Intesis DK-RC-KNX-1 DK RC Interface

DK RC Interface DK-RC-KNX-1

Intesis · Order number DK-RC-KNX-1 · Communication › Interfaces › Daikin Air Conditioning Interfaces

Download .knxprod 0105 DKRCKNX1 T08V15 1.5 · 158 KB

Product

ManufacturerIntesis
Product nameDK RC Interface
Order numberDK-RC-KNX-1
HardwareDK RC Interface
MediumTwisted Pair
Bus current (mA)7
Rail mountedNo
RegistrationCertified
Languageses-ES, en-US
Catalog entryM-0077_H-Y12M05-1_HP-0008-15-37D0_CI-DK.2DRC.2DKNX.2D1-1
Fingerprint37D0
SHA-256d6094d81395b0dbdfe227cf0fb55edea630386c0044d8bb76d562c6c6f692778
First seen2026-11-25
Markets69 markets

Application program: 0105 DKRCKNX1 T08V15 1.5

Application number$0008
Version1.5
Mask versionMV-0025 (2.5)
KNX Data SecureNo
Parameters161
Group objects97
Group objects (97)
NoNameFunctionSizeDPTFlags
0Control_ On/Off [DPT_1.001 - 1bit]0-Off;1-On1 Bit1.1 switchCWT
1Control_ Mode [DPT_20.105 - 1byte]0-Aut;1-Hea;3-Coo;9-Fan;14-Dry1 ByteCWT
2Control_ Mode Cool/Heat [DPT_1.100 - 1bit]0-Cool;1-Heat1 BitCWT
3Control_ Mode Cool & On [DPT_5.001 - 1byte]0%-Off;0.1%-100%-On1 Byte5.1 percentage (0..100%)CWT
4Control_ Mode Heat & On [DPT_5.001 - 1byte]0%-Off;0.1%-100%-On1 Byte5.1 percentage (0..100%)CWT
5Control_ Mode Auto [DPT_1.002 - 1bit]1-Set AUTO mode1 Bit1.2 booleanCWT
6Control_ Mode Heat [DPT_1.002 - 1bit]1-Set HEAT mode1 Bit1.2 booleanCWT
7Control_ Mode Cool [DPT_1.002 - 1bit]1-Set COOL mode1 Bit1.2 booleanCWT
8Control_ Mode Fan [DPT_1.002 - 1bit]1-Set FAN mode1 Bit1.2 booleanCWT
9Control_ Mode Dry [DPT_1.002 - 1bit]1-Set DRY mode1 Bit1.2 booleanCWT
10Control_ Mode +/- [DPT_1.007 - 1bit]0-Decrease;1-Increase1 BitCW
10Control_ Mode +/- [DPT_1.008 - 1bit]0-Up;1-Down1 Bit1.8 up/downCW
11Control_ Fan Speed / 2 Speeds [DPT_5.001 - 1byte] Threshold: 75%1 Byte5.1 percentage (0..100%)CWT
11Control_ Fan Speed / 2 Speeds [DPT_5.010 - 1byte] Speed values: 1,21 Byte5.10 counter pulses (0..255)CWT
11Control_ Fan Speed / 3 Speeds [DPT_5.001 - 1byte] Thresholds: 50% and 83%1 Byte5.1 percentage (0..100%)CWT
11Control_ Fan Speed / 3 Speeds [DPT_5.010 - 1byte] Speed values: 1,2,31 Byte5.10 counter pulses (0..255)CWT
12Control_ Fan Speed 1 [DPT_1.002 - 1bit]1-Set Fan Speed 11 Bit1.2 booleanCWT
13Control_ Fan Speed 2 [DPT_1.002 - 1bit]1-Set Fan Speed 21 Bit1.2 booleanCWT
14Control_ Fan Speed 3 [DPT_1.002 - 1bit]1-Set Fan Speed 31 Bit1.2 booleanCWT
15Control_ Fan Speed +/- [DPT_1.007 - 1bit]0-Decrease;1-Increase1 BitCW
15Control_ Fan Speed +/- [DPT_1.008 - 1bit]0-Up;1-Down1 Bit1.8 up/downCW
16Control_ Vanes Up-Down / 5 Pos [DPT_5.001 - 1byte]Thresholds: 30, 50, 70 and 90%1 Byte5.1 percentage (0..100%)CWT
16Control_ Vanes Up-Down / 5 pos [DPT_5.010 - 1byte]Position values: 1,2,3,4,51 Byte5.10 counter pulses (0..255)CWT
17Control_ Vanes Up-Down Swing [DPT_1.002 - 1bit]0-Stop/1-Swing1 Bit1.2 booleanCWT
18Control_ Vanes Up-Down Pos1 [DPT_1.002 - 1bit]1-Set Vanes Position 11 Bit1.2 booleanCWT
