TO RC interface, 4 binary inputs TO-RC-KNX-1i
Intesis · Order number TO-RC-KNX-1i · Communication › Interfaces › Toshiba Air Conditioning Interfaces
Download .knxprod 0119 TORCKNX1i T1FV13 1.3 · 187 KB
Product
| Manufacturer | Intesis |
|---|---|
| Product name | TO RC interface, 4 binary inputs |
| Order number | TO-RC-KNX-1i |
| Hardware | TO RC Interface |
| Medium | Twisted Pair |
| Bus current (mA) | 5 |
| Rail mounted | No |
| Registration | Certified |
| Languages | es-ES, en-US |
| Catalog entry | M-0077_H-TO.2DRC.2DKNX.2D1i-16_HP-001F-13-7DB3_CI-TO.2DRC.2DKNX.2D1i-1 |
| Fingerprint | 7DB3 |
| SHA-256 | 056714e94f3569689895ce2305caacf2d5e59fbd3f819a56a071f3c00e368bf1 |
| First seen | 2026-11-25 |
| Markets | 69 markets |
Application program: 0119 TORCKNX1i T1FV13 1.3
| Application number | $001F |
|---|---|
| Version | 1.3 |
| Mask version | MV-0025 (2.5) |
| KNX Data Secure | No |
| Parameters | 352 |
| Group objects | 146 |
Group objects (146)
| No | Name | Function | Size | DPT | Flags |
|---|---|---|---|---|---|
| 0 | Control_ On/Off [DPT_1.001 - 1bit] | 0-Off;1-On | 1 Bit | 1.1 switch | CWT |
| 1 | Control_ Mode [DPT_20.105 - 1byte] | 0-Aut;1-Hea;3-Coo;9-Fan;14-Dry | 1 Byte | CWT | |
| 2 | Control_ Mode Cool/Heat [DPT_1.100 - 1bit] | 0-Cool;1-Heat | 1 Bit | CWT | |
| 3 | Control_ Mode Cool & On [DPT_5.001 - 1byte] | 0%-Off;0.1%-100%-On+Cool | 1 Byte | 5.1 percentage (0..100%) | CWT |
| 4 | Control_ Mode Heat & On [DPT_5.001 - 1byte] | 0%-Off;0.1%-100%-On+Heat | 1 Byte | 5.1 percentage (0..100%) | CWT |
| 5 | Control_ Mode Auto [DPT_1.002 - 1bit] | 1-Set AUTO mode | 1 Bit | 1.2 boolean | CWT |
| 6 | Control_ Mode Heat [DPT_1.002 - 1bit] | 1-Set HEAT mode | 1 Bit | 1.2 boolean | CWT |
| 7 | Control_ Mode Cool [DPT_1.002 - 1bit] | 1-Set COOL mode | 1 Bit | 1.2 boolean | CWT |
| 8 | Control_ Mode Fan [DPT_1.002 - 1bit] | 1-Set FAN mode | 1 Bit | 1.2 boolean | CWT |
| 9 | Control_ Mode Dry [DPT_1.002 - 1bit] | 1-Set DRY mode | 1 Bit | 1.2 boolean | CWT |
| 10 | Control_ Mode -/+ [DPT_1.007 - 1bit] | 0-Decrease;1-Increase | 1 Bit | CW | |
| 10 | Control_ Mode +/- [DPT_1.008 - 1bit] | 0-Up;1-Down | 1 Bit | 1.8 up/down | CW |
| 11 | Control_ Fan Speed / 3 Speeds [DPT_5.001 - 1byte] | Thresholds: 50% and 83% | 1 Byte | 5.1 percentage (0..100%) | CWT |
| 11 | Control_ Fan Speed / 3 Speeds [DPT_5.010 - 1byte] | Speed values: 1,2,3 | 1 Byte | 5.10 counter pulses (0..255) | CWT |
| 12 | Control_ Fan Speed Man/Auto [DPT_1.002 - 1bit] | 0-Manual; 1-Auto | 1 Bit | 1.2 boolean | CWT |
| 13 | Control_ Fan Speed 1 [DPT_1.002 - 1bit] | 1-Set Fan Speed 1 | 1 Bit | 1.2 boolean | CWT |
| 14 | Control_ Fan Speed 2 [DPT_1.002 - 1bit] | 1-Set Fan Speed 2 | 1 Bit | 1.2 boolean | CWT |
| 15 | Control_ Fan Speed 3 [DPT_1.002 - 1bit] | 1-Set Fan Speed 3 | 1 Bit | 1.2 boolean | CWT |
| 16 | Control_ Fan Speed -/+ [DPT_1.007 - 1bit] | 0-Decrease;1-Increase | 1 Bit | CW | |
| 16 | Control_ Fan Speed +/- [DPT_1.008 - 1bit] | 0-Up;1-Down | 1 Bit | 1.8 up/down | CW |
| 17 | Control_ Vanes U-D / 5 Pos [DPT_5.001 - 1byte] | Thresholds:30%,50%,70% and 90% | 1 Byte | 5.1 percentage (0..100%) | CWT |
| 17 | Control_ Vanes U-D / 5 Pos [DPT_5.010 - 1byte] | Position values: 1,2,3,4,5 | 1 Byte | 5.10 counter pulses (0..255) | CWT |
| 18 | Control_ Vanes U-D Standby [DPT_1.002 - 1bit] | 0-Off;1-Standby | 1 Bit | 1.2 boolean | CWT |
| 19 | Control_ Vanes U-D Pos 1 [DPT_1.002 - 1bit] | 1-Set Position 1 | 1 Bit | 1.2 boolean | CWT |
| 20 | Control_ Vanes U-D Pos 2 [DPT_1.002 - 1bit] | 1-Set Position 2 | 1 Bit | 1.2 boolean | CWT |
| 21 | Control_ Vanes U-D Pos 3 [DPT_1.002 - 1bit] | 1-Set Position 3 | 1 Bit | 1.2 boolean | CWT |
| 22 | Control_ Vanes U-D Pos 4 [DPT_1.002 - 1bit] | 1-Set Position 4 | 1 Bit | 1.2 boolean | CWT |
| 23 | Control_ Vanes U-D Pos 5 [DPT_1.002 - 1bit] | 1-Set Position 5 | 1 Bit | 1.2 boolean | CWT |
| 24 | Control_ Vanes U-D Swing [DPT_1.002 - 1bit] | 0-Off;1-Swing | 1 Bit | 1.2 boolean | CWT |
| 25 | Control_ Vanes U-D +/- [DPT_1.008 - 1bit] | 0-Up;1-Down | 1 Bit | 1.8 up/down | CWT |
