Intesis HS-RC-KNX-1i HS RC interface, 4 binary inputs

HS RC interface, 4 binary inputs HS-RC-KNX-1i

Intesis · Order number HS-RC-KNX-1i · Communication › Interfaces › Hisense Air Conditioning Interfaces

Download .knxprod HSRCKNX1i T2BV20 2.0 · 194 KB

Product

ManufacturerIntesis
Product nameHS RC interface, 4 binary inputs
Order numberHS-RC-KNX-1i
HardwareHS RC Interface
MediumTwisted Pair
Bus current (mA)7
Rail mountedNo
RegistrationCertified · 2019-03-27
Languageses-ES, en-US
Catalog entryM-0077_H-HS.2DRC.2DKNX.2D1i-1_HP-002B-20-6AF1_CI-HS.2DRC.2DKNX.2D1i-1
Fingerprint6AF1
SHA-256ca3d4cff1951838367cc0c4c8d237b75ea280cb8c814be5fe37309796a4dd1e1
First seen2026-11-25
Markets69 markets

Application program: HSRCKNX1i T2BV20 2.0

Application number$002B
Version2.0
Mask versionMV-0025 (2.5)
KNX Data SecureNo
Minimum ETS version5.0
Parameters364
Group objects181
Group objects (181)
NoNameFunctionSizeDPTFlags
0Control_ On/Off [DPT_1.001 - 1bit]0-Off;1-On1 Bit1.1 switchCWT
1Control_ Mode [DPT_20.105 - 1byte]0-Aut;1-Hea;3-Coo;9-Fan;14-Dry1 Byte20.105 HVAC control modeCWT
1Control_ Mode [DPT_20.105 - 1byte]1-Hea;3-Coo;9-Fan;14-Dry1 Byte20.105 HVAC control modeCWT
2Control_ Mode Cool/Heat [DPT_1.100 - 1bit]0-Cool;1-Heat1 Bit1.100 cooling/heatingCWT
3Control_ Mode Cool & On [DPT_5.001 - 1byte]0%-Off;0.1%-100%-On+Cool1 Byte5.1 percentage (0..100%)CWT
4Control_ Mode Heat & On [DPT_5.001 - 1byte]0%-Off;0.1%-100%-On+Heat1 Byte5.1 percentage (0..100%)CWT
5Control_ Mode Auto [DPT_1.002 - 1bit]1-Set AUTO mode1 Bit1.2 booleanCWT
6Control_ Mode Heat [DPT_1.002 - 1bit]1-Set HEAT mode1 Bit1.2 booleanCWT
7Control_ Mode Cool [DPT_1.002 - 1bit]1-Set COOL mode1 Bit1.2 booleanCWT
8Control_ Mode Fan [DPT_1.002 - 1bit]1-Set FAN mode1 Bit1.2 booleanCWT
9Control_ Mode Dry [DPT_1.002 - 1bit]1-Set DRY mode1 Bit1.2 booleanCWT
10Control_ Mode -/+ [DPT_1.007 - 1bit]0-Decrease;1-Increase1 Bit1.7 stepCW
10Control_ Mode +/- [DPT_1.008 - 1bit]0-Up;1-Down1 Bit1.8 up/downCW
11Control_ Fan Speed / 4 Speeds [DPT_5.010 - 1byte] Speed values: 1,2,3,41 Byte5.10 counter pulses (0..255)CWT
11Control_ Fan Speed / 4 Speeds [DPT_5.001 - 1byte] Thresholds: 38%, 63% and 88%1 Byte5.1 percentage (0..100%)CWT
11Control_ Fan Speed / 3 Speeds [DPT_5.010 - 1byte] Speed values: 1,2,31 Byte5.10 counter pulses (0..255)CWT
11Control_ Fan Speed / 3 Speeds [DPT_5.001 - 1byte] Thresholds: 50% and 83%1 Byte5.1 percentage (0..100%)CWT
12Control_ Fan Speed Man/Auto [DPT_1.002 - 1bit]0-Manual;1-Auto1 Bit1.2 booleanCWT
13Control_ Fan Speed 1 [DPT_1.002 - 1bit]1-Set Fan Speed 11 Bit1.2 booleanCWT
14Control_ Fan Speed 2 [DPT_1.002 - 1bit]1-Set Fan Speed 21 Bit1.2 booleanCWT
15Control_ Fan Speed 3 [DPT_1.002 - 1bit]1-Set Fan Speed 31 Bit1.2 booleanCWT
16Control_ Fan Speed 4 [DPT_1.002 - 1bit]1-Set Fan Speed 41 Bit1.2 booleanCWT
17Control_ Fan Speed -/+ [DPT_1.007 - 1bit]0-Decrease;1-Increase1 Bit1.7 stepCW
17Control_ Fan Speed +/- [DPT_1.008 - 1bit]0-Up;1-Down1 Bit1.8 up/downCW
18Control_ Vanes U-D / 7 Pos [DPT_5.001 - 1byte]Thresholds: 21%, 36%, 50%, 65%, 79% and 93%1 Byte5.1 percentage (0..100%)CWT
18Control_ Vanes U-D / 7 Pos [DPT_5.010 - 1byte]Position values: 1,2,3,4,5,6,71 Byte5.10 counter pulses (0..255)CWT
18Control_ Vanes U-D / 5 Pos [DPT_5.010 - 1byte]Position values: 1,2,3,4,51 Byte5.10 counter pulses (0..255)CWT
18Control_ Vanes U-D / 5 Pos [DPT_5.001 - 1byte]Thresholds: 30, 50, 70 and 90%1 Byte5.1 percentage (0..100%)CWT
18Control_ Vanes U-D / 6 Pos [DPT_5.001 - 1byte]Thresholds: 25, 42, 59, 75 and 92%1 Byte5.1 percentage (0..100%)CWT
18Control_ Vanes U-D / 6 Pos [DPT_5.010 - 1byte]Position values: 1,2,3,4,5,61 Byte5.10 counter pulses (0..255)CWT
19Control_ Vanes U-D Pos 1 [DPT_1.002 - 1bit]1-Set Position 11 Bit1.2 booleanCWT
