Intesis PA-RC2-KNX-1i PA RC2 interface, 4 binary inputs

PA RC2 interface, 4 binary inputs PA-RC2-KNX-1i

Intesis · Order number PA-RC2-KNX-1i · Communication › Interfaces › Panasonic Air Conditioning Interfaces

Download .knxprod 0115 PARC2KNX1i T15V13 1.3 · 143 KB

Product

ManufacturerIntesis
Product namePA RC2 interface, 4 binary inputs
Order numberPA-RC2-KNX-1i
HardwarePA RC2 Interface
MediumTwisted Pair
Bus current (mA)5
Rail mountedNo
RegistrationCertified
Languageses-ES, en-US
Catalog entryM-0077_H-PA.2DRC2.2DKNX.2D1i-16_HP-0015-13-4B73_CI-PA.2DRC2.2DKNX.2D1i-1
Fingerprint4B73
SHA-256de34eab65e6ecf2eb4215963816b303da1bdd91987187ff5a2fe99f9c63b1c8c
First seen2026-11-25
Markets69 markets

Application program: 0115 PARC2KNX1i T15V13 1.3

Application number$0015
Version1.3
Mask versionMV-0025 (2.5)
KNX Data SecureNo
Minimum ETS version4.0
Parameters361
Group objects146
Group objects (146)
NoNameFunctionSizeDPTFlags
0Control_ On/Off [DPT_1.001 - 1bit]0-Off;1-On1 Bit1.1 switchCWT
1Control_ Mode [DPT_20.105 - 1byte]0-Aut;1-Hea;3-Coo;9-Fan;14-Dry1 ByteCWT
2Control_ Mode Cool/Heat [DPT_1.100 - 1bit]0-Cool;1-Heat1 BitCWT
3Control_ Mode Cool & On [DPT_5.001 - 1byte]0%-Off;0.1%-100%-On+Cool1 Byte5.1 percentage (0..100%)CWT
4Control_ Mode Heat & On [DPT_5.001 - 1byte]0%-Off;0.1%-100%-On+Heat1 Byte5.1 percentage (0..100%)CWT
5Control_ Mode Auto [DPT_1.002 - 1bit]1-Set AUTO mode1 Bit1.2 booleanCWT
6Control_ Mode Heat [DPT_1.002 - 1bit]1-Set HEAT mode1 Bit1.2 booleanCWT
7Control_ Mode Cool [DPT_1.002 - 1bit]1-Set COOL mode1 Bit1.2 booleanCWT
8Control_ Mode Fan [DPT_1.002 - 1bit]1-Set FAN mode1 Bit1.2 booleanCWT
9Control_ Mode Dry [DPT_1.002 - 1bit]1-Set DRY mode1 Bit1.2 booleanCWT
10Control_ Mode -/+ [DPT_1.007 - 1bit]0-Decrease;1-Increase1 BitCW
10Control_ Mode +/- [DPT_1.008 - 1bit]0-Up;1-Down1 Bit1.8 up/downCW
11Control_ Fan Speed / 3 Speeds [DPT_5.010 - 1byte] Speed values: 1,2,31 Byte5.10 counter pulses (0..255)CWT
11Control_ Fan Speed / 3 Speeds [DPT_5.001 - 1byte]Thresholds: 50% and 83%1 Byte5.1 percentage (0..100%)CWT
12Control_ Fan Speed Man/Auto [DPT_1.002 - 1bit]0-Manual; 1-Auto1 Bit1.2 booleanCWT
13Control_ Fan Speed 1 [DPT_1.002 - 1bit]1-Set Fan Speed 11 Bit1.2 booleanCWT
14Control_ Fan Speed 2 [DPT_1.002 - 1bit]1-Set Fan Speed 21 Bit1.2 booleanCWT
15Control_ Fan Speed 3 [DPT_1.002 - 1bit]1-Set Fan Speed 31 Bit1.2 booleanCWT
16Control_ Fan Speed -/+ [DPT_1.007 - 1bit]0-Decrease;1-Increase1 BitCW
16Control_ Fan Speed +/- [DPT_1.008 - 1bit]0-Up;1-Down1 Bit1.8 up/downCW
17Control_ Vanes U-D / 5 Pos [DPT_5.001 - 1byte]Thresholds:30%,50%,70% and 90%1 Byte5.1 percentage (0..100%)CWT
17Control_ Vanes U-D / 5 Pos [DPT_5.010 - 1byte]Position values: 1,2,3,4,51 Byte5.10 counter pulses (0..255)CWT
18Control_ Vanes U-D Standby [DPT_1.002 - 1bit]0-Off;1-Standby1 Bit1.2 booleanCWT
19Control_ Vanes U-D Pos 1 [DPT_1.002 - 1bit]1-Set Position 11 Bit1.2 booleanCWT
20Control_ Vanes U-D Pos 2 [DPT_1.002 - 1bit]1-Set Position 21 Bit1.2 booleanCWT
21Control_ Vanes U-D Pos 3 [DPT_1.002 - 1bit]1-Set Position 31 Bit1.2 booleanCWT
22Control_ Vanes U-D Pos 4 [DPT_1.002 - 1bit]1-Set Position 41 Bit1.2 booleanCWT
23Control_ Vanes U-D Pos 5 [DPT_1.002 - 1bit]1-Set Position 51 Bit1.2 booleanCWT
24Control_ Vanes U-D Swing [DPT_1.002 - 1bit]0-Off;1-Swing1 Bit1.2 booleanCWT
