DK RC Interface DK-RC-KNX-1
Intesis · Order number DK-RC-KNX-1 · Communication › Interfaces › Daikin Air Conditioning Interfaces
Download .knxprod 0105 DKRCKNX1 T08V15 1.5 · 158 KB
Product
| Manufacturer | Intesis |
|---|---|
| Product name | DK RC Interface |
| Order number | DK-RC-KNX-1 |
| Hardware | DK RC Interface |
| Medium | Twisted Pair |
| Bus current (mA) | 7 |
| Rail mounted | No |
| Registration | Certified |
| Languages | es-ES, en-US |
| Catalog entry | M-0077_H-Y12M05-1_HP-0008-15-37D0_CI-DK.2DRC.2DKNX.2D1-1 |
| Fingerprint | 37D0 |
| SHA-256 | d6094d81395b0dbdfe227cf0fb55edea630386c0044d8bb76d562c6c6f692778 |
| First seen | 2026-11-25 |
| Markets | 69 markets |
Application program: 0105 DKRCKNX1 T08V15 1.5
| Application number | $0008 |
|---|---|
| Version | 1.5 |
| Mask version | MV-0025 (2.5) |
| KNX Data Secure | No |
| Parameters | 161 |
| Group objects | 97 |
Group objects (97)
| No | Name | Function | Size | DPT | Flags |
|---|---|---|---|---|---|
| 0 | Control_ On/Off [DPT_1.001 - 1bit] | 0-Off;1-On | 1 Bit | 1.1 switch | CWT |
| 1 | Control_ Mode [DPT_20.105 - 1byte] | 0-Aut;1-Hea;3-Coo;9-Fan;14-Dry | 1 Byte | CWT | |
| 2 | Control_ Mode Cool/Heat [DPT_1.100 - 1bit] | 0-Cool;1-Heat | 1 Bit | CWT | |
| 3 | Control_ Mode Cool & On [DPT_5.001 - 1byte] | 0%-Off;0.1%-100%-On | 1 Byte | 5.1 percentage (0..100%) | CWT |
| 4 | Control_ Mode Heat & On [DPT_5.001 - 1byte] | 0%-Off;0.1%-100%-On | 1 Byte | 5.1 percentage (0..100%) | CWT |
| 5 | Control_ Mode Auto [DPT_1.002 - 1bit] | 1-Set AUTO mode | 1 Bit | 1.2 boolean | CWT |
| 6 | Control_ Mode Heat [DPT_1.002 - 1bit] | 1-Set HEAT mode | 1 Bit | 1.2 boolean | CWT |
| 7 | Control_ Mode Cool [DPT_1.002 - 1bit] | 1-Set COOL mode | 1 Bit | 1.2 boolean | CWT |
| 8 | Control_ Mode Fan [DPT_1.002 - 1bit] | 1-Set FAN mode | 1 Bit | 1.2 boolean | CWT |
| 9 | Control_ Mode Dry [DPT_1.002 - 1bit] | 1-Set DRY mode | 1 Bit | 1.2 boolean | CWT |
| 10 | Control_ Mode +/- [DPT_1.007 - 1bit] | 0-Decrease;1-Increase | 1 Bit | CW | |
| 10 | Control_ Mode +/- [DPT_1.008 - 1bit] | 0-Up;1-Down | 1 Bit | 1.8 up/down | CW |
| 11 | Control_ Fan Speed / 2 Speeds [DPT_5.001 - 1byte] | Threshold: 75% | 1 Byte | 5.1 percentage (0..100%) | CWT |
| 11 | Control_ Fan Speed / 2 Speeds [DPT_5.010 - 1byte] | Speed values: 1,2 | 1 Byte | 5.10 counter pulses (0..255) | CWT |
| 11 | Control_ Fan Speed / 3 Speeds [DPT_5.001 - 1byte] | Thresholds: 50% and 83% | 1 Byte | 5.1 percentage (0..100%) | CWT |
| 11 | Control_ Fan Speed / 3 Speeds [DPT_5.010 - 1byte] | Speed values: 1,2,3 | 1 Byte | 5.10 counter pulses (0..255) | CWT |
| 12 | Control_ Fan Speed 1 [DPT_1.002 - 1bit] | 1-Set Fan Speed 1 | 1 Bit | 1.2 boolean | CWT |
| 13 | Control_ Fan Speed 2 [DPT_1.002 - 1bit] | 1-Set Fan Speed 2 | 1 Bit | 1.2 boolean | CWT |
| 14 | Control_ Fan Speed 3 [DPT_1.002 - 1bit] | 1-Set Fan Speed 3 | 1 Bit | 1.2 boolean | CWT |
| 15 | Control_ Fan Speed +/- [DPT_1.007 - 1bit] | 0-Decrease;1-Increase | 1 Bit | CW | |
| 15 | Control_ Fan Speed +/- [DPT_1.008 - 1bit] | 0-Up;1-Down | 1 Bit | 1.8 up/down | CW |
