| 1 | AC01 Control_ On/Off [DPT_1.001] | 0-Off;1-On | 1 Bit | 1.1 switch | CW |
| 2 | AC01 Control_ Operating Mode [DPT_20.102] | 0-Aut;1-Com;2-Stan;3-Eco;4-Pro | 1 Byte | 20.102 HVAC mode | CW |
| 3 | AC01 Control_ Mode [DPT_20.105] | 0-Aut;1-Hea;3-Coo;9-Fan;14-Dry | 1 Byte | 20.105 HVAC control mode | CW |
| 4 | AC01 Control_ Mode Cool/Heat [DPT_1.100] | 0-Cool;1-Heat | 1 Bit | 1.100 heating/cooling | CW |
| 5 | AC01 Control_ Mode Auto [DPT_1.002] | 1-Set AUTO mode | 1 Bit | 1.2 boolean | CW |
| 6 | AC01 Control_ Mode Heat [DPT_1.002] | 1-Set HEAT mode | 1 Bit | 1.2 boolean | CW |
| 7 | AC01 Control_ Mode Cool [DPT_1.002] | 1-Set COOL mode | 1 Bit | 1.2 boolean | CW |
| 8 | AC01 Control_ Mode Fan [DPT_1.002] | 1-Set FAN mode | 1 Bit | 1.2 boolean | CW |
| 9 | AC01 Control_ Mode Dry [DPT_1.002] | 1-Set DRY mode | 1 Bit | 1.2 boolean | CW |
| 10 | AC01 Control_ Mode +/- [DPT_1.007] | 0-Dec.;1-Inc. | 1 Bit | 1.7 step | CW |
| 10 | AC01 Control_ Mode +/- [DPT_1.008] | 0-Up;1-Down | 1 Bit | 1.8 up/down | CW |
| 11 | AC01 Control_ Fan Speed [DPT_5.001] | Thresholds: 75% || 50% and 83% | 1 Byte | 5.1 percentage (0..100%) | CW |
| 11 | AC01 Control_ Fan Speed [DPT_5.010] | Speed values: 1,2 || 1,2,3 | 1 Byte | 5.10 counter pulses (0..255) | CW |
| 12 | AC01 Control_ Fan Speed Man/Auto [DPT_1.002] | 0-Manual;1-Auto | 1 Bit | 1.2 boolean | CW |
| 13 | AC01 Control_ Fan Speed 1 [DPT_1.002] | 1-Set Fan Speed 1 | 1 Bit | 1.2 boolean | CW |
| 14 | AC01 Control_ Fan Speed 2 [DPT_1.002] | 1-Set Fan Speed 2 | 1 Bit | 1.2 boolean | CW |
| 15 | AC01 Control_ Fan Speed 3 [DPT_1.002] | 1-Set Fan Speed 3 | 1 Bit | 1.2 boolean | CW |
| 16 | AC01 Control_ Fan Speed +/- [DPT_1.007] | 0-Dec.;1-Inc. | 1 Bit | 1.7 step | CW |
| 16 | AC01 Control_ Fan Speed +/- [DPT_1.008] | 0-Up;1-Down | 1 Bit | 1.8 up/down | CW |
| 17 | AC01 Control_ Vanes U-D Swing [DPT_1.002] | 0-Stop;1-Swing | 1 Bit | 1.2 boolean | CW |
| 18 | AC01 Control_ Setpoint Temperature [DPT_9.001] | ºC | 2 Bytes | 9.1 temperature (°C) | CW |
| 19 | AC01 Control_ Setpoint Temperature +/- [DPT_1.007] | 0-Dec.;1-Inc. | 1 Bit | 1.7 step | CW |
| 19 | AC01 Control_ Setpoint Temperature +/- [DPT_1.008] | 0-Up;1-Down | 1 Bit | 1.8 up/down | CW |
| 20 | AC01 Control_ Ambient Temperature [DPT_9.001] | ºC | 2 Bytes | 9.1 temperature (°C) | CW |
| 21 | AC01 Control_ Remote Lock [DPT_1.003] | 0-Unlock;1-Lock | 1 Bit | 1.3 enable | CW |
| 22 | AC01 Status_ On/Off [DPT_1.001] | 0-Off;1-On | 1 Bit | 1.1 switch | CRT |
| 23 | AC01 Status_ Operating Mode [DPT_20.102] | 0-Aut;1-Com;2-Stan;3-Eco;4-Pro | 1 Byte | 20.102 HVAC mode | CRT |
| 24 | AC01 Status_ Mode [DPT_20.105] | 0-Aut;1-Hea;3-Coo;9-Fan;14-Dry | 1 Byte | 20.105 HVAC control mode | CRT |
| 25 | AC01 Status_ Mode Cool/Heat [DPT_1.100] | 0-Cool;1-Heat | 1 Bit | 1.100 heating/cooling | CRT |
| 26 | AC01 Status_ Mode Auto [DPT_1.002] | 1-AUTO mode is active | 1 Bit | 1.2 boolean | CRT |
| 27 | AC01 Status_ Mode Heat [DPT_1.002] | 1-HEAT mode is active | 1 Bit | 1.2 boolean | CRT |
| 28 | AC01 Status_ Mode Cool [DPT_1.002] | 1-COOL mode is active | 1 Bit | 1.2 boolean | CRT |
| 29 | AC01 Status_ Mode Fan [DPT_1.002] | 1-FAN mode is active | 1 Bit | 1.2 boolean | CRT |
| 30 | AC01 Status_ Mode Dry [DPT_1.002] | 1-DRY mode is active | 1 Bit | 1.2 boolean | CRT |
| 31 | AC01 Status_ Mode Text [DPT_16.001] | Mode Text | 14 Bytes | 16.1 Character String (ISO 8859-1) | CRT |
| 32 | AC01 Status_ Fan Speed [DPT_5.001] | 50% and 100% || 33%, 66% and 100% | 1 Byte | 5.1 percentage (0..100%) | CRT |
| 32 | AC01 Status_ Fan Speed [DPT_5.010] | Speed values: 1,2 || 1,2,3 | 1 Byte | 5.10 counter pulses (0..255) | CRT |
| 33 | AC01 Status_ Fan Speed Man/Auto [DPT_1.002] | 0-Manual;1-Auto | 1 Bit | 1.2 boolean | CRT |
| 34 | AC01 Status_ Fan Speed 1 [DPT_1.002] | 1-Fan in Speed 1 | 1 Bit | 1.2 boolean | CRT |
| 35 | AC01 Status_ Fan Speed 2 [DPT_1.002] | 1-Fan in Speed 2 | 1 Bit | 1.2 boolean | CRT |
| 36 | AC01 Status_ Fan Speed 3 [DPT_1.002] | 1-Fan in Speed 3 | 1 Bit | 1.2 boolean | CRT |
| 37 | AC01 Status_ Fan Speed Text [DPT_16.001] | Fan Speed Text | 14 Bytes | 16.1 Character String (ISO 8859-1) | CRT |
| 38 | AC01 Status_ Vanes U-D Swing [DPT_1.002] | 0-Stop;1-Swing | 1 Bit | 1.2 boolean | CRT |
| 39 | AC01 Status_ Vanes U-D Text [DPT_16.001] | Vanes Text | 14 Bytes | 16.1 Character String (ISO 8859-1) | CRT |
| 40 | AC01 Status_ AC Setpoint Temperature [DPT_9.001] | ºC | 2 Bytes | 9.1 temperature (°C) | CRT |
| 41 | AC01 Status_ AC Ambient Reference Temperature [DPT_9.001] | ºC | 2 Bytes | 9.1 temperature (°C) | CRT |
| 42 | AC01 Status_ Error/Alarm [DPT_1.005] | 0-No alarm;1-Alarm | 1 Bit | 1.5 alarm | CRT |
| 43 | AC01 Status_ Error Code [2-byte signed value] | Error Code | 2 Bytes | 8.1 pulses difference | CRT |
| 44 | AC01 Status_ Error Text [DPT_16.001] | Error Text | 14 Bytes | 16.1 Character String (ISO 8859-1) | CRT |
| 45 | AC01 Status_ Remote Lock [DPT_1.003] | 0-Unlocked;1-Locked | 1 Bit | 1.3 enable | CRT |
| 46 | AC02 Control_ On/Off [DPT_1.001] | 0-Off;1-On | 1 Bit | 1.1 switch | CW |
| 47 | AC02 Control_ Operating Mode [DPT_20.102] | 0-Aut;1-Com;2-Stan;3-Eco;4-Pro | 1 Byte | 20.102 HVAC mode | CW |
| 48 | AC02 Control_ Mode [DPT_20.105] | 0-Aut;1-Hea;3-Coo;9-Fan;14-Dry | 1 Byte | 20.105 HVAC control mode | CW |
| 49 | AC02 Control_ Mode Cool/Heat [DPT_1.100] | 0-Cool;1-Heat | 1 Bit | 1.100 heating/cooling | CW |
| 50 | AC02 Control_ Mode Auto [DPT_1.002] | 1-Set AUTO mode | 1 Bit | 1.2 boolean | CW |
| 51 | AC02 Control_ Mode Heat [DPT_1.002] | 1-Set HEAT mode | 1 Bit | 1.2 boolean | CW |
| 52 | AC02 Control_ Mode Cool [DPT_1.002] | 1-Set COOL mode | 1 Bit | 1.2 boolean | CW |
| 53 | AC02 Control_ Mode Fan [DPT_1.002] | 1-Set FAN mode | 1 Bit | 1.2 boolean | CW |
| 54 | AC02 Control_ Mode Dry [DPT_1.002] | 1-Set DRY mode | 1 Bit | 1.2 boolean | CW |
| 55 | AC02 Control_ Mode +/- [DPT_1.007] | 0-Dec.;1-Inc. | 1 Bit | 1.7 step | CW |
| 55 | AC02 Control_ Mode +/- [DPT_1.008] | 0-Up;1-Down | 1 Bit | 1.8 up/down | CW |
| 56 | AC02 Control_ Fan Speed [DPT_5.001] | Thresholds: 75% || 50% and 83% | 1 Byte | 5.1 percentage (0..100%) | CW |
| 56 | AC02 Control_ Fan Speed [DPT_5.010] | Speed values: 1,2 || 1,2,3 | 1 Byte | 5.10 counter pulses (0..255) | CW |
| 57 | AC02 Control_ Fan Speed Man/Auto [DPT_1.002] | 0-Manual;1-Auto | 1 Bit | 1.2 boolean | CW |
| 58 | AC02 Control_ Fan Speed 1 [DPT_1.002] | 1-Set Fan Speed 1 | 1 Bit | 1.2 boolean | CW |
| 59 | AC02 Control_ Fan Speed 2 [DPT_1.002] | 1-Set Fan Speed 2 | 1 Bit | 1.2 boolean | CW |
| 60 | AC02 Control_ Fan Speed 3 [DPT_1.002] | 1-Set Fan Speed 3 | 1 Bit | 1.2 boolean | CW |
| 61 | AC02 Control_ Fan Speed +/- [DPT_1.007] | 0-Dec.;1-Inc. | 1 Bit | 1.7 step | CW |
| 61 | AC02 Control_ Fan Speed +/- [DPT_1.008] | 0-Up;1-Down | 1 Bit | 1.8 up/down | CW |
| 62 | AC02 Control_ Vanes U-D Swing [DPT_1.002] | 0-Stop;1-Swing | 1 Bit | 1.2 boolean | CW |
| 63 | AC02 Control_ Setpoint Temperature [DPT_9.001] | ºC | 2 Bytes | 9.1 temperature (°C) | CW |
| 64 | AC02 Control_ Setpoint Temperature +/- [DPT_1.007] | 0-Dec.;1-Inc. | 1 Bit | 1.7 step | CW |
| 64 | AC02 Control_ Setpoint Temperature +/- [DPT_1.008] | 0-Up;1-Down | 1 Bit | 1.8 up/down | CW |
| 65 | AC02 Control_ Ambient Temperature [DPT_9.001] | ºC | 2 Bytes | 9.1 temperature (°C) | CW |
| 66 | AC02 Control_ Remote Lock [DPT_1.003] | 0-Unlock;1-Lock | 1 Bit | 1.3 enable | CW |
| 67 | AC02 Status_ On/Off [DPT_1.001] | 0-Off;1-On | 1 Bit | 1.1 switch | CRT |
| 68 | AC02 Status_ Operating Mode [DPT_20.102] | 0-Aut;1-Com;2-Stan;3-Eco;4-Pro | 1 Byte | 20.102 HVAC mode | CRT |
| 69 | AC02 Status_ Mode [DPT_20.105] | 0-Aut;1-Hea;3-Coo;9-Fan;14-Dry | 1 Byte | 20.105 HVAC control mode | CRT |
| 70 | AC02 Status_ Mode Cool/Heat [DPT_1.100] | 0-Cool;1-Heat | 1 Bit | 1.100 heating/cooling | CRT |
| 71 | AC02 Status_ Mode Auto [DPT_1.002] | 1-AUTO mode is active | 1 Bit | 1.2 boolean | CRT |
| 72 | AC02 Status_ Mode Heat [DPT_1.002] | 1-HEAT mode is active | 1 Bit | 1.2 boolean | CRT |
| 73 | AC02 Status_ Mode Cool [DPT_1.002] | 1-COOL mode is active | 1 Bit | 1.2 boolean | CRT |
| 74 | AC02 Status_ Mode Fan [DPT_1.002] | 1-FAN mode is active | 1 Bit | 1.2 boolean | CRT |
| 75 | AC02 Status_ Mode Dry [DPT_1.002] | 1-DRY mode is active | 1 Bit | 1.2 boolean | CRT |
| 76 | AC02 Status_ Mode Text [DPT_16.001] | Mode Text | 14 Bytes | 16.1 Character String (ISO 8859-1) | CRT |
| 77 | AC02 Status_ Fan Speed [DPT_5.001] | 50% and 100% || 33%, 66% and 100% | 1 Byte | 5.1 percentage (0..100%) | CRT |
| 77 | AC02 Status_ Fan Speed [DPT_5.010] | Speed values: 1,2 || 1,2,3 | 1 Byte | 5.10 counter pulses (0..255) | CRT |
| 78 | AC02 Status_ Fan Speed Man/Auto [DPT_1.002] | 0-Manual;1-Auto | 1 Bit | 1.2 boolean | CRT |
| 79 | AC02 Status_ Fan Speed 1 [DPT_1.002] | 1-Fan in Speed 1 | 1 Bit | 1.2 boolean | CRT |
| 80 | AC02 Status_ Fan Speed 2 [DPT_1.002] | 1-Fan in Speed 2 | 1 Bit | 1.2 boolean | CRT |
| 81 | AC02 Status_ Fan Speed 3 [DPT_1.002] | 1-Fan in Speed 3 | 1 Bit | 1.2 boolean | CRT |
| 82 | AC02 Status_ Fan Speed Text [DPT_16.001] | Fan Speed Text | 14 Bytes | 16.1 Character String (ISO 8859-1) | CRT |
| 83 | AC02 Status_ Vanes U-D Swing [DPT_1.002] | 0-Stop;1-Swing | 1 Bit | 1.2 boolean | CRT |
| 84 | AC02 Status_ Vanes U-D Text [DPT_16.001] | Vanes Text | 14 Bytes | 16.1 Character String (ISO 8859-1) | CRT |
| 85 | AC02 Status_ AC Setpoint Temperature [DPT_9.001] | ºC | 2 Bytes | 9.1 temperature (°C) | CRT |
| 86 | AC02 Status_ AC Ambient Reference Temperature [DPT_9.001] | ºC | 2 Bytes | 9.1 temperature (°C) | CRT |
| 87 | AC02 Status_ Error/Alarm [DPT_1.005] | 0-No alarm;1-Alarm | 1 Bit | 1.5 alarm | CRT |
| 88 | AC02 Status_ Error Code [2-byte signed value] | Error Code | 2 Bytes | 8.1 pulses difference | CRT |
| 89 | AC02 Status_ Error Text [DPT_16.001] | Error Text | 14 Bytes | 16.1 Character String (ISO 8859-1) | CRT |
| 90 | AC02 Status_ Remote Lock [DPT_1.003] | 0-Unlocked;1-Locked | 1 Bit | 1.3 enable | CRT |
| 91 | AC03 Control_ On/Off [DPT_1.001] | 0-Off;1-On | 1 Bit | 1.1 switch | CW |
| 92 | AC03 Control_ Operating Mode [DPT_20.102] | 0-Aut;1-Com;2-Stan;3-Eco;4-Pro | 1 Byte | 20.102 HVAC mode | CW |
| 93 | AC03 Control_ Mode [DPT_20.105] | 0-Aut;1-Hea;3-Coo;9-Fan;14-Dry | 1 Byte | 20.105 HVAC control mode | CW |
| 94 | AC03 Control_ Mode Cool/Heat [DPT_1.100] | 0-Cool;1-Heat | 1 Bit | 1.100 heating/cooling | CW |
| 95 | AC03 Control_ Mode Auto [DPT_1.002] | 1-Set AUTO mode | 1 Bit | 1.2 boolean | CW |
| 96 | AC03 Control_ Mode Heat [DPT_1.002] | 1-Set HEAT mode | 1 Bit | 1.2 boolean | CW |
| 97 | AC03 Control_ Mode Cool [DPT_1.002] | 1-Set COOL mode | 1 Bit | 1.2 boolean | CW |
| 98 | AC03 Control_ Mode Fan [DPT_1.002] | 1-Set FAN mode | 1 Bit | 1.2 boolean | CW |
| 99 | AC03 Control_ Mode Dry [DPT_1.002] | 1-Set DRY mode | 1 Bit | 1.2 boolean | CW |
| 100 | AC03 Control_ Mode +/- [DPT_1.007] | 0-Dec.;1-Inc. | 1 Bit | 1.7 step | CW |
| 100 | AC03 Control_ Mode +/- [DPT_1.008] | 0-Up;1-Down | 1 Bit | 1.8 up/down | CW |
| 101 | AC03 Control_ Fan Speed [DPT_5.001] | Thresholds: 75% || 50% and 83% | 1 Byte | 5.1 percentage (0..100%) | CW |
| 101 | AC03 Control_ Fan Speed [DPT_5.010] | Speed values: 1,2 || 1,2,3 | 1 Byte | 5.10 counter pulses (0..255) | CW |
| 102 | AC03 Control_ Fan Speed Man/Auto [DPT_1.002] | 0-Manual;1-Auto | 1 Bit | 1.2 boolean | CW |
| 103 | AC03 Control_ Fan Speed 1 [DPT_1.002] | 1-Set Fan Speed 1 | 1 Bit | 1.2 boolean | CW |
| 104 | AC03 Control_ Fan Speed 2 [DPT_1.002] | 1-Set Fan Speed 2 | 1 Bit | 1.2 boolean | CW |
| 105 | AC03 Control_ Fan Speed 3 [DPT_1.002] | 1-Set Fan Speed 3 | 1 Bit | 1.2 boolean | CW |
| 106 | AC03 Control_ Fan Speed +/- [DPT_1.007] | 0-Dec.;1-Inc. | 1 Bit | 1.7 step | CW |
| 106 | AC03 Control_ Fan Speed +/- [DPT_1.008] | 0-Up;1-Down | 1 Bit | 1.8 up/down | CW |
| 107 | AC03 Control_ Vanes U-D Swing [DPT_1.002] | 0-Stop;1-Swing | 1 Bit | 1.2 boolean | CW |
| 108 | AC03 Control_ Setpoint Temperature [DPT_9.001] | ºC | 2 Bytes | 9.1 temperature (°C) | CW |
| 109 | AC03 Control_ Setpoint Temperature +/- [DPT_1.007] | 0-Dec.;1-Inc. | 1 Bit | 1.7 step | CW |
| 109 | AC03 Control_ Setpoint Temperature +/- [DPT_1.008] | 0-Up;1-Down | 1 Bit | 1.8 up/down | CW |
| 110 | AC03 Control_ Ambient Temperature [DPT_9.001] | ºC | 2 Bytes | 9.1 temperature (°C) | CW |
| 111 | AC03 Control_ Remote Lock [DPT_1.003] | 0-Unlock;1-Lock | 1 Bit | 1.3 enable | CW |
| 112 | AC03 Status_ On/Off [DPT_1.001] | 0-Off;1-On | 1 Bit | 1.1 switch | CRT |
| 113 | AC03 Status_ Operating Mode [DPT_20.102] | 0-Aut;1-Com;2-Stan;3-Eco;4-Pro | 1 Byte | 20.102 HVAC mode | CRT |
