| 0 | Control_ Unit Run/Stop [DPT_1.010] | 0-Stop;1-Run | 1 Bit | 1.10 start/stop | CW |
| 1 | Control_ Unit Mode [DPT_ 20.105] | 0-Auto;1-Heat;3-Cool | 1 Byte | 20.105 HVAC control mode | CW |
| 2 | Control_ Unit Mode Cool/Heat [DPT_ 1.100] | 0-Cool;1-Heat | 1 Bit | 1.100 heating/cooling | CW |
| 3 | Control_ Unit Mode Auto [DPT_ 1.002] | 1-Set AUTO Mode | 1 Bit | 1.2 boolean | CW |
| 4 | Control_ Unit Mode Heat [DPT_ 1.002] | 1-Set HEAT Mode | 1 Bit | 1.2 boolean | CW |
| 5 | Control_ Unit Mode Cool [DPT_ 1.002] | 1-Set COOL Mode | 1 Bit | 1.2 boolean | CW |
| 6 | Control_ C1 Run/Stop [DPT_1.010] | 0-Stop;1-Run | 1 Bit | 1.10 start/stop | CW |
| 7 | Control_ C1 Heat OTC Mode Off [DPT_1.002] | 1-Set OTC Mode OFF | 1 Bit | 1.2 boolean | CW |
| 8 | Control_ C1 Heat OTC Mode Points [DPT_1.002] | 1-Set OTC Mode POINTS | 1 Bit | 1.2 boolean | CW |
| 9 | Control_ C1 Heat OTC Mode Grad [DPT_1.002] | 1-Set OTC Mode GRAD | 1 Bit | 1.2 boolean | CW |
| 10 | Control_ C1 Heat OTC Mode Fix [DPT_1.002] | 1-Set OTC Mode FIX | 1 Bit | 1.2 boolean | CW |
| 11 | Control_ C1 Cool OTC Mode Off [DPT_1.002] | 1-Set OTC Mode OFF | 1 Bit | 1.2 boolean | CW |
| 12 | Control_ C1 Cool OTC Mode Points [DPT_1.002] | 1-Set OTC Mode POINTS | 1 Bit | 1.2 boolean | CW |
| 13 | Control_ C1 Cool OTC Mode Fix [DPT_1.002] | 1-Set OTC Mode FIX | 1 Bit | 1.2 boolean | CW |
| 14 | Control_ C1 Water Heat Setpoint [DPT_9.001] | ºC | 2 Bytes | 9.1 temperature (°C) | CW |
| 15 | Control_ C1 Water Cool Setpoint [DPT_9.001] | ºC | 2 Bytes | 9.1 temperature (°C) | CW |
| 16 | Control_ C1 ECO Mode [DPT_1.002] | 0-Comfort;1-Eco | 1 Bit | 1.2 boolean | CW |
| 17 | Control_ C1 ECO Heat Offset Temperature [DPT_9.001] | ºC | 2 Bytes | 9.1 temperature (°C) | CW |
| 18 | Control_ C1 ECO Cool Offset Temperature [DPT_9.001] | ºC | 2 Bytes | 9.1 temperature (°C) | CW |
| 19 | Control_ C1 Thermo Setpoint Temp [DPT_9.001] | ºC | 2 Bytes | 9.1 temperature (°C) | CW |
| 20 | Control_ C1 Ambient Temp [DPT_9.001] | ºC | 2 Bytes | 9.1 temperature (°C) | CW |
| 21 | Control_ C2 Run/Stop [DPT_1.010] | 0-Stop;1-Run | 1 Bit | 1.10 start/stop | CW |
| 22 | Control_ C2 Heat OTC Mode Off [DPT_1.002] | 1-Set OTC Mode OFF | 1 Bit | 1.2 boolean | CW |
| 23 | Control_ C2 Heat OTC Mode Points [DPT_1.002] | 1-Set OTC Mode POINTS | 1 Bit | 1.2 boolean | CW |
| 24 | Control_ C2 Heat OTC Mode Grad [DPT_1.002] | 1-Set OTC Mode GRAD | 1 Bit | 1.2 boolean | CW |
| 25 | Control_ C2 Heat OTC Mode Fix [DPT_1.002] | 1-Set OTC Mode FIX | 1 Bit | 1.2 boolean | CW |
| 26 | Control_ C2 Cool OTC Mode Off [DPT_1.002] | 1-Set OTC Mode OFF | 1 Bit | 1.2 boolean | CW |
| 27 | Control_ C2 Cool OTC Mode Points [DPT_1.002] | 1-Set OTC Mode POINTS | 1 Bit | 1.2 boolean | CW |
| 28 | Control_ C2 Cool OTC Mode Fix [DPT_1.002] | 1-Set OTC Mode FIX | 1 Bit | 1.2 boolean | CW |
