| 0 | Control_ Zones On/Off [DPT_1.001] | 1-On, 0-Off | 1 Bit | 1.1 switch | CWTU |
| 1 | Control_ HW On/Off [DPT_1.001] | 1-On, 0-Off | 1 Bit | 1.1 switch | CWTU |
| 2 | Control_ Mode [DPT_20.105] | 1-Heat, 3-Cool | 1 Byte | 20.105 HVAC control mode | CWTU |
| 3 | Control_ Mode Cool/Heat [DPT_1.100] | 0-Cool, 1-Heat | 1 Bit | 1.100 heating/cooling | CWTU |
| 4 | Control_ Mode Heat [DPT_1.002] | 1-Set heat mode | 1 Bit | 1.2 boolean | CWTU |
| 5 | Control_ Mode Cool [DPT_1.002] | 1-Set cool mode | 1 Bit | 1.2 boolean | CWTU |
| 6 | Control_ Zone1 Setting Temperature [DPT_9.001] | ºC | 2 Bytes | 9.1 temperature (°C) | CWTU |
| 7 | Control_ Zone2 Setting Temperature [DPT_9.001] | ºC | 2 Bytes | 9.1 temperature (°C) | CWTU |
| 8 | Control_ HW Setting Temperature [DPT_9.001] | ºC | 2 Bytes | 9.1 temperature (°C) | CWTU |
| 9 | Control_ Auto temperature On/Off [DPT_1.001] | 1-On, 0-Off | 1 Bit | 1.1 switch | CWTU |
| 10 | Control_ Night Setback On/Off [DPT_1.001] | 1-On, 0-Off | 1 Bit | 1.1 switch | CWTU |
| 11 | Control_ HW Boost On/Off [DPT_1.001] | 1-On, 0-Off | 1 Bit | 1.1 switch | CWTU |
| 12 | Control_ Frost Protection On/Off [DPT_1.001] | 1-On, 0-Off | 1 Bit | 1.1 switch | CWTU |
| 13 | Control_ Antibacteria On/Off [DPT_1.001] | 1-On, 0-Off | 1 Bit | 1.1 switch | CWTU |
| 14 | Control_ Remote Controller Permit ALL [DPT_1.002] | 0-Permitted, 1-Not permitted | 1 Bit | 1.2 boolean | CWTU |
| 15 | Control_ Remote Controller Permit OnOff [DPT_1.002] | 0-Permitted, 1-Not permitted | 1 Bit | 1.2 boolean | CWTU |
| 16 | Control_ Remote Controller Permit Mode [DPT_1.002] | 0-Permitted, 1-Not permitted | 1 Bit | 1.2 boolean | CWTU |
| 17 | Control_ Remote Controller Permit Setting Temperature [DPT_1.002] | 0-Permitted, 1-Not permitted | 1 Bit | 1.2 boolean | CWTU |
| 18 | Control_ Error History Reset [DPT_1.015] | 1-Reset, 0-NoAction | 1 Bit | 1.15 reset | CWTU |
| 19 | Status_ Zones On/Off [DPT_1.001] | 1-On, 0-Off | 1 Bit | 1.1 switch | CRT |
| 20 | Status_ HW On/Off [DPT_1.001] | 1-On, 0-Off | 1 Bit | 1.1 switch | CRT |
| 21 | Status_ Mode [DPT_20.105] | 1-Heat, 3-Cool | 1 Byte | 20.105 HVAC control mode | CRT |
| 22 | Status_ Mode Cool/Heat [DPT_1.100] | 0-Cool, 1-Heat | 1 Bit | 1.100 heating/cooling | CRT |
| 23 | Status_ Mode Heat [DPT_1.002] | 1-Heat mode active | 1 Bit | 1.2 boolean | CRT |
| 24 | Status_ Mode Cool [DPT_1.002] | 1-Cool mode active | 1 Bit | 1.2 boolean | CRT |
| 25 | Status_ Zone1 Setting Temperature [DPT_9.001] | ºC | 2 Bytes | 9.1 temperature (°C) | CRT |
| 26 | Status_ Zone2 Setting Temperature [DPT_9.001] | ºC | 2 Bytes | 9.1 temperature (°C) | CRT |