19Control_ Vanes Up-Down Pos2 [DPT_1.002 - 1bit]1-Set Vanes Position 21 Bit1.2 booleanCWT
20Control_ Vanes Up-Down Pos3 [DPT_1.002 - 1bit]1-Set Vanes Position 31 Bit1.2 booleanCWT
21Control_ Vanes Up-Down Pos4 [DPT_1.002 - 1bit]1-Set Vanes Position 41 Bit1.2 booleanCWT
22Control_ Vanes Up-Down Pos5 [DPT_1.002 - 1bit]1-Set Vanes Position 51 Bit1.2 booleanCWT
23Control_ Vanes Up-Down +/- [DPT_1.008 - 1bit]0-Up;1-Down1 Bit1.8 up/downCW
23Control_ Vanes Up-Down +/- [DPT_1.007 - 1bit]0-Decrease;1-Increase1 BitCW
24Control_ Setpoint Temperature [DPT_9.001 - 2byte]16ºC to 32ºC2 Bytes9.1 temperature (°C)CWT
25Control_ Ambient Temperature [DPT_9.001 - 2byte]ºC value in EIS5 format2 Bytes9.1 temperature (°C)CWT
26Control_ Setpoint Temp +/- [DPT_1.007 - 1bit]0-Decrease;1-Increase1 BitCW
26Control_ Setpoint Temp +/- [DPT_1.008 - 1bit]0-Up;1-Down1 Bit1.8 up/downCW
27Control_ Switch Off Timeout [DPT_1.010 - 1bit]0-Stop;1-Start1 Bit1.10 start/stopCWT
27Control_ Window Contact Status [DPT_1.009 - 1bit]0-Open;1-Closed1 Bit1.9 open/closeCWT
28Control_ Occupancy [DPT_1.018 - 1bit]0-Not Occupied;1-Occupied1 BitCWT
29Control_ Sleep Timeout [DPT_1.010 - 1bit]0-Stop;1-Start1 Bit1.10 start/stopCWT
30Control_ Lock Remote Control [DPT_1.002 - 1bit]0-Unlocked;1-Locked1 Bit1.2 booleanCW
31Control_ Lock Control Objects [DPT_1.002 - 1bit]0-Unlocked;1-Locked1 Bit1.2 booleanCWT
32Control_ Power Mode [DPT_1.010 - 1bit]0-Stop;1-Start1 Bit1.10 start/stopCWT
33Control_ Econo Mode [DPT_1.010 - 1bit]0-Stop;1-Start1 Bit1.10 start/stopCWT
34Control_ Additional Heat [DPT_1.010 - 1bit]0-Stop;1-Start1 Bit1.10 start/stopCWT
35Control_ Additional Cool [DPT_1.010 - 1bit]0-Stop;1-Start1 Bit1.10 start/stopCWT
36Control_ Execute Scene [DPT_17.001 - 1byte]0..4-Exec1-51 ByteCWT
36Control_ Save/Exec Scene [DPT_18.001 - 1byte]0..4-Exec1-5;128..132-Save1-51 ByteCWT
37Control_ Store Scene 1 [DPT_1.002 - 1bit]1-Store Scene1 Bit1.2 booleanCWT
38Control_ Store Scene2 [DPT_1.002 - 1bit]1-Store Scene1 Bit1.2 booleanCWT
39Control_ Store Scene3 [DPT_1.002 - 1bit]1-Store Scene1 Bit1.2 booleanCWT
40Control_ Store Scene4 [DPT_1.002 - 1bit]1-Store Scene1 Bit1.2 booleanCWT
41Control_ Store Scene5 [DPT_1.002 - 1bit]1-Store Scene1 Bit1.2 booleanCWT
42Control_ Execute Scene1 [DPT_1.002 - 1bit]1-Execute Scene1 Bit1.2 booleanCWT
43Control_ Execute Scene2 [DPT_1.002 - 1bit]1-Execute Scene1 Bit1.2 booleanCWT
44Control_ Execute Scene3 [DPT_1.002 - 1bit]1-Execute Scene1 Bit1.2 booleanCWT
45Control_ Execute Scene4 [DPT_1.002 - 1bit]1-Execute Scene1 Bit1.2 booleanCWT
46Control_ Execute Scene5 [DPT_1.002 - 1bit]1-Execute Scene1 Bit1.2 booleanCWT
47Status_ On/Off [DPT_1.001 - 1bit]0-Off;1-On1 Bit1.1 switchCRT
48Status_ Mode [DPT_20.105 - 1byte]0-Aut;1-Hea;3-Coo;9-Fan;14-Dry1 ByteCRT
49Status_ Mode Cool/Heat [DPT_1.100 - 1bit]0-Cool;1-Heat1 BitCRT
50Status_ Mode Auto [DPT_1.002 - 1bit]1-AUTO is active1 Bit1.2 booleanCRT