20Control_ Vanes U-D Pos 2 [DPT_1.002 - 1bit]1-Set Position 21 Bit1.2 booleanCWT
21Control_ Vanes U-D Pos 3 [DPT_1.002 - 1bit]1-Set Position 31 Bit1.2 booleanCWT
22Control_ Vanes U-D Pos 4 [DPT_1.002 - 1bit]1-Set Position 41 Bit1.2 booleanCWT
23Control_ Vanes U-D Pos 5 [DPT_1.002 - 1bit]1-Set Position 51 Bit1.2 booleanCWT
24Control_ Vanes U-D Pos 6 [DPT_1.002 - 1bit]1-Set Position 61 Bit1.2 booleanCWT
25Control_ Vanes U-D Pos 7 [DPT_1.002 - 1bit]1-Set Position 71 Bit1.2 booleanCWT
26Control_ Vanes U-D Swing [DPT_1.002 - 1bit]0-Off;1-Swing1 Bit1.2 booleanCWT
27Control_ Vanes U-D -/+ [DPT_1.007 - 1bit]0-Decrease;1-Increase1 Bit1.7 stepCWT
27Control_ Vanes U-D +/- [DPT_1.008 - 1bit]0-Up;1-Down1 Bit1.8 up/downCWT
28Control_ Setpoint Temp [DPT_9.001 - 2byte] ºC2 Bytes9.1 temperature (°C)CWT
29Control_ Setpoint Temp -/+ [DPT_1.007 - 1bit]0-Decrease;1-Increase1 Bit1.7 stepCW
29Control_ Setpoint Temp +/- [DPT_1.008 - 1bit]0-Up;1-Down1 Bit1.8 up/downCW
30Control_ Ambient Temp [DPT_9.001 - 2byte]ºC2 Bytes9.1 temperature (°C)CWT
31Control_ Reset Filter [DPT_1.015 - 1bit]1-Reset filter1 Bit1.15 resetCWT
32Control_ Reset Error [DPT_1.015 - 1bit]1-Reset error1 Bit1.15 resetCWT
33Control_ Window Contact Status [DPT_1.019 - 1bit]0-Closed;1-Open1 Bit1.19 window/doorCWT
33Control_ Window Contact Status [DPT_1.009 - 1bit]0-Open;1-Closed1 Bit1.9 open/closeCWT
34Control_ Occupancy [DPT_1.018 - 1bit]0-Not Occupied;1-Occupied1 Bit1.18 occupancyCWT
35Control_ Sleep Timeout [DPT_1.010 - 1bit]0-Stop;1-Start1 Bit1.10 start/stopCWT
36Control_ Lock Remote Control [DPT_1.002 - 1bit]0-Unlock;1-Lock1 Bit1.2 booleanCWT
37Control_ Lock Control Objects [DPT_1.002 - 1bit]0-Unlock;1-Lock1 Bit1.2 booleanCWT
38Control_ Power Mode [DPT_1.010 - 1bit]0-Stop;1-Start1 Bit1.10 start/stopCWT
39Control_ Econo Mode [DPT_1.010 - 1bit]0-Stop;1-Start1 Bit1.10 start/stopCWT
40Control_ Additional Heat [DPT_1.010 - 1bit]0-Stop;1-Start1 Bit1.10 start/stopCWT
41Control_ Additional Cool [DPT_1.010 - 1bit]0-Stop;1-Start1 Bit1.10 start/stopCWT
42Control_ Execute Scene [DPT_18.001 - 1byte]0..4-Exec1-51 Byte18.1 scene controlCWT
42Control_ Save/Exec Scene [DPT_18.001 - 1byte]0..4-Exec1-5;128..132-Save1-51 Byte18.1 scene controlCWT
43Control_ Store Scene 1 [DPT_1.002 - 1bit]1-Store Scene 11 Bit1.2 booleanCW
44Control_ Store Scene 2 [DPT_1.002 - 1bit]1-Store Scene 21 Bit1.2 booleanCW
45Control_ Store Scene 3 [DPT_1.002 - 1bit]1-Store Scene 31 Bit1.2 booleanCW
46Control_ Store Scene 4 [DPT_1.002 - 1bit]1-Store Scene 41 Bit1.2 booleanCW
47Control_ Store Scene 5 [DPT_1.002 - 1bit]1-Store Scene 51 Bit1.2 booleanCW
48Control_ Execute Scene 1 [DPT_1.002 - 1bit]1-Execute Scene 11 Bit1.2 booleanCWT
49Control_ Execute Scene 2 [DPT_1.002 - 1bit]1-Execute Scene 21 Bit1.2 booleanCWT
50Control_ Execute Scene 3 [DPT_1.002 - 1bit]1-Execute Scene 31 Bit1.2 booleanCWT
51Control_ Execute Scene 4 [DPT_1.002 - 1bit]1-Execute Scene 41 Bit1.2 booleanCWT
52Control_ Execute Scene 5 [DPT_1.002 - 1bit]1-Execute Scene 51 Bit1.2 booleanCWT
53Control_ Disable Input 1 [DPT_1.003 - 1bit]0-Disable;1-Enable1 Bit1.3 enableCWT
53Control_ Disable Input 1 [DPT_1.002 - 1bit]0-False;1-True1 Bit1.2 booleanCWT
54Control_ Disable Input 2 [DPT_1.002 - 1bit]0-False;1-True1 Bit1.2 booleanCWT
54Control_ Disable Input 2 [DPT_1.003 - 1bit]0-Disable;1-Enable1 Bit1.3 enableCWT
55Control_ Disable Input 3 [DPT_1.002 - 1bit]0-False;1-True1 Bit1.2 booleanCWT
55Control_ Disable Input 3 [DPT_1.003 - 1bit]0-Disable;1-Enable1 Bit1.3 enableCWT
56Control_ Disable Input 4 [DPT_1.002 - 1bit]0-False;1-True1 Bit1.2 booleanCWT
56Control_ Disable Input 4 [DPT_1.003 - 1bit]0-Disable;1-Enable1 Bit1.3 enableCWT
57Status_ On/Off [DPT_1.001 - 1bit]0-Off;1-On1 Bit1.1 switchCRT
