Intesis MH-RC-KNX-1i MH RC interface, 4 binary inputs

MH RC interface, 4 binary inputs MH-RC-KNX-1i

Intesis · Order number MH-RC-KNX-1i · Communication › Interfaces › Mitsubishi Heavy Air Conditioning Interfaces

Download .knxprod 0109 MHRCKNX1i T0FV13 1.3 · 146 KB

Product

ManufacturerIntesis
Product nameMH RC interface, 4 binary inputs
Order numberMH-RC-KNX-1i
HardwareMH RC Interface
MediumTwisted Pair
Bus current (mA)7
Rail mountedNo
RegistrationCertified · 2012-12-17
Languageses-ES, en-US
Catalog entryM-0077_H-MH.2DRC.2DKNX.2D1i-1_HP-000F-13-6506_CI-MH.2DRC.2DKNX.2D1i-3
Fingerprint6506
SHA-256c202fe4d8927bc771721b1515d58455adcd8fad8bd29dd65917593511aeea959
First seen2026-11-25
Markets69 markets

Application program: 0109 MHRCKNX1i T0FV13 1.3

Application number$000F
Version1.3
Mask versionMV-0025 (2.5)
KNX Data SecureNo
Parameters365
Group objects154
Group objects (154)
NoNameFunctionSizeDPTFlags
0Control_ On/Off [DPT_1.001 - 1bit]0-Off;1-On1 Bit1.1 switchCWT
1Control_ Mode [DPT_20.105 - 1byte]0-Aut;1-Hea;3-Coo;9-Fan;14-Dry1 ByteCWT
1Control_ Mode [DPT_20.105 - 1byte]1-Hea;3-Coo;9-Fan;14-Dry1 ByteCWT
2Control_ Mode Cool/Heat [DPT_1.100 - 1bit]0-Cool;1-Heat1 BitCWT
3Control_ Mode Cool & On [DPT_5.001 - 1byte]0%-Off;0.1%-100%-On+Cool1 Byte5.1 percentage (0..100%)CWT
4Control_ Mode Heat & On [DPT_5.001 - 1byte]0%-Off;0.1%-100%-On+Heat1 Byte5.1 percentage (0..100%)CWT
5Control_ Mode Auto [DPT_1.002 - 1bit]1-Set AUTO mode1 Bit1.2 booleanCWT
6Control_ Mode Heat [DPT_1.002 - 1bit]1-Set HEAT mode1 Bit1.2 booleanCWT
7Control_ Mode Cool [DPT_1.002 - 1bit]1-Set COOL mode1 Bit1.2 booleanCWT
8Control_ Mode Fan [DPT_1.002 - 1bit]1-Set FAN mode1 Bit1.2 booleanCWT
9Control_ Mode Dry [DPT_1.002 - 1bit]1-Set DRY mode1 Bit1.2 booleanCWT
10Control_ Mode -/+ [DPT_1.007 - 1bit]0-Decrease;1-Increase1 BitCW
10Control_ Mode +/- [DPT_1.008 - 1bit]0-Up;1-Down1 Bit1.8 up/downCW
11Control_ Fan Speed / 3 Speeds [DPT_5.001 - 1byte]Thresholds: 50% and 83%1 Byte5.1 percentage (0..100%)CWT
11Control_ Fan Speed / 3 Speeds [DPT_5.010 - 1byte] Speed values: 1,2,31 Byte5.10 counter pulses (0..255)CWT
11Control_ Fan Speed / 4 Speeds [DPT_5.001 - 1byte] Thresholds: 38%, 63% and 88%1 Byte5.1 percentage (0..100%)CWT
11Control_ Fan Speed / 2 Speeds [DPT_5.001 - 1byte]Threshold: 75%1 Byte5.1 percentage (0..100%)CWT
11Control_ Fan Speed / 2 Speeds [DPT_5.010 - 1byte] Speed values: 1,21 Byte5.10 counter pulses (0..255)CWT
11Control_ Fan Speed / 4 Speeds [DPT_5.010 - 1byte] Speed values: 1,2,3,41 Byte5.10 counter pulses (0..255)CWT
12Control_ Fan Speed 1 [DPT_1.002 - 1bit]1-Set Fan Speed 11 Bit1.2 booleanCWT
13Control_ Fan Speed 2 [DPT_1.002 - 1bit]1-Set Fan Speed 21 Bit1.2 booleanCWT
14Control_ Fan Speed 3 [DPT_1.002 - 1bit]1-Set Fan Speed 31 Bit1.2 booleanCWT
15Control_ Fan Speed 4 [DPT_1.002 - 1bit]1-Set Fan Speed 41 Bit1.2 booleanCWT
16Control_ Fan Speed -/+ [DPT_1.007 - 1bit]0-Decrease;1-Increase1 BitCW
16Control_ Fan Speed +/- [DPT_1.008 - 1bit]0-Up;1-Down1 Bit1.8 up/downCW
17Control_ Vanes U-D / 4 Pos [DPT_5.001 - 1byte]Thresholds: 38%, 63% and 88%1 Byte5.1 percentage (0..100%)CWT
17Control_ Vanes U-D / 4 Pos [DPT_5.010 - 1byte]Position values: 1,2,3,41 Byte5.10 counter pulses (0..255)CWT
18Control_ Vanes U-D Pos 1 [DPT_1.002 - 1bit]1-Set Position 11 Bit1.2 booleanCWT
19Control_ Vanes U-D Pos 2 [DPT_1.002 - 1bit]1-Set Position 21 Bit1.2 booleanCWT