| 25 | Control_ Vanes U-D -/+ [DPT_1.007 - 1bit] | 0-Decrease;1-Increase | 1 Bit | CWT | |
| 26 | Control_ Setpoint Temp [DPT_9.001 - 2byte] | ºC | 2 Bytes | 9.1 temperature (°C) | CWT |
| 27 | Control_ Setpoint Temp -/+ [DPT_1.007 - 1bit] | 0-Decrease;1-Increase | 1 Bit | CW | |
| 27 | Control_ Setpoint Temp +/- [DPT_1.008 - 1bit] | 0-Up;1-Down | 1 Bit | 1.8 up/down | CW |
| 28 | Control_ Ambient Temp [DPT_9.001 - 2byte] | ºC | 2 Bytes | 9.1 temperature (°C) | CWT |
| 29 | Control_ Reset Filter [DPT_1.015 - 1bit] | 1-Reset filter | 1 Bit | CWT | |
| 30 | Control_ Switch Off Timeout [DPT_1.010 - 1bit] | 0-Stop;1-Start | 1 Bit | 1.10 start/stop | CWT |
| 30 | Control_ Window Contact Status [DPT_1.009 - 1bit] | 0-Open;1-Closed | 1 Bit | 1.9 open/close | CWT |
| 31 | Control_ Occupancy [DPT_1.018 - 1bit] | 0-Not Occupied;1-Occupied | 1 Bit | CWT | |
| 32 | Control_ Sleep Timeout [DPT_1.010 - 1bit] | 0-Stop;1-Start | 1 Bit | 1.10 start/stop | CWT |
| 33 | Control_ Lock Remote Control [DPT_1.002 - 1bit] | 0-Unlock;1-Lock | 1 Bit | 1.2 boolean | CWT |
| 34 | Control_ Lock Control Objects [DPT_1.002 - 1bit] | 0-Unlock;1-Lock | 1 Bit | 1.2 boolean | CWT |
| 35 | Control_ Power Mode [DPT_1.010 - 1bit] | 0-Stop;1-Start | 1 Bit | 1.10 start/stop | CWT |
| 36 | Control_ Econo Mode [DPT_1.010 - 1bit] | 0-Stop;1-Start | 1 Bit | 1.10 start/stop | CWT |
| 37 | Control_ Additional Heat [DPT_1.010 - 1bit] | 0-Stop;1-Start | 1 Bit | 1.10 start/stop | CWT |
| 38 | Control_ Additional Cool [DPT_1.010 - 1bit] | 0-Stop;1-Start | 1 Bit | 1.10 start/stop | CWT |
| 39 | Control_ Execute Scene [DPT_17.001 - 1byte] | 0..4-Exec1-5 | 1 Byte | CWT | |
| 39 | Control_ Save/Exec Scene [DPT_18.001 - 1byte] | 0..4-Exec1-5;128..132-Save1-5 | 1 Byte | CWT | |
| 40 | Control_ Store Scene 1 [DPT_1.002 - 1bit] | 1-Store Scene 1 | 1 Bit | 1.2 boolean | CW |
| 41 | Control_ Store Scene 2 [DPT_1.002 - 1bit] | 1-Store Scene 2 | 1 Bit | 1.2 boolean | CW |
| 42 | Control_ Store Scene 3 [DPT_1.002 - 1bit] | 1-Store Scene 3 | 1 Bit | 1.2 boolean | CW |
| 43 | Control_ Store Scene 4 [DPT_1.002 - 1bit] | 1-Store Scene 4 | 1 Bit | 1.2 boolean | CW |
| 44 | Control_ Store Scene 5 [DPT_1.002 - 1bit] | 1-Store Scene 5 | 1 Bit | 1.2 boolean | CW |
| 45 | Control_ Execute Scene 1 [DPT_1.002 - 1bit] | 1-Execute Scene 1 | 1 Bit | 1.2 boolean | CWT |
| 46 | Control_ Execute Scene 2 [DPT_1.002 - 1bit] | 1-Execute Scene 2 | 1 Bit | 1.2 boolean | CWT |
| 47 | Control_ Execute Scene 3 [DPT_1.002 - 1bit] | 1-Execute Scene 3 | 1 Bit | 1.2 boolean | CWT |
| 48 | Control_ Execute Scene 4 [DPT_1.002 - 1bit] | 1-Execute Scene 4 | 1 Bit | 1.2 boolean | CWT |
| 49 | Control_ Execute Scene 5 [DPT_1.002 - 1bit] | 1-Execute Scene 5 | 1 Bit | 1.2 boolean | CWT |
| 50 | Control_ Disable Input 1 [DPT_1.003 - 1bit] | 0-Disable;1-Enable | 1 Bit | 1.3 enable | CWT |
| 50 | Control_ Disable Input 1 [DPT_1.002 - 1bit] | 0-False;1-True | 1 Bit | 1.2 boolean | CWT |
| 51 | Control_ Disable Input 2 [DPT_1.003 - 1bit] | 0-Disable;1-Enable | 1 Bit | 1.3 enable | CWT |
| 51 | Control_ Disable Input 2 [DPT_1.002 - 1bit] | 0-False;1-True | 1 Bit | 1.2 boolean | CWT |
| 52 | Control_ Disable Input 3 [DPT_1.002 - 1bit] | 0-False;1-True | 1 Bit | 1.2 boolean | CWT |
| 52 | Control_ Disable Input 3 [DPT_1.003 - 1bit] | 0-Disable;1-Enable | 1 Bit | 1.3 enable | CWT |
| 53 | Control_ Disable Input 4 [DPT_1.002 - 1bit] | 0-False;1-True | 1 Bit | 1.2 boolean | CWT |
| 53 | Control_ Disable Input 4 [DPT_1.003 - 1bit] | 0-Disable;1-Enable | 1 Bit | 1.3 enable | CWT |
| 54 | Status_ On/Off [DPT_1.001 - 1bit] | 0-Off;1-On | 1 Bit | 1.1 switch | CRT |
| 55 | Status_ Mode [DPT_20.105 - 1byte] | 0-Aut;1-Hea;3-Coo;9-Fan;14-Dry | 1 Byte | CRT | |
| 56 | Status_ Mode Cool/Heat [DPT_1.100 - 1bit] | 0-Cool;1-Heat | 1 Bit | CRT | |
| 57 | Status_ Mode Auto [DPT_1.002 - 1bit] | 1-AUTO mode is active | 1 Bit | 1.2 boolean | CRT |
| 58 | Status_ Mode Heat [DPT_1.002 - 1bit] | 1-HEAT mode is active | 1 Bit | 1.2 boolean | CRT |
| 59 | Status_ Mode Cool [DPT_1.002 - 1bit] | 1-COOL mode is active | 1 Bit | 1.2 boolean | CRT |