25Control_ Vanes U-D -/+ [DPT_1.007 - 1bit]0-Decrease;1-Increase1 BitCWT
25Control_ Vanes U-D +/- [DPT_1.008 - 1bit]0-Up;1-Down1 Bit1.8 up/downCWT
26Control_ Setpoint Temp [DPT_9.001 - 2byte]ºC2 Bytes9.1 temperature (°C)CWT
27Control_ Setpoint Temp -/+ [DPT_1.007 - 1bit]0-Decrease;1-Increase1 BitCW
27Control_ Setpoint Temp +/- [DPT_1.008 - 1bit]0-Up;1-Down1 Bit1.8 up/downCW
28Control_ Ambient Temp [DPT_9.001 - 2byte]ºC2 Bytes9.1 temperature (°C)CWT
29Control_ Reset Filter [DPT_1.015 - 1bit]1-Reset filter1 BitCWT
30Control_ Switch Off Timeout [DPT_1.010 - 1bit]0-Stop;1-Start1 Bit1.10 start/stopCWT
30Control_ Window Contact Status [DPT_1.009 - 1bit]0-Open;1-Closed1 Bit1.9 open/closeCWT
31Control_ Occupancy [DPT_1.018 - 1bit]0-Not Occupied;1-Occupied1 BitCWT
32Control_ Sleep Timeout [DPT_1.010 - 1bit]0-Stop;1-Start1 Bit1.10 start/stopCWT
33Control_ Lock Remote Control [DPT_1.002 - 1bit]0-Unlock;1-Lock1 Bit1.2 booleanCWT
34Control_ Lock Control Objects [DPT_1.002 - 1bit]0-Unlock;1-Lock1 Bit1.2 booleanCWT
35Control_ Power Mode [DPT_1.010 - 1bit]0-Stop;1-Start1 Bit1.10 start/stopCWT
36Control_ Econo Mode [DPT_1.010 - 1bit]0-Stop;1-Start1 Bit1.10 start/stopCWT
37Control_ Additional Heat [DPT_1.010 - 1bit]0-Stop;1-Start1 Bit1.10 start/stopCWT
38Control_ Additional Cool [DPT_1.010 - 1bit]0-Stop;1-Start1 Bit1.10 start/stopCWT
39Control_ Execute Scene [DPT_17.001 - 1byte]0..4-Exec1-51 ByteCWT
39Control_ Save/Exec Scene [DPT_18.001 - 1byte]0..4-Exec1-5;128..132-Save1-51 ByteCWT
40Control_ Store Scene 1 [DPT_1.002 - 1bit]1-Store Scene 11 Bit1.2 booleanCW
41Control_ Store Scene 2 [DPT_1.002 - 1bit]1-Store Scene 21 Bit1.2 booleanCW
42Control_ Store Scene 3 [DPT_1.002 - 1bit]1-Store Scene 31 Bit1.2 booleanCW
43Control_ Store Scene 4 [DPT_1.002 - 1bit]1-Store Scene 41 Bit1.2 booleanCW
44Control_ Store Scene 5 [DPT_1.002 - 1bit]1-Store Scene 51 Bit1.2 booleanCW
45Control_ Execute Scene 1 [DPT_1.002 - 1bit]1-Execute Scene 11 Bit1.2 booleanCWT
46Control_ Execute Scene 2 [DPT_1.002 - 1bit]1-Execute Scene 21 Bit1.2 booleanCWT
47Control_ Execute Scene 3 [DPT_1.002 - 1bit]1-Execute Scene 31 Bit1.2 booleanCWT
48Control_ Execute Scene 4 [DPT_1.002 - 1bit]1-Execute Scene 41 Bit1.2 booleanCWT
49Control_ Execute Scene 5 [DPT_1.002 - 1bit]1-Execute Scene 51 Bit1.2 booleanCWT
50Control_ Disable Input 1 [DPT_1.003 - 1bit]0-Disable;1-Enable1 Bit1.3 enableCWT
50Control_ Disable Input 1 [DPT_1.002 - 1bit]0-False;1-True1 Bit1.2 booleanCWT
51Control_ Disable Input 2 [DPT_1.002 - 1bit]0-False;1-True1 Bit1.2 booleanCWT
51Control_ Disable Input 2 [DPT_1.003 - 1bit]0-Disable;1-Enable1 Bit1.3 enableCWT
52Control_ Disable Input 3 [DPT_1.002 - 1bit]0-False;1-True1 Bit1.2 booleanCWT
52Control_ Disable Input 3 [DPT_1.003 - 1bit]0-Disable;1-Enable1 Bit1.3 enableCWT
53Control_ Disable Input 4 [DPT_1.002 - 1bit]0-False;1-True1 Bit1.2 booleanCWT
53Control_ Disable Input 4 [DPT_1.003 - 1bit]0-Disable;1-Enable1 Bit1.3 enableCWT
54Status_ On/Off [DPT_1.001 - 1bit]0-Off;1-On1 Bit1.1 switchCRT
55Status_ Mode [DPT_20.105 - 1byte]0-Aut;1-Hea;3-Coo;9-Fan;14-Dry1 ByteCRT
56Status_ Mode Cool/Heat [DPT_1.100 - 1bit]0-Cool;1-Heat1 BitCRT
57Status_ Mode Auto [DPT_1.002 - 1bit]1-AUTO mode is active1 Bit1.2 booleanCRT
58Status_ Mode Heat [DPT_1.002 - 1bit]1-HEAT mode is active1 Bit1.2 booleanCRT
59Status_ Mode Cool [DPT_1.002 - 1bit]1-COOL mode is active1 Bit1.2 booleanCRT
