KNX Interface for ESTIA BMS-IFKX0UEW-E

Intesis · Order number BMS-IFKX0UEW-E · Communication › Interfaces › Toshiba Air to Water Interfaces

Download .knxprod BMS-IFKX0UEW-E V0200 2.0 · 97 KB

Product

ManufacturerIntesis
Product nameKNX Interface for ESTIA
Order numberBMS-IFKX0UEW-E
HardwareTO-AW-KNX-1
MediumTwisted Pair
Bus current (mA)8
Rail mountedNo
RegistrationCertified · 2023-02-16
Languagesen-US
Catalog entryM-0077_H-TO.2DAW.2DKNX.2D1-1_HP-002C-20-A99B_CI-BMS.2DIFKX0UEW.2DE-1
FingerprintA99B
SHA-25643026ba489426105869b4258e48e733dde4760c9a106e9897e5f0774e317623a
First seen2026-11-25
Markets69 markets

Application program: BMS-IFKX0UEW-E V0200 2.0

Application number$002C
Version2.0
Mask versionMV-0025 (2.5)
KNX Data SecureNo
Minimum ETS version4.0
Parameters14
Group objects101
Group objects (101)
NoNameFunctionSizeDPTFlags
0Control_ Zones On/Off [DPT_1.001]1-On, 0-Off1 Bit1.1 switchCWTU
1Control_ HW On/Off [DPT_1.001]1-On, 0-Off1 Bit1.1 switchCWTU
2Control_ Mode [DPT_20.105]1-Heat, 3-Cool1 Byte20.105 HVAC control modeCWTU
3Control_ Mode Cool/Heat [DPT_1.100]0-Cool, 1-Heat1 Bit1.100 heating/coolingCWTU
4Control_ Mode Heat [DPT_1.002]1-Set heat mode1 Bit1.2 booleanCWTU
5Control_ Mode Cool [DPT_1.002]1-Set cool mode1 Bit1.2 booleanCWTU
6Control_ Zone1 Setting Temperature [DPT_9.001]ºC2 Bytes9.1 temperature (°C)CWTU
7Control_ Zone2 Setting Temperature [DPT_9.001]ºC2 Bytes9.1 temperature (°C)CWTU
8Control_ HW Setting Temperature [DPT_9.001]ºC2 Bytes9.1 temperature (°C)CWTU
9Control_ Auto temperature On/Off [DPT_1.001]1-On, 0-Off1 Bit1.1 switchCWTU
10Control_ Night Setback On/Off [DPT_1.001]1-On, 0-Off1 Bit1.1 switchCWTU
11Control_ HW Boost On/Off [DPT_1.001]1-On, 0-Off1 Bit1.1 switchCWTU
12Control_ Frost Protection On/Off [DPT_1.001]1-On, 0-Off1 Bit1.1 switchCWTU
13Control_ Antibacteria On/Off [DPT_1.001]1-On, 0-Off1 Bit1.1 switchCWTU
14Control_ Remote Controller Permit ALL [DPT_1.002]0-Permitted, 1-Not permitted1 Bit1.2 booleanCWTU
15Control_ Remote Controller Permit OnOff [DPT_1.002]0-Permitted, 1-Not permitted1 Bit1.2 booleanCWTU
16Control_ Remote Controller Permit Mode [DPT_1.002]0-Permitted, 1-Not permitted1 Bit1.2 booleanCWTU
17Control_ Remote Controller Permit Setting Temperature [DPT_1.002]0-Permitted, 1-Not permitted1 Bit1.2 booleanCWTU
18Control_ Error History Reset [DPT_1.015]1-Reset, 0-NoAction1 Bit1.15 resetCWTU
19Status_ Zones On/Off [DPT_1.001]1-On, 0-Off1 Bit1.1 switchCRT
20Status_ HW On/Off [DPT_1.001]1-On, 0-Off1 Bit1.1 switchCRT
21Status_ Mode [DPT_20.105]1-Heat, 3-Cool1 Byte20.105 HVAC control modeCRT
22Status_ Mode Cool/Heat [DPT_1.100]0-Cool, 1-Heat1 Bit1.100 heating/coolingCRT
23Status_ Mode Heat [DPT_1.002]1-Heat mode active1 Bit1.2 booleanCRT
24Status_ Mode Cool [DPT_1.002]1-Cool mode active1 Bit1.2 booleanCRT
25Status_ Zone1 Setting Temperature [DPT_9.001]ºC2 Bytes9.1 temperature (°C)CRT
26Status_ Zone2 Setting Temperature [DPT_9.001]ºC2 Bytes9.1 temperature (°C)CRT
27Status_ HW Setting Temperature [DPT_9.001]ºC2 Bytes9.1 temperature (°C)CRT
28Status_ Auto Temperature On/Off [DPT_1.001]1-On, 0-Off1 Bit1.1 switchCRT
29Status_ Night Setback On/Off [DPT_1.001]1-On, 0-Off1 Bit1.1 switchCRT
30Status_ HW Boost On/Off [DPT_1.001]1-On, 0-Off1 Bit1.1 switchCRT
31Status_ Frost Protection On/Off [DPT_1.001]1-On, 0-Off1 Bit1.1 switchCRT
32Status_ Antibacteria On/Off [DPT_1.001]1-On, 0-Off1 Bit1.1 switchCRT
33Status_ Alarm [DPT_1.005]1-Alarm, 0-No alarm1 Bit1.5 alarmCRT
34Status_ Alarm Code [2byte]Alarm code2 BytesCRT