| 114 | AC03 Status_ Mode [DPT_20.105] | 0-Aut;1-Hea;3-Coo;9-Fan;14-Dry | 1 Byte | 20.105 HVAC control mode | CRT |
| 115 | AC03 Status_ Mode Cool/Heat [DPT_1.100] | 0-Cool;1-Heat | 1 Bit | 1.100 heating/cooling | CRT |
| 116 | AC03 Status_ Mode Auto [DPT_1.002] | 1-AUTO mode is active | 1 Bit | 1.2 boolean | CRT |
| 117 | AC03 Status_ Mode Heat [DPT_1.002] | 1-HEAT mode is active | 1 Bit | 1.2 boolean | CRT |
| 118 | AC03 Status_ Mode Cool [DPT_1.002] | 1-COOL mode is active | 1 Bit | 1.2 boolean | CRT |
| 119 | AC03 Status_ Mode Fan [DPT_1.002] | 1-FAN mode is active | 1 Bit | 1.2 boolean | CRT |
| 120 | AC03 Status_ Mode Dry [DPT_1.002] | 1-DRY mode is active | 1 Bit | 1.2 boolean | CRT |
| 121 | AC03 Status_ Mode Text [DPT_16.001] | Mode Text | 14 Bytes | 16.1 Character String (ISO 8859-1) | CRT |
| 122 | AC03 Status_ Fan Speed [DPT_5.001] | 50% and 100% || 33%, 66% and 100% | 1 Byte | 5.1 percentage (0..100%) | CRT |
| 122 | AC03 Status_ Fan Speed [DPT_5.010] | Speed values: 1,2 || 1,2,3 | 1 Byte | 5.10 counter pulses (0..255) | CRT |
| 123 | AC03 Status_ Fan Speed Man/Auto [DPT_1.002] | 0-Manual;1-Auto | 1 Bit | 1.2 boolean | CRT |
| 124 | AC03 Status_ Fan Speed 1 [DPT_1.002] | 1-Fan in Speed 1 | 1 Bit | 1.2 boolean | CRT |
| 125 | AC03 Status_ Fan Speed 2 [DPT_1.002] | 1-Fan in Speed 2 | 1 Bit | 1.2 boolean | CRT |
| 126 | AC03 Status_ Fan Speed 3 [DPT_1.002] | 1-Fan in Speed 3 | 1 Bit | 1.2 boolean | CRT |
| 127 | AC03 Status_ Fan Speed Text [DPT_16.001] | Fan Speed Text | 14 Bytes | 16.1 Character String (ISO 8859-1) | CRT |
| 128 | AC03 Status_ Vanes U-D Swing [DPT_1.002] | 0-Stop;1-Swing | 1 Bit | 1.2 boolean | CRT |
| 129 | AC03 Status_ Vanes U-D Text [DPT_16.001] | Vanes Text | 14 Bytes | 16.1 Character String (ISO 8859-1) | CRT |
| 130 | AC03 Status_ AC Setpoint Temperature [DPT_9.001] | ºC | 2 Bytes | 9.1 temperature (°C) | CRT |
| 131 | AC03 Status_ AC Ambient Reference Temperature [DPT_9.001] | ºC | 2 Bytes | 9.1 temperature (°C) | CRT |
| 132 | AC03 Status_ Error/Alarm [DPT_1.005] | 0-No alarm;1-Alarm | 1 Bit | 1.5 alarm | CRT |
| 133 | AC03 Status_ Error Code [2-byte signed value] | Error Code | 2 Bytes | 8.1 pulses difference | CRT |
| 134 | AC03 Status_ Error Text [DPT_16.001] | Error Text | 14 Bytes | 16.1 Character String (ISO 8859-1) | CRT |
| 135 | AC03 Status_ Remote Lock [DPT_1.003] | 0-Unlocked;1-Locked | 1 Bit | 1.3 enable | CRT |
| 136 | AC04 Control_ On/Off [DPT_1.001] | 0-Off;1-On | 1 Bit | 1.1 switch | CW |
| 137 | AC04 Control_ Operating Mode [DPT_20.102] | 0-Aut;1-Com;2-Stan;3-Eco;4-Pro | 1 Byte | 20.102 HVAC mode | CW |
| 138 | AC04 Control_ Mode [DPT_20.105] | 0-Aut;1-Hea;3-Coo;9-Fan;14-Dry | 1 Byte | 20.105 HVAC control mode | CW |
| 139 | AC04 Control_ Mode Cool/Heat [DPT_1.100] | 0-Cool;1-Heat | 1 Bit | 1.100 heating/cooling | CW |
| 140 | AC04 Control_ Mode Auto [DPT_1.002] | 1-Set AUTO mode | 1 Bit | 1.2 boolean | CW |
| 141 | AC04 Control_ Mode Heat [DPT_1.002] | 1-Set HEAT mode | 1 Bit | 1.2 boolean | CW |
| 142 | AC04 Control_ Mode Cool [DPT_1.002] | 1-Set COOL mode | 1 Bit | 1.2 boolean | CW |
| 143 | AC04 Control_ Mode Fan [DPT_1.002] | 1-Set FAN mode | 1 Bit | 1.2 boolean | CW |
| 144 | AC04 Control_ Mode Dry [DPT_1.002] | 1-Set DRY mode | 1 Bit | 1.2 boolean | CW |
| 145 | AC04 Control_ Mode +/- [DPT_1.007] | 0-Dec.;1-Inc. | 1 Bit | 1.7 step | CW |
| 145 | AC04 Control_ Mode +/- [DPT_1.008] | 0-Up;1-Down | 1 Bit | 1.8 up/down | CW |
| 146 | AC04 Control_ Fan Speed [DPT_5.001] | Thresholds: 75% || 50% and 83% | 1 Byte | 5.1 percentage (0..100%) | CW |
| 146 | AC04 Control_ Fan Speed [DPT_5.010] | Speed values: 1,2 || 1,2,3 | 1 Byte | 5.10 counter pulses (0..255) | CW |
| 147 | AC04 Control_ Fan Speed Man/Auto [DPT_1.002] | 0-Manual;1-Auto | 1 Bit | 1.2 boolean | CW |
| 148 | AC04 Control_ Fan Speed 1 [DPT_1.002] | 1-Set Fan Speed 1 | 1 Bit | 1.2 boolean | CW |
| 149 | AC04 Control_ Fan Speed 2 [DPT_1.002] | 1-Set Fan Speed 2 | 1 Bit | 1.2 boolean | CW |
| 150 | AC04 Control_ Fan Speed 3 [DPT_1.002] | 1-Set Fan Speed 3 | 1 Bit | 1.2 boolean | CW |
| 151 | AC04 Control_ Fan Speed +/- [DPT_1.007] | 0-Dec.;1-Inc. | 1 Bit | 1.7 step | CW |
| 151 | AC04 Control_ Fan Speed +/- [DPT_1.008] | 0-Up;1-Down | 1 Bit | 1.8 up/down | CW |
| 152 | AC04 Control_ Vanes U-D Swing [DPT_1.002] | 0-Stop;1-Swing | 1 Bit | 1.2 boolean | CW |
| 153 | AC04 Control_ Setpoint Temperature [DPT_9.001] | ºC | 2 Bytes | 9.1 temperature (°C) | CW |
| 154 | AC04 Control_ Setpoint Temperature +/- [DPT_1.007] | 0-Dec.;1-Inc. | 1 Bit | 1.7 step | CW |
| 154 | AC04 Control_ Setpoint Temperature +/- [DPT_1.008] | 0-Up;1-Down | 1 Bit | 1.8 up/down | CW |
| 155 | AC04 Control_ Ambient Temperature [DPT_9.001] | ºC | 2 Bytes | 9.1 temperature (°C) | CW |
| 156 | AC04 Control_ Remote Lock [DPT_1.003] | 0-Unlock;1-Lock | 1 Bit | 1.3 enable | CW |
| 157 | AC04 Status_ On/Off [DPT_1.001] | 0-Off;1-On | 1 Bit | 1.1 switch | CRT |
| 158 | AC04 Status_ Operating Mode [DPT_20.102] | 0-Aut;1-Com;2-Stan;3-Eco;4-Pro | 1 Byte | 20.102 HVAC mode | CRT |
| 159 | AC04 Status_ Mode [DPT_20.105] | 0-Aut;1-Hea;3-Coo;9-Fan;14-Dry | 1 Byte | 20.105 HVAC control mode | CRT |
| 160 | AC04 Status_ Mode Cool/Heat [DPT_1.100] | 0-Cool;1-Heat | 1 Bit | 1.100 heating/cooling | CRT |
| 161 | AC04 Status_ Mode Auto [DPT_1.002] | 1-AUTO mode is active | 1 Bit | 1.2 boolean | CRT |
| 162 | AC04 Status_ Mode Heat [DPT_1.002] | 1-HEAT mode is active | 1 Bit | 1.2 boolean | CRT |
| 163 | AC04 Status_ Mode Cool [DPT_1.002] | 1-COOL mode is active | 1 Bit | 1.2 boolean | CRT |
| 164 | AC04 Status_ Mode Fan [DPT_1.002] | 1-FAN mode is active | 1 Bit | 1.2 boolean | CRT |
| 165 | AC04 Status_ Mode Dry [DPT_1.002] | 1-DRY mode is active | 1 Bit | 1.2 boolean | CRT |
| 166 | AC04 Status_ Mode Text [DPT_16.001] | Mode Text | 14 Bytes | 16.1 Character String (ISO 8859-1) | CRT |
| 167 | AC04 Status_ Fan Speed [DPT_5.001] | 50% and 100% || 33%, 66% and 100% | 1 Byte | 5.1 percentage (0..100%) | CRT |
| 167 | AC04 Status_ Fan Speed [DPT_5.010] | Speed values: 1,2 || 1,2,3 | 1 Byte | 5.10 counter pulses (0..255) | CRT |
| 168 | AC04 Status_ Fan Speed Man/Auto [DPT_1.002] | 0-Manual;1-Auto | 1 Bit | 1.2 boolean | CRT |
| 169 | AC04 Status_ Fan Speed 1 [DPT_1.002] | 1-Fan in Speed 1 | 1 Bit | 1.2 boolean | CRT |
| 170 | AC04 Status_ Fan Speed 2 [DPT_1.002] | 1-Fan in Speed 2 | 1 Bit | 1.2 boolean | CRT |
| 171 | AC04 Status_ Fan Speed 3 [DPT_1.002] | 1-Fan in Speed 3 | 1 Bit | 1.2 boolean | CRT |
| 172 | AC04 Status_ Fan Speed Text [DPT_16.001] | Fan Speed Text | 14 Bytes | 16.1 Character String (ISO 8859-1) | CRT |
| 173 | AC04 Status_ Vanes U-D Swing [DPT_1.002] | 0-Stop;1-Swing | 1 Bit | 1.2 boolean | CRT |
| 174 | AC04 Status_ Vanes U-D Text [DPT_16.001] | Vanes Text | 14 Bytes | 16.1 Character String (ISO 8859-1) | CRT |
| 175 | AC04 Status_ AC Setpoint Temperature [DPT_9.001] | ºC | 2 Bytes | 9.1 temperature (°C) | CRT |
| 176 | AC04 Status_ AC Ambient Reference Temperature [DPT_9.001] | ºC | 2 Bytes | 9.1 temperature (°C) | CRT |
| 177 | AC04 Status_ Error/Alarm [DPT_1.005] | 0-No alarm;1-Alarm | 1 Bit | 1.5 alarm | CRT |
| 178 | AC04 Status_ Error Code [2-byte signed value] | Error Code | 2 Bytes | 8.1 pulses difference | CRT |
| 179 | AC04 Status_ Error Text [DPT_16.001] | Error Text | 14 Bytes | 16.1 Character String (ISO 8859-1) | CRT |
| 180 | AC04 Status_ Remote Lock [DPT_1.003] | 0-Unlocked;1-Locked | 1 Bit | 1.3 enable | CRT |
| 181 | AC05 Control_ On/Off [DPT_1.001] | 0-Off;1-On | 1 Bit | 1.1 switch | CW |
| 182 | AC05 Control_ Operating Mode [DPT_20.102] | 0-Aut;1-Com;2-Stan;3-Eco;4-Pro | 1 Byte | 20.102 HVAC mode | CW |
| 183 | AC05 Control_ Mode [DPT_20.105] | 0-Aut;1-Hea;3-Coo;9-Fan;14-Dry | 1 Byte | 20.105 HVAC control mode | CW |
| 184 | AC05 Control_ Mode Cool/Heat [DPT_1.100] | 0-Cool;1-Heat | 1 Bit | 1.100 heating/cooling | CW |
| 185 | AC05 Control_ Mode Auto [DPT_1.002] | 1-Set AUTO mode | 1 Bit | 1.2 boolean | CW |
| 186 | AC05 Control_ Mode Heat [DPT_1.002] | 1-Set HEAT mode | 1 Bit | 1.2 boolean | CW |
| 187 | AC05 Control_ Mode Cool [DPT_1.002] | 1-Set COOL mode | 1 Bit | 1.2 boolean | CW |
| 188 | AC05 Control_ Mode Fan [DPT_1.002] | 1-Set FAN mode | 1 Bit | 1.2 boolean | CW |
| 189 | AC05 Control_ Mode Dry [DPT_1.002] | 1-Set DRY mode | 1 Bit | 1.2 boolean | CW |
| 190 | AC05 Control_ Mode +/- [DPT_1.007] | 0-Dec.;1-Inc. | 1 Bit | 1.7 step | CW |
| 190 | AC05 Control_ Mode +/- [DPT_1.008] | 0-Up;1-Down | 1 Bit | 1.8 up/down | CW |
| 191 | AC05 Control_ Fan Speed [DPT_5.001] | Thresholds: 75% || 50% and 83% | 1 Byte | 5.1 percentage (0..100%) | CW |
| 191 | AC05 Control_ Fan Speed [DPT_5.010] | Speed values: 1,2 || 1,2,3 | 1 Byte | 5.10 counter pulses (0..255) | CW |
| 192 | AC05 Control_ Fan Speed Man/Auto [DPT_1.002] | 0-Manual;1-Auto | 1 Bit | 1.2 boolean | CW |
| 193 | AC05 Control_ Fan Speed 1 [DPT_1.002] | 1-Set Fan Speed 1 | 1 Bit | 1.2 boolean | CW |
| 194 | AC05 Control_ Fan Speed 2 [DPT_1.002] | 1-Set Fan Speed 2 | 1 Bit | 1.2 boolean | CW |
| 195 | AC05 Control_ Fan Speed 3 [DPT_1.002] | 1-Set Fan Speed 3 | 1 Bit | 1.2 boolean | CW |
| 196 | AC05 Control_ Fan Speed +/- [DPT_1.007] | 0-Dec.;1-Inc. | 1 Bit | 1.7 step | CW |
| 196 | AC05 Control_ Fan Speed +/- [DPT_1.008] | 0-Up;1-Down | 1 Bit | 1.8 up/down | CW |
| 197 | AC05 Control_ Vanes U-D Swing [DPT_1.002] | 0-Stop;1-Swing | 1 Bit | 1.2 boolean | CW |
| 198 | AC05 Control_ Setpoint Temperature [DPT_9.001] | ºC | 2 Bytes | 9.1 temperature (°C) | CW |
| 199 | AC05 Control_ Setpoint Temperature +/- [DPT_1.007] | 0-Dec.;1-Inc. | 1 Bit | 1.7 step | CW |
| 199 | AC05 Control_ Setpoint Temperature +/- [DPT_1.008] | 0-Up;1-Down | 1 Bit | 1.8 up/down | CW |
| 200 | AC05 Control_ Ambient Temperature [DPT_9.001] | ºC | 2 Bytes | 9.1 temperature (°C) | CW |
| 201 | AC05 Control_ Remote Lock [DPT_1.003] | 0-Unlock;1-Lock | 1 Bit | 1.3 enable | CW |
| 202 | AC05 Status_ On/Off [DPT_1.001] | 0-Off;1-On | 1 Bit | 1.1 switch | CRT |
| 203 | AC05 Status_ Operating Mode [DPT_20.102] | 0-Aut;1-Com;2-Stan;3-Eco;4-Pro | 1 Byte | 20.102 HVAC mode | CRT |
| 204 | AC05 Status_ Mode [DPT_20.105] | 0-Aut;1-Hea;3-Coo;9-Fan;14-Dry | 1 Byte | 20.105 HVAC control mode | CRT |
| 205 | AC05 Status_ Mode Cool/Heat [DPT_1.100] | 0-Cool;1-Heat | 1 Bit | 1.100 heating/cooling | CRT |
| 206 | AC05 Status_ Mode Auto [DPT_1.002] | 1-AUTO mode is active | 1 Bit | 1.2 boolean | CRT |
| 207 | AC05 Status_ Mode Heat [DPT_1.002] | 1-HEAT mode is active | 1 Bit | 1.2 boolean | CRT |
| 208 | AC05 Status_ Mode Cool [DPT_1.002] | 1-COOL mode is active | 1 Bit | 1.2 boolean | CRT |
| 209 | AC05 Status_ Mode Fan [DPT_1.002] | 1-FAN mode is active | 1 Bit | 1.2 boolean | CRT |
| 210 | AC05 Status_ Mode Dry [DPT_1.002] | 1-DRY mode is active | 1 Bit | 1.2 boolean | CRT |
| 211 | AC05 Status_ Mode Text [DPT_16.001] | Mode Text | 14 Bytes | 16.1 Character String (ISO 8859-1) | CRT |
| 212 | AC05 Status_ Fan Speed [DPT_5.001] | 50% and 100% || 33%, 66% and 100% | 1 Byte | 5.1 percentage (0..100%) | CRT |
| 212 | AC05 Status_ Fan Speed [DPT_5.010] | Speed values: 1,2 || 1,2,3 | 1 Byte | 5.10 counter pulses (0..255) | CRT |
| 213 | AC05 Status_ Fan Speed Man/Auto [DPT_1.002] | 0-Manual;1-Auto | 1 Bit | 1.2 boolean | CRT |
| 214 | AC05 Status_ Fan Speed 1 [DPT_1.002] | 1-Fan in Speed 1 | 1 Bit | 1.2 boolean | CRT |
| 215 | AC05 Status_ Fan Speed 2 [DPT_1.002] | 1-Fan in Speed 2 | 1 Bit | 1.2 boolean | CRT |
| 216 | AC05 Status_ Fan Speed 3 [DPT_1.002] | 1-Fan in Speed 3 | 1 Bit | 1.2 boolean | CRT |
| 217 | AC05 Status_ Fan Speed Text [DPT_16.001] | Fan Speed Text | 14 Bytes | 16.1 Character String (ISO 8859-1) | CRT |
| 218 | AC05 Status_ Vanes U-D Swing [DPT_1.002] | 0-Stop;1-Swing | 1 Bit | 1.2 boolean | CRT |
| 219 | AC05 Status_ Vanes U-D Text [DPT_16.001] | Vanes Text | 14 Bytes | 16.1 Character String (ISO 8859-1) | CRT |
| 220 | AC05 Status_ AC Setpoint Temperature [DPT_9.001] | ºC | 2 Bytes | 9.1 temperature (°C) | CRT |
| 221 | AC05 Status_ AC Ambient Reference Temperature [DPT_9.001] | ºC | 2 Bytes | 9.1 temperature (°C) | CRT |
| 222 | AC05 Status_ Error/Alarm [DPT_1.005] | 0-No alarm;1-Alarm | 1 Bit | 1.5 alarm | CRT |
| 223 | AC05 Status_ Error Code [2-byte signed value] | Error Code | 2 Bytes | 8.1 pulses difference | CRT |
| 224 | AC05 Status_ Error Text [DPT_16.001] | Error Text | 14 Bytes | 16.1 Character String (ISO 8859-1) | CRT |
| 225 | AC05 Status_ Remote Lock [DPT_1.003] | 0-Unlocked;1-Locked | 1 Bit | 1.3 enable | CRT |
| 226 | AC06 Control_ On/Off [DPT_1.001] | 0-Off;1-On | 1 Bit | 1.1 switch | CW |