20Control_ Vanes U-D Pos 3 [DPT_1.002 - 1bit]1-Set Position 31 Bit1.2 booleanCWT
21Control_ Vanes U-D Pos 4 [DPT_1.002 - 1bit]1-Set Position 41 Bit1.2 booleanCWT
22Control_ Vanes U-D Swing [DPT_1.002 - 1bit]0-Off;1-Swing1 Bit1.2 booleanCWT
23Control_ Vanes U-D +/- [DPT_1.008 - 1bit]0-Up;1-Down1 Bit1.8 up/downCWT
23Control_ Vanes U-D -/+ [DPT_1.007 - 1bit]0-Decrease;1-Increase1 BitCWT
24Control_ Setpoint Temp [DPT_9.001 - 2byte]ºC2 Bytes9.1 temperature (°C)CWT
25Control_ Setpoint Temp -/+ [DPT_1.007 - 1bit]0-Decrease;1-Increase1 BitCW
25Control_ Setpoint Temp +/- [DPT_1.008 - 1bit]0-Up;1-Down1 Bit1.8 up/downCW
26Control_ Ambient Temp [DPT_9.001 - 2byte]ºC2 Bytes9.1 temperature (°C)CWT
27Control_ Reset Filter [DPT_1.015 - 1bit]1-Reset filter1 BitCWT
28Control_ Reset Error [DPT_1.015 - 1bit]1-Reset error1 BitCWT
29Control_ Switch Off Timeout [DPT_1.010 - 1bit]0-Stop;1-Start1 Bit1.10 start/stopCWT
29Control_ Window Contact Status [DPT_1.009 - 1bit]0-Open;1-Closed1 Bit1.9 open/closeCWT
30Control_ Occupancy [DPT_1.018 - 1bit]0-Not Occupied;1-Occupied1 BitCWT
31Control_ Sleep Timeout [DPT_1.010 - 1bit]0-Stop;1-Start1 Bit1.10 start/stopCWT
32Control_ Lock Remote Control [DPT_1.002 - 1bit]0-Unlock;1-Lock1 Bit1.2 booleanCWT
33Control_ Lock Control Objects [DPT_1.002 - 1bit]0-Unlock;1-Lock1 Bit1.2 booleanCWT
34Control_ Power Mode [DPT_1.010 - 1bit]0-Stop;1-Start1 Bit1.10 start/stopCWT
35Control_ Econo Mode [DPT_1.010 - 1bit]0-Stop;1-Start1 Bit1.10 start/stopCWT
36Control_ Additional Heat [DPT_1.010 - 1bit]0-Stop;1-Start1 Bit1.10 start/stopCWT
37Control_ Additional Cool [DPT_1.010 - 1bit]0-Stop;1-Start1 Bit1.10 start/stopCWT
38Control_ Execute Scene [DPT_17.001 - 1byte]0..4-Exec1-51 ByteCWT
38Control_ Save/Exec Scene [DPT_18.001 - 1byte]0..4-Exec1-5;128..132-Save1-51 ByteCWT
39Control_ Store Scene 1 [DPT_1.002 - 1bit]1-Store Scene 11 Bit1.2 booleanCW
40Control_ Store Scene 2 [DPT_1.002 - 1bit]1-Store Scene 21 Bit1.2 booleanCW
41Control_ Store Scene 3 [DPT_1.002 - 1bit]1-Store Scene 31 Bit1.2 booleanCW
42Control_ Store Scene 4 [DPT_1.002 - 1bit]1-Store Scene 41 Bit1.2 booleanCW
43Control_ Store Scene 5 [DPT_1.002 - 1bit]1-Store Scene 51 Bit1.2 booleanCW
44Control_ Execute Scene 1 [DPT_1.002 - 1bit]1-Execute Scene 11 Bit1.2 booleanCWT
45Control_ Execute Scene 2 [DPT_1.002 - 1bit]1-Execute Scene 21 Bit1.2 booleanCWT
46Control_ Execute Scene 3 [DPT_1.002 - 1bit]1-Execute Scene 31 Bit1.2 booleanCWT
47Control_ Execute Scene 4 [DPT_1.002 - 1bit]1-Execute Scene 41 Bit1.2 booleanCWT
48Control_ Execute Scene 5 [DPT_1.002 - 1bit]1-Execute Scene 51 Bit1.2 booleanCWT
49Control_ Disable Input 1 [DPT_1.003 - 1bit]0-Disable;1-Enable1 Bit1.3 enableCWT
49Control_ Disable Input 1 [DPT_1.002 - 1bit]0-False;1-True1 Bit1.2 booleanCWT
50Control_ Disable Input 2 [DPT_1.003 - 1bit]0-Disable;1-Enable1 Bit1.3 enableCWT
50Control_ Disable Input 2 [DPT_1.002 - 1bit]0-False;1-True1 Bit1.2 booleanCWT
51Control_ Disable Input 3 [DPT_1.002 - 1bit]0-False;1-True1 Bit1.2 booleanCWT
51Control_ Disable Input 3 [DPT_1.003 - 1bit]0-Disable;1-Enable1 Bit1.3 enableCWT
52Control_ Disable Input 4 [DPT_1.002 - 1bit]0-False;1-True1 Bit1.2 booleanCWT
52Control_ Disable Input 4 [DPT_1.003 - 1bit]0-Disable;1-Enable1 Bit1.3 enableCWT
53Status_ On/Off [DPT_1.001 - 1bit]0-Off;1-On1 Bit1.1 switchCRT
54Status_ Mode [DPT_20.105 - 1byte]0-Aut;1-Hea;3-Coo;9-Fan;14-Dry1 ByteCRT