| 29 | Control_ C2 Water Heat Setpoint [DPT_9.001] | ºC | 2 Bytes | 9.1 temperature (°C) | CW |
| 30 | Control_ C2 Water Cool Setpoint [DPT_9.001] | ºC | 2 Bytes | 9.1 temperature (°C) | CW |
| 31 | Control_ C2 ECO Mode [DPT_1.002] | 0-Comfort;1-Eco | 1 Bit | 1.2 boolean | CW |
| 32 | Control_ C2 ECO Heat Offset Temperature [DPT_9.001] | ºC | 2 Bytes | 9.1 temperature (°C) | CW |
| 33 | Control_ C2 ECO Cool Offset Temperature [DPT_9.001] | ºC | 2 Bytes | 9.1 temperature (°C) | CW |
| 34 | Control_ C2 Thermo Setpoint [DPT_9.001] | ºC | 2 Bytes | 9.1 temperature (°C) | CW |
| 35 | Control_ C2 Ambient Temp [DPT_9.001] | ºC | 2 Bytes | 9.1 temperature (°C) | CW |
| 36 | Control_ DHW Run/Stop [DPT_1.010] | 0-Stop;1-Run | 1 Bit | 1.10 start/stop | CW |
| 37 | Control_ DHW Boost [DPT_1.002] | 1-Request | 1 Bit | 1.2 boolean | CW |
| 38 | Control_ DHW High Demand Mode [DPT_1.002] | 0-Standard;1-High | 1 Bit | 1.2 boolean | CW |
| 39 | Control_ DHW Setpoint [DPT_9.001] | ºC | 2 Bytes | 9.1 temperature (°C) | CW |
| 40 | Control_ SwimPool Run/Stop [DPT_1.010] | 0-Stop;1-Run | 1 Bit | 1.10 start/stop | CW |
| 41 | Control_ SwimPool Setpoint [DPT_9.001] | ºC | 2 Bytes | 9.1 temperature (°C) | CW |
| 42 | Control_ AntiLeg Run/Stop [DPT_1.010] | 0-Stop;1-Run | 1 Bit | 1.10 start/stop | CW |
| 43 | Control_ AntiLeg Setpoint [DPT_9.001] | ºC | 2 Bytes | 9.1 temperature (°C) | CW |
| 44 | Control_ KNX Blocks/Enables Menu [DPT_1.003] | 0-Block;1-Enable | 1 Bit | 1.3 enable | CW |
| 45 | Status_ Unit Run/Stop [DPT_1.010] | 0-Stop;1-Run | 1 Bit | 1.10 start/stop | CRT |
| 46 | Status_ Unit Mode [DPT_20.105] | 1-Heat;3-Cool | 1 Byte | 20.105 HVAC control mode | CRT |
| 47 | Status_ Unit Mode Cool/Heat [DPT_1.100] | 0-Cool;1-Heat | 1 Bit | 1.100 heating/cooling | CRT |
| 48 | Status_ Unit Mode Auto [DPT_1.002] | 1-AUTO Mode is active | 1 Bit | 1.2 boolean | CRT |
| 49 | Status_ Unit Mode Heat [DPT_1.002] | 1-HEAT Mode is active | 1 Bit | 1.2 boolean | CRT |
| 50 | Status_ Unit Mode Cool [DPT_1.002] | 1-COOL Mode is active | 1 Bit | 1.2 boolean | CRT |
| 51 | Status_ C1 Run/Stop [DPT_1.010] | 0-Stop;1-Run | 1 Bit | 1.10 start/stop | CRT |
| 52 | Status_ C1 Heat OTC Mode Off [DPT_1.002] | 1-OTC Mode OFF is set | 1 Bit | 1.2 boolean | CRT |
| 53 | Status_ C1 Heat OTC Mode Points [DPT_1.002] | 1-OTC Mode POINTS is set | 1 Bit | 1.2 boolean | CRT |
| 54 | Status_ C1 Heat OTC Mode Grad [DPT_1.002] | 1-OTC Mode GRAD is set | 1 Bit | 1.2 boolean | CRT |
| 55 | Status_ C1 Heat OTC Mode Fix [DPT_1.002] | 1-OTC Mode FIX is set | 1 Bit | 1.2 boolean | CRT |
| 56 | Status_ C1 Cool OTC Mode Off [DPT_1.002] | 1-OTC Mode OFF is set | 1 Bit | 1.2 boolean | CRT |
| 57 | Status_ C1 Cool OTC Mode Points [DPT_1.002] | 1-OTC Mode POINTS is set | 1 Bit | 1.2 boolean | CRT |