| 60 | Status_ Mode Fan [DPT_1.002 - 1bit] | 1-FAN mode is active | 1 Bit | 1.2 boolean | CRT |
| 61 | Status_ Mode Dry [DPT_1.002 - 1bit] | 1-DRY mode is active | 1 Bit | 1.2 boolean | CRT |
| 62 | Status_ Mode Text [DPT_16.001 - 14byte] | ASCII String | 14 Bytes | 16.1 Character String (ISO 8859-1) | CRT |
| 63 | Status_ Fan Speed / 3 Speeds [DPT_5.001 - 1byte] | 33%, 67% and 100% | 1 Byte | 5.1 percentage (0..100%) | CRT |
| 63 | Status_ Fan Speed / 3 Speeds [DPT_5.010 - 1byte] | Speed Values: 1,2,3 | 1 Byte | 5.10 counter pulses (0..255) | CRT |
| 64 | Status_ Fan Speed Man/Auto [DPT_1.002 - 1bit] | 0-Manual;1-Auto | 1 Bit | 1.2 boolean | CRT |
| 65 | Status_ Fan Speed 1 [DPT_1.002 - 1bit] | 1-Fan in speed 1 | 1 Bit | 1.2 boolean | CRT |
| 66 | Status_ Fan Speed 2 [DPT_1.002 - 1bit] | 1-Fan in speed 2 | 1 Bit | 1.2 boolean | CRT |
| 67 | Status_ Fan Speed 3 [DPT_1.002 - 1bit] | 1-Fan in speed 3 | 1 Bit | 1.2 boolean | CRT |
| 68 | Status_ Fan Speed Text [DPT_16.001 - 14byte] | ASCII String | 14 Bytes | 16.1 Character String (ISO 8859-1) | CRT |
| 69 | Status_ Vanes U-D / 5 Pos [DPT_5.001 - 1byte] | 20%, 40%, 60%, 80% and 100% | 1 Byte | 5.1 percentage (0..100%) | CRT |
| 69 | Status_ Vanes U-D / 5 Pos [DPT_5.010 - 1byte] | Position values: 1,2,3,4,5 | 1 Byte | 5.10 counter pulses (0..255) | CRT |
| 70 | Status_ Vanes U-D Standby [DPT_1.002 - 1bit] | 0-Off;1-Standby | 1 Bit | 1.2 boolean | CRT |
| 71 | Status_ Vanes U-D Pos 1 [DPT_1.002 - 1bit] | 1-Vanes in Position 1 | 1 Bit | 1.2 boolean | CRT |
| 72 | Status_ Vanes U-D Pos 2 [DPT_1.002 - 1bit] | 1-Vanes in Position 2 | 1 Bit | 1.2 boolean | CRT |
| 73 | Status_ Vanes U-D Pos 3 [DPT_1.002 - 1bit] | 1-Vanes in Position 3 | 1 Bit | 1.2 boolean | CRT |
| 74 | Status_ Vanes U-D Pos 4 [DPT_1.002 - 1bit] | 1-Vanes in Position 4 | 1 Bit | 1.2 boolean | CRT |
| 75 | Status_ Vanes U-D Pos 5 [DPT_1.002 - 1bit] | 1-Vanes in Position 5 | 1 Bit | 1.2 boolean | CRT |
| 76 | Status_ Vanes U-D Swing [DPT_1.002 - 1bit] | 0-Off;1-Swing | 1 Bit | 1.2 boolean | CRT |
| 77 | Status_ Vanes U-D Text [DPT_16.001 - 14byte] | ASCII String | 14 Bytes | 16.1 Character String (ISO 8859-1) | CRT |
| 78 | Status_ AC Setpoint Temp [DPT_9.001 - 2byte] | ºC | 2 Bytes | 9.1 temperature (°C) | CRT |
| 79 | Status_ AC Ambient Ref Temp [DPT_9.001 - 2byte] | ºC | 2 Bytes | 9.1 temperature (°C) | CRT |
| 80 | Status_ Filter Status [DPT_1.005 - 1bit] | 0-No alarm;1-Alarm | 1 Bit | CRT | |
| 81 | Status_ Error/Alarm [DPT_1.005 - 1bit] | 0-No alarm;1-Alarm | 1 Bit | CRT | |
| 82 | Status_ Error Code [2byte] | 0-No error /Any other see man. | 2 Bytes | CRT | |
| 83 | Status_ Error Text Code [DPT_16.001 - 14byte] | 3-char TO Error; Empty-None | 14 Bytes | 16.1 Character String (ISO 8859-1) | CRT |
| 84 | Status_ Lock Remote Control [DPT_1.002 - 1bit] | 0-Unlocked;1-Locked | 1 Bit | 1.2 boolean | CRT |
| 85 | Status_ Lock Control Objects [DPT_1.002 - 1bit] | 0-Unlocked;1-Locked | 1 Bit | 1.2 boolean | CRT |
| 86 | Status_ Power Mode [DPT_1.001 - 1bit] | 0-Off;1-On | 1 Bit | 1.1 switch | CRT |
| 87 | Status_ Econo Mode [DPT_1.001 - 1bit] | 0-Off;1-On | 1 Bit | 1.1 switch | CRT |
| 88 | Status_ Additional Heat [DPT_1.001 - 1bit] | 0-Off;1-On | 1 Bit | 1.1 switch | CRT |
| 89 | Status_ Additional Cool [DPT_1.001 - 1bit] | 0-Off;1-On | 1 Bit | 1.1 switch | CRT |
| 90 | Status_ Operation Hour Counter [DPT_7.001 - 2byte] | Number of operating hours | 2 Bytes | 7.1 pulses | CRT |
| 91 | Status_ Current Scene [DPT_17.001 - 1byte] | 0..4-Scene X+1;63-No Scene | 1 Byte | CRT | |
| 92 | Status_ In1 - Switching [DPT_1.001 - 1bit] | 0-Off;1-On | 1 Bit | 1.1 switch | CRT |
| 92 | Status_ In1 - Dimming - On/Off [DPT_1.001 - 1bit] | 0-Off;1-On | 1 Bit | 1.1 switch | CRT |
| 92 | Status_ In1 - Shut/Blind - Step [DPT_1.007 - 1bit] | 0-Step Up;1-Step Down | 1 Bit | CRT | |
| 93 | Status_ In1 - Dimming - Step(%) [DPT_3.007 - 4bit] | Dimming step | 4 Bit | 3.7 dimming control | CRT |
| 93 | Status_ In1 - Shut/Blind - Move [DPT_1.008 - 1bit] | 0-Move Up;1-Move Down | 1 Bit | 1.8 up/down | CRT |