| 227 | AC06 Control_ Operating Mode [DPT_20.102] | 0-Aut;1-Com;2-Stan;3-Eco;4-Pro | 1 Byte | 20.102 HVAC mode | CW |
| 228 | AC06 Control_ Mode [DPT_20.105] | 0-Aut;1-Hea;3-Coo;9-Fan;14-Dry | 1 Byte | 20.105 HVAC control mode | CW |
| 229 | AC06 Control_ Mode Cool/Heat [DPT_1.100] | 0-Cool;1-Heat | 1 Bit | 1.100 heating/cooling | CW |
| 230 | AC06 Control_ Mode Auto [DPT_1.002] | 1-Set AUTO mode | 1 Bit | 1.2 boolean | CW |
| 231 | AC06 Control_ Mode Heat [DPT_1.002] | 1-Set HEAT mode | 1 Bit | 1.2 boolean | CW |
| 232 | AC06 Control_ Mode Cool [DPT_1.002] | 1-Set COOL mode | 1 Bit | 1.2 boolean | CW |
| 233 | AC06 Control_ Mode Fan [DPT_1.002] | 1-Set FAN mode | 1 Bit | 1.2 boolean | CW |
| 234 | AC06 Control_ Mode Dry [DPT_1.002] | 1-Set DRY mode | 1 Bit | 1.2 boolean | CW |
| 235 | AC06 Control_ Mode +/- [DPT_1.007] | 0-Dec.;1-Inc. | 1 Bit | 1.7 step | CW |
| 235 | AC06 Control_ Mode +/- [DPT_1.008] | 0-Up;1-Down | 1 Bit | 1.8 up/down | CW |
| 236 | AC06 Control_ Fan Speed [DPT_5.001] | Thresholds: 75% || 50% and 83% | 1 Byte | 5.1 percentage (0..100%) | CW |
| 236 | AC06 Control_ Fan Speed [DPT_5.010] | Speed values: 1,2 || 1,2,3 | 1 Byte | 5.10 counter pulses (0..255) | CW |
| 237 | AC06 Control_ Fan Speed Man/Auto [DPT_1.002] | 0-Manual;1-Auto | 1 Bit | 1.2 boolean | CW |
| 238 | AC06 Control_ Fan Speed 1 [DPT_1.002] | 1-Set Fan Speed 1 | 1 Bit | 1.2 boolean | CW |
| 239 | AC06 Control_ Fan Speed 2 [DPT_1.002] | 1-Set Fan Speed 2 | 1 Bit | 1.2 boolean | CW |
| 240 | AC06 Control_ Fan Speed 3 [DPT_1.002] | 1-Set Fan Speed 3 | 1 Bit | 1.2 boolean | CW |
| 241 | AC06 Control_ Fan Speed +/- [DPT_1.007] | 0-Dec.;1-Inc. | 1 Bit | 1.7 step | CW |
| 241 | AC06 Control_ Fan Speed +/- [DPT_1.008] | 0-Up;1-Down | 1 Bit | 1.8 up/down | CW |
| 242 | AC06 Control_ Vanes U-D Swing [DPT_1.002] | 0-Stop;1-Swing | 1 Bit | 1.2 boolean | CW |
| 243 | AC06 Control_ Setpoint Temperature [DPT_9.001] | ºC | 2 Bytes | 9.1 temperature (°C) | CW |
| 244 | AC06 Control_ Setpoint Temperature +/- [DPT_1.007] | 0-Dec.;1-Inc. | 1 Bit | 1.7 step | CW |
| 244 | AC06 Control_ Setpoint Temperature +/- [DPT_1.008] | 0-Up;1-Down | 1 Bit | 1.8 up/down | CW |
| 245 | AC06 Control_ Ambient Temperature [DPT_9.001] | ºC | 2 Bytes | 9.1 temperature (°C) | CW |
| 246 | AC06 Control_ Remote Lock [DPT_1.003] | 0-Unlock;1-Lock | 1 Bit | 1.3 enable | CW |
| 247 | AC06 Status_ On/Off [DPT_1.001] | 0-Off;1-On | 1 Bit | 1.1 switch | CRT |
| 248 | AC06 Status_ Operating Mode [DPT_20.102] | 0-Aut;1-Com;2-Stan;3-Eco;4-Pro | 1 Byte | 20.102 HVAC mode | CRT |
| 249 | AC06 Status_ Mode [DPT_20.105] | 0-Aut;1-Hea;3-Coo;9-Fan;14-Dry | 1 Byte | 20.105 HVAC control mode | CRT |
| 250 | AC06 Status_ Mode Cool/Heat [DPT_1.100] | 0-Cool;1-Heat | 1 Bit | 1.100 heating/cooling | CRT |
| 251 | AC06 Status_ Mode Auto [DPT_1.002] | 1-AUTO mode is active | 1 Bit | 1.2 boolean | CRT |
| 252 | AC06 Status_ Mode Heat [DPT_1.002] | 1-HEAT mode is active | 1 Bit | 1.2 boolean | CRT |
| 253 | AC06 Status_ Mode Cool [DPT_1.002] | 1-COOL mode is active | 1 Bit | 1.2 boolean | CRT |
| 254 | AC06 Status_ Mode Fan [DPT_1.002] | 1-FAN mode is active | 1 Bit | 1.2 boolean | CRT |
| 255 | AC06 Status_ Mode Dry [DPT_1.002] | 1-DRY mode is active | 1 Bit | 1.2 boolean | CRT |
| 256 | AC06 Status_ Mode Text [DPT_16.001] | Mode Text | 14 Bytes | 16.1 Character String (ISO 8859-1) | CRT |
| 257 | AC06 Status_ Fan Speed [DPT_5.001] | 50% and 100% || 33%, 66% and 100% | 1 Byte | 5.1 percentage (0..100%) | CRT |
| 257 | AC06 Status_ Fan Speed [DPT_5.010] | Speed values: 1,2 || 1,2,3 | 1 Byte | 5.10 counter pulses (0..255) | CRT |
| 258 | AC06 Status_ Fan Speed Man/Auto [DPT_1.002] | 0-Manual;1-Auto | 1 Bit | 1.2 boolean | CRT |
| 259 | AC06 Status_ Fan Speed 1 [DPT_1.002] | 1-Fan in Speed 1 | 1 Bit | 1.2 boolean | CRT |
| 260 | AC06 Status_ Fan Speed 2 [DPT_1.002] | 1-Fan in Speed 2 | 1 Bit | 1.2 boolean | CRT |
| 261 | AC06 Status_ Fan Speed 3 [DPT_1.002] | 1-Fan in Speed 3 | 1 Bit | 1.2 boolean | CRT |
| 262 | AC06 Status_ Fan Speed Text [DPT_16.001] | Fan Speed Text | 14 Bytes | 16.1 Character String (ISO 8859-1) | CRT |
| 263 | AC06 Status_ Vanes U-D Swing [DPT_1.002] | 0-Stop;1-Swing | 1 Bit | 1.2 boolean | CRT |
| 264 | AC06 Status_ Vanes U-D Text [DPT_16.001] | Vanes Text | 14 Bytes | 16.1 Character String (ISO 8859-1) | CRT |
| 265 | AC06 Status_ AC Setpoint Temperature [DPT_9.001] | ºC | 2 Bytes | 9.1 temperature (°C) | CRT |
| 266 | AC06 Status_ AC Ambient Reference Temperature [DPT_9.001] | ºC | 2 Bytes | 9.1 temperature (°C) | CRT |
| 267 | AC06 Status_ Error/Alarm [DPT_1.005] | 0-No alarm;1-Alarm | 1 Bit | 1.5 alarm | CRT |
| 268 | AC06 Status_ Error Code [2-byte signed value] | Error Code | 2 Bytes | 8.1 pulses difference | CRT |
| 269 | AC06 Status_ Error Text [DPT_16.001] | Error Text | 14 Bytes | 16.1 Character String (ISO 8859-1) | CRT |
| 270 | AC06 Status_ Remote Lock [DPT_1.003] | 0-Unlocked;1-Locked | 1 Bit | 1.3 enable | CRT |
| 271 | AC07 Control_ On/Off [DPT_1.001] | 0-Off;1-On | 1 Bit | 1.1 switch | CW |
| 272 | AC07 Control_ Operating Mode [DPT_20.102] | 0-Aut;1-Com;2-Stan;3-Eco;4-Pro | 1 Byte | 20.102 HVAC mode | CW |
| 273 | AC07 Control_ Mode [DPT_20.105] | 0-Aut;1-Hea;3-Coo;9-Fan;14-Dry | 1 Byte | 20.105 HVAC control mode | CW |
| 274 | AC07 Control_ Mode Cool/Heat [DPT_1.100] | 0-Cool;1-Heat | 1 Bit | 1.100 heating/cooling | CW |
| 275 | AC07 Control_ Mode Auto [DPT_1.002] | 1-Set AUTO mode | 1 Bit | 1.2 boolean | CW |
| 276 | AC07 Control_ Mode Heat [DPT_1.002] | 1-Set HEAT mode | 1 Bit | 1.2 boolean | CW |
| 277 | AC07 Control_ Mode Cool [DPT_1.002] | 1-Set COOL mode | 1 Bit | 1.2 boolean | CW |
| 278 | AC07 Control_ Mode Fan [DPT_1.002] | 1-Set FAN mode | 1 Bit | 1.2 boolean | CW |
| 279 | AC07 Control_ Mode Dry [DPT_1.002] | 1-Set DRY mode | 1 Bit | 1.2 boolean | CW |
| 280 | AC07 Control_ Mode +/- [DPT_1.007] | 0-Dec.;1-Inc. | 1 Bit | 1.7 step | CW |
| 280 | AC07 Control_ Mode +/- [DPT_1.008] | 0-Up;1-Down | 1 Bit | 1.8 up/down | CW |
| 281 | AC07 Control_ Fan Speed [DPT_5.001] | Thresholds: 75% || 50% and 83% | 1 Byte | 5.1 percentage (0..100%) | CW |
| 281 | AC07 Control_ Fan Speed [DPT_5.010] | Speed values: 1,2 || 1,2,3 | 1 Byte | 5.10 counter pulses (0..255) | CW |
| 282 | AC07 Control_ Fan Speed Man/Auto [DPT_1.002] | 0-Manual;1-Auto | 1 Bit | 1.2 boolean | CW |
| 283 | AC07 Control_ Fan Speed 1 [DPT_1.002] | 1-Set Fan Speed 1 | 1 Bit | 1.2 boolean | CW |
| 284 | AC07 Control_ Fan Speed 2 [DPT_1.002] | 1-Set Fan Speed 2 | 1 Bit | 1.2 boolean | CW |
| 285 | AC07 Control_ Fan Speed 3 [DPT_1.002] | 1-Set Fan Speed 3 | 1 Bit | 1.2 boolean | CW |
| 286 | AC07 Control_ Fan Speed +/- [DPT_1.007] | 0-Dec.;1-Inc. | 1 Bit | 1.7 step | CW |
| 286 | AC07 Control_ Fan Speed +/- [DPT_1.008] | 0-Up;1-Down | 1 Bit | 1.8 up/down | CW |
| 287 | AC07 Control_ Vanes U-D Swing [DPT_1.002] | 0-Stop;1-Swing | 1 Bit | 1.2 boolean | CW |
| 288 | AC07 Control_ Setpoint Temperature [DPT_9.001] | ºC | 2 Bytes | 9.1 temperature (°C) | CW |
| 289 | AC07 Control_ Setpoint Temperature +/- [DPT_1.007] | 0-Dec.;1-Inc. | 1 Bit | 1.7 step | CW |
| 289 | AC07 Control_ Setpoint Temperature +/- [DPT_1.008] | 0-Up;1-Down | 1 Bit | 1.8 up/down | CW |
| 290 | AC07 Control_ Ambient Temperature [DPT_9.001] | ºC | 2 Bytes | 9.1 temperature (°C) | CW |
| 291 | AC07 Control_ Remote Lock [DPT_1.003] | 0-Unlock;1-Lock | 1 Bit | 1.3 enable | CW |
| 292 | AC07 Status_ On/Off [DPT_1.001] | 0-Off;1-On | 1 Bit | 1.1 switch | CRT |
| 293 | AC07 Status_ Operating Mode [DPT_20.102] | 0-Aut;1-Com;2-Stan;3-Eco;4-Pro | 1 Byte | 20.102 HVAC mode | CRT |
| 294 | AC07 Status_ Mode [DPT_20.105] | 0-Aut;1-Hea;3-Coo;9-Fan;14-Dry | 1 Byte | 20.105 HVAC control mode | CRT |
| 295 | AC07 Status_ Mode Cool/Heat [DPT_1.100] | 0-Cool;1-Heat | 1 Bit | 1.100 heating/cooling | CRT |
| 296 | AC07 Status_ Mode Auto [DPT_1.002] | 1-AUTO mode is active | 1 Bit | 1.2 boolean | CRT |
| 297 | AC07 Status_ Mode Heat [DPT_1.002] | 1-HEAT mode is active | 1 Bit | 1.2 boolean | CRT |
| 298 | AC07 Status_ Mode Cool [DPT_1.002] | 1-COOL mode is active | 1 Bit | 1.2 boolean | CRT |
| 299 | AC07 Status_ Mode Fan [DPT_1.002] | 1-FAN mode is active | 1 Bit | 1.2 boolean | CRT |
| 300 | AC07 Status_ Mode Dry [DPT_1.002] | 1-DRY mode is active | 1 Bit | 1.2 boolean | CRT |
| 301 | AC07 Status_ Mode Text [DPT_16.001] | Mode Text | 14 Bytes | 16.1 Character String (ISO 8859-1) | CRT |
| 302 | AC07 Status_ Fan Speed [DPT_5.001] | 50% and 100% || 33%, 66% and 100% | 1 Byte | 5.1 percentage (0..100%) | CRT |
| 302 | AC07 Status_ Fan Speed [DPT_5.010] | Speed values: 1,2 || 1,2,3 | 1 Byte | 5.10 counter pulses (0..255) | CRT |
| 303 | AC07 Status_ Fan Speed Man/Auto [DPT_1.002] | 0-Manual;1-Auto | 1 Bit | 1.2 boolean | CRT |
| 304 | AC07 Status_ Fan Speed 1 [DPT_1.002] | 1-Fan in Speed 1 | 1 Bit | 1.2 boolean | CRT |
| 305 | AC07 Status_ Fan Speed 2 [DPT_1.002] | 1-Fan in Speed 2 | 1 Bit | 1.2 boolean | CRT |
| 306 | AC07 Status_ Fan Speed 3 [DPT_1.002] | 1-Fan in Speed 3 | 1 Bit | 1.2 boolean | CRT |
| 307 | AC07 Status_ Fan Speed Text [DPT_16.001] | Fan Speed Text | 14 Bytes | 16.1 Character String (ISO 8859-1) | CRT |
| 308 | AC07 Status_ Vanes U-D Swing [DPT_1.002] | 0-Stop;1-Swing | 1 Bit | 1.2 boolean | CRT |
| 309 | AC07 Status_ Vanes U-D Text [DPT_16.001] | Vanes Text | 14 Bytes | 16.1 Character String (ISO 8859-1) | CRT |
| 310 | AC07 Status_ AC Setpoint Temperature [DPT_9.001] | ºC | 2 Bytes | 9.1 temperature (°C) | CRT |
| 311 | AC07 Status_ AC Ambient Reference Temperature [DPT_9.001] | ºC | 2 Bytes | 9.1 temperature (°C) | CRT |
| 312 | AC07 Status_ Error/Alarm [DPT_1.005] | 0-No alarm;1-Alarm | 1 Bit | 1.5 alarm | CRT |
| 313 | AC07 Status_ Error Code [2-byte signed value] | Error Code | 2 Bytes | 8.1 pulses difference | CRT |
| 314 | AC07 Status_ Error Text [DPT_16.001] | Error Text | 14 Bytes | 16.1 Character String (ISO 8859-1) | CRT |
| 315 | AC07 Status_ Remote Lock [DPT_1.003] | 0-Unlocked;1-Locked | 1 Bit | 1.3 enable | CRT |
| 316 | AC08 Control_ On/Off [DPT_1.001] | 0-Off;1-On | 1 Bit | 1.1 switch | CW |
| 317 | AC08 Control_ Operating Mode [DPT_20.102] | 0-Aut;1-Com;2-Stan;3-Eco;4-Pro | 1 Byte | 20.102 HVAC mode | CW |
| 318 | AC08 Control_ Mode [DPT_20.105] | 0-Aut;1-Hea;3-Coo;9-Fan;14-Dry | 1 Byte | 20.105 HVAC control mode | CW |
| 319 | AC08 Control_ Mode Cool/Heat [DPT_1.100] | 0-Cool;1-Heat | 1 Bit | 1.100 heating/cooling | CW |
| 320 | AC08 Control_ Mode Auto [DPT_1.002] | 1-Set AUTO mode | 1 Bit | 1.2 boolean | CW |
| 321 | AC08 Control_ Mode Heat [DPT_1.002] | 1-Set HEAT mode | 1 Bit | 1.2 boolean | CW |
| 322 | AC08 Control_ Mode Cool [DPT_1.002] | 1-Set COOL mode | 1 Bit | 1.2 boolean | CW |
| 323 | AC08 Control_ Mode Fan [DPT_1.002] | 1-Set FAN mode | 1 Bit | 1.2 boolean | CW |
| 324 | AC08 Control_ Mode Dry [DPT_1.002] | 1-Set DRY mode | 1 Bit | 1.2 boolean | CW |
| 325 | AC08 Control_ Mode +/- [DPT_1.007] | 0-Dec.;1-Inc. | 1 Bit | 1.7 step | CW |
| 325 | AC08 Control_ Mode +/- [DPT_1.008] | 0-Up;1-Down | 1 Bit | 1.8 up/down | CW |
| 326 | AC08 Control_ Fan Speed [DPT_5.001] | Thresholds: 75% || 50% and 83% | 1 Byte | 5.1 percentage (0..100%) | CW |
| 326 | AC08 Control_ Fan Speed [DPT_5.010] | Speed values: 1,2 || 1,2,3 | 1 Byte | 5.10 counter pulses (0..255) | CW |
| 327 | AC08 Control_ Fan Speed Man/Auto [DPT_1.002] | 0-Manual;1-Auto | 1 Bit | 1.2 boolean | CW |
| 328 | AC08 Control_ Fan Speed 1 [DPT_1.002] | 1-Set Fan Speed 1 | 1 Bit | 1.2 boolean | CW |
| 329 | AC08 Control_ Fan Speed 2 [DPT_1.002] | 1-Set Fan Speed 2 | 1 Bit | 1.2 boolean | CW |
| 330 | AC08 Control_ Fan Speed 3 [DPT_1.002] | 1-Set Fan Speed 3 | 1 Bit | 1.2 boolean | CW |
| 331 | AC08 Control_ Fan Speed +/- [DPT_1.007] | 0-Dec.;1-Inc. | 1 Bit | 1.7 step | CW |
| 331 | AC08 Control_ Fan Speed +/- [DPT_1.008] | 0-Up;1-Down | 1 Bit | 1.8 up/down | CW |
| 332 | AC08 Control_ Vanes U-D Swing [DPT_1.002] | 0-Stop;1-Swing | 1 Bit | 1.2 boolean | CW |
| 333 | AC08 Control_ Setpoint Temperature [DPT_9.001] | ºC | 2 Bytes | 9.1 temperature (°C) | CW |
| 334 | AC08 Control_ Setpoint Temperature +/- [DPT_1.007] | 0-Dec.;1-Inc. | 1 Bit | 1.7 step | CW |
| 334 | AC08 Control_ Setpoint Temperature +/- [DPT_1.008] | 0-Up;1-Down | 1 Bit | 1.8 up/down | CW |
| 335 | AC08 Control_ Ambient Temperature [DPT_9.001] | ºC | 2 Bytes | 9.1 temperature (°C) | CW |
| 336 | AC08 Control_ Remote Lock [DPT_1.003] | 0-Unlock;1-Lock | 1 Bit | 1.3 enable | CW |
| 337 | AC08 Status_ On/Off [DPT_1.001] | 0-Off;1-On | 1 Bit | 1.1 switch | CRT |
| 338 | AC08 Status_ Operating Mode [DPT_20.102] | 0-Aut;1-Com;2-Stan;3-Eco;4-Pro | 1 Byte | 20.102 HVAC mode | CRT |