58Status_ Mode [DPT_20.105 - 1byte]0-Aut;1-Hea;3-Coo;9-Fan;14-Dry1 Byte20.105 HVAC control modeCRT
58Status_ Mode [DPT_20.105 - 1byte]1-Hea;3-Coo;9-Fan;14-Dry1 Byte20.105 HVAC control modeCRT
59Status_ Mode Cool/Heat [DPT_1.100 - 1bit]0-Cool;1-Heat1 Bit1.100 cooling/heatingCRT
60Status_ Mode Auto [DPT_1.002 - 1bit]1-AUTO mode is active1 Bit1.2 booleanCRT
61Status_ Mode Heat [DPT_1.002 - 1bit]1-HEAT mode is active1 Bit1.2 booleanCRT
62Status_ Mode Cool [DPT_1.002 - 1bit]1-COOL mode is active1 Bit1.2 booleanCRT
63Status_ Mode Fan [DPT_1.002 - 1bit]1-FAN mode is active1 Bit1.2 booleanCRT
64Status_ Mode Dry [DPT_1.002 - 1bit]1-DRY mode is active1 Bit1.2 booleanCRT
65Status_ Mode Text [DPT_16.001 - 14byte]ASCII String14 Bytes16.1 Character String (ISO 8859-1)CRT
66Status_ Fan Speed / 4 Speeds [DPT_5.010 - 1byte]Speed Values: 1,2,3,41 Byte5.10 counter pulses (0..255)CRT
66Status_ Fan Speed / 4 Speeds [DPT_5.001 - 1byte] 25%, 50%, 75% and 100%1 Byte5.1 percentage (0..100%)CRT
66Status_ Fan Speed / 3 Speeds [DPT_5.010 - 1byte]Speed Values: 1,2,31 Byte5.10 counter pulses (0..255)CRT
66Status_ Fan Speed / 3 Speeds [DPT_5.001 - 1byte] 33%, 66% and 100%1 Byte5.1 percentage (0..100%)CRT
67Status_ Fan Speed Man/Auto [DPT_1.002 - 1bit]0-Manual;1-Auto1 Bit1.2 booleanCRT
68Status_ Fan Speed 1 [DPT_1.002 - 1bit]1-Fan in Speed 11 Bit1.2 booleanCRT
69Status_ Fan Speed 2 [DPT_1.002 - 1bit]1-Fan in Speed 21 Bit1.2 booleanCRT
70Status_ Fan Speed 3 [DPT_1.002 - 1bit]1-Fan in Speed 31 Bit1.2 booleanCRT
71Status_ Fan Speed 4 [DPT_1.002 - 1bit]1-Fan in Speed 41 Bit1.2 booleanCRT
72Status_ Fan Speed Text [DPT_16.001 - 14byte]ASCII String14 Bytes16.1 Character String (ISO 8859-1)CRT
73Status_ Vanes U-D / 7 Pos [DPT_5.001 - 1byte]14%, 28%, 43%, 57%, 71%, 85% and 100%1 Byte5.1 percentage (0..100%)CRT
73Status_ Vanes U-D / 7 Pos [DPT_5.010 - 1byte]Position values: 1,2,3,4,5,6,71 Byte5.10 counter pulses (0..255)CRT
73Status_ Vanes U-D / 5 Pos [DPT_5.001 - 1byte]20%, 40%, 60%, 80% and 100%1 Byte5.1 percentage (0..100%)CRT
73Status_ Vanes U-D / 5 Pos [DPT_5.010 - 1byte]Position values: 1,2,3,4,51 Byte5.10 counter pulses (0..255)CRT
73Status_ Vanes U-D / 6 Pos [DPT_5.010 - 1byte]Position values: 1,2,3,4,5,61 Byte5.10 counter pulses (0..255)CRT
73Status_ Vanes U-D / 6 Pos [DPT_5.001 - 1byte]16%,33%,50%,67%,83% and 100%1 Byte5.1 percentage (0..100%)CRT
74Status_ Vanes U-D Pos 1 [DPT_1.002 - 1bit]1-Vanes in Position 11 Bit1.2 booleanCRT
75Status_ Vanes U-D Pos 2 [DPT_1.002 - 1bit]1-Vanes in Position 21 Bit1.2 booleanCRT
76Status_ Vanes U-D Pos 3 [DPT_1.002 - 1bit]1-Vanes in Position 31 Bit1.2 booleanCRT
77Status_ Vanes U-D Pos 4 [DPT_1.002 - 1bit]1-Vanes in Position 41 Bit1.2 booleanCRT
78Status_ Vanes U-D Pos 5 [DPT_1.002 - 1bit]1-Vanes in Position 51 Bit1.2 booleanCRT
79Status_ Vanes U-D Pos 6 [DPT_1.002 - 1bit]1-Vanes in Position 61 Bit1.2 booleanCRT
80Status_ Vanes U-D Pos 7 [DPT_1.002 - 1bit]1-Vanes in Position 71 Bit1.2 booleanCRT
81Status_ Vanes U-D Swing [DPT_1.002 - 1bit]0-Off;1-Swing1 Bit1.2 booleanCRT
82Status_ Vanes U-D Text [DPT_16.001 - 14byte]ASCII String14 Bytes16.1 Character String (ISO 8859-1)CRT
83Status_ AC Setpoint Temp [DPT_9.001 - 2byte]ºC2 Bytes9.1 temperature (°C)CRT
84Status_ AC Reference Temp [DPT_9.001 - 2byte]ºC2 Bytes9.1 temperature (°C)CRT
85Status_ Only Centrally Ctrl [DPT 1.002 - 1bit]1-Only centrally controlled1 Bit1.2 booleanCRT
86Status_ Filter Status [DPT_1.005 - 1bit]0-No alarm;1-Alarm1 Bit1.5 alarmCRT
87Status_ Error/Alarm [DPT_1.005 - 1bit]0-No alarm;1-Alarm1 Bit1.5 alarmCRT
88Status_ Error Code [2byte]0-No error /Any other see man.2 BytesDPT.8CRT
89Status_ Error Text Code [DPT_16.001 - 14byte]HS Error; Empty-None14 Bytes16.1 Character String (ISO 8859-1)CRT