| 93 | Status_ In1 - Value [DPT_12.001 - 12byte] | 4-byte unsigned value | 4 Bytes | 12.1 counter pulses (unsigned) | CRT |
| 93 | Status_ In1 - Value [DPT_5.010 - 1byte] | 1-byte unsigned value | 1 Byte | 5.10 counter pulses (0..255) | CRT |
| 93 | Status_ In1 - Value [DPT_8.001 - 2byte] | 2-byte signed value | 2 Bytes | 8.1 pulses difference | CRT |
| 93 | Status_ In1 - Value [DPT_9.001 - 2byte] | Temperature (ºC) | 2 Bytes | 9.1 temperature (°C) | CRT |
| 93 | Status_ In1 - Value [DPT_7.001 - 2byte] | 2-byte unsigned value | 2 Bytes | 7.1 pulses | CRT |
| 94 | Status_ In2 - Switching [DPT_1.001 - 1bit] | 0-Off;1-On | 1 Bit | 1.1 switch | CRT |
| 94 | Status_ In2 - Dimming - On/Off [DPT_1.001 - 1bit] | 0-Off;1-On | 1 Bit | 1.1 switch | CRT |
| 94 | Status_ In2 - Shut/Blind - Step [DPT_1.007 - 1bit] | 0-Step Up;1-Step Down | 1 Bit | CRT | |
| 95 | Status_ In2 - Dimming - Step(%) [DPT_3.007 - 4bit] | Dimming step | 4 Bit | 3.7 dimming control | CRT |
| 95 | Status_ In2 - Value [DPT_7.001 - 2byte] | 2-byte unsigned value | 2 Bytes | 7.1 pulses | CRT |
| 95 | Status_ In2 - Value [DPT_12.001 - 12byte] | 4-byte unsigned value | 4 Bytes | 12.1 counter pulses (unsigned) | CRT |
| 95 | Status_ In2 - Value [DPT_9.001 - 2byte] | Temperature (ºC) | 2 Bytes | 9.1 temperature (°C) | CRT |
| 95 | Status_ In2 - Value [DPT_8.001 - 2byte] | 2-byte signed value | 2 Bytes | 8.1 pulses difference | CRT |
| 95 | Status_ In2 - Value [DPT_5.010 - 1byte] | 1-byte unsigned value | 1 Byte | 5.10 counter pulses (0..255) | CRT |
| 95 | Status_ In2 - Shut/Blind - Move [DPT_1.008 - 1bit] | 0-Move Up;1-Move Down | 1 Bit | 1.8 up/down | CRT |
| 96 | Status_ In3 - Switching [DPT_1.001 - 1bit] | 0-Off;1-On | 1 Bit | 1.1 switch | CRT |
| 96 | Status_ In3 - Dimming - On/Off [DPT_1.001 - 1bit] | 0-Off;1-On | 1 Bit | 1.1 switch | CRT |
| 96 | Status_ In3 - Shut/Blind - Step [DPT_1.007 - 1bit] | 0-Step Up;1-Step Down | 1 Bit | CRT | |
| 97 | Status_ In3 - Dimming - Step(%) [DPT_3.007 - 4bit] | Dimming step | 4 Bit | 3.7 dimming control | CRT |
| 97 | Status_ In3 - Value [DPT_12.001 - 12byte] | 4-byte unsigned value | 4 Bytes | 12.1 counter pulses (unsigned) | CRT |
| 97 | Status_ In3 - Value [DPT_9.001 - 2byte] | Temperature (ºC) | 2 Bytes | 9.1 temperature (°C) | CRT |
| 97 | Status_ In3 - Value [DPT_8.001 - 2byte] | 2-byte signed value | 2 Bytes | 8.1 pulses difference | CRT |
| 97 | Status_ In3 - Value [DPT_7.001 - 2byte] | 2-byte unsigned value | 2 Bytes | 7.1 pulses | CRT |
| 97 | Status_ In3 - Value [DPT_5.010 - 1byte] | 1-byte unsigned value | 1 Byte | 5.10 counter pulses (0..255) | CRT |
| 97 | Status_ In3 - Shut/Blind - Move [DPT_1.008 - 1bit] | 0-Move Up;1-Move Down | 1 Bit | 1.8 up/down | CRT |
| 98 | Status_ In4 - Switching [DPT_1.001 - 1bit] | 0-Off;1-On | 1 Bit | 1.1 switch | CRT |
| 98 | Status_ In4 - Dimming - On/Off [DPT_1.001 - 1bit] | 0-Off;1-On | 1 Bit | 1.1 switch | CRT |
| 98 | Status_ In4 - Shut/Blind - Step [DPT_1.007 - 1bit] | 0-Step Up;1-Step Down | 1 Bit | CRT | |
| 99 | Status_ In4 - Dimming - Step(%) [DPT_3.007 - 4bit] | Dimming step | 4 Bit | 3.7 dimming control | CRT |
| 99 | Status_ In4 - Value [DPT_12.001 - 12byte] | 4-byte unsigned value | 4 Bytes | 12.1 counter pulses (unsigned) | CRT |
| 99 | Status_ In4 - Value [DPT_9.001 - 2byte] | Temperature (ºC) | 2 Bytes | 9.1 temperature (°C) | CRT |
| 99 | Status_ In4 - Value [DPT_8.001 - 2byte] | 2-byte signed value | 2 Bytes | 8.1 pulses difference | CRT |
| 99 | Status_ In4 - Value [DPT_7.001 - 2byte] | 2-byte unsigned value | 2 Bytes | 7.1 pulses | CRT |
| 99 | Status_ In4 - Value [DPT_5.010 - 1byte] | 1-byte unsigned value | 1 Byte | 5.10 counter pulses (0..255) | CRT |
| 99 | Status_ In4 - Shut/Blind - Move [DPT_1.008 - 1bit] | 0-Move Up;1-Move Down | 1 Bit | 1.8 up/down | CRT |
Parameters (235)
| Parameter | Type | Default |
|---|---|---|
| Download latest database entry for this product and its User Manual from: | text | http://www.intesis.com |
| Send READs for Control_ objects on bus recovery (T & U flags must be active) | list | No |
