| 0 | Control_ System On/Off [DPT_1.001 - 1bit] | 0-Off; 1-On | 1 Bit | 1.1 switch | CWTU |
| 1 | Control_ Operating Mode [DPT_20.105 - 1byte] | 0-Auto, 1-Heat, 3-Cool | 1 Byte | 20.105 HVAC control mode | CWTU |
| 2 | Control_ Operating Mode +/-[DPT_1.007 - 1byte] | 0-Decrease, 1-Increase | 1 Bit | 1.7 step | CWTU |
| 3 | Control_ Mode Cool/Heat [DPT_1.100 - 1bit] | 0-Cool, 1-Heat | 1 Bit | 1.100 heating/cooling | CWTU |
| 4 | Control_ Tank Only Mode [DPT_1.002 - 1bit] | 1-Set tank only mode | 1 Bit | 1.2 boolean | CWTU |
| 5 | Control_ Heat Mode [DPT_1.002 - 1bit] | 1-Set heat mode | 1 Bit | 1.2 boolean | CWTU |
| 6 | Control_ Cool Mode [DPT_1.002 - 1bit] | 1-Set cool mode | 1 Bit | 1.2 boolean | CWTU |
| 7 | Control_ Auto Mode [DPT_1.002 - 1bit] | 1-Set auto mode | 1 Bit | 1.2 boolean | CWTU |
| 8 | Control_ Zones [DPT_1.017 - 1bit] | 0,1-Enable/Disable zones | 1 Bit | 1.17 trigger | CWTU |
| 9 | Control_ Heat Mode Water Temperature Setting Method [DPT_1.014 - 1bit] | 0-Direct, 1-CompensationCurve | 1 Bit | | CWTU |
| 10 | Control_ Cool Mode Water Temperature Setting Method [DPT_1.014 - 1bit] | 0-Direct, 1-CompensationCurve | 1 Bit | | CWTU |
| 11 | Control_ Tank On/Off [DPT_1.001 - 1bit] | 0-Off; 1-On | 1 Bit | 1.1 switch | CWTU |
| 12 | Control_ Tank Water Setpoint Temperature [DPT_9.001 - 2byte] | ºC | 2 Bytes | 9.1 temperature (°C) | CWTU |
| 13 | Control_ Zone1 Setpoint Temperature [DPT_9.001 - 2byte] | ºC | 2 Bytes | 9.1 temperature (°C) | CWTU |
| 14 | Control_ Zone2 Setpoint Temperature [DPT_9.001 - 2byte] | ºC | 2 Bytes | 9.1 temperature (°C) | CWTU |
| 15 | Status_ System On/Off [DPT_1.001 - 1bit] | 0-Off; 1-On | 1 Bit | 1.1 switch | CRT |
| 16 | Status_ Operating Mode [DPT_20.105 - 1byte] | 0-Auto, 1-Heat, 3-Cool | 1 Byte | 20.105 HVAC control mode | CRT |
| 17 | Status_ Mode Cool/Heat [DPT_1.100 - 1bit] | 0-Cool, 1-Heat | 1 Bit | 1.100 heating/cooling | CRT |
| 18 | Status_ Tank Only Mode [DPT_1.002 - 1bit] | 1-Tank only mode active | 1 Bit | 1.2 boolean | CRT |
| 19 | Status_ Heat Mode [DPT_1.002 - 1bit] | 1-Heat mode active | 1 Bit | 1.2 boolean | CRT |
| 20 | Status_ Cool Mode [DPT_1.002 - 1bit] | 1-Cool mode active | 1 Bit | 1.2 boolean | CRT |
| 21 | Status_ Auto Mode [DPT_1.002 - 1bit] | 1-Auto mode active | 1 Bit | 1.2 boolean | CRT |
| 22 | Status_ AutoHeat Mode [DPT_1.002 - 1bit] | 1-Auto+heat mode active | 1 Bit | 1.2 boolean | CRT |
| 23 | Status_ AutoCool Mode [DPT_1.002 - 1bit] | 1-Auto+cool mode active | 1 Bit | 1.2 boolean | CRT |
| 24 | Status_ Number of Zones [DPT_5.010 - 1byte] | 1-1 zone, 2-2 zones | 1 Byte | 5.10 counter pulses (0..255) | CRT |
| 25 | Status_ Zone 1 [DPT_1.003 - 1bit] | 1-Enable, 0-Disable | 1 Bit | 1.3 enable | CRT |
| 26 | Status_ Zone 2 [DPT_1.003 - 1bit] | 1-Enable, 0-Disable | 1 Bit | 1.3 enable | CRT |
| 27 | Status_ Heat Mode Water Temperature Setting Method [DPT_1.014 - 1bit] | 0-Direct, 1-CompensationCurve | 1 Bit | | CRT |
| 28 | Status_ Cool Mode Water Temperature Setting Method [DPT_1.014 - 1bit] | 0-Direct, 1-CompensationCurve | 1 Bit | | CRT |