60Status_ Mode Fan [DPT_1.002 - 1bit]1-FAN mode is active1 Bit1.2 booleanCRT
61Status_ Mode Dry [DPT_1.002 - 1bit]1-DRY mode is active1 Bit1.2 booleanCRT
62Status_ Mode Text [DPT_16.001 - 14byte]ASCII String14 Bytes16.1 Character String (ISO 8859-1)CRT
63Status_ Fan Speed / 3 Speeds [DPT_5.010 - 1byte]Speed Values: 1,2,31 Byte5.10 counter pulses (0..255)CRT
63Status_ Fan Speed / 3 Speeds [DPT_5.001 - 1byte]33%, 67% and 100%1 Byte5.1 percentage (0..100%)CRT
64Status_ Fan Speed Man/Auto [DPT_1.002 - 1bit]0-Manual;1-Auto1 Bit1.2 booleanCRT
65Status_ Fan Speed 1 [DPT_1.002 - 1bit]1-Fan in speed 11 Bit1.2 booleanCRT
66Status_ Fan Speed 2 [DPT_1.002 - 1bit]1-Fan in speed 21 Bit1.2 booleanCRT
67Status_ Fan Speed 3 [DPT_1.002 - 1bit]1-Fan in speed 31 Bit1.2 booleanCRT
68Status_ Fan Speed Text [DPT_16.001 - 14byte]ASCII String14 Bytes16.1 Character String (ISO 8859-1)CRT
69Status_ Vanes U-D / 5 Pos [DPT_5.001 - 1byte]20%, 40%, 60%, 80% and 100%1 Byte5.1 percentage (0..100%)CRT
69Status_ Vanes U-D / 5 Pos [DPT_5.010 - 1byte]Position values: 1,2,3,4,51 Byte5.10 counter pulses (0..255)CRT
70Status_ Vanes U-D Standby [DPT_1.002 - 1bit]0-Off;1-Standby1 Bit1.2 booleanCRT
71Status_ Vanes U-D Pos 1 [DPT_1.002 - 1bit]1-Vanes in Position 11 Bit1.2 booleanCRT
72Status_ Vanes U-D Pos 2 [DPT_1.002 - 1bit]1-Vanes in Position 21 Bit1.2 booleanCRT
73Status_ Vanes U-D Pos 3 [DPT_1.002 - 1bit]1-Vanes in Position 31 Bit1.2 booleanCRT
74Status_ Vanes U-D Pos 4 [DPT_1.002 - 1bit]1-Vanes in Position 41 Bit1.2 booleanCRT
75Status_ Vanes U-D Pos 5 [DPT_1.002 - 1bit]1-Vanes in Position 51 Bit1.2 booleanCRT
76Status_ Vanes U-D Swing [DPT_1.002 - 1bit]0-Off;1-Swing1 Bit1.2 booleanCRT
77Status_ Vanes U-D Text [DPT_16.001 - 14byte]ASCII String14 Bytes16.1 Character String (ISO 8859-1)CRT
78Status_ AC Setpoint Temp [DPT_9.001 - 2byte]ºC2 Bytes9.1 temperature (°C)CRT
79Status_ AC Ambient Ref Temp [DPT_9.001 - 2byte]ºC2 Bytes9.1 temperature (°C)CRT
80Status_ Filter Status [DPT_1.005 - 1bit]0-No alarm;1-Alarm1 BitCRT
81Status_ Error/Alarm [DPT_1.005 - 1bit]0-No alarm;1-Alarm1 BitCRT
82Status_ Error Code [2byte]0-No error /Any other see man.2 BytesCRT
83Status_ Error Text Code [DPT_16.001 - 14byte]3-char PA Error; Empty-None14 Bytes16.1 Character String (ISO 8859-1)CRT
84Status_ Lock Remote Control [DPT_1.002 - 1bit]0-Unlocked;1-Locked1 Bit1.2 booleanCRT
85Status_ Lock Control Objects [DPT_1.002 - 1bit]0-Unlocked;1-Locked1 Bit1.2 booleanCRT
86Status_ Power Mode [DPT_1.001 - 1bit]0-Off;1-On1 Bit1.1 switchCRT
87Status_ Econo Mode [DPT_1.001 - 1bit]0-Off;1-On1 Bit1.1 switchCRT
88Status_ Additional Heat [DPT_1.001 - 1bit]0-Off;1-On1 Bit1.1 switchCRT
89Status_ Additional Cool [DPT_1.001 - 1bit]0-Off;1-On1 Bit1.1 switchCRT
90Status_ Operation Hour Counter [DPT_7.001 - 2byte]Number of operating hours2 Bytes7.1 pulsesCRT
91Status_ Current Scene [DPT_17.001 - 1byte]0..4-Scene X+1;63-No Scene1 ByteCRT
92Status_ In1 - Switching [DPT_1.001 - 1bit]0-Off;1-On1 Bit1.1 switchCRT
92Status_ In1 - Dimming - On/Off [DPT_1.001 - 1bit]0-Off;1-On1 Bit1.1 switchCRT
92Status_ In1 - Shut/Blind - Step [DPT_1.007 - 1bit]0-Step Up;1-Step Down1 BitCRT
93Status_ In1 - Dimming - Step(%) [DPT_3.007 - 4bit]Dimming step4 Bit3.7 dimming controlCRT
93Status_ In1 - Shut/Blind - Move [DPT_1.008 - 1bit]0-Move Up;1-Move Down1 Bit1.8 up/downCRT