| 339 | AC08 Status_ Mode [DPT_20.105] | 0-Aut;1-Hea;3-Coo;9-Fan;14-Dry | 1 Byte | 20.105 HVAC control mode | CRT |
| 340 | AC08 Status_ Mode Cool/Heat [DPT_1.100] | 0-Cool;1-Heat | 1 Bit | 1.100 heating/cooling | CRT |
| 341 | AC08 Status_ Mode Auto [DPT_1.002] | 1-AUTO mode is active | 1 Bit | 1.2 boolean | CRT |
| 342 | AC08 Status_ Mode Heat [DPT_1.002] | 1-HEAT mode is active | 1 Bit | 1.2 boolean | CRT |
| 343 | AC08 Status_ Mode Cool [DPT_1.002] | 1-COOL mode is active | 1 Bit | 1.2 boolean | CRT |
| 344 | AC08 Status_ Mode Fan [DPT_1.002] | 1-FAN mode is active | 1 Bit | 1.2 boolean | CRT |
| 345 | AC08 Status_ Mode Dry [DPT_1.002] | 1-DRY mode is active | 1 Bit | 1.2 boolean | CRT |
| 346 | AC08 Status_ Mode Text [DPT_16.001] | Mode Text | 14 Bytes | 16.1 Character String (ISO 8859-1) | CRT |
| 347 | AC08 Status_ Fan Speed [DPT_5.001] | 50% and 100% || 33%, 66% and 100% | 1 Byte | 5.1 percentage (0..100%) | CRT |
| 347 | AC08 Status_ Fan Speed [DPT_5.010] | Speed values: 1,2 || 1,2,3 | 1 Byte | 5.10 counter pulses (0..255) | CRT |
| 348 | AC08 Status_ Fan Speed Man/Auto [DPT_1.002] | 0-Manual;1-Auto | 1 Bit | 1.2 boolean | CRT |
| 349 | AC08 Status_ Fan Speed 1 [DPT_1.002] | 1-Fan in Speed 1 | 1 Bit | 1.2 boolean | CRT |
| 350 | AC08 Status_ Fan Speed 2 [DPT_1.002] | 1-Fan in Speed 2 | 1 Bit | 1.2 boolean | CRT |
| 351 | AC08 Status_ Fan Speed 3 [DPT_1.002] | 1-Fan in Speed 3 | 1 Bit | 1.2 boolean | CRT |
| 352 | AC08 Status_ Fan Speed Text [DPT_16.001] | Fan Speed Text | 14 Bytes | 16.1 Character String (ISO 8859-1) | CRT |
| 353 | AC08 Status_ Vanes U-D Swing [DPT_1.002] | 0-Stop;1-Swing | 1 Bit | 1.2 boolean | CRT |
| 354 | AC08 Status_ Vanes U-D Text [DPT_16.001] | Vanes Text | 14 Bytes | 16.1 Character String (ISO 8859-1) | CRT |
| 355 | AC08 Status_ AC Setpoint Temperature [DPT_9.001] | ºC | 2 Bytes | 9.1 temperature (°C) | CRT |
| 356 | AC08 Status_ AC Ambient Reference Temperature [DPT_9.001] | ºC | 2 Bytes | 9.1 temperature (°C) | CRT |
| 357 | AC08 Status_ Error/Alarm [DPT_1.005] | 0-No alarm;1-Alarm | 1 Bit | 1.5 alarm | CRT |
| 358 | AC08 Status_ Error Code [2-byte signed value] | Error Code | 2 Bytes | 8.1 pulses difference | CRT |
| 359 | AC08 Status_ Error Text [DPT_16.001] | Error Text | 14 Bytes | 16.1 Character String (ISO 8859-1) | CRT |
| 360 | AC08 Status_ Remote Lock [DPT_1.003] | 0-Unlocked;1-Locked | 1 Bit | 1.3 enable | CRT |
| 361 | AC09 Control_ On/Off [DPT_1.001] | 0-Off;1-On | 1 Bit | 1.1 switch | CW |
| 362 | AC09 Control_ Operating Mode [DPT_20.102] | 0-Aut;1-Com;2-Stan;3-Eco;4-Pro | 1 Byte | 20.102 HVAC mode | CW |
| 363 | AC09 Control_ Mode [DPT_20.105] | 0-Aut;1-Hea;3-Coo;9-Fan;14-Dry | 1 Byte | 20.105 HVAC control mode | CW |
| 364 | AC09 Control_ Mode Cool/Heat [DPT_1.100] | 0-Cool;1-Heat | 1 Bit | 1.100 heating/cooling | CW |
| 365 | AC09 Control_ Mode Auto [DPT_1.002] | 1-Set AUTO mode | 1 Bit | 1.2 boolean | CW |
| 366 | AC09 Control_ Mode Heat [DPT_1.002] | 1-Set HEAT mode | 1 Bit | 1.2 boolean | CW |
| 367 | AC09 Control_ Mode Cool [DPT_1.002] | 1-Set COOL mode | 1 Bit | 1.2 boolean | CW |
| 368 | AC09 Control_ Mode Fan [DPT_1.002] | 1-Set FAN mode | 1 Bit | 1.2 boolean | CW |
| 369 | AC09 Control_ Mode Dry [DPT_1.002] | 1-Set DRY mode | 1 Bit | 1.2 boolean | CW |
| 370 | AC09 Control_ Mode +/- [DPT_1.007] | 0-Dec.;1-Inc. | 1 Bit | 1.7 step | CW |
| 370 | AC09 Control_ Mode +/- [DPT_1.008] | 0-Up;1-Down | 1 Bit | 1.8 up/down | CW |
| 371 | AC09 Control_ Fan Speed [DPT_5.001] | Thresholds: 75% || 50% and 83% | 1 Byte | 5.1 percentage (0..100%) | CW |
| 371 | AC09 Control_ Fan Speed [DPT_5.010] | Speed values: 1,2 || 1,2,3 | 1 Byte | 5.10 counter pulses (0..255) | CW |
| 372 | AC09 Control_ Fan Speed Man/Auto [DPT_1.002] | 0-Manual;1-Auto | 1 Bit | 1.2 boolean | CW |
| 373 | AC09 Control_ Fan Speed 1 [DPT_1.002] | 1-Set Fan Speed 1 | 1 Bit | 1.2 boolean | CW |
| 374 | AC09 Control_ Fan Speed 2 [DPT_1.002] | 1-Set Fan Speed 2 | 1 Bit | 1.2 boolean | CW |
| 375 | AC09 Control_ Fan Speed 3 [DPT_1.002] | 1-Set Fan Speed 3 | 1 Bit | 1.2 boolean | CW |
| 376 | AC09 Control_ Fan Speed +/- [DPT_1.007] | 0-Dec.;1-Inc. | 1 Bit | 1.7 step | CW |
| 376 | AC09 Control_ Fan Speed +/- [DPT_1.008] | 0-Up;1-Down | 1 Bit | 1.8 up/down | CW |
| 377 | AC09 Control_ Vanes U-D Swing [DPT_1.002] | 0-Stop;1-Swing | 1 Bit | 1.2 boolean | CW |
| 378 | AC09 Control_ Setpoint Temperature [DPT_9.001] | ºC | 2 Bytes | 9.1 temperature (°C) | CW |
| 379 | AC09 Control_ Setpoint Temperature +/- [DPT_1.007] | 0-Dec.;1-Inc. | 1 Bit | 1.7 step | CW |
| 379 | AC09 Control_ Setpoint Temperature +/- [DPT_1.008] | 0-Up;1-Down | 1 Bit | 1.8 up/down | CW |
| 380 | AC09 Control_ Ambient Temperature [DPT_9.001] | ºC | 2 Bytes | 9.1 temperature (°C) | CW |
| 381 | AC09 Control_ Remote Lock [DPT_1.003] | 0-Unlock;1-Lock | 1 Bit | 1.3 enable | CW |
| 382 | AC09 Status_ On/Off [DPT_1.001] | 0-Off;1-On | 1 Bit | 1.1 switch | CRT |
| 383 | AC09 Status_ Operating Mode [DPT_20.102] | 0-Aut;1-Com;2-Stan;3-Eco;4-Pro | 1 Byte | 20.102 HVAC mode | CRT |
| 384 | AC09 Status_ Mode [DPT_20.105] | 0-Aut;1-Hea;3-Coo;9-Fan;14-Dry | 1 Byte | 20.105 HVAC control mode | CRT |
| 385 | AC09 Status_ Mode Cool/Heat [DPT_1.100] | 0-Cool;1-Heat | 1 Bit | 1.100 heating/cooling | CRT |
| 386 | AC09 Status_ Mode Auto [DPT_1.002] | 1-AUTO mode is active | 1 Bit | 1.2 boolean | CRT |
| 387 | AC09 Status_ Mode Heat [DPT_1.002] | 1-HEAT mode is active | 1 Bit | 1.2 boolean | CRT |
| 388 | AC09 Status_ Mode Cool [DPT_1.002] | 1-COOL mode is active | 1 Bit | 1.2 boolean | CRT |
| 389 | AC09 Status_ Mode Fan [DPT_1.002] | 1-FAN mode is active | 1 Bit | 1.2 boolean | CRT |
| 390 | AC09 Status_ Mode Dry [DPT_1.002] | 1-DRY mode is active | 1 Bit | 1.2 boolean | CRT |
| 391 | AC09 Status_ Mode Text [DPT_16.001] | Mode Text | 14 Bytes | 16.1 Character String (ISO 8859-1) | CRT |
| 392 | AC09 Status_ Fan Speed [DPT_5.001] | 50% and 100% || 33%, 66% and 100% | 1 Byte | 5.1 percentage (0..100%) | CRT |
| 392 | AC09 Status_ Fan Speed [DPT_5.010] | Speed values: 1,2 || 1,2,3 | 1 Byte | 5.10 counter pulses (0..255) | CRT |
| 393 | AC09 Status_ Fan Speed Man/Auto [DPT_1.002] | 0-Manual;1-Auto | 1 Bit | 1.2 boolean | CRT |
| 394 | AC09 Status_ Fan Speed 1 [DPT_1.002] | 1-Fan in Speed 1 | 1 Bit | 1.2 boolean | CRT |
| 395 | AC09 Status_ Fan Speed 2 [DPT_1.002] | 1-Fan in Speed 2 | 1 Bit | 1.2 boolean | CRT |
| 396 | AC09 Status_ Fan Speed 3 [DPT_1.002] | 1-Fan in Speed 3 | 1 Bit | 1.2 boolean | CRT |
| 397 | AC09 Status_ Fan Speed Text [DPT_16.001] | Fan Speed Text | 14 Bytes | 16.1 Character String (ISO 8859-1) | CRT |
| 398 | AC09 Status_ Vanes U-D Swing [DPT_1.002] | 0-Stop;1-Swing | 1 Bit | 1.2 boolean | CRT |
| 399 | AC09 Status_ Vanes U-D Text [DPT_16.001] | Vanes Text | 14 Bytes | 16.1 Character String (ISO 8859-1) | CRT |
| 400 | AC09 Status_ AC Setpoint Temperature [DPT_9.001] | ºC | 2 Bytes | 9.1 temperature (°C) | CRT |
| 401 | AC09 Status_ AC Ambient Reference Temperature [DPT_9.001] | ºC | 2 Bytes | 9.1 temperature (°C) | CRT |
| 402 | AC09 Status_ Error/Alarm [DPT_1.005] | 0-No alarm;1-Alarm | 1 Bit | 1.5 alarm | CRT |
| 403 | AC09 Status_ Error Code [2-byte signed value] | Error Code | 2 Bytes | 8.1 pulses difference | CRT |
| 404 | AC09 Status_ Error Text [DPT_16.001] | Error Text | 14 Bytes | 16.1 Character String (ISO 8859-1) | CRT |
| 405 | AC09 Status_ Remote Lock [DPT_1.003] | 0-Unlocked;1-Locked | 1 Bit | 1.3 enable | CRT |
| 406 | AC10 Control_ On/Off [DPT_1.001] | 0-Off;1-On | 1 Bit | 1.1 switch | CW |
| 407 | AC10 Control_ Operating Mode [DPT_20.102] | 0-Aut;1-Com;2-Stan;3-Eco;4-Pro | 1 Byte | 20.102 HVAC mode | CW |
| 408 | AC10 Control_ Mode [DPT_20.105] | 0-Aut;1-Hea;3-Coo;9-Fan;14-Dry | 1 Byte | 20.105 HVAC control mode | CW |
| 409 | AC10 Control_ Mode Cool/Heat [DPT_1.100] | 0-Cool;1-Heat | 1 Bit | 1.100 heating/cooling | CW |
| 410 | AC10 Control_ Mode Auto [DPT_1.002] | 1-Set AUTO mode | 1 Bit | 1.2 boolean | CW |
| 411 | AC10 Control_ Mode Heat [DPT_1.002] | 1-Set HEAT mode | 1 Bit | 1.2 boolean | CW |
| 412 | AC10 Control_ Mode Cool [DPT_1.002] | 1-Set COOL mode | 1 Bit | 1.2 boolean | CW |
| 413 | AC10 Control_ Mode Fan [DPT_1.002] | 1-Set FAN mode | 1 Bit | 1.2 boolean | CW |
| 414 | AC10 Control_ Mode Dry [DPT_1.002] | 1-Set DRY mode | 1 Bit | 1.2 boolean | CW |
| 415 | AC10 Control_ Mode +/- [DPT_1.007] | 0-Dec.;1-Inc. | 1 Bit | 1.7 step | CW |
| 415 | AC10 Control_ Mode +/- [DPT_1.008] | 0-Up;1-Down | 1 Bit | 1.8 up/down | CW |
| 416 | AC10 Control_ Fan Speed [DPT_5.001] | Thresholds: 75% || 50% and 83% | 1 Byte | 5.1 percentage (0..100%) | CW |
| 416 | AC10 Control_ Fan Speed [DPT_5.010] | Speed values: 1,2 || 1,2,3 | 1 Byte | 5.10 counter pulses (0..255) | CW |
| 417 | AC10 Control_ Fan Speed Man/Auto [DPT_1.002] | 0-Manual;1-Auto | 1 Bit | 1.2 boolean | CW |
| 418 | AC10 Control_ Fan Speed 1 [DPT_1.002] | 1-Set Fan Speed 1 | 1 Bit | 1.2 boolean | CW |
| 419 | AC10 Control_ Fan Speed 2 [DPT_1.002] | 1-Set Fan Speed 2 | 1 Bit | 1.2 boolean | CW |
| 420 | AC10 Control_ Fan Speed 3 [DPT_1.002] | 1-Set Fan Speed 3 | 1 Bit | 1.2 boolean | CW |
| 421 | AC10 Control_ Fan Speed +/- [DPT_1.007] | 0-Dec.;1-Inc. | 1 Bit | 1.7 step | CW |
| 421 | AC10 Control_ Fan Speed +/- [DPT_1.008] | 0-Up;1-Down | 1 Bit | 1.8 up/down | CW |
| 422 | AC10 Control_ Vanes U-D Swing [DPT_1.002] | 0-Stop;1-Swing | 1 Bit | 1.2 boolean | CW |
| 423 | AC10 Control_ Setpoint Temperature [DPT_9.001] | ºC | 2 Bytes | 9.1 temperature (°C) | CW |
| 424 | AC10 Control_ Setpoint Temperature +/- [DPT_1.007] | 0-Dec.;1-Inc. | 1 Bit | 1.7 step | CW |
| 424 | AC10 Control_ Setpoint Temperature +/- [DPT_1.008] | 0-Up;1-Down | 1 Bit | 1.8 up/down | CW |
| 425 | AC10 Control_ Ambient Temperature [DPT_9.001] | ºC | 2 Bytes | 9.1 temperature (°C) | CW |
| 426 | AC10 Control_ Remote Lock [DPT_1.003] | 0-Unlock;1-Lock | 1 Bit | 1.3 enable | CW |
| 427 | AC10 Status_ On/Off [DPT_1.001] | 0-Off;1-On | 1 Bit | 1.1 switch | CRT |
| 428 | AC10 Status_ Operating Mode [DPT_20.102] | 0-Aut;1-Com;2-Stan;3-Eco;4-Pro | 1 Byte | 20.102 HVAC mode | CRT |
| 429 | AC10 Status_ Mode [DPT_20.105] | 0-Aut;1-Hea;3-Coo;9-Fan;14-Dry | 1 Byte | 20.105 HVAC control mode | CRT |
| 430 | AC10 Status_ Mode Cool/Heat [DPT_1.100] | 0-Cool;1-Heat | 1 Bit | 1.100 heating/cooling | CRT |
| 431 | AC10 Status_ Mode Auto [DPT_1.002] | 1-AUTO mode is active | 1 Bit | 1.2 boolean | CRT |
| 432 | AC10 Status_ Mode Heat [DPT_1.002] | 1-HEAT mode is active | 1 Bit | 1.2 boolean | CRT |
| 433 | AC10 Status_ Mode Cool [DPT_1.002] | 1-COOL mode is active | 1 Bit | 1.2 boolean | CRT |
| 434 | AC10 Status_ Mode Fan [DPT_1.002] | 1-FAN mode is active | 1 Bit | 1.2 boolean | CRT |
| 435 | AC10 Status_ Mode Dry [DPT_1.002] | 1-DRY mode is active | 1 Bit | 1.2 boolean | CRT |
| 436 | AC10 Status_ Mode Text [DPT_16.001] | Mode Text | 14 Bytes | 16.1 Character String (ISO 8859-1) | CRT |
| 437 | AC10 Status_ Fan Speed [DPT_5.001] | 50% and 100% || 33%, 66% and 100% | 1 Byte | 5.1 percentage (0..100%) | CRT |
| 437 | AC10 Status_ Fan Speed [DPT_5.010] | Speed values: 1,2 || 1,2,3 | 1 Byte | 5.10 counter pulses (0..255) | CRT |
| 438 | AC10 Status_ Fan Speed Man/Auto [DPT_1.002] | 0-Manual;1-Auto | 1 Bit | 1.2 boolean | CRT |
| 439 | AC10 Status_ Fan Speed 1 [DPT_1.002] | 1-Fan in Speed 1 | 1 Bit | 1.2 boolean | CRT |
| 440 | AC10 Status_ Fan Speed 2 [DPT_1.002] | 1-Fan in Speed 2 | 1 Bit | 1.2 boolean | CRT |
| 441 | AC10 Status_ Fan Speed 3 [DPT_1.002] | 1-Fan in Speed 3 | 1 Bit | 1.2 boolean | CRT |
| 442 | AC10 Status_ Fan Speed Text [DPT_16.001] | Fan Speed Text | 14 Bytes | 16.1 Character String (ISO 8859-1) | CRT |
| 443 | AC10 Status_ Vanes U-D Swing [DPT_1.002] | 0-Stop;1-Swing | 1 Bit | 1.2 boolean | CRT |
| 444 | AC10 Status_ Vanes U-D Text [DPT_16.001] | Vanes Text | 14 Bytes | 16.1 Character String (ISO 8859-1) | CRT |
| 445 | AC10 Status_ AC Setpoint Temperature [DPT_9.001] | ºC | 2 Bytes | 9.1 temperature (°C) | CRT |
| 446 | AC10 Status_ AC Ambient Reference Temperature [DPT_9.001] | ºC | 2 Bytes | 9.1 temperature (°C) | CRT |
| 447 | AC10 Status_ Error/Alarm [DPT_1.005] | 0-No alarm;1-Alarm | 1 Bit | 1.5 alarm | CRT |
| 448 | AC10 Status_ Error Code [2-byte signed value] | Error Code | 2 Bytes | 8.1 pulses difference | CRT |
| 449 | AC10 Status_ Error Text [DPT_16.001] | Error Text | 14 Bytes | 16.1 Character String (ISO 8859-1) | CRT |
| 450 | AC10 Status_ Remote Lock [DPT_1.003] | 0-Unlocked;1-Locked | 1 Bit | 1.3 enable | CRT |
| 451 | AC11 Control_ On/Off [DPT_1.001] | 0-Off;1-On | 1 Bit | 1.1 switch | CW |