| 58 | Status_ C1 Cool OTC Mode Fix [DPT_1.002] | 1-OTC Mode FIX is set | 1 Bit | 1.2 boolean | CRT |
| 59 | Status_ C1 Water Heat Setpoint [DPT_9.001] | ºC | 2 Bytes | 9.1 temperature (°C) | CRT |
| 60 | Status_ C1 Water Cool Setpoint [DPT_9.001] | ºC | 2 Bytes | 9.1 temperature (°C) | CRT |
| 61 | Status_ C1 ECO Mode [DPT_1.002] | 0-Comfort;1-Eco | 1 Bit | 1.2 boolean | CRT |
| 62 | Status_ C1 ECO Heat Offset Temperature [DPT_9.001] | ºC | 2 Bytes | 9.1 temperature (°C) | CRT |
| 63 | Status_ C1 ECO Cool Offset Temperature [DPT_9.001] | ºC | 2 Bytes | 9.1 temperature (°C) | CRT |
| 64 | Status_ C1 Thermo Setpoint Temp [DPT_9.001] | ºC | 2 Bytes | 9.1 temperature (°C) | CRT |
| 65 | Status_ C1 Ambient Temp [DPT_9.001] | ºC | 2 Bytes | 9.1 temperature (°C) | CRT |
| 66 | Status_ C1 Wireless Setpoint Temp [DPT_9.001] | ºC | 2 Bytes | 9.1 temperature (°C) | CRT |
| 67 | Status_ C1 Wireless Ambient Temp [DPT_9.001] | ºC | 2 Bytes | 9.1 temperature (°C) | CRT |
| 68 | Status_ C2 Run/Stop [DPT_1.010] | 0-Stop;1-Run | 1 Bit | 1.10 start/stop | CRT |
| 69 | Status_ C2 Heat OTC Mode Off [DPT_1.002] | 1-OTC Mode OFF is set | 1 Bit | 1.2 boolean | CRT |
| 70 | Status_ C2 Heat OTC Mode Points [DPT_1.002] | 1-OTC Mode POINTS is set | 1 Bit | 1.2 boolean | CRT |
| 71 | Status_ C2 Heat OTC Mode Grad [DPT_1.002] | 1-OTC Mode GRAD is set | 1 Bit | 1.2 boolean | CRT |
| 72 | Status_ C2 Heat OTC Mode Fix [DPT_1.002] | 1-OTC Mode FIX is set | 1 Bit | 1.2 boolean | CRT |
| 73 | Status_ C2 Cool OTC Mode Off [DPT_1.002] | 1-OTC Mode OFF is set | 1 Bit | 1.2 boolean | CRT |
| 74 | Status_ C2 Cool OTC Mode Points [DPT_1.002] | 1-OTC Mode POINTS is set | 1 Bit | 1.2 boolean | CRT |
| 75 | Status_ C2 Cool OTC Mode Fix [DPT_1.002] | 1-OTC Mode FIX is set | 1 Bit | 1.2 boolean | CRT |
| 76 | Status_ C2 Water Heat Setpoint [DPT_9.001] | ºC | 2 Bytes | 9.1 temperature (°C) | CRT |
| 77 | Status_ C2 Water Cool Setpoint [DPT_9.001] | ºC | 2 Bytes | 9.1 temperature (°C) | CRT |
| 78 | Status_ C2 ECO Mode [DPT_1.002] | 0-Comfort;1-Eco | 1 Bit | 1.2 boolean | CRT |
| 79 | Status_ C2 ECO Heat Offset Temperature [DPT_9.001] | ºC | 2 Bytes | 9.1 temperature (°C) | CRT |
| 80 | Status_ C2 ECO Cool Offset Temperature [DPT_9.001] | ºC | 2 Bytes | 9.1 temperature (°C) | CRT |
| 81 | Status_ C2 Thermo Setpoint [DPT_9.001] | ºC | 2 Bytes | 9.1 temperature (°C) | CRT |
| 82 | Status_ C2 Ambient Temp [DPT_9.001] | ºC | 2 Bytes | 9.1 temperature (°C) | CRT |
| 83 | Status_ C2 Wireless Setpoint Temp [DPT_9.001] | ºC | 2 Bytes | 9.1 temperature (°C) | CRT |
| 84 | Status_ C2 Wireless Ambient Temp [DPT_9.001] | ºC | 2 Bytes | 9.1 temperature (°C) | CRT |
| 85 | Status_ DHW Run/Stop [DPT_1.010] | 0-Stop;1-Run | 1 Bit | 1.10 start/stop | CRT |