51Status_ Mode Heat [DPT_1.002 - 1bit]1-HEAT is active1 Bit1.2 booleanCRT
52Status_ Mode Cool [DPT_1.002 - 1bit]1-COOL is active1 Bit1.2 booleanCRT
53Status_ Mode Fan [DPT_1.002 - 1bit]1-FAN is active1 Bit1.2 booleanCRT
54Status_ Mode Dry [DPT_1.002 - 1bit]1-DRY is active1 Bit1.2 booleanCRT
55Status_ Mode Text [DPT_16.001 - 14byte]ASCII String14 Bytes16.1 Character String (ISO 8859-1)CRT
56Status_ Fan Speed / 2 Speeds [DPT_5.001 - 1byte]50% and 100%1 Byte5.1 percentage (0..100%)CRT
56Status_ Fan Speed / 2 Speeds [DPT_5.010 - 1byte]Speed values: 1,21 Byte5.10 counter pulses (0..255)CRT
56Status_ Fan Speed / 3 Speeds [DPT_5.001 - 1byte]33%, 67% and 100%1 Byte5.1 percentage (0..100%)CRT
56Status_ Fan Speed / 3 Speeds [DPT_5.010 - 1byte]Speed values: 1,2,31 Byte5.10 counter pulses (0..255)CRT
57Status_ Fan Speed 1 [DPT_1.002 - 1bit]1-Fan in Speed 11 Bit1.2 booleanCRT
58Status_ Fan Speed 2 [DPT_1.002 - 1bit]1-Fan in Speed 21 Bit1.2 booleanCRT
59Status_ Fan Speed 3 [DPT_1.002 - 1bit]1-Fan in Speed 31 Bit1.2 booleanCRT
60Status_ Fan Speed Text [DPT_16.001 - 14byte]ASCII String14 Bytes16.1 Character String (ISO 8859-1)CRT
61Status_ Vanes Up-Down / 5 Pos [DPT_5.001 - 1byte]20%, 40%, 60%, 80% and 100%1 Byte5.1 percentage (0..100%)CRT
61Status_ Vanes Up-Down / 5 pos [DPT_5.010 - 1byte]Position values 1,2,3,4,51 Byte5.10 counter pulses (0..255)CRT
62Status_ Vanes Up-Down Swing [DPT_1.002 - 1bit]0-Stop/1-Swing1 Bit1.2 booleanCRT
63Status_ Vanes Up-Down Pos 1 [DPT_1.002 - 1bit]1-Vanes in Position 11 Bit1.2 booleanCRT
64Status_ Vanes Up-Down Pos 2 [DPT_1.002 - 1bit]1-Vanes in Position 21 Bit1.2 booleanCRT
65Status_ Vanes Up-Down Pos 3 [DPT_1.002 - 1bit]1-Vanes in Position 31 Bit1.2 booleanCRT
66Status_ Vanes Up-Down Pos 4 [DPT_1.002 - 1bit]1-Vanes in Position 41 Bit1.2 booleanCRT
67Status_ Vanes Up-Down Pos 5 [DPT_1.002 - 1bit]1-Vanes in Position 51 Bit1.2 booleanCRT
68Status_ Vanes Up-Down Text [DPT_16.001 - 14byte]ASCII String14 Bytes16.1 Character String (ISO 8859-1)CRT
69Status_ AC Setpoint Temp [DPT_9.001 - 2byte]16ºC to 32ºC2 Bytes9.1 temperature (°C)CRT
70Status_ AC Return Temp [DPT_9.001 - 2byte]ºC value in EIS5 format2 Bytes9.1 temperature (°C)CRT
71Status_ Error/Alarm [DPT_1.005 - 1bit]0-No alarm;1-Alarm1 BitCRT
72Status_ Error Code [2byte]0-No error /Any other see man.2 BytesCRT
73Status_ Error Text Code [DPT_16.001 - 14byte]2 char DK Error;Empty-None14 Bytes16.1 Character String (ISO 8859-1)CRT
74Status_ Power Mode [DPT_1.001 - 1bit]0-Off;1-On1 Bit1.1 switchCRT
75Status_ Econo Mode [DPT_1.001 - 1bit]0-Off;1-On1 Bit1.1 switchCRT
76Status_ Additional Heat [DPT_1.001 - 1bit]0-Off;1-On1 Bit1.1 switchCRT
77Status_ Additional Cool [DPT_1.001 - 1bit]0-Off;1-On1 Bit1.1 switchCRT
78Status_ Operation Hour Counter [DPT_7.001 - 2byte]Number of operating hours2 Bytes7.1 pulsesCRT
79Status_ Current Scene [DPT_17.001 - 1byte]0..4-Scene X;63-No Scene1 ByteCRT