| 16 | Control_ Vanes Up-Down / 5 Pos [DPT_5.001 - 1byte] | Thresholds: 30, 50, 70 and 90% | 1 Byte | 5.1 percentage (0..100%) | CWT |
| 16 | Control_ Vanes Up-Down / 5 pos [DPT_5.010 - 1byte] | Position values: 1,2,3,4,5 | 1 Byte | 5.10 counter pulses (0..255) | CWT |
| 17 | Control_ Vanes Up-Down Swing [DPT_1.002 - 1bit] | 0-Stop/1-Swing | 1 Bit | 1.2 boolean | CWT |
| 18 | Control_ Vanes Up-Down Pos1 [DPT_1.002 - 1bit] | 1-Set Vanes Position 1 | 1 Bit | 1.2 boolean | CWT |
| 19 | Control_ Vanes Up-Down Pos2 [DPT_1.002 - 1bit] | 1-Set Vanes Position 2 | 1 Bit | 1.2 boolean | CWT |
| 20 | Control_ Vanes Up-Down Pos3 [DPT_1.002 - 1bit] | 1-Set Vanes Position 3 | 1 Bit | 1.2 boolean | CWT |
| 21 | Control_ Vanes Up-Down Pos4 [DPT_1.002 - 1bit] | 1-Set Vanes Position 4 | 1 Bit | 1.2 boolean | CWT |
| 22 | Control_ Vanes Up-Down Pos5 [DPT_1.002 - 1bit] | 1-Set Vanes Position 5 | 1 Bit | 1.2 boolean | CWT |
| 23 | Control_ Vanes Up-Down +/- [DPT_1.008 - 1bit] | 0-Up;1-Down | 1 Bit | 1.8 up/down | CW |
| 23 | Control_ Vanes Up-Down +/- [DPT_1.007 - 1bit] | 0-Decrease;1-Increase | 1 Bit | CW | |
| 24 | Control_ Setpoint Temperature [DPT_9.001 - 2byte] | 16ºC to 32ºC | 2 Bytes | 9.1 temperature (°C) | CWT |
| 25 | Control_ Ambient Temperature [DPT_9.001 - 2byte] | ºC value in EIS5 format | 2 Bytes | 9.1 temperature (°C) | CWT |
| 26 | Control_ Setpoint Temp +/- [DPT_1.007 - 1bit] | 0-Decrease;1-Increase | 1 Bit | CW | |
| 26 | Control_ Setpoint Temp +/- [DPT_1.008 - 1bit] | 0-Up;1-Down | 1 Bit | 1.8 up/down | CW |
| 27 | Control_ Switch Off Timeout [DPT_1.010 - 1bit] | 0-Stop;1-Start | 1 Bit | 1.10 start/stop | CWT |
| 27 | Control_ Window Contact Status [DPT_1.009 - 1bit] | 0-Open;1-Closed | 1 Bit | 1.9 open/close | CWT |
| 28 | Control_ Occupancy [DPT_1.018 - 1bit] | 0-Not Occupied;1-Occupied | 1 Bit | CWT | |
| 29 | Control_ Sleep Timeout [DPT_1.010 - 1bit] | 0-Stop;1-Start | 1 Bit | 1.10 start/stop | CWT |
| 30 | Control_ Lock Remote Control [DPT_1.002 - 1bit] | 0-Unlocked;1-Locked | 1 Bit | 1.2 boolean | CW |
| 31 | Control_ Lock Control Objects [DPT_1.002 - 1bit] | 0-Unlocked;1-Locked | 1 Bit | 1.2 boolean | CWT |
| 32 | Control_ Power Mode [DPT_1.010 - 1bit] | 0-Stop;1-Start | 1 Bit | 1.10 start/stop | CWT |
| 33 | Control_ Econo Mode [DPT_1.010 - 1bit] | 0-Stop;1-Start | 1 Bit | 1.10 start/stop | CWT |
| 34 | Control_ Additional Heat [DPT_1.010 - 1bit] | 0-Stop;1-Start | 1 Bit | 1.10 start/stop | CWT |
| 35 | Control_ Additional Cool [DPT_1.010 - 1bit] | 0-Stop;1-Start | 1 Bit | 1.10 start/stop | CWT |
| 36 | Control_ Execute Scene [DPT_17.001 - 1byte] | 0..4-Exec1-5 | 1 Byte | CWT | |
| 36 | Control_ Save/Exec Scene [DPT_18.001 - 1byte] | 0..4-Exec1-5;128..132-Save1-5 | 1 Byte | CWT | |
| 37 | Control_ Store Scene 1 [DPT_1.002 - 1bit] | 1-Store Scene | 1 Bit | 1.2 boolean | CWT |
| 38 | Control_ Store Scene2 [DPT_1.002 - 1bit] | 1-Store Scene | 1 Bit | 1.2 boolean | CWT |
| 39 | Control_ Store Scene3 [DPT_1.002 - 1bit] | 1-Store Scene | 1 Bit | 1.2 boolean | CWT |