| > Delay before sending READs (sec) | unsignedInt 0…30 | 10 |
| Scene to load on bus recovery / startup (needs to define vals for that scene) | list | (none) |
| Disallow control from remote controller | list | No |
| > Enable "Lock Remote Control" objs | list | No |
| Enable func "Lock Control Objects" | list | No |
| Enable func "Operating Hours Counter" | list | No |
| Enable use of objects for Filter (for Control and Status) | list | No |
| Enable object "Error Code [2byte]" | list | No |
| Enable object "Error Text Code [14byte]" (3 ASCII-char Error Code) | list | Yes |
| Indoor unit has HEAT mode (see docum. for your indoor unit) | list | Yes |
| Indoor unit has AUTO mode (see docum. for your indoor unit) | list | No |
| Indoor unit has FAN mode (see docum. for your indoor unit) | list | Yes |
| Indoor unit has DRY mode (see docum. for your indoor unit) | list | Yes |
| When mode is AUTO Status_ objs report actual operating status (HEAT/COOL/..) | list | No |
| Enable "Mode Cool/Heat" objects (for Control and Status) | list | No |
| Enable PID-Compat. Scaling Mode objects (for Control) | list | No |
| Enable use of +/- object for Mode | list | No |
| > DPT type for +/- Mode Object | list | 0-Decrease / 1-Increase [DPT_1.007] |
| Enable use of bit-type Mode objects (for Control) | list | No |
| Enable use of bit-type Mode objects (for Status) | list | No |
| Enable use of Text object for Mode | list | No |
| ASCII strings shown in comm object "Status_ Mode Text" | text | << 14-byte string values >> |
| > String when mode is AUTO (if available) | text | AUTO |
| > String when mode is HEAT (if available) | text | HEAT |
| > String when mode is COOL | text | COOL |
| > String when mode is FAN | text | FAN |
| > String when mode is DRY | text | DRY |
| Enable use of Legacy_ object for Mode (compatible with old vers of XXACKNX1) | list | No |
| Enable use of "POWERFUL" mode (AC feature) | list | No |
| Enable use of "QUIET" mode (AC feature) | list | No |
| Enable use of POWER mode | list | No |
| > Action time for this mode (minutes) | unsignedInt 1…180 | 30 |
| > Setpoint delta increase (HEAT) or decrease (COOL) (ºC) | list | 2.0 ºC |
| > Fan Speed for this mode | list | FAN SPEED 3 |
| Enable use of ECONOMY mode | list | No |
| > Setpoint delta decrease (HEAT) or increase (COOL) (ºC) | list | 2.0 ºC |
| > Fan Speed for this mode | list | FAN SPEED 1 |
| Enable use of ADDITIONAL HEATING mode | list | No |
| > Setpoint temp for this mode (ºC) | list | 27.0 ºC |
| > Fan Speed for this mode | list | FAN SPEED AUTO |
| Enable use of ADDITIONAL COOLING mode | list | No |
| > Setpoint temp for this mode (ºC) | list | 20.0 ºC |
| Fan is accessible in Indoor unit (see docum. for your indoor unit) | list | Yes |
| Available fanspeeds in Indoor Unit (see docum. for your indoor unit) | unsignedInt 3…3 | 3 |
| Indoor unit has AUTO fan speed (see docum. for your indoor unit) | list | Yes |
| When fan is AUTO Status_ objs report actual operating status (speed1/2/...) | list | No |
| DPT object type for fanspeed | list | Scaling [DPT_5.001] |
| Enable use of +/- object for Fan Speed | list | No |
| > DPT type for +/- Fan Speed object | list | 0-Decrease / 1-Increase [DPT_1.007] |
| > Does +/- sequence include fan speed AUTO? | list | No |
| > Rollover Speed at upper/lower limit (when controlling with +/- obj) | list | Yes |
| Enable "Fan Speed Man/Auto" objects (for Control and Status) | list | No |
| Enable use of bit-type Fan Speed objects (for Control) | list | No |
| Enable use of bit-type Fan Speed objects (for Status) | list | No |
| Enable use of Text object for Fan Speed | list | No |
| ASCII strings shown in comm object "Status_ Fan Speed Text" | text | << 14-byte string values >> |
| > String when fan speed is AUTO (if available) | text | AUTO |
| > String when fan speed is 1 | text | SPEED 1 |
| > String when fan speed is 2 | text | SPEED 2 |
| > String when fan speed is 3 | text | SPEED 3 |
| > String when fan speed is 4 (if available) | text | SPEED 4 |
| > String when fan speed is 5 | text | SPEED 5 |