80Legacy_ Mode [Enumerated - 1byte]0-Aut;1-Hea;2-Dry;3-Fan;4-Coo1 ByteCRT
81Legacy_ Fan Speed [Enumerated - 1byte]0-Speed 1;1-Speed 2;2-Speed 31 ByteCRT
82Legacy_ Vanes Up-Down [Enumerated - 1byte]0-Pos0..4-Pos4,5-Swing1 ByteCRT
Parameters (144)
ParameterTypeDefault
Download latest database entry for this product and its User Manual from:texthttp://www.intesis.com
DK-RC-KNX-1 is master in P1/P2 bus (If set to "yes", BRC must be SLAVE)listno
> If VRV system, indoor unit is slave of Operating Modelistyes
Send READs for Control_ objs on bus recovery (T and U flags must be active)listno
> Delay before sending READs (sec)unsignedInt 0…2540
Scene to load on bus recovery / startup (needs to define vals for that scene)list(none)
Disallow control from remote controllerlistno
> Enable comm obj "Ctrl_ Remote Lock"listno
Enable func "Control_ Lock Control Obj"listno
Enable func "Operating Hours Counter"listno
Enable object "Error Code [2byte]"listno
Enable object "Error Text Code [14byte]" (2 ASCII-char Error Code)listno
Unidad Interior tiene modo AUTO (véase docum. de su Unidad Interior)listyes
When mode is AUTO, Status_ objs report actual operating status (HEAT/COOL/..)listno
Enable use of Mode Cool/Heat bit-type objectlistno
Enable PID-Compat. Scaling Mode Objectslistno
Enable use of +/- object for Modelistno
> DPT type for +/- Mode Objectlist0-Decrease / 1-Increase [DPT_1.007]
Enable use of bit-type Mode objects (for control)listno
Enable use of bit-type Mode objects (for status)listno
Enable use of Text object for Modelistno
ASCII strings shown in comm object "Status_ Mode Text"text<< 14-byte string values >>
> String when mode is AUTOtextAUTO
> String when mode is HEATtextHEAT
> String when mode is COOLtextCOOL
> String when mode is FANtextFAN
> String when mode is DRYtextDRY
Enable use of Legacy_ object for Mode (compatible with old ver of XXACKNX1)listno
Enable use of POWER modelistno
> Action time for this mode (minutes) (0 = permanent / unlimited)unsignedInt 0…18030
> Setpoint delta increase (HEAT) or decrease (COOL) - in Celsiuslist2.0ºC
> Fanspeed for this modelistSPEED 2
Enable use of ECONOMY modelistno
> Setpoint delta decrease (HEAT) or increase (COOL) - in Celsiuslist2.0ºC
> Fanspeed for this modelistSPEED 1
Enable use of ADDITIONAL HEATING modelistno
> Setpoint temp for this mode (ºC)list30.0ºC
Enable use of ADDITIONAL COOLING modelistno
> Setpoint temp for this mode (ºC)list20.0ºC
Unidad Interior tiene vel. ventilador AUTO (véase docum. de su Unidad Interior)listno
Available fanspeeds in Indoor Unit (see docum. for your indoor unit)list2
DPT object type for fanspeedlistScaling [DPT_5.001]
Enable use of +/- object for Fan Speedlistno
> DPT type for +/- Fan Speed objectlist0-Decrease / 1-Increase [DPT_1.007]
> La secuencia +/- incluye AUTO?listno
> Rollover Speed at upper/lower limit (when controlling with +/- obj)listyes
Enable use of bit-type Fan Speed objects (for control)listno