| 40 | Control_ Store Scene4 [DPT_1.002 - 1bit] | 1-Store Scene | 1 Bit | 1.2 boolean | CWT |
| 41 | Control_ Store Scene5 [DPT_1.002 - 1bit] | 1-Store Scene | 1 Bit | 1.2 boolean | CWT |
| 42 | Control_ Execute Scene1 [DPT_1.002 - 1bit] | 1-Execute Scene | 1 Bit | 1.2 boolean | CWT |
| 43 | Control_ Execute Scene2 [DPT_1.002 - 1bit] | 1-Execute Scene | 1 Bit | 1.2 boolean | CWT |
| 44 | Control_ Execute Scene3 [DPT_1.002 - 1bit] | 1-Execute Scene | 1 Bit | 1.2 boolean | CWT |
| 45 | Control_ Execute Scene4 [DPT_1.002 - 1bit] | 1-Execute Scene | 1 Bit | 1.2 boolean | CWT |
| 46 | Control_ Execute Scene5 [DPT_1.002 - 1bit] | 1-Execute Scene | 1 Bit | 1.2 boolean | CWT |
| 47 | Status_ On/Off [DPT_1.001 - 1bit] | 0-Off;1-On | 1 Bit | 1.1 switch | CRT |
| 48 | Status_ Mode [DPT_20.105 - 1byte] | 0-Aut;1-Hea;3-Coo;9-Fan;14-Dry | 1 Byte | CRT | |
| 49 | Status_ Mode Cool/Heat [DPT_1.100 - 1bit] | 0-Cool;1-Heat | 1 Bit | CRT | |
| 50 | Status_ Mode Auto [DPT_1.002 - 1bit] | 1-AUTO is active | 1 Bit | 1.2 boolean | CRT |
| 51 | Status_ Mode Heat [DPT_1.002 - 1bit] | 1-HEAT is active | 1 Bit | 1.2 boolean | CRT |
| 52 | Status_ Mode Cool [DPT_1.002 - 1bit] | 1-COOL is active | 1 Bit | 1.2 boolean | CRT |
| 53 | Status_ Mode Fan [DPT_1.002 - 1bit] | 1-FAN is active | 1 Bit | 1.2 boolean | CRT |
| 54 | Status_ Mode Dry [DPT_1.002 - 1bit] | 1-DRY is active | 1 Bit | 1.2 boolean | CRT |
| 55 | Status_ Mode Text [DPT_16.001 - 14byte] | ASCII String | 14 Bytes | 16.1 Character String (ISO 8859-1) | CRT |
| 56 | Status_ Fan Speed / 2 Speeds [DPT_5.001 - 1byte] | 50% and 100% | 1 Byte | 5.1 percentage (0..100%) | CRT |
| 56 | Status_ Fan Speed / 2 Speeds [DPT_5.010 - 1byte] | Speed values: 1,2 | 1 Byte | 5.10 counter pulses (0..255) | CRT |
| 56 | Status_ Fan Speed / 3 Speeds [DPT_5.001 - 1byte] | 33%, 67% and 100% | 1 Byte | 5.1 percentage (0..100%) | CRT |
| 56 | Status_ Fan Speed / 3 Speeds [DPT_5.010 - 1byte] | Speed values: 1,2,3 | 1 Byte | 5.10 counter pulses (0..255) | CRT |
| 57 | Status_ Fan Speed 1 [DPT_1.002 - 1bit] | 1-Fan in Speed 1 | 1 Bit | 1.2 boolean | CRT |
| 58 | Status_ Fan Speed 2 [DPT_1.002 - 1bit] | 1-Fan in Speed 2 | 1 Bit | 1.2 boolean | CRT |
| 59 | Status_ Fan Speed 3 [DPT_1.002 - 1bit] | 1-Fan in Speed 3 | 1 Bit | 1.2 boolean | CRT |
| 60 | Status_ Fan Speed Text [DPT_16.001 - 14byte] | ASCII String | 14 Bytes | 16.1 Character String (ISO 8859-1) | CRT |
| 61 | Status_ Vanes Up-Down / 5 Pos [DPT_5.001 - 1byte] | 20%, 40%, 60%, 80% and 100% | 1 Byte | 5.1 percentage (0..100%) | CRT |
| 61 | Status_ Vanes Up-Down / 5 pos [DPT_5.010 - 1byte] | Position values 1,2,3,4,5 | 1 Byte | 5.10 counter pulses (0..255) | CRT |
| 62 | Status_ Vanes Up-Down Swing [DPT_1.002 - 1bit] | 0-Stop/1-Swing | 1 Bit | 1.2 boolean | CRT |
| 63 | Status_ Vanes Up-Down Pos 1 [DPT_1.002 - 1bit] | 1-Vanes in Position 1 | 1 Bit | 1.2 boolean | CRT |
| 64 | Status_ Vanes Up-Down Pos 2 [DPT_1.002 - 1bit] | 1-Vanes in Position 2 | 1 Bit | 1.2 boolean | CRT |
| 65 | Status_ Vanes Up-Down Pos 3 [DPT_1.002 - 1bit] | 1-Vanes in Position 3 | 1 Bit | 1.2 boolean | CRT |