90Status_ Lock Remote Control [DPT_1.002 - 1bit]0-Unlocked;1-Locked1 Bit1.2 booleanCRT
91Status_ Lock Control Objects [DPT_1.002 - 1bit]0-Unlocked;1-Locked1 Bit1.2 booleanCRT
92Status_ Power Mode [DPT_1.001 - 1bit]0-Off;1-On1 Bit1.1 switchCRT
93Status_ Econo Mode [DPT_1.001 - 1bit]0-Off;1-On1 Bit1.1 switchCRT
94Status_ Additional Heat [DPT_1.001 - 1bit]0-Off;1-On1 Bit1.1 switchCRT
95Status_ Additional Cool [DPT_1.001 - 1bit]0-Off;1-On1 Bit1.1 switchCRT
96Status_ Operation Hour Counter [DPT_7.001 - 2byte]Number of operating hours2 Bytes7.7 time (h)CRT
97Status_ Operating Sec Counter [DPT_13.100 - 4byte]Number of operating seconds4 Bytes13.100 time lag (s)CRT
98Status_ Current Scene [DPT_17.001 - 1byte]0..4-Scene X+1;63-No Scene1 Byte17.1 scene numberCRT
99Status_ In1 - Switching [DPT_1.001 - 1bit]0-Off;1-On1 Bit1.1 switchCRT
99Status_ In1 - Dimming - On/Off [DPT_1.001 - 1bit]0-Off;1-On1 Bit1.1 switchCRT
99Status_ In1 - Shut/Blind - Step [DPT_1.007 - 1bit]0-Step Up;1-Step Down1 Bit1.1 switchCRT
100Status_ In1 - Dimming - Step(%) [DPT_3.007 - 4bit]Dimming step4 Bit3.7 dimming controlCRT
100Status_ In1 - Shut/Blind - Move [DPT_1.008 - 1bit]0-Move Up;1-Move Down1 Bit1.8 up/downCRT
100Status_ In1 - Value [DPT_12.001 - 4byte]4-byte unsigned value4 Bytes12.1 counter pulses (unsigned)CRT
100Status_ In1 - Value [DPT_5.010 - 1byte]1-byte unsigned value1 Byte5.10 counter pulses (0..255)CRT
100Status_ In1 - Value [DPT_8.001 - 2byte]2-byte signed value2 Bytes8.1 pulses differenceCRT
100Status_ In1 - Value [DPT_9.001 - 2byte]Temperature (ºC)2 Bytes9.1 temperature (°C)CRT
100Status_ In1 - Value [DPT_7.001 - 2byte]2-byte unsigned value2 Bytes7.1 pulsesCRT
101Status_ In2 - Switching [DPT_1.001 - 1bit]0-Off;1-On1 Bit1.1 switchCRT
101Status_ In2 - Dimming - On/Off [DPT_1.001 - 1bit]0-Off;1-On1 Bit1.1 switchCRT
101Status_ In2 - Shut/Blind - Step [DPT_1.007 - 1bit]0-Step Up;1-Step Down1 Bit1.1 switchCRT
102Status_ In2 - Dimming - Step(%) [DPT_3.007 - 4bit]Dimming step4 Bit3.7 dimming controlCRT
102Status_ In2 - Value [DPT_7.001 - 2byte]2-byte unsigned value2 Bytes7.1 pulsesCRT
102Status_ In2 - Value [DPT_5.010 - 1byte]1-byte unsigned value1 Byte5.10 counter pulses (0..255)CRT
102Status_ In2 - Shut/Blind - Move [DPT_1.008 - 1bit]0-Move Up;1-Move Down1 Bit1.8 up/downCRT
102Status_ In2 - Value [DPT_12.001 - 4byte]4-byte unsigned value4 Bytes12.1 counter pulses (unsigned)CRT
102Status_ In2 - Value [DPT_9.001 - 2byte]Temperature (ºC)2 Bytes9.1 temperature (°C)CRT
102Status_ In2 - Value [DPT_8.001 - 2byte]2-byte signed value2 Bytes8.1 pulses differenceCRT
103Status_ In3 - Switching [DPT_1.001 - 1bit]0-Off;1-On1 Bit1.1 switchCRT
103Status_ In3 - Dimming - On/Off [DPT_1.001 - 1bit]0-Off;1-On1 Bit1.1 switchCRT
103Status_ In3 - Shut/Blind - Step [DPT_1.007 - 1bit]0-Step Up;1-Step Down1 Bit1.1 switchCRT
104Status_ In3 - Dimming - Step(%) [DPT_3.007 - 4bit]Dimming step4 Bit3.7 dimming controlCRT
104Status_ In3 - Value [DPT_12.001 - 4byte]4-byte unsigned value4 Bytes12.1 counter pulses (unsigned)CRT
104Status_ In3 - Value [DPT_9.001 - 2byte]Temperature (ºC)2 Bytes9.1 temperature (°C)CRT
104Status_ In3 - Value [DPT_8.001 - 2byte]2-byte signed value2 Bytes8.1 pulses differenceCRT
104Status_ In3 - Value [DPT_7.001 - 2byte]2-byte unsigned value2 Bytes7.1 pulsesCRT
104Status_ In3 - Value [DPT_5.010 - 1byte]1-byte unsigned value1 Byte5.10 counter pulses (0..255)CRT
104Status_ In3 - Shut/Blind - Move [DPT_1.008 - 1bit]0-Move Up;1-Move Down1 Bit1.8 up/downCRT
105Status_ In4 - Switching [DPT_1.001 - 1bit]0-Off;1-On1 Bit1.1 switchCRT
105Status_ In4 - Dimming - On/Off [DPT_1.001 - 1bit]0-Off;1-On1 Bit1.1 switchCRT
105Status_ In4 - Shut/Blind - Step [DPT_1.007 - 1bit]0-Step Up;1-Step Down1 Bit1.1 switchCRT