35Status_ Alarm Text [DPT_16.001]Alarm description14 Bytes16.1 Character String (ISO 8859-1)CRT
36Status_ Alarm Address [2byte]Alarm address2 BytesCRT
37Status_ Zone1 Control Temperature [DPT_9.001]ºC2 Bytes9.1 temperature (°C)CRT
38Status_ Zone2 Control Temperature [DPT_9.001]ºC2 Bytes9.1 temperature (°C)CRT
39Status_ HW Control Temperature [DPT_9.001]ºC2 Bytes9.1 temperature (°C)CRT
40Status_ Control Temperature [DPT_9.001]ºC2 Bytes9.1 temperature (°C)CRT
41Status_ Outdoor Liquid Temperature [DPT_9.001]ºC2 Bytes9.1 temperature (°C)CRT
42Status_ HW Cylinder Water Temperature (TTW) [DPT_9.001]ºC2 Bytes9.1 temperature (°C)CRT
43Status_ Condensed Refrigerant Temperature [DPT_9.001]ºC2 Bytes9.1 temperature (°C)CRT
44Status_ Water Inlet Temperature (TWI) [DPT_9.001]ºC2 Bytes9.1 temperature (°C)CRT
45Status_ Water Outlet Temperature (TWO) [DPT_9.001]ºC2 Bytes9.1 temperature (°C)CRT
46Status_ Water Heater Outlet Temperature (THO) [DPT_9.001]ºC2 Bytes9.1 temperature (°C)CRT
47Status_ Zone2 Inlet Temperature (TFI) [DPT_9.001]ºC2 Bytes9.1 temperature (°C)CRT
48Status_ Motorized Mixing Valve Position [DPT_7.001]Position2 Bytes7.1 pulsesCRT
49Status_ System Low Pressure [DPT_14.058]Pa4 Bytes14.58 pressure (Pa)CRT
50Status_ Outdoor Heat Exchanger Temperature [DPT_9.001]ºC2 Bytes9.1 temperature (°C)CRT
51Status_ Discharge Temperature [DPT_9.001]ºC2 Bytes9.1 temperature (°C)CRT
52Status_ Outdoor Suction Temperature [DPT_9.001]ºC2 Bytes9.1 temperature (°C)CRT
53Status_ Outside Temperature [DPT_9.001]ºC2 Bytes9.1 temperature (°C)CRT
54Status_ Outdoor Compressor Frequency [DPT_14.033]Hz4 Bytes14.33 frequency (Hz)CRT
55Status_ Outdoor Lower Fan Speed [DPT_14.033]Hz4 Bytes14.33 frequency (Hz)CRT
56Status_ Outdoor Upper Fan Speed [DPT_14.033]Hz4 Bytes14.33 frequency (Hz)CRT
57Status_ HW mode compressor Second Counter [DPT_13.100]Sec4 Bytes13.100 time lag (s)CRT
58Status_ HW mode compressor Hour Counter [DPT_7.007]Hours2 Bytes7.7 time (h)CRT
59Status_ Heating mode compressor Second Counter [DPT_13.100]Sec4 Bytes13.100 time lag (s)CRT
60Status_ Heating mode compressor Hour Counter [DPT_7.007]Hours2 Bytes7.7 time (h)CRT
61Status_ Cooling mode compressor Second Counter [DPT_13.100]Sec4 Bytes13.100 time lag (s)CRT
62Status_ Cooling mode compressor Hour Counter [DPT_7.007]Hours2 Bytes7.7 time (h)CRT
63Status_ HU water pump operation Second Counter [DPT_13.100]Sec4 Bytes13.100 time lag (s)CRT
64Status_ HU water pump operation Hour Counter [DPT_7.007]Hours2 Bytes7.7 time (h)CRT
65Status_ HW cylinder heater Second Counter [DPT_13.100]Sec4 Bytes13.100 time lag (s)CRT
66Status_ HW cylinder heater Hour Counter [DPT_7.007]Hours2 Bytes7.7 time (h)CRT
67Status_ HU back up Heater Second Counter [DPT_13.100]Sec4 Bytes13.100 time lag (s)CRT
68Status_ HU back up Heater Hour Counter [DPT_7.007]Hours2 Bytes7.7 time (h)CRT
69Status_ Zone1 Device Connected [DPT_1.002]0-Not connected, 1-Connected1 Bit1.2 booleanCRT
70Status_ Zone2 Device Connected [DPT_1.002]0-Not connected, 1-Connected1 Bit1.2 booleanCRT
71Status_ HW Device Connected [DPT_1.002]0-Not connected, 1-Connected1 Bit1.2 booleanCRT
72Status_ Zones Cool Setting Temperature MAX [DPT_9.001]ºC2 Bytes9.1 temperature (°C)CRT
73Status_ Zones Cool Setting Temperature MIN [DPT_9.001]ºC2 Bytes9.1 temperature (°C)CRT
74Status_ Zone1 Heat Setting Temperature MAX [DPT_9.001]ºC2 Bytes9.1 temperature (°C)CRT
75Status_ Zone1 Heat Setting Temperature MIN [DPT_9.001]ºC2 Bytes9.1 temperature (°C)CRT
76Status_ Zone2 Heat Setting Temperature MAX [DPT_9.001]ºC2 Bytes9.1 temperature (°C)CRT