| 66 | Status_ Vanes Up-Down Pos 4 [DPT_1.002 - 1bit] | 1-Vanes in Position 4 | 1 Bit | 1.2 boolean | CRT |
| 67 | Status_ Vanes Up-Down Pos 5 [DPT_1.002 - 1bit] | 1-Vanes in Position 5 | 1 Bit | 1.2 boolean | CRT |
| 68 | Status_ Vanes Up-Down Text [DPT_16.001 - 14byte] | ASCII String | 14 Bytes | 16.1 Character String (ISO 8859-1) | CRT |
| 69 | Status_ AC Setpoint Temp [DPT_9.001 - 2byte] | 16ºC to 32ºC | 2 Bytes | 9.1 temperature (°C) | CRT |
| 70 | Status_ AC Return Temp [DPT_9.001 - 2byte] | ºC value in EIS5 format | 2 Bytes | 9.1 temperature (°C) | CRT |
| 71 | Status_ Error/Alarm [DPT_1.005 - 1bit] | 0-No alarm;1-Alarm | 1 Bit | CRT | |
| 72 | Status_ Error Code [2byte] | 0-No error /Any other see man. | 2 Bytes | CRT | |
| 73 | Status_ Error Text Code [DPT_16.001 - 14byte] | 2 char DK Error;Empty-None | 14 Bytes | 16.1 Character String (ISO 8859-1) | CRT |
| 74 | Status_ Power Mode [DPT_1.001 - 1bit] | 0-Off;1-On | 1 Bit | 1.1 switch | CRT |
| 75 | Status_ Econo Mode [DPT_1.001 - 1bit] | 0-Off;1-On | 1 Bit | 1.1 switch | CRT |
| 76 | Status_ Additional Heat [DPT_1.001 - 1bit] | 0-Off;1-On | 1 Bit | 1.1 switch | CRT |
| 77 | Status_ Additional Cool [DPT_1.001 - 1bit] | 0-Off;1-On | 1 Bit | 1.1 switch | CRT |
| 78 | Status_ Operation Hour Counter [DPT_7.001 - 2byte] | Number of operating hours | 2 Bytes | 7.1 pulses | CRT |
| 79 | Status_ Current Scene [DPT_17.001 - 1byte] | 0..4-Scene X;63-No Scene | 1 Byte | CRT | |
| 80 | Legacy_ Mode [Enumerated - 1byte] | 0-Aut;1-Hea;2-Dry;3-Fan;4-Coo | 1 Byte | CRT | |
| 81 | Legacy_ Fan Speed [Enumerated - 1byte] | 0-Speed 1;1-Speed 2;2-Speed 3 | 1 Byte | CRT | |
| 82 | Legacy_ Vanes Up-Down [Enumerated - 1byte] | 0-Pos0..4-Pos4,5-Swing | 1 Byte | CRT |
Parameters (144)
| Parameter | Type | Default |
|---|---|---|
| Download latest database entry for this product and its User Manual from: | text | http://www.intesis.com |
| DK-RC-KNX-1 is master in P1/P2 bus (If set to "yes", BRC must be SLAVE) | list | no |
| > If VRV system, indoor unit is slave of Operating Mode | list | yes |
| Send READs for Control_ objs on bus recovery (T and U flags must be active) | list | no |
| > Delay before sending READs (sec) | unsignedInt 0…254 | 0 |
| Scene to load on bus recovery / startup (needs to define vals for that scene) | list | (none) |
| Disallow control from remote controller | list | no |
| > Enable comm obj "Ctrl_ Remote Lock" | list | no |
| Enable func "Control_ Lock Control Obj" | list | no |
| Enable func "Operating Hours Counter" | list | no |
| Enable object "Error Code [2byte]" | list | no |
| Enable object "Error Text Code [14byte]" (2 ASCII-char Error Code) | list | no |
| Unidad Interior tiene modo AUTO (véase docum. de su Unidad Interior) | list | yes |
| When mode is AUTO, Status_ objs report actual operating status (HEAT/COOL/..) | list | no |
| Enable use of Mode Cool/Heat bit-type object | list | no |
| Enable PID-Compat. Scaling Mode Objects | list | no |
| Enable use of +/- object for Mode | list | no |
| > DPT type for +/- Mode Object | list | 0-Decrease / 1-Increase [DPT_1.007] |