93Status_ In1 - Value [DPT_12.001 - 12byte]4-byte unsigned value4 Bytes12.1 counter pulses (unsigned)CRT
93Status_ In1 - Value [DPT_5.010 - 1byte]1-byte unsigned value1 Byte5.10 counter pulses (0..255)CRT
93Status_ In1 - Value [DPT_8.001 - 2byte]2-byte signed value2 Bytes8.1 pulses differenceCRT
93Status_ In1 - Value [DPT_9.001 - 2byte]Temperature (ºC)2 Bytes9.1 temperature (°C)CRT
93Status_ In1 - Value [DPT_7.001 - 2byte]2-byte unsigned value2 Bytes7.1 pulsesCRT
94Status_ In2 - Switching [DPT_1.001 - 1bit]0-Off;1-On1 Bit1.1 switchCRT
94Status_ In2 - Dimming - On/Off [DPT_1.001 - 1bit]0-Off;1-On1 Bit1.1 switchCRT
94Status_ In2 - Shut/Blind - Step [DPT_1.007 - 1bit]0-Step Up;1-Step Down1 BitCRT
95Status_ In2 - Dimming - Step(%) [DPT_3.007 - 4bit]Dimming step4 Bit3.7 dimming controlCRT
95Status_ In2 - Value [DPT_7.001 - 2byte]2-byte unsigned value2 Bytes7.1 pulsesCRT
95Status_ In2 - Value [DPT_5.010 - 1byte]1-byte unsigned value1 Byte5.10 counter pulses (0..255)CRT
95Status_ In2 - Shut/Blind - Move [DPT_1.008 - 1bit]0-Move Up;1-Move Down1 Bit1.8 up/downCRT
95Status_ In2 - Value [DPT_12.001 - 12byte]4-byte unsigned value4 Bytes12.1 counter pulses (unsigned)CRT
95Status_ In2 - Value [DPT_9.001 - 2byte]Temperature (ºC)2 Bytes9.1 temperature (°C)CRT
95Status_ In2 - Value [DPT_8.001 - 2byte]2-byte signed value2 Bytes8.1 pulses differenceCRT
96Status_ In3 - Switching [DPT_1.001 - 1bit]0-Off;1-On1 Bit1.1 switchCRT
96Status_ In3 - Dimming - On/Off [DPT_1.001 - 1bit]0-Off;1-On1 Bit1.1 switchCRT
96Status_ In3 - Shut/Blind - Step [DPT_1.007 - 1bit]0-Step Up;1-Step Down1 BitCRT
97Status_ In3 - Dimming - Step(%) [DPT_3.007 - 4bit]Dimming step4 Bit3.7 dimming controlCRT
97Status_ In3 - Value [DPT_12.001 - 12byte]4-byte unsigned value4 Bytes12.1 counter pulses (unsigned)CRT
97Status_ In3 - Value [DPT_9.001 - 2byte]Temperature (ºC)2 Bytes9.1 temperature (°C)CRT
97Status_ In3 - Value [DPT_8.001 - 2byte]2-byte signed value2 Bytes8.1 pulses differenceCRT
97Status_ In3 - Value [DPT_7.001 - 2byte]2-byte unsigned value2 Bytes7.1 pulsesCRT
97Status_ In3 - Value [DPT_5.010 - 1byte]1-byte unsigned value1 Byte5.10 counter pulses (0..255)CRT
97Status_ In3 - Shut/Blind - Move [DPT_1.008 - 1bit]0-Move Up;1-Move Down1 Bit1.8 up/downCRT
98Status_ In4 - Switching [DPT_1.001 - 1bit]0-Off;1-On1 Bit1.1 switchCRT
98Status_ In4 - Dimming - On/Off [DPT_1.001 - 1bit]0-Off;1-On1 Bit1.1 switchCRT
98Status_ In4 - Shut/Blind - Step [DPT_1.007 - 1bit]0-Step Up;1-Step Down1 BitCRT
99Status_ In4 - Dimming - Step(%) [DPT_3.007 - 4bit]Dimming step4 Bit3.7 dimming controlCRT
99Status_ In4 - Value [DPT_12.001 - 12byte]4-byte unsigned value4 Bytes12.1 counter pulses (unsigned)CRT
99Status_ In4 - Value [DPT_9.001 - 2byte]Temperature (ºC)2 Bytes9.1 temperature (°C)CRT
99Status_ In4 - Value [DPT_8.001 - 2byte]2-byte signed value2 Bytes8.1 pulses differenceCRT
99Status_ In4 - Value [DPT_7.001 - 2byte]2-byte unsigned value2 Bytes7.1 pulsesCRT
99Status_ In4 - Value [DPT_5.010 - 1byte]1-byte unsigned value1 Byte5.10 counter pulses (0..255)CRT
99Status_ In4 - Shut/Blind - Move [DPT_1.008 - 1bit]0-Move Up;1-Move Down1 Bit1.8 up/downCRT
Parameters (233)
ParameterTypeDefault
Download latest database entry for this product and its User Manual from:texthttp://www.intesis.com