106Status_ In4 - Dimming - Step(%) [DPT_3.007 - 4bit]Dimming step4 Bit3.7 dimming controlCRT
106Status_ In4 - Value [DPT_12.001 - 4byte]4-byte unsigned value4 Bytes12.1 counter pulses (unsigned)CRT
106Status_ In4 - Value [DPT_9.001 - 2byte]Temperature (ºC)2 Bytes9.1 temperature (°C)CRT
106Status_ In4 - Value [DPT_8.001 - 2byte]2-byte signed value2 Bytes8.1 pulses differenceCRT
106Status_ In4 - Value [DPT_7.001 - 2byte]2-byte unsigned value2 Bytes7.1 pulsesCRT
106Status_ In4 - Value [DPT_5.010 - 1byte]1-byte unsigned value1 Byte5.10 counter pulses (0..255)CRT
106Status_ In4 - Shut/Blind - Move [DPT_1.008 - 1bit]0-Move Up;1-Move Down1 Bit1.8 up/downCRT
107Status_ Input 1 Active [DPT_1.011 - 1bit]0-Inactive; 1-Active1 Bit1.11 stateCRT
108Status_ Input 2 Active [DPT_1.011 - 1bit]0-Inactive; 1-Active1 Bit1.11 stateCRT
109Status_ Input 3 Active [DPT_1.011 - 1bit]0-Inactive; 1-Active1 Bit1.11 stateCRT
110Status_ Input 4 Active [DPT_1.011 - 1bit]0-Inactive; 1-Active1 Bit1.11 stateCRT
111Status_ Input 1 In Use [DPT_1.002 - 1bit]0-False; 1-True1 Bit1.2 booleanCRT
112Status_ Input 2 In Use [DPT_1.002 - 1bit]0-False; 1-True1 Bit1.2 booleanCRT
113Status_ Input 3 In Use [DPT_1.002 - 1bit]0-False; 1-True1 Bit1.2 booleanCRT
114Status_ Input 4 In Use [DPT_1.002 - 1bit]0-False; 1-True1 Bit1.2 booleanCRT
115Status_ Input 1 Enabled [DPT_1.002 - 1bit]0-False; 1-True1 Bit1.2 booleanCRT
116Status_ Input 2 Enabled [DPT_1.002 - 1bit]0-False; 1-True1 Bit1.2 booleanCRT
117Status_ Input 3 Enabled [DPT_1.002 - 1bit]0-False; 1-True1 Bit1.2 booleanCRT
118Status_ Input 4 Enabled [DPT_1.002 - 1bit]0-False; 1-True1 Bit1.2 booleanCRT
119Status_ Eeprom Writes [DPT_7.001 - 2byte]Eeprom Writes Counter2 Bytes7.1 pulsesCRT
120Status_ Device Reboot [DPT_1.005 - 1bit]1-Rebooted1 Bit1.5 alarmCRT
Parameters (235)
ParameterTypeDefault
Download latest database entry for this product and its User Manual from:texthttp://www.intesisbox.com
Send READs for Control_ objects on bus recovery (T & U flags must be active)listNo
> Delay before sending READs (sec)unsignedInt 0…3010
Scene to load on bus recovery / startup (needs to define vals for that scene)list(none)
Enable object "Error Code [2byte]"listNo
Disallow control from remote controllerlistNo
> Enable comm obj "Ctrl_ Remote Lock"listNo
Enable func "Control_ Lock Control Obj"listNo
> Enable func "Operating Hours Counter"listNo
When mode is AUTO Status_ objs report actual operating status (HEAT/COOL/..)listNo
Enable "Mode Cool/Heat" objects (for Control and Status)listNo
Enable PID-Compat. Scaling Mode objects (for Control)listNo
Enable use of +/- object for ModelistNo
> DPT type for +/- Mode Objectlist0-Decrease / 1-Increase [DPT_1.007]
Enable use of bit-type Mode objects (for Control)listNo
Enable use of bit-type Mode objects (for Status)listNo
Enable use of Text object for ModelistNo
ASCII strings shown in comm object "Status_ Mode Text"text<< 14-byte string values >>
> String when mode is AUTOtextAUTO
> String when mode is HEATtextHEAT
> String when mode is COOLtextCOOL
> String when mode is FANtextFAN
> String when mode is DRYtextDRY
Enable use of "POWERFUL" mode (AC feature)listNo
Enable use of "QUIET" mode (AC feature)listNo
Enable use of POWER modelistNo
> Action time for this mode (minutes)unsignedInt 1…18030
> Setpoint delta increase (HEAT) or decrease (COOL) (ºC)list2.0 ºC
> Fan Speed for this modelistFAN SPEED 4
Enable use of ECONOMY modelistNo
> Setpoint delta decrease (HEAT) or increase (COOL) (ºC)list2.0 ºC
> Fan Speed for this modelistFAN SPEED 1
Enable use of Sleep functionlistNo
> Sleep function switch-off timeout (minutes)unsignedInt 0…18060
Enable use of ADDITIONAL HEATING modelistNo
Enable use of ADDITIONAL COOLING modelistNo