| Enable use of Legacy_ object for Fan (compatible with old vers of XXACKNX1) | list | No |
| Indoor unit has U-D Vanes (see docum. for your indoor unit) | list | Yes |
| Available positions in Indoor Unit (see docum. for your indoor unit) | unsignedInt 0…5 | 5 |
| IU has the following U-D Vanes values (see docum. for your indoor unit) | list | 5 positions, SWING and STANDBY |
| Indoor unit has STANDBY Vanes U-D (see docum. for your indoor unit) | list | Yes |
| Indoor unit has SWING Vanes U-D (see docum. for your indoor unit) | list | Yes |
| DPT object type for Vanes Up-Down | list | Scaling [DPT_5.001] |
| Enable use of +/- object for Vanes U-D | list | No |
| > DPT type for +/- Vanes U-D object | list | 0-Decrease / 1-Increase [DPT_1.007] |
| > Does +/- sequence include STANDBY vanes Up-Down? | list | No |
| > Does +/- sequence include SWING vanes Up-Down? | list | No |
| > Rollover Vanes at upper/lower limit (when controlling with +/- obj) | list | Yes |
| Enable "Vanes U-D Standby" objects (for Control and Status) | list | Yes |
| Enable "Vanes U-D Standby" objects (for Control and Status) | list | No |
| Enable use of bit-type Vanes U-D objects (for Control) | list | No |
| Enable use of bit-type Vanes U-D objects (for Status) | list | No |
| Enable "Vanes U-D Swing" objects (for Control and Status) | list | Yes |
| Enable "Vanes U-D Swing" objects (for Control and Status) | list | No |
| Enable use of Text object for Vanes U-D | list | No |
| ASCII strings shown in comm object "Status_ Vanes U-D Text" | text | << 14-byte string values >> |
| > String when vanes U-D in STANDBY | text | U-D STANDBY |
| > String when vanes U-D in POS 1 (if available) | text | U-D POS 1 |
| > String when vanes U-D in POS 2 (if available) | text | U-D POS 2 |
| > String when vanes U-D in POS 3 (if available) | text | U-D POS 3 |
| > String when vanes U-D in POS 4 (if available) | text | U-D POS 4 |
| > String when vanes U-D in POS 5 (if available) | text | U-D POS 5 |
| > String when vanes U-D in SWING | text | U-D SWING |
| Enable use of Legacy_ object for Vanes (compatible with old vers of XXACKNX1) | list | No |
| Indoor unit has L-R Vanes (see docum. for your indoor unit) | list | No |
| Available positions in Indoor Unit (see docum. for your indoor unit) | unsignedInt 3…5 | 5 |
| Indoor unit has AUTO Vanes L-R (see docum. for your indoor unit) | list | No |
| Indoor unit has SWING Vanes L-R (see docum. for your indoor unit) | list | No |
| DPT object type for Vanes Left-Right | list | Scaling [DPT_5.001] |
| Enable use of +/- object for Vanes L-R | list | No |
| > DPT type for +/- Vanes L-R object | list | 0-Decrease / 1-Increase [DPT_1.007] |
| > Does +/- sequence include vanes Left-Right AUTO? | list | No |
| Enable use of bit-type Vanes L-R objects (for Control) | list | No |
| Enable use of bit-type Vanes L-R objects (for Status) | list | No |
| Enable use of Text object for Vanes L-R | list | No |
| ASCII strings shown in comm object "Status_ Vanes L-R Text" | text | << 14-byte string values >> |
| > String when vanes L-R in AUTO | text | L-R AUTO |
| > String when vanes L-R in POS 1 | text | L-R POS 1 |
| > String when vanes L-R in POS 2 | text | L-R POS 2 |
| > String when vanes L-R in POS 3 | text | L-R POS 3 |
| > String when vanes L-R in POS 4 | text | L-R POS 4 |
| > String when vanes L-R in POS 5 | text | L-R POS 5 |
| AC unit has Humidifier (see docum. for your indoor unit) | list | No |
| Available intensities in Indoor Unit (see docum. for your indoor unit) | list | Yes |
| DPT object type for Humidifying | list | Scaling [DPT_5.001] |
| Enable use of +/- object for Humidifying | list | No |
| > DPT type for +/- Humidifying object | list | 0-Decrease / 1-Increase [DPT_1.007] |
| > Rollover Humi. at upper/lower limit (when controlling with +/- obj) | list | No |
| Enable use of bit-type Humidif. objects (for Control) | list | No |
| Enable use of bit-type Humidif. objects (for Status) | list | No |
| Enable use of Text obj for Humidifying | list | No |