54Status_ Mode [DPT_20.105 - 1byte]1-Hea;3-Coo;9-Fan;14-Dry1 ByteCRT
55Status_ Mode Cool/Heat [DPT_1.100 - 1bit]0-Cool;1-Heat1 BitCRT
56Status_ Mode Auto [DPT_1.002 - 1bit]1-AUTO mode is active1 Bit1.2 booleanCRT
57Status_ Mode Heat [DPT_1.002 - 1bit]1-HEAT mode is active1 Bit1.2 booleanCRT
58Status_ Mode Cool [DPT_1.002 - 1bit]1-COOL mode is active1 Bit1.2 booleanCRT
59Status_ Mode Fan [DPT_1.002 - 1bit]1-FAN mode is active1 Bit1.2 booleanCRT
60Status_ Mode Dry [DPT_1.002 - 1bit]1-DRY mode is active1 Bit1.2 booleanCRT
61Status_ Mode Text [DPT_16.001 - 14byte]ASCII String14 Bytes16.1 Character String (ISO 8859-1)CRT
62Status_ Fan Speed / 3 Speeds [DPT_5.001 - 1byte]33%, 66% and 100%1 Byte5.1 percentage (0..100%)CRT
62Status_ Fan Speed / 4 Speeds [DPT_5.001 - 1byte] 25%, 50%, 75% and 100%1 Byte5.1 percentage (0..100%)CRT
62Status_ Fan Speed / 3 Speeds [DPT_5.010 - 1byte]Speed Values: 1,2,31 Byte5.10 counter pulses (0..255)CRT
62Status_ Fan Speed / 2 Speeds [DPT_5.001 - 1byte]50% and 100%1 Byte5.1 percentage (0..100%)CRT
62Status_ Fan Speed / 2 Speeds [DPT_5.010 - 1byte]Speed Values: 1,21 Byte5.10 counter pulses (0..255)CRT
62Status_ Fan Speed / 4 Speeds [DPT_5.010 - 1byte]Speed Values: 1,2,3,41 Byte5.10 counter pulses (0..255)CRT
63Status_ Fan Speed 1 [DPT_1.002 - 1bit]1-Fan in Speed 11 Bit1.2 booleanCRT
64Status_ Fan Speed 2 [DPT_1.002 - 1bit]1-Fan in Speed 21 Bit1.2 booleanCRT
65Status_ Fan Speed 3 [DPT_1.002 - 1bit]1-Fan in Speed 31 Bit1.2 booleanCRT
66Status_ Fan Speed 4 [DPT_1.002 - 1bit]1-Fan in Speed 41 Bit1.2 booleanCRT
67Status_ Fan Speed Text [DPT_16.001 - 14byte]ASCII String14 Bytes16.1 Character String (ISO 8859-1)CRT
68Status_ Vanes U-D / 4 Pos [DPT_5.001 - 1byte]25%, 50%, 75% and 100%1 Byte5.1 percentage (0..100%)CRT
68Status_ Vanes U-D / 4 Pos [DPT_5.010 - 1byte]Position values: 1,2,3,41 Byte5.10 counter pulses (0..255)CRT
69Status_ Vanes U-D Pos 1 [DPT_1.002 - 1bit]1-Vanes in Position 11 Bit1.2 booleanCRT
70Status_ Vanes U-D Pos 2 [DPT_1.002 - 1bit]1-Vanes in Position 21 Bit1.2 booleanCRT
71Status_ Vanes U-D Pos 3 [DPT_1.002 - 1bit]1-Vanes in Position 31 Bit1.2 booleanCRT
72Status_ Vanes U-D Pos 4 [DPT_1.002 - 1bit]1-Vanes in Position 41 Bit1.2 booleanCRT
73Status_ Vanes U-D Swing [DPT_1.002 - 1bit]0-Off;1-Swing1 Bit1.2 booleanCRT
74Status_ Vanes U-D Text [DPT_16.001 - 14byte]ASCII String14 Bytes16.1 Character String (ISO 8859-1)CRT
75Status_ AC Setpoint Temp [DPT_9.001 - 2byte]ºC2 Bytes9.1 temperature (°C)CRT
76Status_ AC Reference Temp [DPT_9.001 - 2byte]ºC2 Bytes9.1 temperature (°C)CRT
77Status_ Only Centrally Ctrl [DPT 1.002 - 1bit]1-Only centrally controlled1 Bit1.2 booleanCRT
78Status_ Filter Status [DPT_1.005 - 1bit]0-No alarm;1-Alarm1 BitCRT
79Status_ Error/Alarm [DPT_1.005 - 1bit]0-No alarm;1-Alarm1 BitCRT
80Status_ Error Code [2byte]0-No error /Any other see man.2 BytesCRT
81Status_ Error Text Code [DPT_16.001 - 14byte]3-char MH Error; Empty-None14 Bytes16.1 Character String (ISO 8859-1)CRT
82Status_ Lock Remote Control [DPT_1.002 - 1bit]0-Unlocked;1-Locked1 Bit1.2 booleanCRT
83Status_ Lock Control Objects [DPT_1.002 - 1bit]0-Unlocked;1-Locked1 Bit1.2 booleanCRT
84Status_ Power Mode [DPT_1.001 - 1bit]0-Off;1-On1 Bit1.1 switchCRT
85Status_ Econo Mode [DPT_1.001 - 1bit]0-Off;1-On1 Bit1.1 switchCRT
86Status_ Additional Heat [DPT_1.001 - 1bit]0-Off;1-On1 Bit1.1 switchCRT
87Status_ Additional Cool [DPT_1.001 - 1bit]0-Off;1-On1 Bit1.1 switchCRT