| 86 | Status_ DHW Boost [DPT_1.002] | 0-Not requested;1-Requested | 1 Bit | 1.2 boolean | CRT |
| 87 | Status_ DHW High Demand Mode [DPT_1.002] | 0-Standard;1-High | 1 Bit | 1.2 boolean | CRT |
| 88 | Status_ DHW Setpoint [DPT_9.001] | ºC | 2 Bytes | 9.1 temperature (°C) | CRT |
| 89 | Status_ DHW Temperature [DPT_9.001] | ºC | 2 Bytes | 9.1 temperature (°C) | CRT |
| 90 | Status_ SwimPool Run/Stop [DPT_1.010] | 0-Stop;1-Run | 1 Bit | 1.10 start/stop | CRT |
| 91 | Status_ SwimPool Setpoint [DPT_9.001] | ºC | 2 Bytes | 9.1 temperature (°C) | CRT |
| 92 | Status_ SwimPool Temperature [DPT_9.001] | ºC | 2 Bytes | 9.1 temperature (°C) | CRT |
| 93 | Status_ AntiLeg Run/Stop [DPT_1.010] | 0-Stop;1-Run | 1 Bit | 1.10 start/stop | CRT |
| 94 | Status_ AntiLeg Setpoint [DPT_9.001] | ºC | 2 Bytes | 9.1 temperature (°C) | CRT |
| 95 | Status_ KNX Blocks/Enables Menu [DPT_1.003] | 0-Block;1-Enable | 1 Bit | 1.3 enable | CRT |
| 96 | Status_ Error/Alarm [DPT_1.005] | 0-No alarm;1-Alarm | 1 Bit | 1.5 alarm | CRT |
| 97 | Status_ Error Code [2byte] | 0-No error/Any other see man. | 2 Bytes | | CRT |
| 98 | Status_ Operation State Unit On/Off [DPT_1.001] | 0-Off;1-On | 1 Bit | 1.1 switch | CRT |
| 99 | Status_ Operation State Cool Demand [DPT_1.001] | 0-Off;1-On | 1 Bit | 1.1 switch | CRT |
| 100 | Status_ Operation State Cool Thermo [DPT_1.001] | 0-Off;1-On | 1 Bit | 1.1 switch | CRT |
| 101 | Status_ Operation State Heat Demand [DPT_1.001] | 0-Off;1-On | 1 Bit | 1.1 switch | CRT |
| 102 | Status_ Operation State Heat Thermo [DPT_1.001] | 0-Off;1-On | 1 Bit | 1.1 switch | CRT |
| 103 | Status_ Operation State DHW [DPT_1.001] | 0-Off;1-On | 1 Bit | 1.1 switch | CRT |
| 104 | Status_ Operation State SwimPool [DPT_1.001] | 0-Off;1-On | 1 Bit | 1.1 switch | CRT |
| 105 | Status_ Operation State Alarm [DPT_1.005] | 0-No alarm;1-Alarm | 1 Bit | 1.5 alarm | CRT |
| 106 | Status_ Outdoor Ambient Temp [DPT_9.001] | ºC | 2 Bytes | 9.1 temperature (°C) | CRT |
| 107 | Status_ Second Ambient Temp [DPT_9.001] | ºC | 2 Bytes | 9.1 temperature (°C) | CRT |
| 108 | Status_ Water Inlet Temp [DPT_9.001] | ºC | 2 Bytes | 9.1 temperature (°C) | CRT |
| 109 | Status_ Water Outlet Temp [DPT_9.001] | ºC | 2 Bytes | 9.1 temperature (°C) | CRT |
| 110 | Status_ Defrost Operation [DPT_1.001] | 0-Off;1-On | 1 Bit | 1.1 switch | CRT |
| 111 | Status_ Water Pump 1 Operation [DPT_1.001] | 0-Off;1-On | 1 Bit | 1.1 switch | CRT |
| 112 | Status_ Water Pump 2 Operation [DPT_1.001] | 0-Off;1-On | 1 Bit | 1.1 switch | CRT |
| 113 | Status_ Water Pump 3 Operation [DPT_1.001] | 0-Off;1-On | 1 Bit | 1.1 switch | CRT |
| 114 | Status_ Disch. Gas Temp [DPT_9.001] | ºC | 2 Bytes | 9.1 temperature (°C) | CRT |
| 115 | Status_ Suct. Gas Temp [DPT_9.001] | ºC | 2 Bytes | 9.1 temperature (°C) | CRT |