| 452 | AC11 Control_ Operating Mode [DPT_20.102] | 0-Aut;1-Com;2-Stan;3-Eco;4-Pro | 1 Byte | 20.102 HVAC mode | CW |
| 453 | AC11 Control_ Mode [DPT_20.105] | 0-Aut;1-Hea;3-Coo;9-Fan;14-Dry | 1 Byte | 20.105 HVAC control mode | CW |
| 454 | AC11 Control_ Mode Cool/Heat [DPT_1.100] | 0-Cool;1-Heat | 1 Bit | 1.100 heating/cooling | CW |
| 455 | AC11 Control_ Mode Auto [DPT_1.002] | 1-Set AUTO mode | 1 Bit | 1.2 boolean | CW |
| 456 | AC11 Control_ Mode Heat [DPT_1.002] | 1-Set HEAT mode | 1 Bit | 1.2 boolean | CW |
| 457 | AC11 Control_ Mode Cool [DPT_1.002] | 1-Set COOL mode | 1 Bit | 1.2 boolean | CW |
| 458 | AC11 Control_ Mode Fan [DPT_1.002] | 1-Set FAN mode | 1 Bit | 1.2 boolean | CW |
| 459 | AC11 Control_ Mode Dry [DPT_1.002] | 1-Set DRY mode | 1 Bit | 1.2 boolean | CW |
| 460 | AC11 Control_ Mode +/- [DPT_1.007] | 0-Dec.;1-Inc. | 1 Bit | 1.7 step | CW |
| 460 | AC11 Control_ Mode +/- [DPT_1.008] | 0-Up;1-Down | 1 Bit | 1.8 up/down | CW |
| 461 | AC11 Control_ Fan Speed [DPT_5.001] | Thresholds: 75% || 50% and 83% | 1 Byte | 5.1 percentage (0..100%) | CW |
| 461 | AC11 Control_ Fan Speed [DPT_5.010] | Speed values: 1,2 || 1,2,3 | 1 Byte | 5.10 counter pulses (0..255) | CW |
| 462 | AC11 Control_ Fan Speed Man/Auto [DPT_1.002] | 0-Manual;1-Auto | 1 Bit | 1.2 boolean | CW |
| 463 | AC11 Control_ Fan Speed 1 [DPT_1.002] | 1-Set Fan Speed 1 | 1 Bit | 1.2 boolean | CW |
| 464 | AC11 Control_ Fan Speed 2 [DPT_1.002] | 1-Set Fan Speed 2 | 1 Bit | 1.2 boolean | CW |
| 465 | AC11 Control_ Fan Speed 3 [DPT_1.002] | 1-Set Fan Speed 3 | 1 Bit | 1.2 boolean | CW |
| 466 | AC11 Control_ Fan Speed +/- [DPT_1.007] | 0-Dec.;1-Inc. | 1 Bit | 1.7 step | CW |
| 466 | AC11 Control_ Fan Speed +/- [DPT_1.008] | 0-Up;1-Down | 1 Bit | 1.8 up/down | CW |
| 467 | AC11 Control_ Vanes U-D Swing [DPT_1.002] | 0-Stop;1-Swing | 1 Bit | 1.2 boolean | CW |
| 468 | AC11 Control_ Setpoint Temperature [DPT_9.001] | ºC | 2 Bytes | 9.1 temperature (°C) | CW |
| 469 | AC11 Control_ Setpoint Temperature +/- [DPT_1.007] | 0-Dec.;1-Inc. | 1 Bit | 1.7 step | CW |
| 469 | AC11 Control_ Setpoint Temperature +/- [DPT_1.008] | 0-Up;1-Down | 1 Bit | 1.8 up/down | CW |
| 470 | AC11 Control_ Ambient Temperature [DPT_9.001] | ºC | 2 Bytes | 9.1 temperature (°C) | CW |
| 471 | AC11 Control_ Remote Lock [DPT_1.003] | 0-Unlock;1-Lock | 1 Bit | 1.3 enable | CW |
| 472 | AC11 Status_ On/Off [DPT_1.001] | 0-Off;1-On | 1 Bit | 1.1 switch | CRT |
| 473 | AC11 Status_ Operating Mode [DPT_20.102] | 0-Aut;1-Com;2-Stan;3-Eco;4-Pro | 1 Byte | 20.102 HVAC mode | CRT |
| 474 | AC11 Status_ Mode [DPT_20.105] | 0-Aut;1-Hea;3-Coo;9-Fan;14-Dry | 1 Byte | 20.105 HVAC control mode | CRT |
| 475 | AC11 Status_ Mode Cool/Heat [DPT_1.100] | 0-Cool;1-Heat | 1 Bit | 1.100 heating/cooling | CRT |
| 476 | AC11 Status_ Mode Auto [DPT_1.002] | 1-AUTO mode is active | 1 Bit | 1.2 boolean | CRT |
| 477 | AC11 Status_ Mode Heat [DPT_1.002] | 1-HEAT mode is active | 1 Bit | 1.2 boolean | CRT |
| 478 | AC11 Status_ Mode Cool [DPT_1.002] | 1-COOL mode is active | 1 Bit | 1.2 boolean | CRT |
| 479 | AC11 Status_ Mode Fan [DPT_1.002] | 1-FAN mode is active | 1 Bit | 1.2 boolean | CRT |
| 480 | AC11 Status_ Mode Dry [DPT_1.002] | 1-DRY mode is active | 1 Bit | 1.2 boolean | CRT |
| 481 | AC11 Status_ Mode Text [DPT_16.001] | Mode Text | 14 Bytes | 16.1 Character String (ISO 8859-1) | CRT |
| 482 | AC11 Status_ Fan Speed [DPT_5.001] | 50% and 100% || 33%, 66% and 100% | 1 Byte | 5.1 percentage (0..100%) | CRT |
| 482 | AC11 Status_ Fan Speed [DPT_5.010] | Speed values: 1,2 || 1,2,3 | 1 Byte | 5.10 counter pulses (0..255) | CRT |
| 483 | AC11 Status_ Fan Speed Man/Auto [DPT_1.002] | 0-Manual;1-Auto | 1 Bit | 1.2 boolean | CRT |
| 484 | AC11 Status_ Fan Speed 1 [DPT_1.002] | 1-Fan in Speed 1 | 1 Bit | 1.2 boolean | CRT |
| 485 | AC11 Status_ Fan Speed 2 [DPT_1.002] | 1-Fan in Speed 2 | 1 Bit | 1.2 boolean | CRT |
| 486 | AC11 Status_ Fan Speed 3 [DPT_1.002] | 1-Fan in Speed 3 | 1 Bit | 1.2 boolean | CRT |
| 487 | AC11 Status_ Fan Speed Text [DPT_16.001] | Fan Speed Text | 14 Bytes | 16.1 Character String (ISO 8859-1) | CRT |
| 488 | AC11 Status_ Vanes U-D Swing [DPT_1.002] | 0-Stop;1-Swing | 1 Bit | 1.2 boolean | CRT |
| 489 | AC11 Status_ Vanes U-D Text [DPT_16.001] | Vanes Text | 14 Bytes | 16.1 Character String (ISO 8859-1) | CRT |
| 490 | AC11 Status_ AC Setpoint Temperature [DPT_9.001] | ºC | 2 Bytes | 9.1 temperature (°C) | CRT |
| 491 | AC11 Status_ AC Ambient Reference Temperature [DPT_9.001] | ºC | 2 Bytes | 9.1 temperature (°C) | CRT |
| 492 | AC11 Status_ Error/Alarm [DPT_1.005] | 0-No alarm;1-Alarm | 1 Bit | 1.5 alarm | CRT |
| 493 | AC11 Status_ Error Code [2-byte signed value] | Error Code | 2 Bytes | 8.1 pulses difference | CRT |
| 494 | AC11 Status_ Error Text [DPT_16.001] | Error Text | 14 Bytes | 16.1 Character String (ISO 8859-1) | CRT |
| 495 | AC11 Status_ Remote Lock [DPT_1.003] | 0-Unlocked;1-Locked | 1 Bit | 1.3 enable | CRT |
| 496 | AC12 Control_ On/Off [DPT_1.001] | 0-Off;1-On | 1 Bit | 1.1 switch | CW |
| 497 | AC12 Control_ Operating Mode [DPT_20.102] | 0-Aut;1-Com;2-Stan;3-Eco;4-Pro | 1 Byte | 20.102 HVAC mode | CW |
| 498 | AC12 Control_ Mode [DPT_20.105] | 0-Aut;1-Hea;3-Coo;9-Fan;14-Dry | 1 Byte | 20.105 HVAC control mode | CW |
| 499 | AC12 Control_ Mode Cool/Heat [DPT_1.100] | 0-Cool;1-Heat | 1 Bit | 1.100 heating/cooling | CW |
| 500 | AC12 Control_ Mode Auto [DPT_1.002] | 1-Set AUTO mode | 1 Bit | 1.2 boolean | CW |
| 501 | AC12 Control_ Mode Heat [DPT_1.002] | 1-Set HEAT mode | 1 Bit | 1.2 boolean | CW |
| 502 | AC12 Control_ Mode Cool [DPT_1.002] | 1-Set COOL mode | 1 Bit | 1.2 boolean | CW |
| 503 | AC12 Control_ Mode Fan [DPT_1.002] | 1-Set FAN mode | 1 Bit | 1.2 boolean | CW |
| 504 | AC12 Control_ Mode Dry [DPT_1.002] | 1-Set DRY mode | 1 Bit | 1.2 boolean | CW |
| 505 | AC12 Control_ Mode +/- [DPT_1.007] | 0-Dec.;1-Inc. | 1 Bit | 1.7 step | CW |
| 505 | AC12 Control_ Mode +/- [DPT_1.008] | 0-Up;1-Down | 1 Bit | 1.8 up/down | CW |
| 506 | AC12 Control_ Fan Speed [DPT_5.001] | Thresholds: 75% || 50% and 83% | 1 Byte | 5.1 percentage (0..100%) | CW |
| 506 | AC12 Control_ Fan Speed [DPT_5.010] | Speed values: 1,2 || 1,2,3 | 1 Byte | 5.10 counter pulses (0..255) | CW |
| 507 | AC12 Control_ Fan Speed Man/Auto [DPT_1.002] | 0-Manual;1-Auto | 1 Bit | 1.2 boolean | CW |
| 508 | AC12 Control_ Fan Speed 1 [DPT_1.002] | 1-Set Fan Speed 1 | 1 Bit | 1.2 boolean | CW |
| 509 | AC12 Control_ Fan Speed 2 [DPT_1.002] | 1-Set Fan Speed 2 | 1 Bit | 1.2 boolean | CW |
| 510 | AC12 Control_ Fan Speed 3 [DPT_1.002] | 1-Set Fan Speed 3 | 1 Bit | 1.2 boolean | CW |
| 511 | AC12 Control_ Fan Speed +/- [DPT_1.007] | 0-Dec.;1-Inc. | 1 Bit | 1.7 step | CW |
| 511 | AC12 Control_ Fan Speed +/- [DPT_1.008] | 0-Up;1-Down | 1 Bit | 1.8 up/down | CW |
| 512 | AC12 Control_ Vanes U-D Swing [DPT_1.002] | 0-Stop;1-Swing | 1 Bit | 1.2 boolean | CW |
| 513 | AC12 Control_ Setpoint Temperature [DPT_9.001] | ºC | 2 Bytes | 9.1 temperature (°C) | CW |
| 514 | AC12 Control_ Setpoint Temperature +/- [DPT_1.007] | 0-Dec.;1-Inc. | 1 Bit | 1.7 step | CW |
| 514 | AC12 Control_ Setpoint Temperature +/- [DPT_1.008] | 0-Up;1-Down | 1 Bit | 1.8 up/down | CW |
| 515 | AC12 Control_ Ambient Temperature [DPT_9.001] | ºC | 2 Bytes | 9.1 temperature (°C) | CW |
| 516 | AC12 Control_ Remote Lock [DPT_1.003] | 0-Unlock;1-Lock | 1 Bit | 1.3 enable | CW |
| 517 | AC12 Status_ On/Off [DPT_1.001] | 0-Off;1-On | 1 Bit | 1.1 switch | CRT |
| 518 | AC12 Status_ Operating Mode [DPT_20.102] | 0-Aut;1-Com;2-Stan;3-Eco;4-Pro | 1 Byte | 20.102 HVAC mode | CRT |
| 519 | AC12 Status_ Mode [DPT_20.105] | 0-Aut;1-Hea;3-Coo;9-Fan;14-Dry | 1 Byte | 20.105 HVAC control mode | CRT |
| 520 | AC12 Status_ Mode Cool/Heat [DPT_1.100] | 0-Cool;1-Heat | 1 Bit | 1.100 heating/cooling | CRT |
| 521 | AC12 Status_ Mode Auto [DPT_1.002] | 1-AUTO mode is active | 1 Bit | 1.2 boolean | CRT |
| 522 | AC12 Status_ Mode Heat [DPT_1.002] | 1-HEAT mode is active | 1 Bit | 1.2 boolean | CRT |
| 523 | AC12 Status_ Mode Cool [DPT_1.002] | 1-COOL mode is active | 1 Bit | 1.2 boolean | CRT |
| 524 | AC12 Status_ Mode Fan [DPT_1.002] | 1-FAN mode is active | 1 Bit | 1.2 boolean | CRT |
| 525 | AC12 Status_ Mode Dry [DPT_1.002] | 1-DRY mode is active | 1 Bit | 1.2 boolean | CRT |
| 526 | AC12 Status_ Mode Text [DPT_16.001] | Mode Text | 14 Bytes | 16.1 Character String (ISO 8859-1) | CRT |
| 527 | AC12 Status_ Fan Speed [DPT_5.001] | 50% and 100% || 33%, 66% and 100% | 1 Byte | 5.1 percentage (0..100%) | CRT |
| 527 | AC12 Status_ Fan Speed [DPT_5.010] | Speed values: 1,2 || 1,2,3 | 1 Byte | 5.10 counter pulses (0..255) | CRT |
| 528 | AC12 Status_ Fan Speed Man/Auto [DPT_1.002] | 0-Manual;1-Auto | 1 Bit | 1.2 boolean | CRT |
| 529 | AC12 Status_ Fan Speed 1 [DPT_1.002] | 1-Fan in Speed 1 | 1 Bit | 1.2 boolean | CRT |
| 530 | AC12 Status_ Fan Speed 2 [DPT_1.002] | 1-Fan in Speed 2 | 1 Bit | 1.2 boolean | CRT |
| 531 | AC12 Status_ Fan Speed 3 [DPT_1.002] | 1-Fan in Speed 3 | 1 Bit | 1.2 boolean | CRT |
| 532 | AC12 Status_ Fan Speed Text [DPT_16.001] | Fan Speed Text | 14 Bytes | 16.1 Character String (ISO 8859-1) | CRT |
| 533 | AC12 Status_ Vanes U-D Swing [DPT_1.002] | 0-Stop;1-Swing | 1 Bit | 1.2 boolean | CRT |
| 534 | AC12 Status_ Vanes U-D Text [DPT_16.001] | Vanes Text | 14 Bytes | 16.1 Character String (ISO 8859-1) | CRT |
| 535 | AC12 Status_ AC Setpoint Temperature [DPT_9.001] | ºC | 2 Bytes | 9.1 temperature (°C) | CRT |
| 536 | AC12 Status_ AC Ambient Reference Temperature [DPT_9.001] | ºC | 2 Bytes | 9.1 temperature (°C) | CRT |
| 537 | AC12 Status_ Error/Alarm [DPT_1.005] | 0-No alarm;1-Alarm | 1 Bit | 1.5 alarm | CRT |
| 538 | AC12 Status_ Error Code [2-byte signed value] | Error Code | 2 Bytes | 8.1 pulses difference | CRT |
| 539 | AC12 Status_ Error Text [DPT_16.001] | Error Text | 14 Bytes | 16.1 Character String (ISO 8859-1) | CRT |
| 540 | AC12 Status_ Remote Lock [DPT_1.003] | 0-Unlocked;1-Locked | 1 Bit | 1.3 enable | CRT |
| 541 | AC13 Control_ On/Off [DPT_1.001] | 0-Off;1-On | 1 Bit | 1.1 switch | CW |
| 542 | AC13 Control_ Operating Mode [DPT_20.102] | 0-Aut;1-Com;2-Stan;3-Eco;4-Pro | 1 Byte | 20.102 HVAC mode | CW |
| 543 | AC13 Control_ Mode [DPT_20.105] | 0-Aut;1-Hea;3-Coo;9-Fan;14-Dry | 1 Byte | 20.105 HVAC control mode | CW |
| 544 | AC13 Control_ Mode Cool/Heat [DPT_1.100] | 0-Cool;1-Heat | 1 Bit | 1.100 heating/cooling | CW |
| 545 | AC13 Control_ Mode Auto [DPT_1.002] | 1-Set AUTO mode | 1 Bit | 1.2 boolean | CW |
| 546 | AC13 Control_ Mode Heat [DPT_1.002] | 1-Set HEAT mode | 1 Bit | 1.2 boolean | CW |
| 547 | AC13 Control_ Mode Cool [DPT_1.002] | 1-Set COOL mode | 1 Bit | 1.2 boolean | CW |
| 548 | AC13 Control_ Mode Fan [DPT_1.002] | 1-Set FAN mode | 1 Bit | 1.2 boolean | CW |
| 549 | AC13 Control_ Mode Dry [DPT_1.002] | 1-Set DRY mode | 1 Bit | 1.2 boolean | CW |
| 550 | AC13 Control_ Mode +/- [DPT_1.007] | 0-Dec.;1-Inc. | 1 Bit | 1.7 step | CW |
| 550 | AC13 Control_ Mode +/- [DPT_1.008] | 0-Up;1-Down | 1 Bit | 1.8 up/down | CW |
| 551 | AC13 Control_ Fan Speed [DPT_5.001] | Thresholds: 75% || 50% and 83% | 1 Byte | 5.1 percentage (0..100%) | CW |
| 551 | AC13 Control_ Fan Speed [DPT_5.010] | Speed values: 1,2 || 1,2,3 | 1 Byte | 5.10 counter pulses (0..255) | CW |
| 552 | AC13 Control_ Fan Speed Man/Auto [DPT_1.002] | 0-Manual;1-Auto | 1 Bit | 1.2 boolean | CW |
| 553 | AC13 Control_ Fan Speed 1 [DPT_1.002] | 1-Set Fan Speed 1 | 1 Bit | 1.2 boolean | CW |
| 554 | AC13 Control_ Fan Speed 2 [DPT_1.002] | 1-Set Fan Speed 2 | 1 Bit | 1.2 boolean | CW |
| 555 | AC13 Control_ Fan Speed 3 [DPT_1.002] | 1-Set Fan Speed 3 | 1 Bit | 1.2 boolean | CW |
| 556 | AC13 Control_ Fan Speed +/- [DPT_1.007] | 0-Dec.;1-Inc. | 1 Bit | 1.7 step | CW |
| 556 | AC13 Control_ Fan Speed +/- [DPT_1.008] | 0-Up;1-Down | 1 Bit | 1.8 up/down | CW |
| 557 | AC13 Control_ Vanes U-D Swing [DPT_1.002] | 0-Stop;1-Swing | 1 Bit | 1.2 boolean | CW |
| 558 | AC13 Control_ Setpoint Temperature [DPT_9.001] | ºC | 2 Bytes | 9.1 temperature (°C) | CW |
| 559 | AC13 Control_ Setpoint Temperature +/- [DPT_1.007] | 0-Dec.;1-Inc. | 1 Bit | 1.7 step | CW |
| 559 | AC13 Control_ Setpoint Temperature +/- [DPT_1.008] | 0-Up;1-Down | 1 Bit | 1.8 up/down | CW |
| 560 | AC13 Control_ Ambient Temperature [DPT_9.001] | ºC | 2 Bytes | 9.1 temperature (°C) | CW |
| 561 | AC13 Control_ Remote Lock [DPT_1.003] | 0-Unlock;1-Lock | 1 Bit | 1.3 enable | CW |
| 562 | AC13 Status_ On/Off [DPT_1.001] | 0-Off;1-On | 1 Bit | 1.1 switch | CRT |
