KNX Interface for ESTIA BMS-IFKX0AWR-E

Intesis · Order number BMS-IFKX0AWR-E · Communication › Interfaces › Toshiba Air to Water Interfaces

Download .knxprod BMS-IFKX0AWR-E V0101 1.1 · 93 KB

Product

ManufacturerIntesis
Product nameKNX Interface for ESTIA
Order numberBMS-IFKX0AWR-E
HardwareTO-AW-KNX-1
MediumTwisted Pair
Bus current (mA)8
Rail mountedNo
RegistrationCertified · 2017-10-17
Languagesen-US
Catalog entryM-0077_H-TO.2DAW.2DKNX.2D1-0_HP-002C-11-9086_CI-BMS.2DIFKX0AWR.2DE-1
Fingerprint9086
SHA-256b8104599f11e37796c85e8ed1582b08d5c468e26100b795f1a30f6bec3460830
First seen2026-11-25
Markets69 markets

Application program: BMS-IFKX0AWR-E V0101 1.1

Application number$002C
Version1.1
Mask versionMV-0025 (2.5)
KNX Data SecureNo
Minimum ETS version4.0
Parameters14
Group objects85
Group objects (85)
NoNameFunctionSizeDPTFlags
0Control_ Zones On/Off [DPT_1.001]1-On, 0-Off1 Bit1.1 switchCWTU
1Control_ HW On/Off [DPT_1.001]1-On, 0-Off1 Bit1.1 switchCWTU
2Control_ Mode [DPT_20.105]1-Heat, 3-Cool1 Byte20.105 HVAC control modeCWTU
3Control_ Mode Cool/Heat [DPT_1.100]0-Cool, 1-Heat1 Bit1.100 heating/coolingCWTU
4Control_ Mode Heat [DPT_1.002]1-Set heat mode1 Bit1.2 booleanCWTU
5Control_ Mode Cool [DPT_1.002]1-Set cool mode1 Bit1.2 booleanCWTU
6Control_ Zone1 Setting Temperature [DPT_9.001]ºC2 Bytes9.1 temperature (°C)CWTU
7Control_ Zone2 Setting Temperature [DPT_9.001]ºC2 Bytes9.1 temperature (°C)CWTU
8Control_ HW Setting Temperature [DPT_9.001]ºC2 Bytes9.1 temperature (°C)CWTU
9Control_ Auto temperature On/Off [DPT_1.001]1-On, 0-Off1 Bit1.1 switchCWTU
10Control_ Night Setback On/Off [DPT_1.001]1-On, 0-Off1 Bit1.1 switchCWTU
11Control_ HW Boost On/Off [DPT_1.001]1-On, 0-Off1 Bit1.1 switchCWTU
12Control_ Frost Protection On/Off [DPT_1.001]1-On, 0-Off1 Bit1.1 switchCWTU
13Control_ Antibacteria On/Off [DPT_1.001]1-On, 0-Off1 Bit1.1 switchCWTU
14Status_ Zones On/Off [DPT_1.001]1-On, 0-Off1 Bit1.1 switchCRT
15Status_ HW On/Off [DPT_1.001]1-On, 0-Off1 Bit1.1 switchCRT
16Status_ Mode [DPT_20.105]1-Heat, 3-Cool1 Byte20.105 HVAC control modeCRT
17Status_ Mode Cool/Heat [DPT_1.100]0-Cool, 1-Heat1 Bit1.100 heating/coolingCRT
18Status_ Mode Heat [DPT_1.002]1-Heat mode active1 Bit1.2 booleanCRT
19Status_ Mode Cool [DPT_1.002]1-Cool mode active1 Bit1.2 booleanCRT
20Status_ Zone1 Setting Temperature [DPT_9.001]ºC2 Bytes9.1 temperature (°C)CRT
21Status_ Zone2 Setting Temperature [DPT_9.001]ºC2 Bytes9.1 temperature (°C)CRT
22Status_ HW Setting Temperature [DPT_9.001]ºC2 Bytes9.1 temperature (°C)CRT
23Status_ Auto Temperature On/Off [DPT_1.001]1-On, 0-Off1 Bit1.1 switchCRT
24Status_ Night Setback On/Off [DPT_1.001]1-On, 0-Off1 Bit1.1 switchCRT
25Status_ HW Boost On/Off [DPT_1.001]1-On, 0-Off1 Bit1.1 switchCRT
26Status_ Frost Protection On/Off [DPT_1.001]1-On, 0-Off1 Bit1.1 switchCRT
27Status_ Antibacteria On/Off [DPT_1.001]1-On, 0-Off1 Bit1.1 switchCRT
28Status_ Alarm [DPT_1.005]1-Alarm, 0-No alarm1 Bit1.5 alarmCRT
29Status_ Alarm Code [2byte]Alarm code2 BytesCRT