| Enable use of bit-type Mode objects (for control) | list | no |
| Enable use of bit-type Mode objects (for status) | list | no |
| Enable use of Text object for Mode | list | no |
| ASCII strings shown in comm object "Status_ Mode Text" | text | << 14-byte string values >> |
| > String when mode is AUTO | text | AUTO |
| > String when mode is HEAT | text | HEAT |
| > String when mode is COOL | text | COOL |
| > String when mode is FAN | text | FAN |
| > String when mode is DRY | text | DRY |
| Enable use of Legacy_ object for Mode (compatible with old ver of XXACKNX1) | list | no |
| Enable use of POWER mode | list | no |
| > Action time for this mode (minutes) (0 = permanent / unlimited) | unsignedInt 0…180 | 30 |
| > Setpoint delta increase (HEAT) or decrease (COOL) - in Celsius | list | 2.0ºC |
| > Fanspeed for this mode | list | SPEED 2 |
| Enable use of ECONOMY mode | list | no |
| > Setpoint delta decrease (HEAT) or increase (COOL) - in Celsius | list | 2.0ºC |
| > Fanspeed for this mode | list | SPEED 1 |
| Enable use of ADDITIONAL HEATING mode | list | no |
| > Setpoint temp for this mode (ºC) | list | 30.0ºC |
| Enable use of ADDITIONAL COOLING mode | list | no |
| > Setpoint temp for this mode (ºC) | list | 20.0ºC |
| Unidad Interior tiene vel. ventilador AUTO (véase docum. de su Unidad Interior) | list | no |
| Available fanspeeds in Indoor Unit (see docum. for your indoor unit) | list | 2 |
| DPT object type for fanspeed | list | Scaling [DPT_5.001] |
| Enable use of +/- object for Fan Speed | list | no |
| > DPT type for +/- Fan Speed object | list | 0-Decrease / 1-Increase [DPT_1.007] |
| > La secuencia +/- incluye AUTO? | list | no |
| > Rollover Speed at upper/lower limit (when controlling with +/- obj) | list | yes |
| Enable use of bit-type Fan Speed objects (for control) | list | no |
| Enable use of bit-type Fan Speed objects (for Control) | list | no |
| Enable use of bit-type Fan Speed objects (for Status) | list | no |
| Enable use of Text object for Fan Speed | list | no |
| ASCII strings shown in comm object "Status_ Fan Speed Text" | text | << 14-byte string values >> |
| > String when fan speed is 1 | text | SPEED 1 |
| > String when fan speed is 2 | text | SPEED 2 |
| > String when fan speed is 3 | text | SPEED 3 |
| Enable use of Legacy_ obj for Fan Speed (compatible with old ver of XXACKNX1) | list | no |
| Indoor unit has Up-Down Vanes (see docum. for your indoor unit) | list | no |
| Lamas Up-Down tienen operación AUTO (véase docum. de su Unidad Interior) | list | no |
| Enable "Control_ Vanes U-D Swing" | list | no |
| Pos. dispon. de Lamas U-D en Unidad Interior (véase docum. de Unidad Interior) | unsignedInt 5…7 | 7 |
| DPT object type for Vanes Up-Down | list | Scaling [DPT_5.001] |
| Enable use of +/- object for Vanes Up-Down | list | no |
| > DPT type for +/- Vanes Up-Down obj | list | 0-Decrease / 1-Increase [DPT_1.007] |
| > La secuencia +/- incluye Lamas AUTO? | list | no |
| > Does +/- sequen. incl. vanes SWING? | list | no |