77Status_ Zone2 Heat Setting Temperature MIN [DPT_9.001]ºC2 Bytes9.1 temperature (°C)CRT
78Status_ HW mode water Temp MAX [DPT_9.001]ºC2 Bytes9.1 temperature (°C)CRT
79Status_ HW mode water Temp MIN [DPT_9.001]ºC2 Bytes9.1 temperature (°C)CRT
80Status_ Frost protection Setting Temperature [DPT_9.001]ºC2 Bytes9.1 temperature (°C)CRT
81Status_ HW Boost Setting Temperature [DPT_9.001]ºC2 Bytes9.1 temperature (°C)CRT
82Status_ Antibacteria Setting Temperature [DPT_9.001]ºC2 Bytes9.1 temperature (°C)CRT
83Status_ Operation Heat Mode Permitted [DPT_1.002]0-Not permitted, 1-Permitted1 Bit1.2 booleanCRT
84Status_ Operation Cool Mode Permitted [DPT_1.002]0-Not permitted, 1-Permitted1 Bit1.2 booleanCRT
85Status_ Auto Temperature Permitted [DPT_1.002]0-Not permitted, 1-Permitted1 Bit1.2 booleanCRT
86Status_ Frost Protection Permitted [DPT_1.002]0-Not permitted, 1-Permitted1 Bit1.2 booleanCRT
87Status_ Night Setback Permitted [DPT_1.002]0-Not permitted, 1-Permitted1 Bit1.2 booleanCRT
88Status_ HW Boost Permitted [DPT_1.002]0-Not permitted, 1-Permitted1 Bit1.2 booleanCRT
89Status_ Antibacteria Permitted [DPT_1.002]0-Not permitted, 1-Permitted1 Bit1.2 booleanCRT
90Status_ Remote Controller Permit ALL [DPT_1.002]0-Permitted, 1-Not permitted1 Bit1.2 booleanCRT
91Status_ Remote Controller Permit OnOff [DPT_1.002]0-Permitted, 1-Not permitted1 Bit1.2 booleanCRT
92Status_ Remote Controller Permit Mode [DPT_1.002]0-Permitted, 1-Not permitted1 Bit1.2 booleanCRT
93Status_ Remote Controller Permit Setting Temperature [DPT_1.002]0-Permitted, 1-Not permitted1 Bit1.2 booleanCRT
94Status_ Floor Dry Status [DPT_1.001]1-On, 0-Off1 Bit1.1 switchCRT
95Status_ Zone1 Auto Curve Target Tempearture [DPT_9_001]ºC2 Bytes9.1 temperature (°C)CRT
96Status_ Zone2 Auto Curve Target Tempearture [DPT_9_001]ºC2 Bytes9.1 temperature (°C)CRT
97Status_ Frost Protection Function Setting Status [DPT_1_001]1-On, 0-Off1 Bit1.1 switchCRT
98Status_ Low Noise Function Setting Status [DPT_1_001]1-On, 0-Off1 Bit1.1 switchCRT
99Status_ Hot Water Tank Thermo Status [DPT_1_001]1-On, 0-Off1 Bit1.1 switchCRT
100Status_ External Thermo Control Status [DPT_1_001]1-On, 0-Off1 Bit1.1 switchCRT
Parameters (14)
ParameterTypeDefault
Send READs for objects on bus recovery (T & U flags must be active)listYes
Delay before sending READsunsignedInt 0…3010
Download latest database entry for this product and its User Manual from:texthttp://www.toshiba-carrier.co.jp/global/
ModellistESTIA R32 1 Series
Number of zones availablelist1 zone
Cool/Heat mode objects (control and status)listEnabled
1 byte mode objects (control and status)listDisabled
1 bit mode objects (control and status)listEnabled
Enable additional signals of zoneslistNo
Monitor outdoor unit signalslistNo
Monitor hydro unit signalslistNo
Hot Water CylinderlistDisabled
Enable additional signals of Hot Water CylinderlistNo
Alarm objectslistDisabled

Version history

ApplicationApp noFingerprintFirst seenSizeFile
BMS-IFKX0UEW-E V0200 2.0 latest$002CA99B2026-11-2597 KBDownload

About this file

This is the official ETS product database for the Intesis KNX Interface for ESTIA (BMS-IFKX0UEW-E), published by the manufacturer in the KNX online catalog. To use it, open ETS, go to Catalogs → Import and choose the downloaded .knxprod file. The device then appears in your catalog and can be added to a project. Older versions are kept so existing projects can be matched to the application program they were commissioned with.