Send READs for Control_ objects on bus recovery (T & U flags must be active)listNo
> Delay before sending READs (sec)unsignedInt 0…3010
Scene to load on bus recovery / startup (needs to define vals for that scene)list(none)
Enable object "Error Code [2byte]"listNo
Disallow control from remote controllerlistNo
> Enable "Lock Remote Control" objslistNo
Enable func "Lock Control Objects"listNo
Enable func "Operating Hours Counter"listNo
When mode is AUTO Status_ objs report actual operating status (HEAT/COOL/..)listNo
Enable "Mode Cool/Heat" objects (for Control and Status)listNo
Enable PID-Compat. Scaling Mode objects (for Control)listNo
Enable use of +/- object for ModelistNo
> DPT type for +/- Mode Objectlist0-Decrease / 1-Increase [DPT_1.007]
Enable use of bit-type Mode objects (for Control)listNo
Enable use of bit-type Mode objects (for Status)listNo
Enable use of Text object for ModelistNo
ASCII strings shown in comm object "Status_ Mode Text"text<< 14-byte string values >>
> String when mode is AUTO (if available)textAUTO
> String when mode is HEAT (if available)textHEAT
> String when mode is COOLtextCOOL
> String when mode is FANtextFAN
> String when mode is DRYtextDRY
Enable use of "POWERFUL" mode (AC feature)listNo
Enable use of "QUIET" mode (AC feature)listNo
Enable use of POWER modelistNo
> Action time for this mode (minutes)unsignedInt 1…18030
> Setpoint delta increase (HEAT) or decrease (COOL) (ºC)list2.0 ºC
> Fan Speed for this modelistFAN SPEED 3
Enable use of ECONOMY modelistNo
> Setpoint delta decrease (HEAT) or increase (COOL) (ºC)list2.0 ºC
> Fan Speed for this modelistFAN SPEED 1
Enable use of Sleep functionlistNo
> Sleep function switch-off timeout (minutes)unsignedInt 0…18060
Enable use of ADDITIONAL HEATING modelistNo
> Fan Speed for this modelistFAN SPEED AUTO
Enable use of ADDITIONAL COOLING modelistNo
Enable "Fan Speed Man/Auto" objects (for Control and Status)listNo
Enable use of +/- object for Fan SpeedlistNo
> DPT type for +/- Fan Speed objectlist0-Decrease / 1-Increase [DPT_1.007]
> Does +/- sequence include fan speed AUTO?listNo
> Rollover Speed at upper/lower limit (when controlling with +/- obj)listYes
Enable "Vanes U-D Standby" objects (for Control and Status)listNo
Enable use of +/- object for Vanes U-DlistNo
> DPT type for +/- Vanes U-D objectlist0-Decrease / 1-Increase [DPT_1.007]
> Does +/- sequence include STANDBY vanes Up-Down?listNo
> Rollover Vanes at upper/lower limit (when controlling with +/- obj)listYes
Enable use of Text object for Vanes U-DlistNo
ASCII strings shown in comm object "Status_ Vanes U-D Text"text<< 14-byte string values >>
> String when vanes U-D in STANDBYtextU-D STANDBY
> String when vanes U-D in POS 1 (if available)textU-D POS 1
> String when vanes U-D in POS 2 (if available)textU-D POS 2
> String when vanes U-D in POS 3 (if available)textU-D POS 3
> String when vanes U-D in POS 4 (if available)textU-D POS 4
> String when vanes U-D in POS 5 (if available)textU-D POS 5
DPT object type for Vanes Left-RightlistScaling [DPT_5.001]
Enable use of +/- object for Vanes L-RlistNo
> DPT type for +/- Vanes L-R objectlist0-Decrease / 1-Increase [DPT_1.007]
> Does +/- sequence include vanes Left-Right AUTO?listNo
Enable use of bit-type Vanes L-R objects (for Control)listNo
Enable use of bit-type Vanes L-R objects (for Status)listNo