| > Rollover Vanes at upper/lower limit (when controlling with +/- obj) | list | yes |
| Enable use of bit-type Vanes U-D objects (for control) | list | no |
| Enable use of bit-type Vanes U-D objects (for status) | list | no |
| Enable use of Text object for Vanes U-D | list | no |
| ASCII strings shown in comm object "Status_ Vanes Up-Down Text" | text | << 14-byte string values >> |
| > String when vanes U-D is in POS1 | text | U-D POS1 |
| > String when vanes U-D is in POS2 | text | U-D POS2 |
| > String when vanes U-D is in POS3 | text | U-D POS3 |
| > String when vanes U-D is in POS4 | text | U-D POS4 |
| > String when vanes U-D is in POS5 | text | U-D POS5 |
| > String when vanes U-D is in SWING | text | U-D SWING |
| Enable use of Legacy_ obj for Vanes U-D (compatible with old ver of XXACKNX1) | list | no |
| Periodic sending of "Status_ AC Setp" (in seconds; 0 = No periodic sending) | unsignedInt 0…255 | 0 |
| Transmission of "Status_ AC Return Temp" | list | only cyclically |
| > "Status_ AC Return Temp" periodic sending time (in sec) | unsignedInt 1…255 | 200 |
| Enable use of +/- object for Setpoint Temperature | list | no |
| > DPT type for Setp Temp +/- object | list | 0-Decrease / 1-Increase [DPT_1.007] |
| > Longitud de paso [+/-] | list | 1.0ºC |
| Enable limits on Control_ Setpoint obj | list | no |
| > Control_ Set Temp Lower limit (ºC) | list | 16.0ºC |
| > Control_ Set Temp Upper limit (ºC) | list | 32.0ºC |
| Ambient temp.ref. is provided from KNX (carefully read User Guide if enabled) | list | no |
| Enable use of scenes | list | no |
| Scenes can be stored from KNX bus | list | no |
| > Enable use of bit objects for storing scenes (from bus) | list | no |
| Enable use of bit objects for scene execution | list | no |
| Scene 1 preset | list | no |
| > Scene 1 / Value for On-Off | list | (unchanged) |
| > Scene 1 / Value for Mode | list | (unchanged) |
| > Scene 1 / Value for Fan Speed | list | (unchanged) |
| > Scene 1 / Value for Vanes Up-Down (if indoor unit has Vanes U-D) | list | (unchanged) |
| > Scene 1 / Value for Setp Temp (ºC) | list | (unchanged) |
| > Scene 1 / Value for Remote Lock | list | (unchanged) |
| Scene 2 preset | list | no |
| > Scene 2 / Value for On-Off | list | (unchanged) |
| > Scene 2 / Value for Mode | list | (unchanged) |
| > Scene 2 / Value for Fan Speed | list | (unchanged) |
| > Scene 2 / Value for Vanes Up-Down (if indoor unit has Vanes U-D) | list | (unchanged) |
| > Scene 2 / Value for Setp Temp (ºC) | list | (unchanged) |
| > Scene 2 / Value for Remote Lock | list | (unchanged) |
| Scene 3 preset | list | no |
| > Scene 3 / Value for On-Off | list | (unchanged) |
| > Scene 3 / Value for Mode | list | (unchanged) |
| > Scene 3 / Value for Fan Speed | list | (unchanged) |
| > Scene 3 / Value for Vanes Up-Down (if indoor unit has Vanes U-D) | list | (unchanged) |
| > Scene 3 / Value for Setp Temp (ºC) | list | (unchanged) |
| > Scene 3 / Value for Remote Lock | list | (unchanged) |
| Scene 4 preset | list | no |
| > Scene 4 / Value for On-Off | list | (unchanged) |
| > Scene 4 / Value for Mode | list | (unchanged) |