Enable "Fan Speed Man/Auto" objects (for Control and Status)listNo
Enable use of +/- object for Fan SpeedlistNo
> DPT type for +/- Fan Speed objectlist0-Decrease / 1-Increase [DPT_1.007]
> Does +/- sequence include fan speed AUTO?listNo
> Rollover Speed at upper/lower limit (when controlling with +/- obj)listYes
Enable "Vanes U-D Man/Auto" objects (for Control and Status)listNo
Enable use of +/- object for Vanes U-DlistNo
> DPT type for +/- Vanes U-D objectlist0-Decrease / 1-Increase [DPT_1.007]
> Does +/- sequence include AUTO vanes Up-Down?listNo
> Rollover Vanes at upper/lower limit (when controlling with +/- obj)listYes
Enable use of Text object for Vanes U-DlistNo
ASCII strings shown in comm object "Status_ Vanes U-D Text"text<< 14-byte string values >>
> String when vanes U-D in AUTOtextU-D AUTO
> String when vanes U-D in POS 1textU-D POS 1
> String when vanes U-D in POS 2textU-D POS 2
> String when vanes U-D in POS 3textU-D POS 3
> String when vanes U-D in POS 4textU-D POS 4
> String when vanes U-D in POS 5textU-D POS 5
> String when vanes U-D in POS 6textU-D POS 6
> String when vanes U-D in POS 7textU-D POS 7
DPT object type for Vanes Left-RightlistScaling [DPT_5.001]
Enable use of +/- object for Vanes L-RlistNo
> DPT type for +/- Vanes L-R objectlist0-Decrease / 1-Increase [DPT_1.007]
> Does +/- sequence include vanes Left-Right AUTO?listNo
Enable use of bit-type Vanes L-R objects (for Control)listNo
Enable use of bit-type Vanes L-R objects (for Status)listNo
Enable use of Text object for Vanes L-RlistNo
ASCII strings shown in comm object "Status_ Vanes L-R Text"text<< 14-byte string values >>
> String when vanes L-R in AUTOtextL-R AUTO
> String when vanes L-R in POS 1textL-R POS 1
> String when vanes L-R in POS 2textL-R POS 2
> String when vanes L-R in POS 3textL-R POS 3
> String when vanes L-R in POS 4textL-R POS 4
> String when vanes L-R in POS 5textL-R POS 5
Periodic sending of "Status_ AC Setp" (in seconds;0=No periodic sending)unsignedInt 0…2550
Enable use of +/- obj for Setpoint TemplistNo
> DPT type for +/- Setp Temp objectlist0-Decrease / 1-Increase [DPT_1.007]
> [+/-] step sizelist1.0 ºC
Enable limits on Setpoint Temperature (applies only to Heat and Cool modes)listNo
> Lower limit (ºC)list17.0 ºC
> Upper limit (ºC)list30.0 ºC
Ambient temp. ref. is provided from KNX (carefully read User Guide if enabled)listNo
Enable use of sceneslistNo
Scenes can be stored from KNX buslistNo
Enable use of bit objects for scene executionlistNo
> Enable use of bit objects for storing scenes (from bus)listNo
Scene 1 presetlistNo
> Scene 1 / Value for On-Offlist(unchanged)
> Scene 1 / Value for Modelist(unchanged)
> Scene 1 / Value for Fan Speedlist(unchanged)
> Scene 1 / Value for Vanes U-Dlist(unchanged)
> Scene 1 / Value for Vanes L-R (if available)list(unchanged)
> Scene 1 / Value for Setpoint Templist(unchanged)
> Scene 1 / Value for Remote Locklist(unchanged)
Scene 2 presetlistNo
> Scene 2 / Value for On-Offlist(unchanged)
> Scene 2 / Value for Modelist(unchanged)
> Scene 2 / Value for Fan Speedlist(unchanged)
> Scene 2 / Value for Vanes U-Dlist(unchanged)
> Scene 2 / Value for Vanes L-R (if available)list(unchanged)
> Scene 2 / Value for Setpoint Templist(unchanged)
> Scene 2 / Value for Remote Locklist(unchanged)
Scene 3 presetlistNo
> Scene 3 / Value for On-Offlist(unchanged)
> Scene 3 / Value for Modelist(unchanged)
> Scene 3 / Value for Fan Speedlist(unchanged)
> Scene 3 / Value for Vanes U-Dlist(unchanged)
> Scene 3 / Value for Vanes L-R (if available)list(unchanged)
> Scene 3 / Value for Setpoint Templist(unchanged)
> Scene 3 / Value for Remote Locklist(unchanged)
Scene 4 presetlistNo
> Scene 4 / Value for On-Offlist(unchanged)