88Status_ Operation Hour Counter [DPT_7.001 - 2byte]Number of operating hours2 Bytes7.1 pulsesCRT
89Status_ Current Scene [DPT_17.001 - 1byte]0..4-Scene X+1;63-No Scene1 ByteCRT
90Status_ In1 - Switching [DPT_1.001 - 1bit]0-Off;1-On1 Bit1.1 switchCRT
90Status_ In1 - Dimming - On/Off [DPT_1.001 - 1bit]0-Off;1-On1 Bit1.1 switchCRT
90Status_ In1 - Shut/Blind - Step [DPT_1.007 - 1bit]0-Step Up;1-Step Down1 BitCRT
91Status_ In1 - Dimming - Step(%) [DPT_3.007 - 4bit]Dimming step4 Bit3.7 dimming controlCRT
91Status_ In1 - Shut/Blind - Move [DPT_1.008 - 1bit]0-Move Up;1-Move Down1 Bit1.8 up/downCRT
91Status_ In1 - Value [DPT_12.001 - 4byte]4-byte unsigned value4 Bytes12.1 counter pulses (unsigned)CRT
91Status_ In1 - Value [DPT_5.010 - 1byte]1-byte unsigned value1 Byte5.10 counter pulses (0..255)CRT
91Status_ In1 - Value [DPT_8.001 - 2byte]2-byte signed value2 Bytes8.1 pulses differenceCRT
91Status_ In1 - Value [DPT_9.001 - 2byte]Temperature (ºC)2 Bytes9.1 temperature (°C)CRT
91Status_ In1 - Value [DPT_7.001 - 2byte]2-byte unsigned value2 Bytes7.1 pulsesCRT
92Status_ In2 - Switching [DPT_1.001 - 1bit]0-Off;1-On1 Bit1.1 switchCRT
92Status_ In2 - Dimming - On/Off [DPT_1.001 - 1bit]0-Off;1-On1 Bit1.1 switchCRT
92Status_ In2 - Shut/Blind - Step [DPT_1.007 - 1bit]0-Step Up;1-Step Down1 BitCRT
93Status_ In2 - Dimming - Step(%) [DPT_3.007 - 4bit]Dimming step4 Bit3.7 dimming controlCRT
93Status_ In2 - Value [DPT_7.001 - 2byte]2-byte unsigned value2 Bytes7.1 pulsesCRT
93Status_ In2 - Value [DPT_12.001 - 4byte]4-byte unsigned value4 Bytes12.1 counter pulses (unsigned)CRT
93Status_ In2 - Value [DPT_9.001 - 2byte]Temperature (ºC)2 Bytes9.1 temperature (°C)CRT
93Status_ In2 - Value [DPT_8.001 - 2byte]2-byte signed value2 Bytes8.1 pulses differenceCRT
93Status_ In2 - Value [DPT_5.010 - 1byte]1-byte unsigned value1 Byte5.10 counter pulses (0..255)CRT
93Status_ In2 - Shut/Blind - Move [DPT_1.008 - 1bit]0-Move Up;1-Move Down1 Bit1.8 up/downCRT
94Status_ In3 - Switching [DPT_1.001 - 1bit]0-Off;1-On1 Bit1.1 switchCRT
94Status_ In3 - Dimming - On/Off [DPT_1.001 - 1bit]0-Off;1-On1 Bit1.1 switchCRT
94Status_ In3 - Shut/Blind - Step [DPT_1.007 - 1bit]0-Step Up;1-Step Down1 BitCRT
95Status_ In3 - Dimming - Step(%) [DPT_3.007 - 4bit]Dimming step4 Bit3.7 dimming controlCRT
95Status_ In3 - Value [DPT_12.001 - 4byte]4-byte unsigned value4 Bytes12.1 counter pulses (unsigned)CRT
95Status_ In3 - Value [DPT_9.001 - 2byte]Temperature (ºC)2 Bytes9.1 temperature (°C)CRT
95Status_ In3 - Value [DPT_8.001 - 2byte]2-byte signed value2 Bytes8.1 pulses differenceCRT
95Status_ In3 - Value [DPT_7.001 - 2byte]2-byte unsigned value2 Bytes7.1 pulsesCRT
95Status_ In3 - Value [DPT_5.010 - 1byte]1-byte unsigned value1 Byte5.10 counter pulses (0..255)CRT
95Status_ In3 - Shut/Blind - Move [DPT_1.008 - 1bit]0-Move Up;1-Move Down1 Bit1.8 up/downCRT
96Status_ In4 - Switching [DPT_1.001 - 1bit]0-Off;1-On1 Bit1.1 switchCRT
96Status_ In4 - Dimming - On/Off [DPT_1.001 - 1bit]0-Off;1-On1 Bit1.1 switchCRT
96Status_ In4 - Shut/Blind - Step [DPT_1.007 - 1bit]0-Step Up;1-Step Down1 BitCRT
97Status_ In4 - Dimming - Step(%) [DPT_3.007 - 4bit]Dimming step4 Bit3.7 dimming controlCRT
97Status_ In4 - Value [DPT_12.001 - 4byte]4-byte unsigned value4 Bytes12.1 counter pulses (unsigned)CRT
97Status_ In4 - Value [DPT_9.001 - 2byte]Temperature (ºC)2 Bytes9.1 temperature (°C)CRT