| ASCII strings shown in comm object "Status_ Humidifying Text" | text | << 14-byte string values >> |
| > String when Humidifying is OFF | text | HUMI OFF |
| > String when Humidifying is LOW | text | HUMI LOW |
| > String when Humidifying is MID | text | HUMI MID |
| > String when Humidifying is HIGH | text | HUMI HIGH |
| > String when Humidifying is CONT. | text | HUMI CONT |
| Enable use of Legacy_ object for Humi. (compatible with old vers of XXACKNX1) | list | No |
| Periodic sending of "Status_ AC Setp" (in seconds;0=No periodic sending) | unsignedInt 0…255 | 0 |
| Transmission of "Status_ AC Ambient Ref Temp" | list | Only on change |
| > "Status_ AC Ambient Ref Temp" periodic sending time (in sec) | unsignedInt 1…255 | 180 |
| Enable use of +/- obj for Setpoint Temp | list | No |
| > DPT type for +/- Setp Temp object | list | 0-Decrease / 1-Increase [DPT_1.007] |
| > [+/-] step size | list | 1.0 ºC |
| Enable limits on Control_ Setpoint obj | list | No |
| > Lower limit (ºC) | list | 18.0 ºC |
| > Upper limit (ºC) | list | 27.0 ºC |
| Ambient temp. ref. is provided from KNX (carefully read User Guide if enabled) | list | No |
| Enable use of scenes | list | No |
| Scenes can be stored from KNX bus | list | No |
| > Enable use of bit objects for storing scenes (from bus) | list | No |
| Enable use of bit objects for scene execution | list | No |
| Scene 1 preset | list | No |
| > Scene 1 / Value for On-Off | list | (unchanged) |
| > Scene 1 / Value for Mode | list | (unchanged) |
| > Scene 1 / Value for Fan Speed | list | (unchanged) |
| > Scene 1 / Value for Vanes U-D (if available) | list | (unchanged) |
| > Scene 1 / Value for Vanes L-R (if available) | list | (unchanged) |
| > Scene 1 / Value for Setpoint Temp | list | (unchanged) |
| > Scene 1 / Value for Remote Lock | list | (unchanged) |
| > Scene 1 / Value for Humidifying (if available) | list | (unchanged) |
| Scene 2 preset | list | No |
| > Scene 2 / Value for On-Off | list | (unchanged) |
| > Scene 2 / Value for Mode | list | (unchanged) |
| > Scene 2 / Value for Fan Speed | list | (unchanged) |
| > Scene 2 / Value for Vanes U-D (if available) | list | (unchanged) |
| > Scene 2 / Value for Vanes L-R (if available) | list | (unchanged) |
| > Scene 2 / Value for Setpoint Temp | list | (unchanged) |
| > Scene 2 / Value for Remote Lock | list | (unchanged) |
| > Scene 2 / Value for Humidifying (if available) | list | (unchanged) |
| Scene 3 preset | list | No |
| > Scene 3 / Value for On-Off | list | (unchanged) |
| > Scene 3 / Value for Mode | list | (unchanged) |
| > Scene 3 / Value for Fan Speed | list | (unchanged) |
| > Scene 3 / Value for Vanes U-D (if available) | list | (unchanged) |
| > Scene 3 / Value for Vanes L-R (if available) | list | (unchanged) |
| > Scene 3 / Value for Setpoint Temp | list | (unchanged) |
| > Scene 3 / Value for Remote Lock | list | (unchanged) |
| > Scene 3 / Value for Humidifying (if available) | list | (unchanged) |
| Scene 4 preset | list | No |
| > Scene 4 / Value for On-Off | list | (unchanged) |
| > Scene 4 / Value for Mode | list | (unchanged) |
| > Scene 4 / Value for Fan Speed | list | (unchanged) |
| > Scene 4 / Value for Vanes U-D (if available) | list | (unchanged) |
| > Scene 4 / Value for Vanes L-R (if available) | list | (unchanged) |
| > Scene 4 / Value for Setpoint Temp | list | (unchanged) |
| > Scene 4 / Value for Remote Lock | list | (unchanged) |
| > Scene 4 / Value for Humidifying (if available) | list | (unchanged) |
| Scene 5 preset | list | No |
| > Scene 5 / Value for On-Off | list | (unchanged) |
| > Scene 5 / Value for Mode | list | (unchanged) |
| > Scene 5 / Value for Fan Speed | list | (unchanged) |
| > Scene 5 / Value for Vanes U-D (if available) | list | (unchanged) |
| > Scene 5 / Value for Vanes L-R (if available) | list | (unchanged) |
| > Scene 5 / Value for Setpoint Temp | list | (unchanged) |
| > Scene 5 / Value for Remote Lock | list | (unchanged) |
| > Scene 5 / Value for Humidifying (if available) | list | (unchanged) |
| Enable use of Open Window / Switch off timeout function | list | No |