> Scene 4 / Value for Modelist(unchanged)
> Scene 4 / Value for Fan Speedlist(unchanged)
> Scene 4 / Value for Vanes U-Dlist(unchanged)
> Scene 4 / Value for Vanes L-R (if available)list(unchanged)
> Scene 4 / Value for Setpoint Templist(unchanged)
> Scene 4 / Value for Remote Locklist(unchanged)
Scene 5 presetlistNo
> Scene 5 / Value for On-Offlist(unchanged)
> Scene 5 / Value for Modelist(unchanged)
> Scene 5 / Value for Fan Speedlist(unchanged)
> Scene 5 / Value for Vanes U-Dlist(unchanged)
> Scene 5 / Value for Vanes L-R (if available)list(unchanged)
> Scene 5 / Value for Setpoint Templist(unchanged)
> Scene 5 / Value for Remote Locklist(unchanged)
Enable use of Open WindowlistNo
> AC switch-off timeout (min)unsignedInt 0…3010
> DPT for Windowlist0-Closed / 1-Open Window [DPT_1.019]
> Reload last On/Off val once window is ClosedlistNo
Enable use of Occupancy functionlistNo
> Timeout to apply action (minutes)unsignedInt 0…18020
> Action after timeout elapsedlistSwitch-Off AC
> Temp delta decrease (HEAT) or increase (COOL) (ºC)list2.0 ºC
> Enable secondary timeoutlistNo
> Timeout to apply action (min)unsignedInt 1…18020
> Action after timeout elapsedlistSwitch-Off AC
> Temp delta dec (HEAT) or inc (COOL) (ºC)list3.0 ºC
Enable object "Error Text Code [14byte]"listYes
Indoor unit has HEAT mode (see docum. for your indoor unit)listYes
> Disallow On/Off operation while window is OpenlistNo
> Disallow On/Off operation while timeout is elapsedlistNo
> Reload last On/Off val once timeout is stoppedlistNo
> Disallow On/Off operation while not OccupiedlistNo
> Reload last On/Off value when OccupiedlistNo
> Debounce timelist50 ms
> Contact typelistNO: Normally Open
> Disabling functionlistNo
> FunctionlistSwitching
> Sending delay after bus recovery (seconds)unsignedInt 0…25510
> Send telegram after bus recoverylistNo action
Indoor unit has FAN mode (see docum. for your indoor unit)listYes
> Value on raising edge (contact activated)listNo action
> Value on falling edge (contact deactivated)listNo action
> Period for cyclical sending (seconds)unsignedInt 1…6553510
> Cyclical sendinglistNever
> Scene when contact is activated (needs to be defined)listScene 1
> Setpoint temp for this mode (ºC)list17.0 ºC
> Setpoint temp for this mode (ºC)list30.0 ºC
Enable use of Input 1listNo
Enable use of Input 2listNo
Enable use of Input 3listNo
Enable use of Input 4listNo
> Reset Input when enablinglistNo
> Mode for short (long) operationlistToggle: On/Off (increase/decrease)
> Increasing steplist25%
> Decreasing steplist-25%
> Short/long operation limit (x100ms)unsignedInt 1…25510
> Cycl. send. period in long oper. (x100ms)(0-No cyclical send.)unsignedInt 0…2550
> OperationlistToggle (Up/Down)
> MethodlistStep-Move-Step
> Vanes adjustment time (x100ms)unsignedInt 1…25510
> DPT to be sentlistDPT 5.010 (1byte)
> Value on raising edge (when contact activated)unsignedInt 0…2550
> Value on raising edge (when contact activated)unsignedInt 0…655350
> Value on raising edge (when contact activated)signedInt -32768…327670
> Value on rais. edge (x0.1ºC) (when contact activated)signedInt -2730…3276250
> Value on raising edge (when contact activated)unsignedInt 0…42949672950
Enable use of Legacy_ object for Mode (compatible with old vers of XXACKNX1)listNo
Enable use of Legacy_ object for Vanes (compatible with old vers of XXACKNX1)listNo
AC unit has Humidifier (see docum. for your indoor unit)listNo
DPT object type for HumidifyinglistScaling [DPT_5.001]
Enable use of +/- object for HumidifyinglistNo
> DPT type for +/- Humidifying objectlist0-Decrease / 1-Increase [DPT_1.007]
> Rollover Humi. at upper/lower limit (when controlling with +/- obj)listNo
Enable use of bit-type Humidif. objects (for Control)listNo