Enable use of Text object for Vanes L-RlistNo
ASCII strings shown in comm object "Status_ Vanes L-R Text"text<< 14-byte string values >>
> String when vanes L-R in AUTOtextL-R AUTO
> String when vanes L-R in POS 1textL-R POS 1
> String when vanes L-R in POS 2textL-R POS 2
> String when vanes L-R in POS 3textL-R POS 3
> String when vanes L-R in POS 4textL-R POS 4
> String when vanes L-R in POS 5textL-R POS 5
Periodic sending of "Status_ AC Setp" (in seconds;0=No periodic sending)unsignedInt 0…2550
Enable use of +/- obj for Setpoint TemplistNo
> DPT type for +/- Setp Temp objectlist0-Decrease / 1-Increase [DPT_1.007]
> [+/-] step sizelist1.0 ºC
Enable limits on Control_ Setpoint objlistNo
> Lower limit (ºC)list18.0 ºC
> Upper limit (ºC)list27.0 ºC
Ambient temp. ref. is provided from KNX (carefully read User Guide if enabled)listNo
Enable use of sceneslistNo
Scenes can be stored from KNX buslistNo
Enable use of bit objects for scene executionlistNo
> Enable use of bit objects for storing scenes (from bus)listNo
Scene 1 presetlistNo
> Scene 1 / Value for On-Offlist(unchanged)
> Scene 1 / Value for Modelist(unchanged)
> Scene 1 / Value for Fan Speedlist(unchanged)
> Scene 1 / Value for Vanes U-D (if available)list(unchanged)
> Scene 1 / Value for Vanes L-R (if available)list(unchanged)
> Scene 1 / Value for Setpoint Templist(unchanged)
> Scene 1 / Value for Remote Locklist(unchanged)
Scene 2 presetlistNo
> Scene 2 / Value for On-Offlist(unchanged)
> Scene 2 / Value for Modelist(unchanged)
> Scene 2 / Value for Fan Speedlist(unchanged)
> Scene 2 / Value for Vanes U-D (if available)list(unchanged)
> Scene 2 / Value for Vanes L-R (if available)list(unchanged)
> Scene 2 / Value for Setpoint Templist(unchanged)
> Scene 2 / Value for Remote Locklist(unchanged)
Scene 3 presetlistNo
> Scene 3 / Value for On-Offlist(unchanged)
> Scene 3 / Value for Modelist(unchanged)
> Scene 3 / Value for Fan Speedlist(unchanged)
> Scene 3 / Value for Vanes U-D (if available)list(unchanged)
> Scene 3 / Value for Vanes L-R (if available)list(unchanged)
> Scene 3 / Value for Setpoint Templist(unchanged)
> Scene 3 / Value for Remote Locklist(unchanged)
Scene 4 presetlistNo
> Scene 4 / Value for On-Offlist(unchanged)
> Scene 4 / Value for Modelist(unchanged)
> Scene 4 / Value for Fan Speedlist(unchanged)
> Scene 4 / Value for Vanes U-D (if available)list(unchanged)
> Scene 4 / Value for Vanes L-R (if available)list(unchanged)
> Scene 4 / Value for Setpoint Templist(unchanged)
> Scene 4 / Value for Remote Locklist(unchanged)
Scene 5 presetlistNo
> Scene 5 / Value for On-Offlist(unchanged)
> Scene 5 / Value for Modelist(unchanged)
> Scene 5 / Value for Fan Speedlist(unchanged)
> Scene 5 / Value for Vanes U-D (if available)list(unchanged)
> Scene 5 / Value for Vanes L-R (if available)list(unchanged)
> Scene 5 / Value for Setpoint Templist(unchanged)
> Scene 5 / Value for Remote Locklist(unchanged)
Enable use of Open Window / Switch off timeout functionlistNo
> AC switch-off timeout (min)unsignedInt 0…3010
> DPT for Window / Switch-off timeoutlist0-Stop / 1-Start Timeout [DPT_1.010]
> Reload last On/Off val once window is ClosedlistNo
Enable use of Occupancy functionlistNo
> Timeout to apply action (minutes)unsignedInt 0…18020
> Action after timeout elapsedlistSwitch-Off AC