| 563 | AC13 Status_ Operating Mode [DPT_20.102] | 0-Aut;1-Com;2-Stan;3-Eco;4-Pro | 1 Byte | 20.102 HVAC mode | CRT |
| 564 | AC13 Status_ Mode [DPT_20.105] | 0-Aut;1-Hea;3-Coo;9-Fan;14-Dry | 1 Byte | 20.105 HVAC control mode | CRT |
| 565 | AC13 Status_ Mode Cool/Heat [DPT_1.100] | 0-Cool;1-Heat | 1 Bit | 1.100 heating/cooling | CRT |
| 566 | AC13 Status_ Mode Auto [DPT_1.002] | 1-AUTO mode is active | 1 Bit | 1.2 boolean | CRT |
| 567 | AC13 Status_ Mode Heat [DPT_1.002] | 1-HEAT mode is active | 1 Bit | 1.2 boolean | CRT |
| 568 | AC13 Status_ Mode Cool [DPT_1.002] | 1-COOL mode is active | 1 Bit | 1.2 boolean | CRT |
| 569 | AC13 Status_ Mode Fan [DPT_1.002] | 1-FAN mode is active | 1 Bit | 1.2 boolean | CRT |
| 570 | AC13 Status_ Mode Dry [DPT_1.002] | 1-DRY mode is active | 1 Bit | 1.2 boolean | CRT |
| 571 | AC13 Status_ Mode Text [DPT_16.001] | Mode Text | 14 Bytes | 16.1 Character String (ISO 8859-1) | CRT |
| 572 | AC13 Status_ Fan Speed [DPT_5.001] | 50% and 100% || 33%, 66% and 100% | 1 Byte | 5.1 percentage (0..100%) | CRT |
| 572 | AC13 Status_ Fan Speed [DPT_5.010] | Speed values: 1,2 || 1,2,3 | 1 Byte | 5.10 counter pulses (0..255) | CRT |
| 573 | AC13 Status_ Fan Speed Man/Auto [DPT_1.002] | 0-Manual;1-Auto | 1 Bit | 1.2 boolean | CRT |
| 574 | AC13 Status_ Fan Speed 1 [DPT_1.002] | 1-Fan in Speed 1 | 1 Bit | 1.2 boolean | CRT |
| 575 | AC13 Status_ Fan Speed 2 [DPT_1.002] | 1-Fan in Speed 2 | 1 Bit | 1.2 boolean | CRT |
| 576 | AC13 Status_ Fan Speed 3 [DPT_1.002] | 1-Fan in Speed 3 | 1 Bit | 1.2 boolean | CRT |
| 577 | AC13 Status_ Fan Speed Text [DPT_16.001] | Fan Speed Text | 14 Bytes | 16.1 Character String (ISO 8859-1) | CRT |
| 578 | AC13 Status_ Vanes U-D Swing [DPT_1.002] | 0-Stop;1-Swing | 1 Bit | 1.2 boolean | CRT |
| 579 | AC13 Status_ Vanes U-D Text [DPT_16.001] | Vanes Text | 14 Bytes | 16.1 Character String (ISO 8859-1) | CRT |
| 580 | AC13 Status_ AC Setpoint Temperature [DPT_9.001] | ºC | 2 Bytes | 9.1 temperature (°C) | CRT |
| 581 | AC13 Status_ AC Ambient Reference Temperature [DPT_9.001] | ºC | 2 Bytes | 9.1 temperature (°C) | CRT |
| 582 | AC13 Status_ Error/Alarm [DPT_1.005] | 0-No alarm;1-Alarm | 1 Bit | 1.5 alarm | CRT |
| 583 | AC13 Status_ Error Code [2-byte signed value] | Error Code | 2 Bytes | 8.1 pulses difference | CRT |
| 584 | AC13 Status_ Error Text [DPT_16.001] | Error Text | 14 Bytes | 16.1 Character String (ISO 8859-1) | CRT |
| 585 | AC13 Status_ Remote Lock [DPT_1.003] | 0-Unlocked;1-Locked | 1 Bit | 1.3 enable | CRT |
| 586 | AC14 Control_ On/Off [DPT_1.001] | 0-Off;1-On | 1 Bit | 1.1 switch | CW |
| 587 | AC14 Control_ Operating Mode [DPT_20.102] | 0-Aut;1-Com;2-Stan;3-Eco;4-Pro | 1 Byte | 20.102 HVAC mode | CW |
| 588 | AC14 Control_ Mode [DPT_20.105] | 0-Aut;1-Hea;3-Coo;9-Fan;14-Dry | 1 Byte | 20.105 HVAC control mode | CW |
| 589 | AC14 Control_ Mode Cool/Heat [DPT_1.100] | 0-Cool;1-Heat | 1 Bit | 1.100 heating/cooling | CW |
| 590 | AC14 Control_ Mode Auto [DPT_1.002] | 1-Set AUTO mode | 1 Bit | 1.2 boolean | CW |
| 591 | AC14 Control_ Mode Heat [DPT_1.002] | 1-Set HEAT mode | 1 Bit | 1.2 boolean | CW |
| 592 | AC14 Control_ Mode Cool [DPT_1.002] | 1-Set COOL mode | 1 Bit | 1.2 boolean | CW |
| 593 | AC14 Control_ Mode Fan [DPT_1.002] | 1-Set FAN mode | 1 Bit | 1.2 boolean | CW |
| 594 | AC14 Control_ Mode Dry [DPT_1.002] | 1-Set DRY mode | 1 Bit | 1.2 boolean | CW |
| 595 | AC14 Control_ Mode +/- [DPT_1.007] | 0-Dec.;1-Inc. | 1 Bit | 1.7 step | CW |
| 595 | AC14 Control_ Mode +/- [DPT_1.008] | 0-Up;1-Down | 1 Bit | 1.8 up/down | CW |
| 596 | AC14 Control_ Fan Speed [DPT_5.001] | Thresholds: 75% || 50% and 83% | 1 Byte | 5.1 percentage (0..100%) | CW |
| 596 | AC14 Control_ Fan Speed [DPT_5.010] | Speed values: 1,2 || 1,2,3 | 1 Byte | 5.10 counter pulses (0..255) | CW |
| 597 | AC14 Control_ Fan Speed Man/Auto [DPT_1.002] | 0-Manual;1-Auto | 1 Bit | 1.2 boolean | CW |
| 598 | AC14 Control_ Fan Speed 1 [DPT_1.002] | 1-Set Fan Speed 1 | 1 Bit | 1.2 boolean | CW |
| 599 | AC14 Control_ Fan Speed 2 [DPT_1.002] | 1-Set Fan Speed 2 | 1 Bit | 1.2 boolean | CW |
| 600 | AC14 Control_ Fan Speed 3 [DPT_1.002] | 1-Set Fan Speed 3 | 1 Bit | 1.2 boolean | CW |
| 601 | AC14 Control_ Fan Speed +/- [DPT_1.007] | 0-Dec.;1-Inc. | 1 Bit | 1.7 step | CW |
| 601 | AC14 Control_ Fan Speed +/- [DPT_1.008] | 0-Up;1-Down | 1 Bit | 1.8 up/down | CW |
| 602 | AC14 Control_ Vanes U-D Swing [DPT_1.002] | 0-Stop;1-Swing | 1 Bit | 1.2 boolean | CW |
| 603 | AC14 Control_ Setpoint Temperature [DPT_9.001] | ºC | 2 Bytes | 9.1 temperature (°C) | CW |
| 604 | AC14 Control_ Setpoint Temperature +/- [DPT_1.007] | 0-Dec.;1-Inc. | 1 Bit | 1.7 step | CW |
| 604 | AC14 Control_ Setpoint Temperature +/- [DPT_1.008] | 0-Up;1-Down | 1 Bit | 1.8 up/down | CW |
| 605 | AC14 Control_ Ambient Temperature [DPT_9.001] | ºC | 2 Bytes | 9.1 temperature (°C) | CW |
| 606 | AC14 Control_ Remote Lock [DPT_1.003] | 0-Unlock;1-Lock | 1 Bit | 1.3 enable | CW |
| 607 | AC14 Status_ On/Off [DPT_1.001] | 0-Off;1-On | 1 Bit | 1.1 switch | CRT |
| 608 | AC14 Status_ Operating Mode [DPT_20.102] | 0-Aut;1-Com;2-Stan;3-Eco;4-Pro | 1 Byte | 20.102 HVAC mode | CRT |
| 609 | AC14 Status_ Mode [DPT_20.105] | 0-Aut;1-Hea;3-Coo;9-Fan;14-Dry | 1 Byte | 20.105 HVAC control mode | CRT |
| 610 | AC14 Status_ Mode Cool/Heat [DPT_1.100] | 0-Cool;1-Heat | 1 Bit | 1.100 heating/cooling | CRT |
| 611 | AC14 Status_ Mode Auto [DPT_1.002] | 1-AUTO mode is active | 1 Bit | 1.2 boolean | CRT |
| 612 | AC14 Status_ Mode Heat [DPT_1.002] | 1-HEAT mode is active | 1 Bit | 1.2 boolean | CRT |
| 613 | AC14 Status_ Mode Cool [DPT_1.002] | 1-COOL mode is active | 1 Bit | 1.2 boolean | CRT |
| 614 | AC14 Status_ Mode Fan [DPT_1.002] | 1-FAN mode is active | 1 Bit | 1.2 boolean | CRT |
| 615 | AC14 Status_ Mode Dry [DPT_1.002] | 1-DRY mode is active | 1 Bit | 1.2 boolean | CRT |
| 616 | AC14 Status_ Mode Text [DPT_16.001] | Mode Text | 14 Bytes | 16.1 Character String (ISO 8859-1) | CRT |
| 617 | AC14 Status_ Fan Speed [DPT_5.001] | 50% and 100% || 33%, 66% and 100% | 1 Byte | 5.1 percentage (0..100%) | CRT |
| 617 | AC14 Status_ Fan Speed [DPT_5.010] | Speed values: 1,2 || 1,2,3 | 1 Byte | 5.10 counter pulses (0..255) | CRT |
| 618 | AC14 Status_ Fan Speed Man/Auto [DPT_1.002] | 0-Manual;1-Auto | 1 Bit | 1.2 boolean | CRT |
| 619 | AC14 Status_ Fan Speed 1 [DPT_1.002] | 1-Fan in Speed 1 | 1 Bit | 1.2 boolean | CRT |
| 620 | AC14 Status_ Fan Speed 2 [DPT_1.002] | 1-Fan in Speed 2 | 1 Bit | 1.2 boolean | CRT |
| 621 | AC14 Status_ Fan Speed 3 [DPT_1.002] | 1-Fan in Speed 3 | 1 Bit | 1.2 boolean | CRT |
| 622 | AC14 Status_ Fan Speed Text [DPT_16.001] | Fan Speed Text | 14 Bytes | 16.1 Character String (ISO 8859-1) | CRT |
| 623 | AC14 Status_ Vanes U-D Swing [DPT_1.002] | 0-Stop;1-Swing | 1 Bit | 1.2 boolean | CRT |
| 624 | AC14 Status_ Vanes U-D Text [DPT_16.001] | Vanes Text | 14 Bytes | 16.1 Character String (ISO 8859-1) | CRT |
| 625 | AC14 Status_ AC Setpoint Temperature [DPT_9.001] | ºC | 2 Bytes | 9.1 temperature (°C) | CRT |
| 626 | AC14 Status_ AC Ambient Reference Temperature [DPT_9.001] | ºC | 2 Bytes | 9.1 temperature (°C) | CRT |
| 627 | AC14 Status_ Error/Alarm [DPT_1.005] | 0-No alarm;1-Alarm | 1 Bit | 1.5 alarm | CRT |
| 628 | AC14 Status_ Error Code [2-byte signed value] | Error Code | 2 Bytes | 8.1 pulses difference | CRT |
| 629 | AC14 Status_ Error Text [DPT_16.001] | Error Text | 14 Bytes | 16.1 Character String (ISO 8859-1) | CRT |
| 630 | AC14 Status_ Remote Lock [DPT_1.003] | 0-Unlocked;1-Locked | 1 Bit | 1.3 enable | CRT |
| 631 | AC15 Control_ On/Off [DPT_1.001] | 0-Off;1-On | 1 Bit | 1.1 switch | CW |
| 632 | AC15 Control_ Operating Mode [DPT_20.102] | 0-Aut;1-Com;2-Stan;3-Eco;4-Pro | 1 Byte | 20.102 HVAC mode | CW |
| 633 | AC15 Control_ Mode [DPT_20.105] | 0-Aut;1-Hea;3-Coo;9-Fan;14-Dry | 1 Byte | 20.105 HVAC control mode | CW |
| 634 | AC15 Control_ Mode Cool/Heat [DPT_1.100] | 0-Cool;1-Heat | 1 Bit | 1.100 heating/cooling | CW |
| 635 | AC15 Control_ Mode Auto [DPT_1.002] | 1-Set AUTO mode | 1 Bit | 1.2 boolean | CW |
| 636 | AC15 Control_ Mode Heat [DPT_1.002] | 1-Set HEAT mode | 1 Bit | 1.2 boolean | CW |
| 637 | AC15 Control_ Mode Cool [DPT_1.002] | 1-Set COOL mode | 1 Bit | 1.2 boolean | CW |
| 638 | AC15 Control_ Mode Fan [DPT_1.002] | 1-Set FAN mode | 1 Bit | 1.2 boolean | CW |
| 639 | AC15 Control_ Mode Dry [DPT_1.002] | 1-Set DRY mode | 1 Bit | 1.2 boolean | CW |
| 640 | AC15 Control_ Mode +/- [DPT_1.007] | 0-Dec.;1-Inc. | 1 Bit | 1.7 step | CW |
| 640 | AC15 Control_ Mode +/- [DPT_1.008] | 0-Up;1-Down | 1 Bit | 1.8 up/down | CW |
| 641 | AC15 Control_ Fan Speed [DPT_5.001] | Thresholds: 75% || 50% and 83% | 1 Byte | 5.1 percentage (0..100%) | CW |
| 641 | AC15 Control_ Fan Speed [DPT_5.010] | Speed values: 1,2 || 1,2,3 | 1 Byte | 5.10 counter pulses (0..255) | CW |
| 642 | AC15 Control_ Fan Speed Man/Auto [DPT_1.002] | 0-Manual;1-Auto | 1 Bit | 1.2 boolean | CW |
| 643 | AC15 Control_ Fan Speed 1 [DPT_1.002] | 1-Set Fan Speed 1 | 1 Bit | 1.2 boolean | CW |
| 644 | AC15 Control_ Fan Speed 2 [DPT_1.002] | 1-Set Fan Speed 2 | 1 Bit | 1.2 boolean | CW |
| 645 | AC15 Control_ Fan Speed 3 [DPT_1.002] | 1-Set Fan Speed 3 | 1 Bit | 1.2 boolean | CW |
| 646 | AC15 Control_ Fan Speed +/- [DPT_1.007] | 0-Dec.;1-Inc. | 1 Bit | 1.7 step | CW |
| 646 | AC15 Control_ Fan Speed +/- [DPT_1.008] | 0-Up;1-Down | 1 Bit | 1.8 up/down | CW |
| 647 | AC15 Control_ Vanes U-D Swing [DPT_1.002] | 0-Stop;1-Swing | 1 Bit | 1.2 boolean | CW |
| 648 | AC15 Control_ Setpoint Temperature [DPT_9.001] | ºC | 2 Bytes | 9.1 temperature (°C) | CW |
| 649 | AC15 Control_ Setpoint Temperature +/- [DPT_1.007] | 0-Dec.;1-Inc. | 1 Bit | 1.7 step | CW |
| 649 | AC15 Control_ Setpoint Temperature +/- [DPT_1.008] | 0-Up;1-Down | 1 Bit | 1.8 up/down | CW |
| 650 | AC15 Control_ Ambient Temperature [DPT_9.001] | ºC | 2 Bytes | 9.1 temperature (°C) | CW |
| 651 | AC15 Control_ Remote Lock [DPT_1.003] | 0-Unlock;1-Lock | 1 Bit | 1.3 enable | CW |
| 652 | AC15 Status_ On/Off [DPT_1.001] | 0-Off;1-On | 1 Bit | 1.1 switch | CRT |
| 653 | AC15 Status_ Operating Mode [DPT_20.102] | 0-Aut;1-Com;2-Stan;3-Eco;4-Pro | 1 Byte | 20.102 HVAC mode | CRT |
| 654 | AC15 Status_ Mode [DPT_20.105] | 0-Aut;1-Hea;3-Coo;9-Fan;14-Dry | 1 Byte | 20.105 HVAC control mode | CRT |
| 655 | AC15 Status_ Mode Cool/Heat [DPT_1.100] | 0-Cool;1-Heat | 1 Bit | 1.100 heating/cooling | CRT |
| 656 | AC15 Status_ Mode Auto [DPT_1.002] | 1-AUTO mode is active | 1 Bit | 1.2 boolean | CRT |
| 657 | AC15 Status_ Mode Heat [DPT_1.002] | 1-HEAT mode is active | 1 Bit | 1.2 boolean | CRT |
| 658 | AC15 Status_ Mode Cool [DPT_1.002] | 1-COOL mode is active | 1 Bit | 1.2 boolean | CRT |
| 659 | AC15 Status_ Mode Fan [DPT_1.002] | 1-FAN mode is active | 1 Bit | 1.2 boolean | CRT |
| 660 | AC15 Status_ Mode Dry [DPT_1.002] | 1-DRY mode is active | 1 Bit | 1.2 boolean | CRT |
| 661 | AC15 Status_ Mode Text [DPT_16.001] | Mode Text | 14 Bytes | 16.1 Character String (ISO 8859-1) | CRT |
| 662 | AC15 Status_ Fan Speed [DPT_5.001] | 50% and 100% || 33%, 66% and 100% | 1 Byte | 5.1 percentage (0..100%) | CRT |
| 662 | AC15 Status_ Fan Speed [DPT_5.010] | Speed values: 1,2 || 1,2,3 | 1 Byte | 5.10 counter pulses (0..255) | CRT |
| 663 | AC15 Status_ Fan Speed Man/Auto [DPT_1.002] | 0-Manual;1-Auto | 1 Bit | 1.2 boolean | CRT |
| 664 | AC15 Status_ Fan Speed 1 [DPT_1.002] | 1-Fan in Speed 1 | 1 Bit | 1.2 boolean | CRT |
| 665 | AC15 Status_ Fan Speed 2 [DPT_1.002] | 1-Fan in Speed 2 | 1 Bit | 1.2 boolean | CRT |
| 666 | AC15 Status_ Fan Speed 3 [DPT_1.002] | 1-Fan in Speed 3 | 1 Bit | 1.2 boolean | CRT |
| 667 | AC15 Status_ Fan Speed Text [DPT_16.001] | Fan Speed Text | 14 Bytes | 16.1 Character String (ISO 8859-1) | CRT |
| 668 | AC15 Status_ Vanes U-D Swing [DPT_1.002] | 0-Stop;1-Swing | 1 Bit | 1.2 boolean | CRT |
| 669 | AC15 Status_ Vanes U-D Text [DPT_16.001] | Vanes Text | 14 Bytes | 16.1 Character String (ISO 8859-1) | CRT |
| 670 | AC15 Status_ AC Setpoint Temperature [DPT_9.001] | ºC | 2 Bytes | 9.1 temperature (°C) | CRT |
| 671 | AC15 Status_ AC Ambient Reference Temperature [DPT_9.001] | ºC | 2 Bytes | 9.1 temperature (°C) | CRT |
| 672 | AC15 Status_ Error/Alarm [DPT_1.005] | 0-No alarm;1-Alarm | 1 Bit | 1.5 alarm | CRT |
| 673 | AC15 Status_ Error Code [2-byte signed value] | Error Code | 2 Bytes | 8.1 pulses difference | CRT |
| 674 | AC15 Status_ Error Text [DPT_16.001] | Error Text | 14 Bytes | 16.1 Character String (ISO 8859-1) | CRT |
| 675 | AC15 Status_ Remote Lock [DPT_1.003] | 0-Unlocked;1-Locked | 1 Bit | 1.3 enable | CRT |