| 27 | Status_ HW Setting Temperature [DPT_9.001] | ºC | 2 Bytes | 9.1 temperature (°C) | CRT |
| 28 | Status_ Auto Temperature On/Off [DPT_1.001] | 1-On, 0-Off | 1 Bit | 1.1 switch | CRT |
| 29 | Status_ Night Setback On/Off [DPT_1.001] | 1-On, 0-Off | 1 Bit | 1.1 switch | CRT |
| 30 | Status_ HW Boost On/Off [DPT_1.001] | 1-On, 0-Off | 1 Bit | 1.1 switch | CRT |
| 31 | Status_ Frost Protection On/Off [DPT_1.001] | 1-On, 0-Off | 1 Bit | 1.1 switch | CRT |
| 32 | Status_ Antibacteria On/Off [DPT_1.001] | 1-On, 0-Off | 1 Bit | 1.1 switch | CRT |
| 33 | Status_ Alarm [DPT_1.005] | 1-Alarm, 0-No alarm | 1 Bit | 1.5 alarm | CRT |
| 34 | Status_ Alarm Code [2byte] | Alarm code | 2 Bytes | | CRT |
| 35 | Status_ Alarm Text [DPT_16.001] | Alarm description | 14 Bytes | 16.1 Character String (ISO 8859-1) | CRT |
| 36 | Status_ Alarm Address [2byte] | Alarm address | 2 Bytes | | CRT |
| 37 | Status_ Zone1 Control Temperature [DPT_9.001] | ºC | 2 Bytes | 9.1 temperature (°C) | CRT |
| 38 | Status_ Zone2 Control Temperature [DPT_9.001] | ºC | 2 Bytes | 9.1 temperature (°C) | CRT |
| 39 | Status_ HW Control Temperature [DPT_9.001] | ºC | 2 Bytes | 9.1 temperature (°C) | CRT |
| 40 | Status_ Control Temperature [DPT_9.001] | ºC | 2 Bytes | 9.1 temperature (°C) | CRT |
| 41 | Status_ Outdoor Liquid Temperature [DPT_9.001] | ºC | 2 Bytes | 9.1 temperature (°C) | CRT |
| 42 | Status_ HW Cylinder Water Temperature (TTW) [DPT_9.001] | ºC | 2 Bytes | 9.1 temperature (°C) | CRT |
| 43 | Status_ Condensed Refrigerant Temperature [DPT_9.001] | ºC | 2 Bytes | 9.1 temperature (°C) | CRT |
| 44 | Status_ Water Inlet Temperature (TWI) [DPT_9.001] | ºC | 2 Bytes | 9.1 temperature (°C) | CRT |
| 45 | Status_ Water Outlet Temperature (TWO) [DPT_9.001] | ºC | 2 Bytes | 9.1 temperature (°C) | CRT |
| 46 | Status_ Water Heater Outlet Temperature (THO) [DPT_9.001] | ºC | 2 Bytes | 9.1 temperature (°C) | CRT |
| 47 | Status_ Zone2 Inlet Temperature (TFI) [DPT_9.001] | ºC | 2 Bytes | 9.1 temperature (°C) | CRT |
| 48 | Status_ Motorized Mixing Valve Position [DPT_7.001] | Position | 2 Bytes | 7.1 pulses | CRT |
| 49 | Status_ System Low Pressure [DPT_14.058] | Pa | 4 Bytes | 14.58 pressure (Pa) | CRT |
| 50 | Status_ Outdoor Heat Exchanger Temperature [DPT_9.001] | ºC | 2 Bytes | 9.1 temperature (°C) | CRT |
| 51 | Status_ Discharge Temperature [DPT_9.001] | ºC | 2 Bytes | 9.1 temperature (°C) | CRT |
| 52 | Status_ Outdoor Suction Temperature [DPT_9.001] | ºC | 2 Bytes | 9.1 temperature (°C) | CRT |