30Status_ Alarm Text [DPT_16.001]Alarm description14 Bytes16.1 Character String (ISO 8859-1)CRT
31Status_ Alarm Address [1byte]Alarm address1 ByteCRT
32Status_ Zone1 Control Temperature [DPT_9.001]ºC2 Bytes9.1 temperature (°C)CRT
33Status_ Zone2 Control Temperature [DPT_9.001]ºC2 Bytes9.1 temperature (°C)CRT
34Status_ HW Control Temperature [DPT_9.001]ºC2 Bytes9.1 temperature (°C)CRT
35Status_ Control Temperature [DPT_9.001]ºC2 Bytes9.1 temperature (°C)CRT
36Status_ Outdoor Liquid Temperature [DPT_9.001]ºC2 Bytes9.1 temperature (°C)CRT
37Status_ HW Cylinder Water Temperature (TTW) [DPT_9.001]ºC2 Bytes9.1 temperature (°C)CRT
38Status_ Condensed Refrigerant Temperature [DPT_9.001]ºC2 Bytes9.1 temperature (°C)CRT
39Status_ Water Inlet Temperature (TWI) [DPT_9.001]ºC2 Bytes9.1 temperature (°C)CRT
40Status_ Water Outlet Temperature (TWO) [DPT_9.001]ºC2 Bytes9.1 temperature (°C)CRT
41Status_ Water Heater Outlet Temperature (THO) [DPT_9.001]ºC2 Bytes9.1 temperature (°C)CRT
42Status_ Zone2 Inlet Temperature (TFI) [DPT_9.001]ºC2 Bytes9.1 temperature (°C)CRT
43Status_ Motorized Mixing Valve Position [DPT_5.010]Position1 Byte5.10 counter pulses (0..255)CRT
44Status_ System Low Pressure [DPT_14.058]Pa4 Bytes14.58 pressure (Pa)CRT
45Status_ Outdoor Heat Exchanger Temperature [DPT_9.001]ºC2 Bytes9.1 temperature (°C)CRT
46Status_ Discharge Temperature [DPT_9.001]ºC2 Bytes9.1 temperature (°C)CRT
47Status_ Outdoor Suction Temperature [DPT_9.001]ºC2 Bytes9.1 temperature (°C)CRT
48Status_ Outside Temperature [DPT_9.001]ºC2 Bytes9.1 temperature (°C)CRT
49Status_ Outdoor Compressor Frequency [DPT_14.033]Hz4 Bytes14.33 frequency (Hz)CRT
50Status_ Outdoor Lower Fan Speed [DPT_14.033]Hz4 Bytes14.33 frequency (Hz)CRT
51Status_ Outdoor Upper Fan Speed [DPT_14.033]Hz4 Bytes14.33 frequency (Hz)CRT
52Status_ HW mode compressor Second Counter [DPT_13.100]Sec4 Bytes13.100 time lag (s)CRT
53Status_ HW mode compressor Hour Counter [DPT_7.007]Hours2 Bytes7.7 time (h)CRT
54Status_ Heating mode compressor Second Counter [DPT_13.100]Sec4 Bytes13.100 time lag (s)CRT
55Status_ Heating mode compressor Hour Counter [DPT_7.007]Hours2 Bytes7.7 time (h)CRT
56Status_ Cooling mode compressor Second Counter [DPT_13.100]Sec4 Bytes13.100 time lag (s)CRT
57Status_ Cooling mode compressor Hour Counter [DPT_7.007]Hours2 Bytes7.7 time (h)CRT
58Status_ HU water pump operation Second Counter [DPT_13.100]Sec4 Bytes13.100 time lag (s)CRT
59Status_ HU water pump operation Hour Counter [DPT_7.007]Hours2 Bytes7.7 time (h)CRT
60Status_ HW cylinder heater Second Counter [DPT_13.100]Sec4 Bytes13.100 time lag (s)CRT
61Status_ HW cylinder heater Hour Counter [DPT_7.007]Hours2 Bytes7.7 time (h)CRT
62Status_ HU back up Heater Second Counter [DPT_13.100]Sec4 Bytes13.100 time lag (s)CRT
63Status_ HU back up Heater Hour Counter [DPT_7.007]Hours2 Bytes7.7 time (h)CRT
64Status_ Zone1 Device Connected [DPT_1.002]0-Not connected, 1-Connected1 Bit1.2 booleanCRT
65Status_ Zone2 Device Connected [DPT_1.002]0-Not connected, 1-Connected1 Bit1.2 booleanCRT