> Temp delta decrease (HEAT) or increase (COOL) (ºC)list2.0 ºC
> Enable secondary timeoutlistNo
> Timeout to apply action (min)unsignedInt 1…18020
> Action after timeout elapsedlistSwitch-Off AC
> Temp delta dec (HEAT) or inc (COOL) (ºC)list3.0 ºC
Enable object "Error Text Code [14byte]" (3 ASCII-char Error Code)listYes
Indoor unit has HEAT mode (see docum. for your indoor unit)listYes
> Disallow On/Off operation while window is OpenlistNo
> Disallow On/Off operation while timeout is elapsedlistNo
> Reload last On/Off val once timeout is stoppedlistNo
> Disallow On/Off operation while not OccupiedlistNo
> Reload last On/Off value when OccupiedlistNo
> Debounce timelist50 ms
> Contact typelistNO: Normally Open
> Disabling functionlistNo
> FunctionlistSwitching
> Sending delay after bus recovery (seconds)unsignedInt 0…25510
> Send telegram after bus recoverylistNo action
Indoor unit has FAN mode (see docum. for your indoor unit)listYes
> Value on raising edge (contact activated)listNo action
> Value on falling edge (contact deactivated)listNo action
> Period for cyclical sending (seconds)unsignedInt 1…6553510
> Cyclical sendinglistNever
> Scene when contact is activated (needs to be defined)listScene 1
> Setpoint temp for this mode (ºC)list20.0 ºC
> Setpoint temp for this mode (ºC)list27.0 ºC
Enable use of Input 1listNo
Enable use of Input 2listNo
Enable use of Input 3listNo
Enable use of Input 4listNo
> Reset Input when enablinglistNo
> Mode for short (long) operationlistToggle: On/Off (increase/decrease)
> Increasing steplist+ 25 %
> Decreasing steplist- 25 %
> Short/long operation limit (x100ms)unsignedInt 1…25510
> Cycl. send. period in long oper. (x100ms)(0-No cyclical send.)unsignedInt 0…2550
> OperationlistToggle (Up/Down)
> MethodlistStep-Move-Step
> Vanes adjustment time (x100ms)unsignedInt 1…25510
> DPT to be sentlistDPT 5.010 (1byte)
> Value on raising edge (when contact activated)unsignedInt 0…2550
> Value on raising edge (when contact activated)unsignedInt 0…655350
> Value on raising edge (when contact activated)signedInt -32768…327670
> Value on rais. edge (x0.1ºC) (when contact activated)signedInt -2730…3276250
> Value on raising edge (when contact activated)unsignedInt 0…42949672950
Enable use of Legacy_ object for Mode (compatible with old vers of XXACKNX1)listNo
Enable use of Legacy_ object for Fan (compatible with old vers of XXACKNX1)listNo
Enable use of Legacy_ object for Vanes (compatible with old vers of XXACKNX1)listNo
AC unit has Humidifier (see docum. for your indoor unit)listNo
DPT object type for HumidifyinglistScaling [DPT_5.001]
Enable use of +/- object for HumidifyinglistNo
> DPT type for +/- Humidifying objectlist0-Decrease / 1-Increase [DPT_1.007]
> Rollover Humi. at upper/lower limit (when controlling with +/- obj)listNo
Enable use of bit-type Humidif. objects (for Control)listNo
Enable use of bit-type Humidif. objects (for Status)listNo
Enable use of Text obj for HumidifyinglistNo
Enable use of Legacy_ object for Humi. (compatible with old vers of XXACKNX1)listNo
ASCII strings shown in comm object "Status_ Humidifying Text"text<< 14-byte string values >>
> String when Humidifying is OFFtextHUMI OFF
> String when Humidifying is LOWtextHUMI LOW
> String when Humidifying is MIDtextHUMI MID
> String when Humidifying is HIGHtextHUMI HIGH