| > Scene 4 / Value for Fan Speed | list | (unchanged) |
| > Scene 4 / Value for Vanes Up-Down (if indoor unit has Vanes U-D) | list | (unchanged) |
| > Scene 4 / Value for Setp Temp (ºC) | list | (unchanged) |
| > Scene 4 / Value for Remote Lock | list | (unchanged) |
| Scene 5 preset | list | no |
| > Scene 5 / Value for On-Off | list | (unchanged) |
| > Scene 5 / Value for Mode | list | (unchanged) |
| > Scene 5 / Value for Fan Speed | list | (unchanged) |
| > Scene 5 / Value for Vanes Up-Down (if indoor unit has Vanes U-D) | list | (unchanged) |
| > Scene 5 / Value for Setp Temp (ºC) | list | (unchanged) |
| > Scene 5 / Value for Remote Lock | list | (unchanged) |
| Enable use of Open Window / Switch off timeout function | list | no |
| > AC switch-off timeout (min) | unsignedInt 0…30 | 10 |
| > DPT for Window / Switch-off timeout | list | 0-Stop / 1-Start Timeout [DPT_1.010] |
| > Disallow On/Off operation while timeout is elapsed | list | no |
| > Disallow On/Off operation while window is Open | list | no |
| > Reload last On/Off value once window is Closed | list | no |
| > Reload last On/Off value once timeout is stopped | list | no |
| Enable use of Occupancy function | list | no |
| > Timeout to apply action (minutes) | unsignedInt 0…180 | 20 |
| > Action after timeout elapsed | list | Apply Preset Delta |
| > Temp delta decrease (HEAT) or increase (COOL) (ºC) | list | 2.0ºC |
| > Enable secondary timeout | list | no |
| > Timeout to apply action (min) | unsignedInt 0…180 | 20 |
| > Action after timeout elapsed | list | Switch-Off |
| > Temp delta dec (HEAT) or inc (COOL) (ºC) | list | 4.0ºC |
| > Disallow On/Off operation while not Occupied | list | no |
| > Reload last On/Off value when Occupied | list | no |
| Enable use of SLEEP timeout | list | no |
| > Sleep function switch-off timeout (minutes) | unsignedInt 0…180 | 60 |
Version history
| Application | App no | Fingerprint | First seen | Size | File |
|---|---|---|---|---|---|
| 0105 DKRCKNX1 T08V15 1.5 latest | $0008 | 37D0 | 2026-11-25 | 158 KB | Download |
About this file
This is the official ETS product database for the Intesis DK RC Interface (DK-RC-KNX-1), published by the manufacturer in the KNX online catalog. To use it, open ETS, go to Catalogs → Import and choose the downloaded .knxprod file. The device then appears in your catalog and can be added to a project. Older versions are kept so existing projects can be matched to the application program they were commissioned with.
More from Intesis
- ACA interface (multiple indoor units) ACA-AC-KNX
- KNX Interface for ESTIA BMS-IFKX0AWR-E
- KNX Interface for Toshiba AC BMS-IFKX0TLR-E
- KNX Interface for ESTIA BMS-IFKX0UEW-E
- DK AC Interface DK-AC-KNX-1
- DK AC interface, 4 binary inputs DK-AC-KNX-1i
- DK RC interface, 4 binary inputs DK-RC-KNX-1i
- FJ RC interface, 4 binary inputs FJ-RC-KNX-1i
- HA AC interface (multiple indoor units) HA-AC-KNX
- HI AW Interface HI-AW-KNX-1
- HI RC interface, 4 binary inputs HI-RC-KNX-1i
- HS RC interface, 4 binary inputs HS-RC-KNX-1i