| > AC switch-off timeout (min) | unsignedInt 0…30 | 10 |
| > DPT for Window / Switch-off timeout | list | 0-Stop / 1-Start Timeout [DPT_1.010] |
| > Disallow On/Off operation while window is Open | list | No |
| > Disallow On/Off operation while timeout is elapsed | list | No |
| > Reload last On/Off val once timeout is stopped | list | No |
| > Reload last On/Off val once window is Closed | list | No |
| Enable use of Occupancy function | list | No |
| > Timeout to apply action (minutes) | unsignedInt 0…180 | 20 |
| > Action after timeout elapsed | list | Switch-Off AC |
| > Temp delta decrease (HEAT) or increase (COOL) (ºC) | list | 2.0 ºC |
| > Enable secondary timeout | list | No |
| > Timeout to apply action (min) | unsignedInt 1…180 | 20 |
| > Action after timeout elapsed | list | Switch-Off AC |
| > Temp delta dec (HEAT) or inc (COOL) (ºC) | list | 3.0 ºC |
| > Disallow On/Off operation while not Occupied | list | No |
| > Reload last On/Off value when Occupied | list | No |
| Enable use of Sleep function | list | No |
| > Sleep function switch-off timeout (minutes) | unsignedInt 0…180 | 60 |
| Enable use of Input 1 | list | No |
| > Contact type | list | NO: Normally Open |
| > Debounce time | list | 50 ms |
| > Disabling function | list | No |
| > Reset Input when enabling | list | No |
| > Function | list | Switching |
| > Send telegram after bus recovery | list | No action |
| > Sending delay after bus recovery (seconds) | unsignedInt 0…255 | 10 |
| > Value on raising edge (contact activated) | list | No action |
| > Scene when contact is activated (needs to be defined) | list | Scene 1 |
| > Mode for short (long) operation | list | Toggle: On/Off (increase/decrease) |
| > Operation | list | Toggle (Up/Down) |
| > DPT to be sent | list | DPT 5.010 (1byte) |
| > Value on falling edge (contact deactivated) | list | No action |
| > Increasing step | list | + 25 % |
| > Method | list | Step-Move-Step |
| > Cyclical sending | list | Never |
| > Decreasing step | list | - 25 % |
| > Short/long operation limit (x100ms) | unsignedInt 1…255 | 10 |
| > Period for cyclical sending (seconds) | unsignedInt 1…65535 | 10 |
| > Vanes adjustment time (x100ms) | unsignedInt 1…255 | 10 |
| > Value on raising edge (when contact activated) | unsignedInt 0…255 | 0 |
| > Value on raising edge (when contact activated) | unsignedInt 0…65535 | 0 |
| > Value on raising edge (when contact activated) | signedInt -32768…32767 | 0 |
| > Value on rais. edge (x0.1ºC) (when contact activated) | signedInt -2730…3276 | 250 |
| > Value on raising edge (when contact activated) | unsignedInt 0…4294967295 | 0 |
| > Cycl. send. period in long oper. (x100ms)(0-No cyclical send.) | unsignedInt 0…255 | 0 |
| Enable use of Input 2 | list | No |
| Enable use of Input 3 | list | No |
| Enable use of Input 4 | list | No |
| Hide items?! | list | Yes |
Version history
| Application | App no | Fingerprint | First seen | Size | File |
|---|---|---|---|---|---|
| 0119 TORCKNX1i T1FV13 1.3 latest | $001F | 7DB3 | 2026-11-25 | 187 KB | Download |
About this file
This is the official ETS product database for the Intesis TO RC interface, 4 binary inputs (TO-RC-KNX-1i), published by the manufacturer in the KNX online catalog. To use it, open ETS, go to Catalogs → Import and choose the downloaded .knxprod file. The device then appears in your catalog and can be added to a project. Older versions are kept so existing projects can be matched to the application program they were commissioned with.
More from Intesis
- ACA interface (multiple indoor units) ACA-AC-KNX
- KNX Interface for ESTIA BMS-IFKX0AWR-E
- KNX Interface for Toshiba AC BMS-IFKX0TLR-E
- KNX Interface for ESTIA BMS-IFKX0UEW-E
- DK AC Interface DK-AC-KNX-1
- DK AC interface, 4 binary inputs DK-AC-KNX-1i
- DK RC Interface DK-RC-KNX-1
- DK RC interface, 4 binary inputs DK-RC-KNX-1i
- FJ RC interface, 4 binary inputs FJ-RC-KNX-1i
- HA AC interface (multiple indoor units) HA-AC-KNX
- HI AW Interface HI-AW-KNX-1
- HI RC interface, 4 binary inputs HI-RC-KNX-1i