Enable use of bit-type Fan Speed objects (for Control)listno
Enable use of bit-type Fan Speed objects (for Status)listno
Enable use of Text object for Fan Speedlistno
ASCII strings shown in comm object "Status_ Fan Speed Text"text<< 14-byte string values >>
> String when fan speed is 1textSPEED 1
> String when fan speed is 2textSPEED 2
> String when fan speed is 3textSPEED 3
Enable use of Legacy_ obj for Fan Speed (compatible with old ver of XXACKNX1)listno
Indoor unit has Up-Down Vanes (see docum. for your indoor unit)listno
Lamas Up-Down tienen operación AUTO (véase docum. de su Unidad Interior)listno
Enable "Control_ Vanes U-D Swing"listno
Pos. dispon. de Lamas U-D en Unidad Interior (véase docum. de Unidad Interior)unsignedInt 5…77
DPT object type for Vanes Up-DownlistScaling [DPT_5.001]
Enable use of +/- object for Vanes Up-Downlistno
> DPT type for +/- Vanes Up-Down objlist0-Decrease / 1-Increase [DPT_1.007]
> La secuencia +/- incluye Lamas AUTO?listno
> Does +/- sequen. incl. vanes SWING?listno
> Rollover Vanes at upper/lower limit (when controlling with +/- obj)listyes
Enable use of bit-type Vanes U-D objects (for control)listno
Enable use of bit-type Vanes U-D objects (for status)listno
Enable use of Text object for Vanes U-Dlistno
ASCII strings shown in comm object "Status_ Vanes Up-Down Text"text<< 14-byte string values >>
> String when vanes U-D is in POS1textU-D POS1
> String when vanes U-D is in POS2textU-D POS2
> String when vanes U-D is in POS3textU-D POS3
> String when vanes U-D is in POS4textU-D POS4
> String when vanes U-D is in POS5textU-D POS5
> String when vanes U-D is in SWINGtextU-D SWING
Enable use of Legacy_ obj for Vanes U-D (compatible with old ver of XXACKNX1)listno
Periodic sending of "Status_ AC Setp" (in seconds; 0 = No periodic sending)unsignedInt 0…2550
Transmission of "Status_ AC Return Temp"listonly cyclically
> "Status_ AC Return Temp" periodic sending time (in sec)unsignedInt 1…255200
Enable use of +/- object for Setpoint Temperaturelistno
> DPT type for Setp Temp +/- objectlist0-Decrease / 1-Increase [DPT_1.007]
> Longitud de paso [+/-]list1.0ºC
Enable limits on Control_ Setpoint objlistno
> Control_ Set Temp Lower limit (ºC)list16.0ºC
> Control_ Set Temp Upper limit (ºC)list32.0ºC
Ambient temp.ref. is provided from KNX (carefully read User Guide if enabled)listno
Enable use of sceneslistno
Scenes can be stored from KNX buslistno
> Enable use of bit objects for storing scenes (from bus)listno
Enable use of bit objects for scene executionlistno
Scene 1 presetlistno
> Scene 1 / Value for On-Offlist(unchanged)
> Scene 1 / Value for Modelist(unchanged)
> Scene 1 / Value for Fan Speedlist(unchanged)
> Scene 1 / Value for Vanes Up-Down (if indoor unit has Vanes U-D)list(unchanged)
> Scene 1 / Value for Setp Temp (ºC)list(unchanged)
> Scene 1 / Value for Remote Locklist(unchanged)
Scene 2 presetlistno