| 676 | AC16 Control_ On/Off [DPT_1.001] | 0-Off;1-On | 1 Bit | 1.1 switch | CW |
| 677 | AC16 Control_ Operating Mode [DPT_20.102] | 0-Aut;1-Com;2-Stan;3-Eco;4-Pro | 1 Byte | 20.102 HVAC mode | CW |
| 678 | AC16 Control_ Mode [DPT_20.105] | 0-Aut;1-Hea;3-Coo;9-Fan;14-Dry | 1 Byte | 20.105 HVAC control mode | CW |
| 679 | AC16 Control_ Mode Cool/Heat [DPT_1.100] | 0-Cool;1-Heat | 1 Bit | 1.100 heating/cooling | CW |
| 680 | AC16 Control_ Mode Auto [DPT_1.002] | 1-Set AUTO mode | 1 Bit | 1.2 boolean | CW |
| 681 | AC16 Control_ Mode Heat [DPT_1.002] | 1-Set HEAT mode | 1 Bit | 1.2 boolean | CW |
| 682 | AC16 Control_ Mode Cool [DPT_1.002] | 1-Set COOL mode | 1 Bit | 1.2 boolean | CW |
| 683 | AC16 Control_ Mode Fan [DPT_1.002] | 1-Set FAN mode | 1 Bit | 1.2 boolean | CW |
| 684 | AC16 Control_ Mode Dry [DPT_1.002] | 1-Set DRY mode | 1 Bit | 1.2 boolean | CW |
| 685 | AC16 Control_ Mode +/- [DPT_1.007] | 0-Dec.;1-Inc. | 1 Bit | 1.7 step | CW |
| 685 | AC16 Control_ Mode +/- [DPT_1.008] | 0-Up;1-Down | 1 Bit | 1.8 up/down | CW |
| 686 | AC16 Control_ Fan Speed [DPT_5.001] | Thresholds: 75% || 50% and 83% | 1 Byte | 5.1 percentage (0..100%) | CW |
| 686 | AC16 Control_ Fan Speed [DPT_5.010] | Speed values: 1,2 || 1,2,3 | 1 Byte | 5.10 counter pulses (0..255) | CW |
| 687 | AC16 Control_ Fan Speed Man/Auto [DPT_1.002] | 0-Manual;1-Auto | 1 Bit | 1.2 boolean | CW |
| 688 | AC16 Control_ Fan Speed 1 [DPT_1.002] | 1-Set Fan Speed 1 | 1 Bit | 1.2 boolean | CW |
| 689 | AC16 Control_ Fan Speed 2 [DPT_1.002] | 1-Set Fan Speed 2 | 1 Bit | 1.2 boolean | CW |
| 690 | AC16 Control_ Fan Speed 3 [DPT_1.002] | 1-Set Fan Speed 3 | 1 Bit | 1.2 boolean | CW |
| 691 | AC16 Control_ Fan Speed +/- [DPT_1.007] | 0-Dec.;1-Inc. | 1 Bit | 1.7 step | CW |
| 691 | AC16 Control_ Fan Speed +/- [DPT_1.008] | 0-Up;1-Down | 1 Bit | 1.8 up/down | CW |
| 692 | AC16 Control_ Vanes U-D Swing [DPT_1.002] | 0-Stop;1-Swing | 1 Bit | 1.2 boolean | CW |
| 693 | AC16 Control_ Setpoint Temperature [DPT_9.001] | ºC | 2 Bytes | 9.1 temperature (°C) | CW |
| 694 | AC16 Control_ Setpoint Temperature +/- [DPT_1.007] | 0-Dec.;1-Inc. | 1 Bit | 1.7 step | CW |
| 694 | AC16 Control_ Setpoint Temperature +/- [DPT_1.008] | 0-Up;1-Down | 1 Bit | 1.8 up/down | CW |
| 695 | AC16 Control_ Ambient Temperature [DPT_9.001] | ºC | 2 Bytes | 9.1 temperature (°C) | CW |
| 696 | AC16 Control_ Remote Lock [DPT_1.003] | 0-Unlock;1-Lock | 1 Bit | 1.3 enable | CW |
| 697 | AC16 Status_ On/Off [DPT_1.001] | 0-Off;1-On | 1 Bit | 1.1 switch | CRT |
| 698 | AC16 Status_ Operating Mode [DPT_20.102] | 0-Aut;1-Com;2-Stan;3-Eco;4-Pro | 1 Byte | 20.102 HVAC mode | CRT |
| 699 | AC16 Status_ Mode [DPT_20.105] | 0-Aut;1-Hea;3-Coo;9-Fan;14-Dry | 1 Byte | 20.105 HVAC control mode | CRT |
| 700 | AC16 Status_ Mode Cool/Heat [DPT_1.100] | 0-Cool;1-Heat | 1 Bit | 1.100 heating/cooling | CRT |
| 701 | AC16 Status_ Mode Auto [DPT_1.002] | 1-AUTO mode is active | 1 Bit | 1.2 boolean | CRT |
| 702 | AC16 Status_ Mode Heat [DPT_1.002] | 1-HEAT mode is active | 1 Bit | 1.2 boolean | CRT |
| 703 | AC16 Status_ Mode Cool [DPT_1.002] | 1-COOL mode is active | 1 Bit | 1.2 boolean | CRT |
| 704 | AC16 Status_ Mode Fan [DPT_1.002] | 1-FAN mode is active | 1 Bit | 1.2 boolean | CRT |
| 705 | AC16 Status_ Mode Dry [DPT_1.002] | 1-DRY mode is active | 1 Bit | 1.2 boolean | CRT |
| 706 | AC16 Status_ Mode Text [DPT_16.001] | Mode Text | 14 Bytes | 16.1 Character String (ISO 8859-1) | CRT |
| 707 | AC16 Status_ Fan Speed [DPT_5.001] | 50% and 100% || 33%, 66% and 100% | 1 Byte | 5.1 percentage (0..100%) | CRT |
| 707 | AC16 Status_ Fan Speed [DPT_5.010] | Speed values: 1,2 || 1,2,3 | 1 Byte | 5.10 counter pulses (0..255) | CRT |
| 708 | AC16 Status_ Fan Speed Man/Auto [DPT_1.002] | 0-Manual;1-Auto | 1 Bit | 1.2 boolean | CRT |
| 709 | AC16 Status_ Fan Speed 1 [DPT_1.002] | 1-Fan in Speed 1 | 1 Bit | 1.2 boolean | CRT |
| 710 | AC16 Status_ Fan Speed 2 [DPT_1.002] | 1-Fan in Speed 2 | 1 Bit | 1.2 boolean | CRT |
| 711 | AC16 Status_ Fan Speed 3 [DPT_1.002] | 1-Fan in Speed 3 | 1 Bit | 1.2 boolean | CRT |
| 712 | AC16 Status_ Fan Speed Text [DPT_16.001] | Fan Speed Text | 14 Bytes | 16.1 Character String (ISO 8859-1) | CRT |
| 713 | AC16 Status_ Vanes U-D Swing [DPT_1.002] | 0-Stop;1-Swing | 1 Bit | 1.2 boolean | CRT |
| 714 | AC16 Status_ Vanes U-D Text [DPT_16.001] | Vanes Text | 14 Bytes | 16.1 Character String (ISO 8859-1) | CRT |
| 715 | AC16 Status_ AC Setpoint Temperature [DPT_9.001] | ºC | 2 Bytes | 9.1 temperature (°C) | CRT |
| 716 | AC16 Status_ AC Ambient Reference Temperature [DPT_9.001] | ºC | 2 Bytes | 9.1 temperature (°C) | CRT |
| 717 | AC16 Status_ Error/Alarm [DPT_1.005] | 0-No alarm;1-Alarm | 1 Bit | 1.5 alarm | CRT |
| 718 | AC16 Status_ Error Code [2-byte signed value] | Error Code | 2 Bytes | 8.1 pulses difference | CRT |
| 719 | AC16 Status_ Error Text [DPT_16.001] | Error Text | 14 Bytes | 16.1 Character String (ISO 8859-1) | CRT |
| 720 | AC16 Status_ Remote Lock [DPT_1.003] | 0-Unlocked;1-Locked | 1 Bit | 1.3 enable | CRT |
| 721 | AC17 Control_ On/Off [DPT_1.001] | 0-Off;1-On | 1 Bit | 1.1 switch | CW |
| 722 | AC17 Control_ Operating Mode [DPT_20.102] | 0-Aut;1-Com;2-Stan;3-Eco;4-Pro | 1 Byte | 20.102 HVAC mode | CW |
| 723 | AC17 Control_ Mode [DPT_20.105] | 0-Aut;1-Hea;3-Coo;9-Fan;14-Dry | 1 Byte | 20.105 HVAC control mode | CW |
| 724 | AC17 Control_ Mode Cool/Heat [DPT_1.100] | 0-Cool;1-Heat | 1 Bit | 1.100 heating/cooling | CW |
| 725 | AC17 Control_ Mode Auto [DPT_1.002] | 1-Set AUTO mode | 1 Bit | 1.2 boolean | CW |
| 726 | AC17 Control_ Mode Heat [DPT_1.002] | 1-Set HEAT mode | 1 Bit | 1.2 boolean | CW |
| 727 | AC17 Control_ Mode Cool [DPT_1.002] | 1-Set COOL mode | 1 Bit | 1.2 boolean | CW |
| 728 | AC17 Control_ Mode Fan [DPT_1.002] | 1-Set FAN mode | 1 Bit | 1.2 boolean | CW |
| 729 | AC17 Control_ Mode Dry [DPT_1.002] | 1-Set DRY mode | 1 Bit | 1.2 boolean | CW |
| 730 | AC17 Control_ Mode +/- [DPT_1.007] | 0-Dec.;1-Inc. | 1 Bit | 1.7 step | CW |
| 730 | AC17 Control_ Mode +/- [DPT_1.008] | 0-Up;1-Down | 1 Bit | 1.8 up/down | CW |
| 731 | AC17 Control_ Fan Speed [DPT_5.001] | Thresholds: 75% || 50% and 83% | 1 Byte | 5.1 percentage (0..100%) | CW |
| 731 | AC17 Control_ Fan Speed [DPT_5.010] | Speed values: 1,2 || 1,2,3 | 1 Byte | 5.10 counter pulses (0..255) | CW |
| 732 | AC17 Control_ Fan Speed Man/Auto [DPT_1.002] | 0-Manual;1-Auto | 1 Bit | 1.2 boolean | CW |
| 733 | AC17 Control_ Fan Speed 1 [DPT_1.002] | 1-Set Fan Speed 1 | 1 Bit | 1.2 boolean | CW |
| 734 | AC17 Control_ Fan Speed 2 [DPT_1.002] | 1-Set Fan Speed 2 | 1 Bit | 1.2 boolean | CW |
| 735 | AC17 Control_ Fan Speed 3 [DPT_1.002] | 1-Set Fan Speed 3 | 1 Bit | 1.2 boolean | CW |
| 736 | AC17 Control_ Fan Speed +/- [DPT_1.007] | 0-Dec.;1-Inc. | 1 Bit | 1.7 step | CW |
| 736 | AC17 Control_ Fan Speed +/- [DPT_1.008] | 0-Up;1-Down | 1 Bit | 1.8 up/down | CW |
| 737 | AC17 Control_ Vanes U-D Swing [DPT_1.002] | 0-Stop;1-Swing | 1 Bit | 1.2 boolean | CW |
| 738 | AC17 Control_ Setpoint Temperature [DPT_9.001] | ºC | 2 Bytes | 9.1 temperature (°C) | CW |
| 739 | AC17 Control_ Setpoint Temperature +/- [DPT_1.007] | 0-Dec.;1-Inc. | 1 Bit | 1.7 step | CW |
| 739 | AC17 Control_ Setpoint Temperature +/- [DPT_1.008] | 0-Up;1-Down | 1 Bit | 1.8 up/down | CW |
| 740 | AC17 Control_ Ambient Temperature [DPT_9.001] | ºC | 2 Bytes | 9.1 temperature (°C) | CW |
| 741 | AC17 Control_ Remote Lock [DPT_1.003] | 0-Unlock;1-Lock | 1 Bit | 1.3 enable | CW |
| 742 | AC17 Status_ On/Off [DPT_1.001] | 0-Off;1-On | 1 Bit | 1.1 switch | CRT |
| 743 | AC17 Status_ Operating Mode [DPT_20.102] | 0-Aut;1-Com;2-Stan;3-Eco;4-Pro | 1 Byte | 20.102 HVAC mode | CRT |
| 744 | AC17 Status_ Mode [DPT_20.105] | 0-Aut;1-Hea;3-Coo;9-Fan;14-Dry | 1 Byte | 20.105 HVAC control mode | CRT |
| 745 | AC17 Status_ Mode Cool/Heat [DPT_1.100] | 0-Cool;1-Heat | 1 Bit | 1.100 heating/cooling | CRT |
| 746 | AC17 Status_ Mode Auto [DPT_1.002] | 1-AUTO mode is active | 1 Bit | 1.2 boolean | CRT |
| 747 | AC17 Status_ Mode Heat [DPT_1.002] | 1-HEAT mode is active | 1 Bit | 1.2 boolean | CRT |
| 748 | AC17 Status_ Mode Cool [DPT_1.002] | 1-COOL mode is active | 1 Bit | 1.2 boolean | CRT |
| 749 | AC17 Status_ Mode Fan [DPT_1.002] | 1-FAN mode is active | 1 Bit | 1.2 boolean | CRT |
| 750 | AC17 Status_ Mode Dry [DPT_1.002] | 1-DRY mode is active | 1 Bit | 1.2 boolean | CRT |
| 751 | AC17 Status_ Mode Text [DPT_16.001] | Mode Text | 14 Bytes | 16.1 Character String (ISO 8859-1) | CRT |
| 752 | AC17 Status_ Fan Speed [DPT_5.001] | 50% and 100% || 33%, 66% and 100% | 1 Byte | 5.1 percentage (0..100%) | CRT |
| 752 | AC17 Status_ Fan Speed [DPT_5.010] | Speed values: 1,2 || 1,2,3 | 1 Byte | 5.10 counter pulses (0..255) | CRT |
| 753 | AC17 Status_ Fan Speed Man/Auto [DPT_1.002] | 0-Manual;1-Auto | 1 Bit | 1.2 boolean | CRT |
| 754 | AC17 Status_ Fan Speed 1 [DPT_1.002] | 1-Fan in Speed 1 | 1 Bit | 1.2 boolean | CRT |
| 755 | AC17 Status_ Fan Speed 2 [DPT_1.002] | 1-Fan in Speed 2 | 1 Bit | 1.2 boolean | CRT |
| 756 | AC17 Status_ Fan Speed 3 [DPT_1.002] | 1-Fan in Speed 3 | 1 Bit | 1.2 boolean | CRT |
| 757 | AC17 Status_ Fan Speed Text [DPT_16.001] | Fan Speed Text | 14 Bytes | 16.1 Character String (ISO 8859-1) | CRT |
| 758 | AC17 Status_ Vanes U-D Swing [DPT_1.002] | 0-Stop;1-Swing | 1 Bit | 1.2 boolean | CRT |
| 759 | AC17 Status_ Vanes U-D Text [DPT_16.001] | Vanes Text | 14 Bytes | 16.1 Character String (ISO 8859-1) | CRT |
| 760 | AC17 Status_ AC Setpoint Temperature [DPT_9.001] | ºC | 2 Bytes | 9.1 temperature (°C) | CRT |
| 761 | AC17 Status_ AC Ambient Reference Temperature [DPT_9.001] | ºC | 2 Bytes | 9.1 temperature (°C) | CRT |
| 762 | AC17 Status_ Error/Alarm [DPT_1.005] | 0-No alarm;1-Alarm | 1 Bit | 1.5 alarm | CRT |
| 763 | AC17 Status_ Error Code [2-byte signed value] | Error Code | 2 Bytes | 8.1 pulses difference | CRT |
| 764 | AC17 Status_ Error Text [DPT_16.001] | Error Text | 14 Bytes | 16.1 Character String (ISO 8859-1) | CRT |
| 765 | AC17 Status_ Remote Lock [DPT_1.003] | 0-Unlocked;1-Locked | 1 Bit | 1.3 enable | CRT |
| 766 | AC18 Control_ On/Off [DPT_1.001] | 0-Off;1-On | 1 Bit | 1.1 switch | CW |
| 767 | AC18 Control_ Operating Mode [DPT_20.102] | 0-Aut;1-Com;2-Stan;3-Eco;4-Pro | 1 Byte | 20.102 HVAC mode | CW |
| 768 | AC18 Control_ Mode [DPT_20.105] | 0-Aut;1-Hea;3-Coo;9-Fan;14-Dry | 1 Byte | 20.105 HVAC control mode | CW |
| 769 | AC18 Control_ Mode Cool/Heat [DPT_1.100] | 0-Cool;1-Heat | 1 Bit | 1.100 heating/cooling | CW |
| 770 | AC18 Control_ Mode Auto [DPT_1.002] | 1-Set AUTO mode | 1 Bit | 1.2 boolean | CW |
| 771 | AC18 Control_ Mode Heat [DPT_1.002] | 1-Set HEAT mode | 1 Bit | 1.2 boolean | CW |
| 772 | AC18 Control_ Mode Cool [DPT_1.002] | 1-Set COOL mode | 1 Bit | 1.2 boolean | CW |
| 773 | AC18 Control_ Mode Fan [DPT_1.002] | 1-Set FAN mode | 1 Bit | 1.2 boolean | CW |
| 774 | AC18 Control_ Mode Dry [DPT_1.002] | 1-Set DRY mode | 1 Bit | 1.2 boolean | CW |
| 775 | AC18 Control_ Mode +/- [DPT_1.007] | 0-Dec.;1-Inc. | 1 Bit | 1.7 step | CW |
| 775 | AC18 Control_ Mode +/- [DPT_1.008] | 0-Up;1-Down | 1 Bit | 1.8 up/down | CW |
| 776 | AC18 Control_ Fan Speed [DPT_5.001] | Thresholds: 75% || 50% and 83% | 1 Byte | 5.1 percentage (0..100%) | CW |
| 776 | AC18 Control_ Fan Speed [DPT_5.010] | Speed values: 1,2 || 1,2,3 | 1 Byte | 5.10 counter pulses (0..255) | CW |
| 777 | AC18 Control_ Fan Speed Man/Auto [DPT_1.002] | 0-Manual;1-Auto | 1 Bit | 1.2 boolean | CW |
| 778 | AC18 Control_ Fan Speed 1 [DPT_1.002] | 1-Set Fan Speed 1 | 1 Bit | 1.2 boolean | CW |
| 779 | AC18 Control_ Fan Speed 2 [DPT_1.002] | 1-Set Fan Speed 2 | 1 Bit | 1.2 boolean | CW |
| 780 | AC18 Control_ Fan Speed 3 [DPT_1.002] | 1-Set Fan Speed 3 | 1 Bit | 1.2 boolean | CW |
| 781 | AC18 Control_ Fan Speed +/- [DPT_1.007] | 0-Dec.;1-Inc. | 1 Bit | 1.7 step | CW |
| 781 | AC18 Control_ Fan Speed +/- [DPT_1.008] | 0-Up;1-Down | 1 Bit | 1.8 up/down | CW |
| 782 | AC18 Control_ Vanes U-D Swing [DPT_1.002] | 0-Stop;1-Swing | 1 Bit | 1.2 boolean | CW |
| 783 | AC18 Control_ Setpoint Temperature [DPT_9.001] | ºC | 2 Bytes | 9.1 temperature (°C) | CW |
| 784 | AC18 Control_ Setpoint Temperature +/- [DPT_1.007] | 0-Dec.;1-Inc. | 1 Bit | 1.7 step | CW |
| 784 | AC18 Control_ Setpoint Temperature +/- [DPT_1.008] | 0-Up;1-Down | 1 Bit | 1.8 up/down | CW |
| 785 | AC18 Control_ Ambient Temperature [DPT_9.001] | ºC | 2 Bytes | 9.1 temperature (°C) | CW |
| 786 | AC18 Control_ Remote Lock [DPT_1.003] | 0-Unlock;1-Lock | 1 Bit | 1.3 enable | CW |
| 787 | AC18 Status_ On/Off [DPT_1.001] | 0-Off;1-On | 1 Bit | 1.1 switch | CRT |