97Status_ In4 - Value [DPT_8.001 - 2byte]2-byte signed value2 Bytes8.1 pulses differenceCRT
97Status_ In4 - Value [DPT_7.001 - 2byte]2-byte unsigned value2 Bytes7.1 pulsesCRT
97Status_ In4 - Value [DPT_5.010 - 1byte]1-byte unsigned value1 Byte5.10 counter pulses (0..255)CRT
97Status_ In4 - Shut/Blind - Move [DPT_1.008 - 1bit]0-Move Up;1-Move Down1 Bit1.8 up/downCRT
Parameters (232)
ParameterTypeDefault
Download latest database entry for this product and its User Manual from:texthttp://www.intesis.com
MH-RC-KNX-1i is master in X Y buslistNo
> Use slow polling frequencylistYes
Send READs for Control_ objects on bus recovery (T & U flags must be active)listNo
> Delay before sending READs (sec)unsignedInt 0…3010
Scene to load on bus recovery / startup (needs to define vals for that scene)list(none)
Disallow control from remote controllerlistNo
> Enable comm obj "Ctrl_ Remote Lock"listNo
Enable func "Control_ Lock Control Obj"listNo
Enable func "Operating Hours Counter"listNo
Enable use of objects for Filter (for Control and Status)listNo
Enable object "Error Code [2byte]"listNo
Enable object "Error Text Code [14byte]" (3 ASCII-char Error Code)listYes
Indoor unit has AUTO mode (see docum. for your indoor unit)listYes
Indoor unit has HEAT mode (see docum. for your indoor unit)listYes
Indoor unit has FAN mode (see docum. for your indoor unit)listYes
Indoor unit has DRY mode (see docum. for your indoor unit)listYes
When mode is AUTO Status_ objs report actual operating status (HEAT/COOL/..)listNo
Enable "Mode Cool/Heat" objects (for Control and Status)listNo
Enable PID-Compat. Scaling Mode objects (for Control)listNo
Enable use of +/- object for ModelistNo
> DPT type for +/- Mode Objectlist0-Decrease / 1-Increase [DPT_1.007]
Enable use of bit-type Mode objects (for Control)listNo
Enable use of bit-type Mode objects (for Status)listNo
Enable use of Text object for ModelistNo
ASCII strings shown in comm object "Status_ Mode Text"text<< 14-byte string values >>
> String when mode is AUTO (if available)textAUTO
> String when mode is HEATtextHEAT
> String when mode is COOLtextCOOL
> String when mode is FANtextFAN
> String when mode is DRYtextDRY
Enable use of Legacy_ object for Mode (compatible with old vers of XXACKNX1)listNo
Enable use of "POWERFUL" mode (AC feature)listNo
Enable use of "QUIET" mode (AC feature)listNo
Enable use of POWER modelistNo
> Action time for this mode (minutes)unsignedInt 1…18030
> Setpoint delta increase (HEAT) or decrease (COOL) (ºC)list2.0 ºC
> Fan Speed for this modelistFAN SPEED 3 (if available)
Enable use of ECONOMY modelistNo
> Setpoint delta decrease (HEAT) or increase (COOL) (ºC)list2.0 ºC
> Fan Speed for this modelistFAN SPEED 1
Enable use of ADDITIONAL HEATING modelistNo
> Setpoint temp for this mode (ºC)list30.0 ºC
Enable use of ADDITIONAL COOLING modelistNo
> Setpoint temp for this mode (ºC)list20.0 ºC
Fan is accessible in Indoor unit (see docum. for your indoor unit)listYes
Available fanspeeds in Indoor Unit (see docum. for your indoor unit)list1 (fixed speed)
Indoor unit has AUTO fan speed (see docum. for your indoor unit)listNo
When fan is AUTO Status_ objs report actual operating status (speed1/2/...)listNo
DPT object type for fanspeedlistScaling [DPT_5.001]
Enable use of +/- object for Fan SpeedlistNo
> DPT type for +/- Fan Speed objectlist0-Decrease / 1-Increase [DPT_1.007]
> Does +/- sequence include fan speed AUTO?listNo