| 53 | Status_ Outside Temperature [DPT_9.001] | ºC | 2 Bytes | 9.1 temperature (°C) | CRT |
| 54 | Status_ Outdoor Compressor Frequency [DPT_14.033] | Hz | 4 Bytes | 14.33 frequency (Hz) | CRT |
| 55 | Status_ Outdoor Lower Fan Speed [DPT_14.033] | Hz | 4 Bytes | 14.33 frequency (Hz) | CRT |
| 56 | Status_ Outdoor Upper Fan Speed [DPT_14.033] | Hz | 4 Bytes | 14.33 frequency (Hz) | CRT |
| 57 | Status_ HW mode compressor Second Counter [DPT_13.100] | Sec | 4 Bytes | 13.100 time lag (s) | CRT |
| 58 | Status_ HW mode compressor Hour Counter [DPT_7.007] | Hours | 2 Bytes | 7.7 time (h) | CRT |
| 59 | Status_ Heating mode compressor Second Counter [DPT_13.100] | Sec | 4 Bytes | 13.100 time lag (s) | CRT |
| 60 | Status_ Heating mode compressor Hour Counter [DPT_7.007] | Hours | 2 Bytes | 7.7 time (h) | CRT |
| 61 | Status_ Cooling mode compressor Second Counter [DPT_13.100] | Sec | 4 Bytes | 13.100 time lag (s) | CRT |
| 62 | Status_ Cooling mode compressor Hour Counter [DPT_7.007] | Hours | 2 Bytes | 7.7 time (h) | CRT |
| 63 | Status_ HU water pump operation Second Counter [DPT_13.100] | Sec | 4 Bytes | 13.100 time lag (s) | CRT |
| 64 | Status_ HU water pump operation Hour Counter [DPT_7.007] | Hours | 2 Bytes | 7.7 time (h) | CRT |
| 65 | Status_ HW cylinder heater Second Counter [DPT_13.100] | Sec | 4 Bytes | 13.100 time lag (s) | CRT |
| 66 | Status_ HW cylinder heater Hour Counter [DPT_7.007] | Hours | 2 Bytes | 7.7 time (h) | CRT |
| 67 | Status_ HU back up Heater Second Counter [DPT_13.100] | Sec | 4 Bytes | 13.100 time lag (s) | CRT |
| 68 | Status_ HU back up Heater Hour Counter [DPT_7.007] | Hours | 2 Bytes | 7.7 time (h) | CRT |
| 69 | Status_ Zone1 Device Connected [DPT_1.002] | 0-Not connected, 1-Connected | 1 Bit | 1.2 boolean | CRT |
| 70 | Status_ Zone2 Device Connected [DPT_1.002] | 0-Not connected, 1-Connected | 1 Bit | 1.2 boolean | CRT |
| 71 | Status_ HW Device Connected [DPT_1.002] | 0-Not connected, 1-Connected | 1 Bit | 1.2 boolean | CRT |
| 72 | Status_ Zones Cool Setting Temperature MAX [DPT_9.001] | ºC | 2 Bytes | 9.1 temperature (°C) | CRT |
| 73 | Status_ Zones Cool Setting Temperature MIN [DPT_9.001] | ºC | 2 Bytes | 9.1 temperature (°C) | CRT |
| 74 | Status_ Zone1 Heat Setting Temperature MAX [DPT_9.001] | ºC | 2 Bytes | 9.1 temperature (°C) | CRT |
| 75 | Status_ Zone1 Heat Setting Temperature MIN [DPT_9.001] | ºC | 2 Bytes | 9.1 temperature (°C) | CRT |
| 76 | Status_ Zone2 Heat Setting Temperature MAX [DPT_9.001] | ºC | 2 Bytes | 9.1 temperature (°C) | CRT |