| 788 | AC18 Status_ Operating Mode [DPT_20.102] | 0-Aut;1-Com;2-Stan;3-Eco;4-Pro | 1 Byte | 20.102 HVAC mode | CRT |
| 789 | AC18 Status_ Mode [DPT_20.105] | 0-Aut;1-Hea;3-Coo;9-Fan;14-Dry | 1 Byte | 20.105 HVAC control mode | CRT |
| 790 | AC18 Status_ Mode Cool/Heat [DPT_1.100] | 0-Cool;1-Heat | 1 Bit | 1.100 heating/cooling | CRT |
| 791 | AC18 Status_ Mode Auto [DPT_1.002] | 1-AUTO mode is active | 1 Bit | 1.2 boolean | CRT |
| 792 | AC18 Status_ Mode Heat [DPT_1.002] | 1-HEAT mode is active | 1 Bit | 1.2 boolean | CRT |
| 793 | AC18 Status_ Mode Cool [DPT_1.002] | 1-COOL mode is active | 1 Bit | 1.2 boolean | CRT |
| 794 | AC18 Status_ Mode Fan [DPT_1.002] | 1-FAN mode is active | 1 Bit | 1.2 boolean | CRT |
| 795 | AC18 Status_ Mode Dry [DPT_1.002] | 1-DRY mode is active | 1 Bit | 1.2 boolean | CRT |
| 796 | AC18 Status_ Mode Text [DPT_16.001] | Mode Text | 14 Bytes | 16.1 Character String (ISO 8859-1) | CRT |
| 797 | AC18 Status_ Fan Speed [DPT_5.001] | 50% and 100% || 33%, 66% and 100% | 1 Byte | 5.1 percentage (0..100%) | CRT |
| 797 | AC18 Status_ Fan Speed [DPT_5.010] | Speed values: 1,2 || 1,2,3 | 1 Byte | 5.10 counter pulses (0..255) | CRT |
| 798 | AC18 Status_ Fan Speed Man/Auto [DPT_1.002] | 0-Manual;1-Auto | 1 Bit | 1.2 boolean | CRT |
| 799 | AC18 Status_ Fan Speed 1 [DPT_1.002] | 1-Fan in Speed 1 | 1 Bit | 1.2 boolean | CRT |
| 800 | AC18 Status_ Fan Speed 2 [DPT_1.002] | 1-Fan in Speed 2 | 1 Bit | 1.2 boolean | CRT |
| 801 | AC18 Status_ Fan Speed 3 [DPT_1.002] | 1-Fan in Speed 3 | 1 Bit | 1.2 boolean | CRT |
| 802 | AC18 Status_ Fan Speed Text [DPT_16.001] | Fan Speed Text | 14 Bytes | 16.1 Character String (ISO 8859-1) | CRT |
| 803 | AC18 Status_ Vanes U-D Swing [DPT_1.002] | 0-Stop;1-Swing | 1 Bit | 1.2 boolean | CRT |
| 804 | AC18 Status_ Vanes U-D Text [DPT_16.001] | Vanes Text | 14 Bytes | 16.1 Character String (ISO 8859-1) | CRT |
| 805 | AC18 Status_ AC Setpoint Temperature [DPT_9.001] | ºC | 2 Bytes | 9.1 temperature (°C) | CRT |
| 806 | AC18 Status_ AC Ambient Reference Temperature [DPT_9.001] | ºC | 2 Bytes | 9.1 temperature (°C) | CRT |
| 807 | AC18 Status_ Error/Alarm [DPT_1.005] | 0-No alarm;1-Alarm | 1 Bit | 1.5 alarm | CRT |
| 808 | AC18 Status_ Error Code [2-byte signed value] | Error Code | 2 Bytes | 8.1 pulses difference | CRT |
| 809 | AC18 Status_ Error Text [DPT_16.001] | Error Text | 14 Bytes | 16.1 Character String (ISO 8859-1) | CRT |
| 810 | AC18 Status_ Remote Lock [DPT_1.003] | 0-Unlocked;1-Locked | 1 Bit | 1.3 enable | CRT |
| 811 | AC19 Control_ On/Off [DPT_1.001] | 0-Off;1-On | 1 Bit | 1.1 switch | CW |
| 812 | AC19 Control_ Operating Mode [DPT_20.102] | 0-Aut;1-Com;2-Stan;3-Eco;4-Pro | 1 Byte | 20.102 HVAC mode | CW |
| 813 | AC19 Control_ Mode [DPT_20.105] | 0-Aut;1-Hea;3-Coo;9-Fan;14-Dry | 1 Byte | 20.105 HVAC control mode | CW |
| 814 | AC19 Control_ Mode Cool/Heat [DPT_1.100] | 0-Cool;1-Heat | 1 Bit | 1.100 heating/cooling | CW |
| 815 | AC19 Control_ Mode Auto [DPT_1.002] | 1-Set AUTO mode | 1 Bit | 1.2 boolean | CW |
| 816 | AC19 Control_ Mode Heat [DPT_1.002] | 1-Set HEAT mode | 1 Bit | 1.2 boolean | CW |
| 817 | AC19 Control_ Mode Cool [DPT_1.002] | 1-Set COOL mode | 1 Bit | 1.2 boolean | CW |
| 818 | AC19 Control_ Mode Fan [DPT_1.002] | 1-Set FAN mode | 1 Bit | 1.2 boolean | CW |
| 819 | AC19 Control_ Mode Dry [DPT_1.002] | 1-Set DRY mode | 1 Bit | 1.2 boolean | CW |
| 820 | AC19 Control_ Mode +/- [DPT_1.007] | 0-Dec.;1-Inc. | 1 Bit | 1.7 step | CW |
| 820 | AC19 Control_ Mode +/- [DPT_1.008] | 0-Up;1-Down | 1 Bit | 1.8 up/down | CW |
| 821 | AC19 Control_ Fan Speed [DPT_5.001] | Thresholds: 75% || 50% and 83% | 1 Byte | 5.1 percentage (0..100%) | CW |
| 821 | AC19 Control_ Fan Speed [DPT_5.010] | Speed values: 1,2 || 1,2,3 | 1 Byte | 5.10 counter pulses (0..255) | CW |
| 822 | AC19 Control_ Fan Speed Man/Auto [DPT_1.002] | 0-Manual;1-Auto | 1 Bit | 1.2 boolean | CW |
| 823 | AC19 Control_ Fan Speed 1 [DPT_1.002] | 1-Set Fan Speed 1 | 1 Bit | 1.2 boolean | CW |
| 824 | AC19 Control_ Fan Speed 2 [DPT_1.002] | 1-Set Fan Speed 2 | 1 Bit | 1.2 boolean | CW |
| 825 | AC19 Control_ Fan Speed 3 [DPT_1.002] | 1-Set Fan Speed 3 | 1 Bit | 1.2 boolean | CW |
| 826 | AC19 Control_ Fan Speed +/- [DPT_1.007] | 0-Dec.;1-Inc. | 1 Bit | 1.7 step | CW |
| 826 | AC19 Control_ Fan Speed +/- [DPT_1.008] | 0-Up;1-Down | 1 Bit | 1.8 up/down | CW |
| 827 | AC19 Control_ Vanes U-D Swing [DPT_1.002] | 0-Stop;1-Swing | 1 Bit | 1.2 boolean | CW |
| 828 | AC19 Control_ Setpoint Temperature [DPT_9.001] | ºC | 2 Bytes | 9.1 temperature (°C) | CW |
| 829 | AC19 Control_ Setpoint Temperature +/- [DPT_1.007] | 0-Dec.;1-Inc. | 1 Bit | 1.7 step | CW |
| 829 | AC19 Control_ Setpoint Temperature +/- [DPT_1.008] | 0-Up;1-Down | 1 Bit | 1.8 up/down | CW |
| 830 | AC19 Control_ Ambient Temperature [DPT_9.001] | ºC | 2 Bytes | 9.1 temperature (°C) | CW |
| 831 | AC19 Control_ Remote Lock [DPT_1.003] | 0-Unlock;1-Lock | 1 Bit | 1.3 enable | CW |
| 832 | AC19 Status_ On/Off [DPT_1.001] | 0-Off;1-On | 1 Bit | 1.1 switch | CRT |
| 833 | AC19 Status_ Operating Mode [DPT_20.102] | 0-Aut;1-Com;2-Stan;3-Eco;4-Pro | 1 Byte | 20.102 HVAC mode | CRT |
| 834 | AC19 Status_ Mode [DPT_20.105] | 0-Aut;1-Hea;3-Coo;9-Fan;14-Dry | 1 Byte | 20.105 HVAC control mode | CRT |
| 835 | AC19 Status_ Mode Cool/Heat [DPT_1.100] | 0-Cool;1-Heat | 1 Bit | 1.100 heating/cooling | CRT |
| 836 | AC19 Status_ Mode Auto [DPT_1.002] | 1-AUTO mode is active | 1 Bit | 1.2 boolean | CRT |
| 837 | AC19 Status_ Mode Heat [DPT_1.002] | 1-HEAT mode is active | 1 Bit | 1.2 boolean | CRT |
| 838 | AC19 Status_ Mode Cool [DPT_1.002] | 1-COOL mode is active | 1 Bit | 1.2 boolean | CRT |
| 839 | AC19 Status_ Mode Fan [DPT_1.002] | 1-FAN mode is active | 1 Bit | 1.2 boolean | CRT |
| 840 | AC19 Status_ Mode Dry [DPT_1.002] | 1-DRY mode is active | 1 Bit | 1.2 boolean | CRT |
| 841 | AC19 Status_ Mode Text [DPT_16.001] | Mode Text | 14 Bytes | 16.1 Character String (ISO 8859-1) | CRT |
| 842 | AC19 Status_ Fan Speed [DPT_5.001] | 50% and 100% || 33%, 66% and 100% | 1 Byte | 5.1 percentage (0..100%) | CRT |
| 842 | AC19 Status_ Fan Speed [DPT_5.010] | Speed values: 1,2 || 1,2,3 | 1 Byte | 5.10 counter pulses (0..255) | CRT |
| 843 | AC19 Status_ Fan Speed Man/Auto [DPT_1.002] | 0-Manual;1-Auto | 1 Bit | 1.2 boolean | CRT |
| 844 | AC19 Status_ Fan Speed 1 [DPT_1.002] | 1-Fan in Speed 1 | 1 Bit | 1.2 boolean | CRT |
| 845 | AC19 Status_ Fan Speed 2 [DPT_1.002] | 1-Fan in Speed 2 | 1 Bit | 1.2 boolean | CRT |
| 846 | AC19 Status_ Fan Speed 3 [DPT_1.002] | 1-Fan in Speed 3 | 1 Bit | 1.2 boolean | CRT |
| 847 | AC19 Status_ Fan Speed Text [DPT_16.001] | Fan Speed Text | 14 Bytes | 16.1 Character String (ISO 8859-1) | CRT |
| 848 | AC19 Status_ Vanes U-D Swing [DPT_1.002] | 0-Stop;1-Swing | 1 Bit | 1.2 boolean | CRT |
| 849 | AC19 Status_ Vanes U-D Text [DPT_16.001] | Vanes Text | 14 Bytes | 16.1 Character String (ISO 8859-1) | CRT |
| 850 | AC19 Status_ AC Setpoint Temperature [DPT_9.001] | ºC | 2 Bytes | 9.1 temperature (°C) | CRT |
| 851 | AC19 Status_ AC Ambient Reference Temperature [DPT_9.001] | ºC | 2 Bytes | 9.1 temperature (°C) | CRT |
| 852 | AC19 Status_ Error/Alarm [DPT_1.005] | 0-No alarm;1-Alarm | 1 Bit | 1.5 alarm | CRT |
| 853 | AC19 Status_ Error Code [2-byte signed value] | Error Code | 2 Bytes | 8.1 pulses difference | CRT |
| 854 | AC19 Status_ Error Text [DPT_16.001] | Error Text | 14 Bytes | 16.1 Character String (ISO 8859-1) | CRT |
| 855 | AC19 Status_ Remote Lock [DPT_1.003] | 0-Unlocked;1-Locked | 1 Bit | 1.3 enable | CRT |
| 856 | AC20 Control_ On/Off [DPT_1.001] | 0-Off;1-On | 1 Bit | 1.1 switch | CW |
| 857 | AC20 Control_ Operating Mode [DPT_20.102] | 0-Aut;1-Com;2-Stan;3-Eco;4-Pro | 1 Byte | 20.102 HVAC mode | CW |
| 858 | AC20 Control_ Mode [DPT_20.105] | 0-Aut;1-Hea;3-Coo;9-Fan;14-Dry | 1 Byte | 20.105 HVAC control mode | CW |
| 859 | AC20 Control_ Mode Cool/Heat [DPT_1.100] | 0-Cool;1-Heat | 1 Bit | 1.100 heating/cooling | CW |
| 860 | AC20 Control_ Mode Auto [DPT_1.002] | 1-Set AUTO mode | 1 Bit | 1.2 boolean | CW |
| 861 | AC20 Control_ Mode Heat [DPT_1.002] | 1-Set HEAT mode | 1 Bit | 1.2 boolean | CW |
| 862 | AC20 Control_ Mode Cool [DPT_1.002] | 1-Set COOL mode | 1 Bit | 1.2 boolean | CW |
| 863 | AC20 Control_ Mode Fan [DPT_1.002] | 1-Set FAN mode | 1 Bit | 1.2 boolean | CW |
| 864 | AC20 Control_ Mode Dry [DPT_1.002] | 1-Set DRY mode | 1 Bit | 1.2 boolean | CW |
| 865 | AC20 Control_ Mode +/- [DPT_1.007] | 0-Dec.;1-Inc. | 1 Bit | 1.7 step | CW |
| 865 | AC20 Control_ Mode +/- [DPT_1.008] | 0-Up;1-Down | 1 Bit | 1.8 up/down | CW |
| 866 | AC20 Control_ Fan Speed [DPT_5.001] | Thresholds: 75% || 50% and 83% | 1 Byte | 5.1 percentage (0..100%) | CW |
| 866 | AC20 Control_ Fan Speed [DPT_5.010] | Speed values: 1,2 || 1,2,3 | 1 Byte | 5.10 counter pulses (0..255) | CW |
| 867 | AC20 Control_ Fan Speed Man/Auto [DPT_1.002] | 0-Manual;1-Auto | 1 Bit | 1.2 boolean | CW |
| 868 | AC20 Control_ Fan Speed 1 [DPT_1.002] | 1-Set Fan Speed 1 | 1 Bit | 1.2 boolean | CW |
| 869 | AC20 Control_ Fan Speed 2 [DPT_1.002] | 1-Set Fan Speed 2 | 1 Bit | 1.2 boolean | CW |
| 870 | AC20 Control_ Fan Speed 3 [DPT_1.002] | 1-Set Fan Speed 3 | 1 Bit | 1.2 boolean | CW |
| 871 | AC20 Control_ Fan Speed +/- [DPT_1.007] | 0-Dec.;1-Inc. | 1 Bit | 1.7 step | CW |
| 871 | AC20 Control_ Fan Speed +/- [DPT_1.008] | 0-Up;1-Down | 1 Bit | 1.8 up/down | CW |
| 872 | AC20 Control_ Vanes U-D Swing [DPT_1.002] | 0-Stop;1-Swing | 1 Bit | 1.2 boolean | CW |
| 873 | AC20 Control_ Setpoint Temperature [DPT_9.001] | ºC | 2 Bytes | 9.1 temperature (°C) | CW |
| 874 | AC20 Control_ Setpoint Temperature +/- [DPT_1.007] | 0-Dec.;1-Inc. | 1 Bit | 1.7 step | CW |
| 874 | AC20 Control_ Setpoint Temperature +/- [DPT_1.008] | 0-Up;1-Down | 1 Bit | 1.8 up/down | CW |
| 875 | AC20 Control_ Ambient Temperature [DPT_9.001] | ºC | 2 Bytes | 9.1 temperature (°C) | CW |
| 876 | AC20 Control_ Remote Lock [DPT_1.003] | 0-Unlock;1-Lock | 1 Bit | 1.3 enable | CW |
| 877 | AC20 Status_ On/Off [DPT_1.001] | 0-Off;1-On | 1 Bit | 1.1 switch | CRT |
| 878 | AC20 Status_ Operating Mode [DPT_20.102] | 0-Aut;1-Com;2-Stan;3-Eco;4-Pro | 1 Byte | 20.102 HVAC mode | CRT |
| 879 | AC20 Status_ Mode [DPT_20.105] | 0-Aut;1-Hea;3-Coo;9-Fan;14-Dry | 1 Byte | 20.105 HVAC control mode | CRT |
| 880 | AC20 Status_ Mode Cool/Heat [DPT_1.100] | 0-Cool;1-Heat | 1 Bit | 1.100 heating/cooling | CRT |
| 881 | AC20 Status_ Mode Auto [DPT_1.002] | 1-AUTO mode is active | 1 Bit | 1.2 boolean | CRT |
| 882 | AC20 Status_ Mode Heat [DPT_1.002] | 1-HEAT mode is active | 1 Bit | 1.2 boolean | CRT |
| 883 | AC20 Status_ Mode Cool [DPT_1.002] | 1-COOL mode is active | 1 Bit | 1.2 boolean | CRT |
| 884 | AC20 Status_ Mode Fan [DPT_1.002] | 1-FAN mode is active | 1 Bit | 1.2 boolean | CRT |
| 885 | AC20 Status_ Mode Dry [DPT_1.002] | 1-DRY mode is active | 1 Bit | 1.2 boolean | CRT |
| 886 | AC20 Status_ Mode Text [DPT_16.001] | Mode Text | 14 Bytes | 16.1 Character String (ISO 8859-1) | CRT |
| 887 | AC20 Status_ Fan Speed [DPT_5.001] | 50% and 100% || 33%, 66% and 100% | 1 Byte | 5.1 percentage (0..100%) | CRT |
| 887 | AC20 Status_ Fan Speed [DPT_5.010] | Speed values: 1,2 || 1,2,3 | 1 Byte | 5.10 counter pulses (0..255) | CRT |
| 888 | AC20 Status_ Fan Speed Man/Auto [DPT_1.002] | 0-Manual;1-Auto | 1 Bit | 1.2 boolean | CRT |
| 889 | AC20 Status_ Fan Speed 1 [DPT_1.002] | 1-Fan in Speed 1 | 1 Bit | 1.2 boolean | CRT |
| 890 | AC20 Status_ Fan Speed 2 [DPT_1.002] | 1-Fan in Speed 2 | 1 Bit | 1.2 boolean | CRT |
| 891 | AC20 Status_ Fan Speed 3 [DPT_1.002] | 1-Fan in Speed 3 | 1 Bit | 1.2 boolean | CRT |
| 892 | AC20 Status_ Fan Speed Text [DPT_16.001] | Fan Speed Text | 14 Bytes | 16.1 Character String (ISO 8859-1) | CRT |
| 893 | AC20 Status_ Vanes U-D Swing [DPT_1.002] | 0-Stop;1-Swing | 1 Bit | 1.2 boolean | CRT |
| 894 | AC20 Status_ Vanes U-D Text [DPT_16.001] | Vanes Text | 14 Bytes | 16.1 Character String (ISO 8859-1) | CRT |
| 895 | AC20 Status_ AC Setpoint Temperature [DPT_9.001] | ºC | 2 Bytes | 9.1 temperature (°C) | CRT |
| 896 | AC20 Status_ AC Ambient Reference Temperature [DPT_9.001] | ºC | 2 Bytes | 9.1 temperature (°C) | CRT |
| 897 | AC20 Status_ Error/Alarm [DPT_1.005] | 0-No alarm;1-Alarm | 1 Bit | 1.5 alarm | CRT |
| 898 | AC20 Status_ Error Code [2-byte signed value] | Error Code | 2 Bytes | 8.1 pulses difference | CRT |
| 899 | AC20 Status_ Error Text [DPT_16.001] | Error Text | 14 Bytes | 16.1 Character String (ISO 8859-1) | CRT |
| 900 | AC20 Status_ Remote Lock [DPT_1.003] | 0-Unlocked;1-Locked | 1 Bit | 1.3 enable | CRT |