> Rollover Speed at upper/lower limit (when controlling with +/- obj)listYes
Enable "Fan Speed Man/Auto" objects (for Control and Status)listNo
Enable use of bit-type Fan Speed objects (for Control)listNo
Enable use of bit-type Fan Speed objects (for Status)listNo
Enable use of Text object for Fan SpeedlistNo
ASCII strings shown in comm object "Status_ Fan Speed Text"text<< 14-byte string values >>
> String when fan speed is AUTOtextAUTO
> String when fan speed is 1textSPEED 1
> String when fan speed is 2textSPEED 2
> String when fan speed is 3 (if available)textSPEED 3
> String when fan speed is 4 (if available)textSPEED 4
> String when fan speed is 5textSPEED 5
Indoor unit has U-D Vanes (see docum. for your indoor unit)listYes
Available positions in Indoor Unit (see docum. for your indoor unit)unsignedInt 4…44
Available AUTOs in Indoor Unit (see docum. for your indoor unit)list0
Indoor unit has SWING Vanes U-D (see docum. for your indoor unit)listYes
DPT object type for Vanes Up-DownlistScaling [DPT_5.001]
Enable use of +/- object for Vanes U-DlistNo
> DPT type for +/- Vanes U-D objectlist0-Decrease / 1-Increase [DPT_1.007]
> Does +/- sequence include AUTO vanes Up-Down?listNo
> Does +/- sequence include SWING vanes Up-Down?listNo
> Rollover Vanes at upper/lower limit (when controlling with +/- obj)listYes
Enable "Vanes U-D Man/Auto" objects (for Control and Status)listNo
Enable use of bit-type Vanes U-D objects (for Control)listNo
Enable use of bit-type Vanes U-D objects (for Status)listNo
Enable "Vanes U-D Swing" objects (for Control and Status)listNo
Enable use of Text object for Vanes U-DlistNo
ASCII strings shown in comm object "Status_ Vanes U-D Text"text<< 14-byte string values >>
> String when vanes U-D in AUTOtextU-D AUTO
> String when vanes U-D in POS 1textU-D POS 1
> String when vanes U-D in POS 2textU-D POS 2
> String when vanes U-D in POS 3textU-D POS 3
> String when vanes U-D in POS 4textU-D POS 4
> String when vanes U-D in POS 5 (if available)textU-D POS 5
> String when vanes U-D in SWINGtextU-D SWING
Enable use of Legacy_ object for Vanes (compatible with old vers of XXACKNX1)listNo
Indoor unit has L-R Vanes (see docum. for your indoor unit)listNo
Available positions in Indoor Unit (see docum. for your indoor unit)unsignedInt 3…55
Indoor unit has AUTO Vanes L-R (see docum. for your indoor unit)listNo
Indoor unit has SWING Vanes L-R (see docum. for your indoor unit)listNo
DPT object type for Vanes Left-RightlistScaling [DPT_5.001]
Enable use of +/- object for Vanes L-RlistNo
> DPT type for +/- Vanes L-R objectlist0-Decrease / 1-Increase [DPT_1.007]
> Does +/- sequence include vanes Left-Right AUTO?listNo
Enable use of bit-type Vanes L-R objects (for Control)listNo
Enable use of bit-type Vanes L-R objects (for Status)listNo
Enable use of Text object for Vanes L-RlistNo
ASCII strings shown in comm object "Status_ Vanes L-R Text"text<< 14-byte string values >>
> String when vanes L-R in AUTOtextL-R AUTO
> String when vanes L-R in POS 1textL-R POS 1
> String when vanes L-R in POS 2textL-R POS 2
> String when vanes L-R in POS 3textL-R POS 3
> String when vanes L-R in POS 4textL-R POS 4
> String when vanes L-R in POS 5textL-R POS 5
AC unit has Humidifier (see docum. for your indoor unit)listNo
Available intensities in Indoor Unit (see docum. for your indoor unit)listYes
DPT object type for HumidifyinglistScaling [DPT_5.001]