| 116 | Status_ Gas Temp THMg [DPT_9.001] | ºC | 2 Bytes | 9.1 temperature (°C) | CRT |
| 117 | Status_ Liquid Temp THMI [DPT_9.001] | ºC | 2 Bytes | 9.1 temperature (°C) | CRT |
| 118 | Status_ Water Outlet Temp 3 [DPT_9.001] | ºC | 2 Bytes | 9.1 temperature (°C) | CRT |
| 119 | Status_ Outdoor AmbAvg Temp [DPT_9.001] | ºC | 2 Bytes | 9.1 temperature (°C) | CRT |
| 120 | Status_ Inv Oper Freq [DPT_14.033] | Hz | 4 Bytes | 14.33 frequency (Hz) | CRT |
| 121 | Status_ Indoor Exp. Valve Opening [DPT_5.001] | % | 1 Byte | 5.1 percentage (0..100%) | CRT |
| 122 | Status_ Outdoor Exp. Valve Opening [DPT_5.001] | % | 1 Byte | 5.1 percentage (0..100%) | CRT |
| 123 | Status_ Mixing Valve Position [DPT_5.001] | % | 1 Byte | 5.1 percentage (0..100%) | CRT |
| 124 | Status_ Compressor Run Current [DPT_9.021] | mA | 2 Bytes | 9.21 current (mA) | CRT |
| 125 | Status_ Water Flow [DPT_13.002] | m3/h | 4 Bytes | 13.2 flow rate (m³/h) | CRT |
| 126 | Status_ Water Pump Speed [DPT_5.001] | % | 1 Byte | 5.1 percentage (0..100%) | CRT |
| 127 | Status_ Unit Model Yutaki S [DPT_1.002] | 1-Model is Yutaki S | 1 Bit | 1.2 boolean | CRT |
| 128 | Status_ Unit Model Yutaki S Combi [DPT_1.002] | 1-Model is Yutaki S Combi | 1 Bit | 1.2 boolean | CRT |
| 129 | Status_ Unit Model Yutaki S80 [DPT_1.002] | 1-Model is Yutaki S80 | 1 Bit | 1.2 boolean | CRT |
| 130 | Status_ Unit Model Yutaki M [DPT_1.002] | 1-Model is Yutaki M | 1 Bit | 1.2 boolean | CRT |
| 131 | Status_ PCB Software Version [DPT_217.001] | Software version | 2 Bytes | 217.1 DPT version | CRT |
| 132 | Status_ LCD Software Version [DPT_217.001] | Software version | 2 Bytes | 217.1 DPT version | CRT |
| 133 | Status_ Instant Capacity [DPT_13.013] | kWh | 4 Bytes | 13.13 active energy (kWh) | CRT |
| 134 | Status_ Unit Power Consumption [DPT_13.013] | kWh | 4 Bytes | 13.13 active energy (kWh) | CRT |
| 135 | Status_ Disch. Gas Temp R134A [DPT_9.001] | ºC | 2 Bytes | 9.1 temperature (°C) | CRT |
| 136 | Status_ Suct. Gas Temp R134A [DPT_9.001] | ºC | 2 Bytes | 9.1 temperature (°C) | CRT |
| 137 | Status_ Liquid Gas Temp R134A [DPT_9.001] | ºC | 2 Bytes | 9.1 temperature (°C) | CRT |
| 138 | Status_ Evap. Gas Temp R134A [DPT_9.001] | ºC | 2 Bytes | 9.1 temperature (°C) | CRT |
| 139 | Status_ Disch. Pressure R134A [DPT_14.058] | Pa | 4 Bytes | 14.58 pressure (Pa) | CRT |
| 140 | Status_ Suct. Pressure R134A [DPT_14.058] | Pa | 4 Bytes | 14.58 pressure (Pa) | CRT |
| 141 | Status_ Inv Oper Freq R134A [DPT_14.033] | Hz | 4 Bytes | 14.33 frequency (Hz) | CRT |
| 142 | Status_ Indoor Exp. Valve Open R134A [DPT_5.001] | % | 1 Byte | 5.1 percentage (0..100%) | CRT |
| 143 | Status_ Compressor Run Current R134A [DPT_9.021] | mA | 2 Bytes | 9.21 current (mA) | CRT |
| 144 | Status_ Error Code R134A [1byte] | HI error code | 1 Byte | | CRT |