperature (°C) | CRT |
| 143 | Status_ AutoCool Temperature Setting [DPT_9.001] | ºC | 2 Bytes | 9.1 temperature (°C) | CRT |
| 144 | Status_ AutoHeat Temperature Setting [DPT_9.001] | ºC | 2 Bytes | 9.1 temperature (°C) | CRT |
| 145 | Status_ TA [DPT_9.001] | ºC | 2 Bytes | 9.1 temperature (°C) | CRT |
| 146 | Status_ Control Temperature [DPT_9.001] | ºC | 2 Bytes | 9.1 temperature (°C) | CRT |
| 147 | Status_ Permit/Prohibit control of Remote Controller ALL [DPT_1.002] | 0-Permited; 1-Prohibited | 1 Bit | 1.2 boolean | CRT |
| 148 | Status_ Permit/Prohibit control of Remote Controller On/Off [1.002] | 0-Permited; 1-Prohibited | 1 Bit | 1.2 boolean | CRT |
| 149 | Status_ Permit/Prohibit control of Remote Controller Mode [1.002] | 0-Permited; 1-Prohibited | 1 Bit | 1.2 boolean | CRT |
| 150 | Status_ Permit/Prohibit control of Remote Controller Temperature Setting [1.002] | 0-Permited; 1-Prohibited | 1 Bit | 1.2 boolean | CRT |
| 151 | Status_ Permit/Prohibit control of Remote Controller FAN speed [1.002] | 0-Permited; 1-Prohibited | 1 Bit | 1.2 boolean | CRT |
| 152 | Status_ Permit/Prohibit control of Remote Controller Louver [1.002] | 0-Permited; 1-Prohibited | 1 Bit | 1.2 boolean | CRT |
| 153 | Status_ Filter Sign Status [DPT_1.005] | 0-No alarm;1-Alarm | 1 Bit | 1.5 alarm | CRT |
| 154 | Status_ Alarm [DPT_1.005] | 0-No alarm;1-Alarm | 1 Bit | 1.5 alarm | CRT |
| 155 | Status_ Alarm Code [2byte] | 0-No alarm /Any other see man. | 2 Bytes | DPT.8 | CRT |
| 156 | Status_ Alarm Text [DPT_16.001] | ASCII String | 14 Bytes | 16.0 Character String (ASCII) | CRT |
| 157 | Status_ Alarm Address Interface [DPT_1.001] | 0-Off; 1-On | 1 Bit | 1.1 switch | CRT |
| 158 | Status_ Alarm Address RC [DPT_1.001] | 0-Off; 1-On | 1 Bit | 1.1 switch | CRT |
| 159 | Status_ Alarm Address IU's [DPT_1.001] | 0-Off; 1-On | 1 Bit | 1.1 switch | CRT |
| 160 | Status_ Save Operation Normal Operation [DPT_1.002] | 1-No save is active | 1 Bit | 1.2 boolean | CRT |
| 161 | Status_ Save Operation 100-50% Operation [DPT_1.002] | 1-1..49% save is active | 1 Bit | 1.2 boolean | CRT |
| 162 | Status_ Save Operation 50% Operation [DPT_1.002] | 1-50% save is active | 1 Bit | 1.2 boolean | CRT |
| 163 | Status_ Save Operation Thermo Off [DPT_1.002] | 1-100% save is active | 1 Bit | 1.2 boolean | CRT |
| 164 | Status_ Ventilation On/Off [DPT_1.001] | 0-Off; 1-On | 1 Bit | 1.1 switch | CRT |
| 165 | Status_ Ventilation Mode Heat Exchange [DPT_1.002] | 1-Ventilation Heat Exchange Mode is active | 1 Bit | 1.2 boolean | CRT |
| 166 | Status_ Ventilation Mode Bypass [DPT_1.002] | 1-Activate Ventilation Bypass Mode | 1 Bit | 1.2 boolean | CRT |