66Status_ HW Device Connected [DPT_1.002]0-Not connected, 1-Connected1 Bit1.2 booleanCRT
67Status_ Zones Cool Setting Temperature MAX [DPT_9.001]ºC2 Bytes9.1 temperature (°C)CRT
68Status_ Zones Cool Setting Temperature MIN [DPT_9.001]ºC2 Bytes9.1 temperature (°C)CRT
69Status_ Zone1 Heat Setting Temperature MAX [DPT_9.001]ºC2 Bytes9.1 temperature (°C)CRT
70Status_ Zone1 Heat Setting Temperature MIN [DPT_9.001]ºC2 Bytes9.1 temperature (°C)CRT
71Status_ Zone2 Heat Setting Temperature MAX [DPT_9.001]ºC2 Bytes9.1 temperature (°C)CRT
72Status_ Zone2 Heat Setting Temperature MIN [DPT_9.001]ºC2 Bytes9.1 temperature (°C)CRT
73Status_ HW mode water Temp MAX [DPT_9.001]ºC2 Bytes9.1 temperature (°C)CRT
74Status_ HW mode water Temp MIN [DPT_9.001]ºC2 Bytes9.1 temperature (°C)CRT
75Status_ Frost protection Setting Temperature [DPT_9.001]ºC2 Bytes9.1 temperature (°C)CRT
76Status_ HW Boost Setting Temperature [DPT_9.001]ºC2 Bytes9.1 temperature (°C)CRT
77Status_ Antibacteria Setting Temperature [DPT_9.001]ºC2 Bytes9.1 temperature (°C)CRT
78Status_ Operation Heat Mode Permitted [DPT_1.002]0-Not permitted, 1-Permitted1 Bit1.2 booleanCRT
79Status_ Operation Cool Mode Permitted [DPT_1.002]0-Not permitted, 1-Permitted1 Bit1.2 booleanCRT
80Status_ Auto Temperature Permitted [DPT_1.002]0-Not permitted, 1-Permitted1 Bit1.2 booleanCRT
81Status_ Frost Protection Permitted [DPT_1.002]0-Not permitted, 1-Permitted1 Bit1.2 booleanCRT
82Status_ Night Setback Permitted [DPT_1.002]0-Not permitted, 1-Permitted1 Bit1.2 booleanCRT
83Status_ HW Boost Permitted [DPT_1.002]0-Not permitted, 1-Permitted1 Bit1.2 booleanCRT
84Status_ Antibacteria Permitted [DPT_1.002]0-Not permitted, 1-Permitted1 Bit1.2 booleanCRT
Parameters (14)
ParameterTypeDefault
Send READs for objects on bus recovery (T & U flags must be active)listYes
Delay before sending READsunsignedInt 0…3010
Download latest database entry for this product and its User Manual from:texthttp://www.toshiba-carrier.co.jp/global/
ModellistESTIA 5 Series
Number of zones availablelist1 zone
Cool/Heat mode objects (control and status)listEnabled
1 byte mode objects (control and status)listDisabled
1 bit mode objects (control and status)listEnabled
Enable additional signals of zoneslistNo
Monitor outdoor unit signalslistNo
Monitor hydro unit signalslistNo
Hot Water CylinderlistDisabled
Enable additional signals of Hot Water CylinderlistNo
Alarm objectslistDisabled

Version history

ApplicationApp noFingerprintFirst seenSizeFile
BMS-IFKX0AWR-E V0101 1.1 latest$002C90862026-11-2593 KBDownload

About this file

This is the official ETS product database for the Intesis KNX Interface for ESTIA (BMS-IFKX0AWR-E), published by the manufacturer in the KNX online catalog. To use it, open ETS, go to Catalogs → Import and choose the downloaded .knxprod file. The device then appears in your catalog and can be added to a project. Older versions are kept so existing projects can be matched to the application program they were commissioned with.