> String when Humidifying is CONT.textHUMI CONT
Indoor unit has U-D Vanes (see docum. for your indoor unit)listYes
Indoor unit has L-R Vanes (see docum. for your indoor unit)listNo
Indoor unit has AUTO fan speed (see docum. for your indoor unit)listYes
> Scene 1 / Value for Humidifying (if available)list(unchanged)
> Scene 2 / Value for Humidifying (if available)list(unchanged)
> Scene 3 / Value for Humidifying (if available)list(unchanged)
> Scene 4 / Value for Humidifying (if available)list(unchanged)
> Scene 5 / Value for Humidifying (if available)list(unchanged)
Hide items?!listYes
Fan is accessible in Indoor unit (see docum. for your indoor unit)listYes
Enable use of bit-type Fan Speed objects (for Status)listNo
Enable use of bit-type Fan Speed objects (for Control)listNo
DPT object type for fanspeedlistScaling [DPT_5.001]
ASCII strings shown in comm object "Status_ Fan Speed Text"text<< 14-byte string values >>
> String when fan speed is AUTO (if available)textAUTO
> String when fan speed is 1textSPEED 1
> String when fan speed is 2textSPEED 2
> String when fan speed is 3textSPEED 3
> String when fan speed is 4 (if available)textSPEED 4
> String when fan speed is 5textSPEED 5
Enable use of Text object for Fan SpeedlistNo
Available positions in Indoor Unit (see docum. for your indoor unit)unsignedInt 0…51
Available fanspeeds in Indoor Unit (see docum. for your indoor unit)unsignedInt 3…33
Indoor unit has SWING Vanes U-D (see docum. for your indoor unit)listYes
Enable "Vanes U-D Swing" objects (for Control and Status)listNo
Enable use of bit-type Vanes U-D objects (for Status)listNo
Enable use of bit-type Vanes U-D objects (for Control)listNo
DPT object type for Vanes Up-DownlistScaling [DPT_5.001]
> Does +/- sequence include SWING vanes Up-Down?listNo
> String when vanes U-D in SWINGtextU-D SWING
Transmission of "Status_ AC Ambient Ref Temp"listOnly on change
> "Status_ AC Ambient Ref Temp" periodic sending time (in sec)unsignedInt 1…255180
Indoor unit has DRY mode (see docum. for your indoor unit)listYes
Indoor unit has AUTO mode (see docum. for your indoor unit)listYes
Available positions in Indoor Unit (see docum. for your indoor unit)unsignedInt 3…55
Indoor unit has AUTO Vanes L-R (see docum. for your indoor unit)listNo
Indoor unit has SWING Vanes L-R (see docum. for your indoor unit)listNo
Available intensities in Indoor Unit (see docum. for your indoor unit)listYes
Indoor unit has STANDBY Vanes U-D (see docum. for your indoor unit)listNo
Enable use of objects for Filter (for Control and Status)listNo
When fan is AUTO Status_ objs report actual operating status (speed1/2/...)listNo
IU has the following U-D Vanes values (see docum. for your indoor unit)list5 positions, SWING and STANDBY

Version history

ApplicationApp noFingerprintFirst seenSizeFile
0115 PARC2KNX1i T15V13 1.3 latest$00154B732026-11-25143 KBDownload

About this file

This is the official ETS product database for the Intesis PA RC2 interface, 4 binary inputs (PA-RC2-KNX-1i), published by the manufacturer in the KNX online catalog. To use it, open ETS, go to Catalogs → Import and choose the downloaded .knxprod file. The device then appears in your catalog and can be added to a project. Older versions are kept so existing projects can be matched to the application program they were commissioned with.