| 167 | Status_ Ventilation Mode Automatic [DPT_1.002] | 1-Activate Ventilation Automatic Mode | 1 Bit | 1.2 boolean | CRT |
| 168 | Status_ Ventilation Air Volume Stop [DPT_1.002] | 1-Ventilation air volume stop is active | 1 Bit | 1.2 boolean | CRT |
| 169 | Status_ Ventilation Air Volume H [DPT_1.002] | 1-Ventilation air volume H is active | 1 Bit | 1.2 boolean | CRT |
| 170 | Status_ Ventilation Air Volume L [DPT_1.002] | 1-Ventilation air volume L is active | 1 Bit | 1.2 boolean | CRT |
| 171 | Status_ Ventilation Air Volume Imbalance [DPT_1.002] | 1-Ventilation air volume imbalance is active | 1 Bit | 1.2 boolean | CRT |
| 172 | Status_ TF [DPT_9.001] | ºC | 2 Bytes | 9.1 temperature (°C) | CRT |
| 173 | Status_ Soft Cooling [DPT_1.001] | 0-Off; 1-On | 1 Bit | 1.1 switch | CRT |
| 174 | Status_ Operation Standby [DPT_1.001] | 0-Off; 1-On | 1 Bit | 1.1 switch | CRT |
| 175 | Status_ Heating Standby [DPT_1.001] | 0-Off; 1-On | 1 Bit | 1.1 switch | CRT |
| 176 | Status_ Frost Protection Setting [DPT_1.003] | 0-Disable; 1-Enable | 1 Bit | 1.3 enable | CRT |
| 177 | Status_ Night Low Noise [DPT_1.001] | 0-Off; 1-On | 1 Bit | 1.1 switch | CRT |
| 178 | Status_ Cleaning [DPT_1.001] | 0-Off; 1-On | 1 Bit | 1.1 switch | CRT |
| 179 | Status_ Heat Exchanger Clean Operation [DPT_1.001] | 0-Off; 1-On | 1 Bit | 1.1 switch | CRT |
| 180 | Status_ Frost Protection [DPT_1.001] | 0-Off; 1-On | 1 Bit | 1.1 switch | CRT |
| 181 | Status_ Refrigerant Leakage [DPT_1.001] | 0-Off; 1-On | 1 Bit | 1.1 switch | CRT |
| 182 | Status_ Energy Saving Operation [DPT_1.001] | 0-Off; 1-On | 1 Bit | 1.1 switch | CRT |
| 183 | Status_ Demand Response [DPT_5.001] | 0-100% | 1 Byte | 5.1 percentage (0..100%) | CRT |
| 184 | Status_ Multi Tenant Control [DPT_1.001] | 0-Off; 1-On | 1 Bit | 1.1 switch | CRT |
| 185 | Status_ Night Purge [DPT_1.001] | 0-Off; 1-On | 1 Bit | 1.1 switch | CRT |
| 186 | Status_ 24 Hours Operation [DPT_1.001] | 0-Off; 1-On | 1 Bit | 1.1 switch | CRT |
| 187 | Status_ Ventilation Standby [DPT_1.001] | 0-Off; 1-On | 1 Bit | 1.1 switch | CRT |
| 188 | Status_ Central Controll Address [DPT_5.010] | 0-255 | 1 Byte | 5.10 counter pulses (0..255) | CRT |
| 189 | Status_ Cooling Temp Upper Limit [DPT_9.001] | ºC | 2 Bytes | 9.1 temperature (°C) | CRT |
| 190 | Status_ Cooling Temp Lower Limit [DPT_9.001] | ºC | 2 Bytes | 9.1 temperature (°C) | CRT |
| 191 | Status_ Heating Temp Upper Limit [DPT_9.001] | ºC | 2 Bytes | 9.1 temperature (°C) | CRT |
| 192 | Status_ Heating Temp Lower Limit [DPT_9.001] | ºC | 2 Bytes | 9.1 temperature (°C) | CRT |