Enable use of bit-type Humidif. objects (for Status)listNo
Enable use of Text obj for HumidifyinglistNo
Enable use of Legacy_ object for Humi. (compatible with old vers of XXACKNX1)listNo
ASCII strings shown in comm object "Status_ Humidifying Text"text<< 14-byte string values >>
> String when Humidifying is OFFtextHUMI OFF
> String when Humidifying is LOWtextHUMI LOW
> String when Humidifying is MIDtextHUMI MID
> String when Humidifying is HIGHtextHUMI HIGH
> String when Humidifying is CONT.textHUMI CONT
Indoor unit has U-D Vanes (see docum. for your indoor unit)listYes
Indoor unit has L-R Vanes (see docum. for your indoor unit)listNo
Indoor unit has AUTO fan speed (see docum. for your indoor unit)listYes
> Scene 1 / Value for Humidifying (if available)list(unchanged)
> Scene 2 / Value for Humidifying (if available)list(unchanged)
> Scene 3 / Value for Humidifying (if available)list(unchanged)
> Scene 4 / Value for Humidifying (if available)list(unchanged)
> Scene 5 / Value for Humidifying (if available)list(unchanged)
Hide items?!listYes
Fan is accessible in Indoor unit (see docum. for your indoor unit)listYes
ASCII strings shown in comm object "Status_ Fan Speed Text"text<< 14-byte string values >>
> String when fan speed is AUTOtextAUTO
> String when fan speed is 1textSPEED 1
> String when fan speed is 2textSPEED 2
> String when fan speed is 3textSPEED 3
> String when fan speed is 4textSPEED 4
Enable use of Text object for Fan SpeedlistNo
Available positions in Indoor Unit (see docum. for your indoor unit)unsignedInt 5…75
Available fanspeeds in Indoor Unit (see docum. for your indoor unit)list3
Indoor unit has SWING Vanes U-D (see docum. for your indoor unit)listYes
Enable "Vanes U-D Swing" objects (for Control and Status)listNo
Enable use of bit-type Vanes U-D objects (for Status)listNo
Enable use of bit-type Vanes U-D objects (for Control)listNo
DPT object type for Vanes Up-DownlistScaling [DPT_5.001]
> Does +/- sequence include SWING vanes Up-Down?listNo
> String when vanes U-D in SWINGtextU-D SWING
Transmission of "Status_ AC Refer. Temp"listOnly on change
> "Status_ AC Refer. Temp" periodic sending time (in sec)unsignedInt 1…255180
Indoor unit has DRY mode (see docum. for your indoor unit)listYes
Indoor unit has AUTO mode (see docum. for your indoor unit)listYes
Available positions in Indoor Unit (see docum. for your indoor unit)unsignedInt 3…55
Indoor unit has AUTO Vanes L-R (see docum. for your indoor unit)listNo
Indoor unit has SWING Vanes L-R (see docum. for your indoor unit)listNo
Available intensities in Indoor Unit (see docum. for your indoor unit)listYes
Available AUTOs in Indoor Unit (see docum. for your indoor unit)list0
Enable use of objects for Filter (for Control and Status)listNo
HS-RC-KNX-1i is master in A B buslistNo
DPT object type for fanspeedlistScaling [DPT_5.001]
Enable use of bit-type Fan Speed objects (for Control)listNo
Enable use of bit-type Fan Speed objects (for Status)listNo
Enable func "Operating Time Counter"listNo
Store AC status in NVMlistNo
Show debug objectslistNo
Periodic sending timeout <0=no periodic>unsignedInt 0…2550

Version history

ApplicationApp noFingerprintFirst seenSizeFile
HSRCKNX1i T2BV20 2.0 latest$002B6AF12026-11-25194 KBDownload

About this file

This is the official ETS product database for the Intesis HS RC interface, 4 binary inputs (HS-RC-KNX-1i), published by the manufacturer in the KNX online catalog. To use it, open ETS, go to Catalogs → Import and choose the downloaded .knxprod file. The device then appears in your catalog and can be added to a project. Older versions are kept so existing projects can be matched to the application program they were commissioned with.