Enable use of +/- object for HumidifyinglistNo
> DPT type for +/- Humidifying objectlist0-Decrease / 1-Increase [DPT_1.007]
> Rollover Humi. at upper/lower limit (when controlling with +/- obj)listNo
Enable use of bit-type Humidif. objects (for Control)listNo
Enable use of bit-type Humidif. objects (for Status)listNo
Enable use of Text obj for HumidifyinglistNo
ASCII strings shown in comm object "Status_ Humidifying Text"text<< 14-byte string values >>
> String when Humidifying is OFFtextHUMI OFF
> String when Humidifying is LOWtextHUMI LOW
> String when Humidifying is MIDtextHUMI MID
> String when Humidifying is HIGHtextHUMI HIGH
> String when Humidifying is CONT.textHUMI CONT
Enable use of Legacy_ object for Humi. (compatible with old vers of XXACKNX1)listNo
Periodic sending of "Status_ AC Setp" (in seconds;0=No periodic sending)unsignedInt 0…2550
Transmission of "Status_ AC Refer. Temp"listOnly on change
> "Status_ AC Refer. Temp" periodic sending time (in sec)unsignedInt 1…255180
Enable use of +/- obj for Setpoint TemplistNo
> DPT type for +/- Setp Temp objectlist0-Decrease / 1-Increase [DPT_1.007]
> [+/-] step sizelist1.0 ºC
Enable limits on Control_ Setpoint objlistNo
> Lower limit (ºC)list18.0 ºC
> Upper limit (ºC)list30.0 ºC
Ambient temp. ref. is provided from KNX (carefully read User Guide if enabled)listNo
Enable use of sceneslistNo
Scenes can be stored from KNX buslistNo
> Enable use of bit objects for storing scenes (from bus)listNo
Enable use of bit objects for scene executionlistNo
Scene 1 presetlistNo
> Scene 1 / Value for On-Offlist(unchanged)
> Scene 1 / Value for Modelist(unchanged)
> Scene 1 / Value for Fan Speedlist(unchanged)
> Scene 1 / Value for Vanes U-D (if available)list(unchanged)
> Scene 1 / Value for Vanes L-R (if available)list(unchanged)
> Scene 1 / Value for Setpoint Templist(unchanged)
> Scene 1 / Value for Remote Locklist(unchanged)
> Scene 1 / Value for Humidifying (if available)list(unchanged)
Scene 2 presetlistNo
> Scene 2 / Value for On-Offlist(unchanged)
> Scene 2 / Value for Modelist(unchanged)
> Scene 2 / Value for Fan Speedlist(unchanged)
> Scene 2 / Value for Vanes U-D (if available)list(unchanged)
> Scene 2 / Value for Vanes L-R (if available)list(unchanged)
> Scene 2 / Value for Setpoint Templist(unchanged)
> Scene 2 / Value for Remote Locklist(unchanged)
> Scene 2 / Value for Humidifying (if available)list(unchanged)
Scene 3 presetlistNo
> Scene 3 / Value for On-Offlist(unchanged)
> Scene 3 / Value for Modelist(unchanged)
> Scene 3 / Value for Fan Speedlist(unchanged)
> Scene 3 / Value for Vanes U-D (if available)list(unchanged)
> Scene 3 / Value for Vanes L-R (if available)list(unchanged)
> Scene 3 / Value for Setpoint Templist(unchanged)
> Scene 3 / Value for Remote Locklist(unchanged)
> Scene 3 / Value for Humidifying (if available)list(unchanged)
Scene 4 presetlistNo
> Scene 4 / Value for On-Offlist(unchanged)
> Scene 4 / Value for Modelist(unchanged)
> Scene 4 / Value for Fan Speedlist(unchanged)
> Scene 4 / Value for Vanes U-D (if available)list(unchanged)
> Scene 4 / Value for Vanes L-R (if available)list(unchanged)
> Scene 4 / Value for Setpoint Templist(unchanged)
> Scene 4 / Value for Remote Locklist(unchanged)
> Scene 4 / Value for Humidifying (if available)list(unchanged)
Scene 5 presetlistNo
> Scene 5 / Value for On-Offlist(unchanged)