| 193 | Status_ Dry Temp Upper Limit [DPT_9.001] | ºC | 2 Bytes | 9.1 temperature (°C) | CRT |
| 194 | Status_ Dry Temp Lower Limit [DPT_9.001] | ºC | 2 Bytes | 9.1 temperature (°C) | CRT |
| 195 | Status_ AutoTemp Upper Limit [DPT_9.001] | ºC | 2 Bytes | 9.1 temperature (°C) | CRT |
| 196 | Status_ AutoTemp Lower Limit [DPT_9.001] | ºC | 2 Bytes | 9.1 temperature (°C) | CRT |
| 197 | Status_ Setting Permit Mode-Fan [DPT_1.003] | 0-Disable; 1-Enable | 1 Bit | 1.3 enable | CRT |
| 198 | Status_ Setting Permit Mode-Cooling [DPT_1.003] | 0-Disable; 1-Enable | 1 Bit | 1.3 enable | CRT |
| 199 | Status_ Setting Permit Mode-Dry [DPT_1.003] | 0-Disable; 1-Enable | 1 Bit | 1.3 enable | CRT |
| 200 | Status_ Setting Permit Mode-Heating [DPT_1.003] | 0-Disable; 1-Enable | 1 Bit | 1.3 enable | CRT |
| 201 | Status_ Setting Permit Mode-Auto [DPT_1.003] | 0-Disable; 1-Enable | 1 Bit | 1.3 enable | CRT |
| 202 | Status_ Setting Fan Auto [DPT_1.003] | 0-Disable; 1-Enable | 1 Bit | 1.3 enable | CRT |
| 203 | Status_ Setting Fan LL [DPT_1.003] | 0-Disable; 1-Enable | 1 Bit | 1.3 enable | CRT |
| 204 | Status_ Setting Fan Speed Range [DPT_5.010] | Num of Fan Speeds | 1 Byte | 5.10 counter pulses (0..255) | CRT |
| 205 | Status_ Setting Louver [DPT_1.003] | 0-Disable; 1-Enable | 1 Bit | 1.3 enable | CRT |
| 206 | Status_ Setting Louver Num Ways [DPT_5.010] | 0-No ways. 1-1 way, 2-2 ways, 4-4 ways | 1 Byte | 5.10 counter pulses (0..255) | CRT |
| 207 | Status_ Setting Ventilation [DPT_1.003] | 0-Disable; 1-Enable | 1 Bit | 1.3 enable | CRT |
| 208 | Status_ Setting Ventilation Heat Exchange Mode [DPT_1.003] | 0-Disable; 1-Enable | 1 Bit | 1.3 enable | CRT |
| 209 | Status_ Setting Ventilation Bypass Mode [DPT_1.003] | 0-Disable; 1-Enable | 1 Bit | 1.3 enable | CRT |
| 210 | Status_ Setting Ventilation Automatic Mode [DPT_1.003] | 0-Disable; 1-Enable | 1 Bit | 1.3 enable | CRT |
| 211 | Status_ Setting Ventilation Fan Speed Low [DPT_1.003] | 0-Disable; 1-Enable | 1 Bit | 1.3 enable | CRT |
| 212 | Status_ Setting Ventilation Fan Speed High [DPT_1.003] | 0-Disable; 1-Enable | 1 Bit | 1.3 enable | CRT |
| 213 | Status_ Setting Ventilation Fan Speed Unbalance [DPT_1.003] | 0-Disable; 1-Enable | 1 Bit | 1.3 enable | CRT |
| 214 | Status_ Setting Dual Setpoint Function [DPT_1.003] | 0-Disable; 1-Enable | 1 Bit | 1.3 enable | CRT |
| 215 | Status_ Setting Soft Cooling Function [DPT_1.003] | 0-Disable; 1-Enable | 1 Bit | 1.3 enable | CRT |
| 216 | Status_ Setting Fan 5 Speed Function [DPT_1.003] | 0-Disable; 1-Enable | 1 Bit | 1.3 enable | CRT |
| 217 | Status_ Setting Save Function [DPT_1.003] | 0-Disable; 1-Enable | 1 Bit | 1.3 enable | CRT |