| 77 | Status_ Zone2 Heat Setting Temperature MIN [DPT_9.001] | ºC | 2 Bytes | 9.1 temperature (°C) | CRT |
| 78 | Status_ HW mode water Temp MAX [DPT_9.001] | ºC | 2 Bytes | 9.1 temperature (°C) | CRT |
| 79 | Status_ HW mode water Temp MIN [DPT_9.001] | ºC | 2 Bytes | 9.1 temperature (°C) | CRT |
| 80 | Status_ Frost protection Setting Temperature [DPT_9.001] | ºC | 2 Bytes | 9.1 temperature (°C) | CRT |
| 81 | Status_ HW Boost Setting Temperature [DPT_9.001] | ºC | 2 Bytes | 9.1 temperature (°C) | CRT |
| 82 | Status_ Antibacteria Setting Temperature [DPT_9.001] | ºC | 2 Bytes | 9.1 temperature (°C) | CRT |
| 83 | Status_ Operation Heat Mode Permitted [DPT_1.002] | 0-Not permitted, 1-Permitted | 1 Bit | 1.2 boolean | CRT |
| 84 | Status_ Operation Cool Mode Permitted [DPT_1.002] | 0-Not permitted, 1-Permitted | 1 Bit | 1.2 boolean | CRT |
| 85 | Status_ Auto Temperature Permitted [DPT_1.002] | 0-Not permitted, 1-Permitted | 1 Bit | 1.2 boolean | CRT |
| 86 | Status_ Frost Protection Permitted [DPT_1.002] | 0-Not permitted, 1-Permitted | 1 Bit | 1.2 boolean | CRT |
| 87 | Status_ Night Setback Permitted [DPT_1.002] | 0-Not permitted, 1-Permitted | 1 Bit | 1.2 boolean | CRT |
| 88 | Status_ HW Boost Permitted [DPT_1.002] | 0-Not permitted, 1-Permitted | 1 Bit | 1.2 boolean | CRT |
| 89 | Status_ Antibacteria Permitted [DPT_1.002] | 0-Not permitted, 1-Permitted | 1 Bit | 1.2 boolean | CRT |
| 90 | Status_ Remote Controller Permit ALL [DPT_1.002] | 0-Permitted, 1-Not permitted | 1 Bit | 1.2 boolean | CRT |
| 91 | Status_ Remote Controller Permit OnOff [DPT_1.002] | 0-Permitted, 1-Not permitted | 1 Bit | 1.2 boolean | CRT |
| 92 | Status_ Remote Controller Permit Mode [DPT_1.002] | 0-Permitted, 1-Not permitted | 1 Bit | 1.2 boolean | CRT |
| 93 | Status_ Remote Controller Permit Setting Temperature [DPT_1.002] | 0-Permitted, 1-Not permitted | 1 Bit | 1.2 boolean | CRT |
| 94 | Status_ Floor Dry Status [DPT_1.001] | 1-On, 0-Off | 1 Bit | 1.1 switch | CRT |
| 95 | Status_ Zone1 Auto Curve Target Tempearture [DPT_9_001] | ºC | 2 Bytes | 9.1 temperature (°C) | CRT |
| 96 | Status_ Zone2 Auto Curve Target Tempearture [DPT_9_001] | ºC | 2 Bytes | 9.1 temperature (°C) | CRT |
| 97 | Status_ Frost Protection Function Setting Status [DPT_1_001] | 1-On, 0-Off | 1 Bit | 1.1 switch | CRT |
| 98 | Status_ Low Noise Function Setting Status [DPT_1_001] | 1-On, 0-Off | 1 Bit | 1.1 switch | CRT |
| 99 | Status_ Hot Water Tank Thermo Status [DPT_1_001] | 1-On, 0-Off | 1 Bit | 1.1 switch | CRT |
| 100 | Status_ External Thermo Control Status [DPT_1_001] | 1-On, 0-Off | 1 Bit | 1.1 switch | CRT |