> Scene 5 / Value for Modelist(unchanged)
> Scene 5 / Value for Fan Speedlist(unchanged)
> Scene 5 / Value for Vanes U-D (if available)list(unchanged)
> Scene 5 / Value for Vanes L-R (if available)list(unchanged)
> Scene 5 / Value for Setpoint Templist(unchanged)
> Scene 5 / Value for Remote Locklist(unchanged)
> Scene 5 / Value for Humidifying (if available)list(unchanged)
Enable use of Open Window / Switch off timeout functionlistNo
> AC switch-off timeout (min)unsignedInt 0…3010
> DPT for Window / Switch-off timeoutlist0-Stop / 1-Start Timeout [DPT_1.010]
> Disallow On/Off operation while window is OpenlistNo
> Disallow On/Off operation while timeout is elapsedlistNo
> Reload last On/Off val once timeout is stoppedlistNo
> Reload last On/Off val once window is ClosedlistNo
Enable use of Occupancy functionlistNo
> Timeout to apply action (minutes)unsignedInt 0…18020
> Action after timeout elapsedlistSwitch-Off AC
> Temp delta decrease (HEAT) or increase (COOL) (ºC)list2.0 ºC
> Enable secondary timeoutlistNo
> Timeout to apply action (min)unsignedInt 1…18020
> Action after timeout elapsedlistSwitch-Off AC
> Temp delta dec (HEAT) or inc (COOL) (ºC)list3.0 ºC
> Disallow On/Off operation while not OccupiedlistNo
> Reload last On/Off value when OccupiedlistNo
Enable use of Sleep functionlistNo
> Sleep function switch-off timeout (minutes)unsignedInt 0…18060
Enable use of Input 1listNo
> Contact typelistNO: Normally Open
> Debounce timelist50 ms
> Disabling functionlistNo
> Reset Input when enablinglistNo
> FunctionlistSwitching
> Send telegram after bus recoverylistNo action
> Sending delay after bus recovery (seconds)unsignedInt 0…25510
> Value on raising edge (contact activated)listNo action
> Scene when contact is activated (needs to be defined)listScene 1
> Mode for short (long) operationlistToggle: On/Off (increase/decrease)
> OperationlistToggle (Up/Down)
> DPT to be sentlistDPT 5.010 (1byte)
> Value on falling edge (contact deactivated)listNo action
> Increasing steplist+ 25 %
> MethodlistStep-Move-Step
> Cyclical sendinglistNever
> Decreasing steplist- 25 %
> Short/long operation limit (x100ms)unsignedInt 1…25510
> Period for cyclical sending (seconds)unsignedInt 1…6553510
> Vanes adjustment time (x100ms)unsignedInt 1…25510
> Value on raising edge (when contact activated)unsignedInt 0…2550
> Value on raising edge (when contact activated)unsignedInt 0…655350
> Value on raising edge (when contact activated)signedInt -32768…327670
> Value on rais. edge (x0.1ºC) (when contact activated)signedInt -2730…3276250
> Value on raising edge (when contact activated)unsignedInt 0…42949672950
> Cycl. send. period in long oper. (x100ms)(0-No cyclical send.)unsignedInt 0…2550
Enable use of Input 2listNo
Enable use of Input 3listNo
Enable use of Input 4listNo
Hide items?!listYes

Version history

ApplicationApp noFingerprintFirst seenSizeFile
0109 MHRCKNX1i T0FV13 1.3 latest$000F65062026-11-25146 KBDownload

About this file

This is the official ETS product database for the Intesis MH RC interface, 4 binary inputs (MH-RC-KNX-1i), published by the manufacturer in the KNX online catalog. To use it, open ETS, go to Catalogs → Import and choose the downloaded .knxprod file. The device then appears in your catalog and can be added to a project. Older versions are kept so existing projects can be matched to the application program they were commissioned with.