> Scene 2 / Value for On-Offlist(unchanged)
> Scene 2 / Value for Modelist(unchanged)
> Scene 2 / Value for Fan Speedlist(unchanged)
> Scene 2 / Value for Vanes Up-Down (if indoor unit has Vanes U-D)list(unchanged)
> Scene 2 / Value for Setp Temp (ºC)list(unchanged)
> Scene 2 / Value for Remote Locklist(unchanged)
Scene 3 presetlistno
> Scene 3 / Value for On-Offlist(unchanged)
> Scene 3 / Value for Modelist(unchanged)
> Scene 3 / Value for Fan Speedlist(unchanged)
> Scene 3 / Value for Vanes Up-Down (if indoor unit has Vanes U-D)list(unchanged)
> Scene 3 / Value for Setp Temp (ºC)list(unchanged)
> Scene 3 / Value for Remote Locklist(unchanged)
Scene 4 presetlistno
> Scene 4 / Value for On-Offlist(unchanged)
> Scene 4 / Value for Modelist(unchanged)
> Scene 4 / Value for Fan Speedlist(unchanged)
> Scene 4 / Value for Vanes Up-Down (if indoor unit has Vanes U-D)list(unchanged)
> Scene 4 / Value for Setp Temp (ºC)list(unchanged)
> Scene 4 / Value for Remote Locklist(unchanged)
Scene 5 presetlistno
> Scene 5 / Value for On-Offlist(unchanged)
> Scene 5 / Value for Modelist(unchanged)
> Scene 5 / Value for Fan Speedlist(unchanged)
> Scene 5 / Value for Vanes Up-Down (if indoor unit has Vanes U-D)list(unchanged)
> Scene 5 / Value for Setp Temp (ºC)list(unchanged)
> Scene 5 / Value for Remote Locklist(unchanged)
Enable use of Open Window / Switch off timeout functionlistno
> AC switch-off timeout (min)unsignedInt 0…3010
> DPT for Window / Switch-off timeoutlist0-Stop / 1-Start Timeout [DPT_1.010]
> Disallow On/Off operation while timeout is elapsedlistno
> Disallow On/Off operation while window is Openlistno
> Reload last On/Off value once window is Closedlistno
> Reload last On/Off value once timeout is stoppedlistno
Enable use of Occupancy functionlistno
> Timeout to apply action (minutes)unsignedInt 0…18020
> Action after timeout elapsedlistApply Preset Delta
> Temp delta decrease (HEAT) or increase (COOL) (ºC)list2.0ºC
> Enable secondary timeoutlistno
> Timeout to apply action (min)unsignedInt 0…18020
> Action after timeout elapsedlistSwitch-Off
> Temp delta dec (HEAT) or inc (COOL) (ºC)list4.0ºC
> Disallow On/Off operation while not Occupiedlistno
> Reload last On/Off value when Occupiedlistno
Enable use of SLEEP timeoutlistno
> Sleep function switch-off timeout (minutes)unsignedInt 0…18060

Version history

ApplicationApp noFingerprintFirst seenSizeFile
0105 DKRCKNX1 T08V15 1.5 latest$000837D02026-11-25158 KBDownload

About this file

This is the official ETS product database for the Intesis DK RC Interface (DK-RC-KNX-1), published by the manufacturer in the KNX online catalog. To use it, open ETS, go to Catalogs → Import and choose the downloaded .knxprod file. The device then appears in your catalog and can be added to a project. Older versions are kept so existing projects can be matched to the application program they were commissioned with.