| 29 | Status_ Deice [DPT_1.011 - 1bit] | 1-Active, 0-Deactive | 1 Bit | 1.11 state | CRT |
| 30 | Status_ Outdoor Temperature [DPT_9.001 - 2byte] | ºC | 2 Bytes | 9.1 temperature (°C) | CRT |
| 31 | Status_ Inlet Water Temperature [DPT_9.001 - 2byte] | ºC | 2 Bytes | 9.1 temperature (°C) | CRT |
| 32 | Status_ Outlet Water Temperature [DPT_9.001 - 2byte] | ºC | 2 Bytes | 9.1 temperature (°C) | CRT |
| 33 | Status_ Outdoor Type STD [DPT_1.002 - 1bit] | 1: STD unit is active | 1 Bit | 1.2 boolean | CRT |
| 34 | Status_ Outdoor Type TCAP [DPT_1.002 - 1bit] | 1: TCAP unit is active | 1 Bit | 1.2 boolean | CRT |
| 35 | Status_ Outdoor Type HWT [DPT_1.002 - 1bit] | 1: HWT unit is active | 1 Bit | 1.2 boolean | CRT |
| 36 | Status_ Heat Mode Energy Consumption [DPT_9.024 - 2byte] | kW | 2 Bytes | 9.24 power (kW) | CRT |
| 37 | Status_ Cool Mode Energy Consumption [DPT_9.024 - 2byte] | kW | 2 Bytes | 9.24 power (kW) | CRT |
| 38 | Status_ Tank Mode Energy Consumption [DPT_9.024 - 2byte] | kW | 2 Bytes | 9.24 power (kW) | CRT |
| 39 | Status_ Current Error [DPT_1.005 - 1bit] | 1-Error, 0-No error | 1 Bit | 1.5 alarm | CRT |
| 40 | Status_ Error Code [2byte] | Error code | 2 Bytes | DPT.8 | CRT |
| 41 | Status_ Error Text [DPT_16.001 - 14byte] | Error description | 14 Bytes | 16.1 Character String (ISO 8859-1) | CRT |
| 42 | Status_ Tank On/Off [DPT_1.001 - 1bit] | 0-Off; 1-On | 1 Bit | 1.1 switch | CRT |
| 43 | Status_ Tank Connection [DPT_1.002 - 1bit] | 1-Tank is connected | 1 Bit | 1.2 boolean | CRT |
| 44 | Status_ Tank Water Sepoint Temperature [DPT_9.001 - 2byte] | ºC | 2 Bytes | 9.1 temperature (°C) | CRT |
| 45 | Status_ Tank Actual Water Temperature [DPT_9.001 - 2byte] | ºC | 2 Bytes | 9.1 temperature (°C) | CRT |
| 46 | Status_ Tank Water Min Setpoint Temperature [DPT_9.001 - 2byte] | ºC | 2 Bytes | 9.1 temperature (°C) | CRT |
| 47 | Status_ Tank Water Max Setpoint Temperature [DPT_9.001 - 2byte] | ºC | 2 Bytes | 9.1 temperature (°C) | CRT |
| 48 | Status_ Zone1 Setup Room [DPT_1.002 - 1bit] | 1- Active | 1 Bit | 1.2 boolean | CRT |
| 49 | Status_ Zone1 Setup Pool [DPT_1.002 - 1bit] | 1- Active | 1 Bit | 1.2 boolean | CRT |
| 50 | Status_ Zone1 Water Temperature Sensor [DPT_1.002 - 1bit] | 1- Active | 1 Bit | 1.2 boolean | CRT |
| 51 | Status_ Zone1 Room Temperature External Sensor [DPT_1.002 - 1bit] | 1- Active | 1 Bit | 1.2 boolean | CRT |
| 52 | Status_ Zone1 Room Temperature Internal Sensor [DPT_1.002 - 1bit] | 1- Active | 1 Bit | 1.2 boolean | CRT |
| 53 | Status_ Zone1 Room Temperature Thermistor Sensor [DPT_1.002 - 1bit] | 1- Active | 1 Bit | 1.2 boolean | CRT |
| 54 | Status_ Zone1 Pool Temperature Sensor [DPT_1.002 - 1bit] | 1- Active | 1 Bit | 1.2 boolean | CRT |
| 55 | Status_ Zone1 Setpoint Temperature [DPT_9.001 - 2byte] | ºC | 2 Bytes | 9.1 temperature (°C) | CRT |
| 56 | Status_ Zone1 Actual (Water Outlet/Room) Temperature [DPT_9.001 - 2byte] | ºC | 2 Bytes | 9.1 temperature (°C) | CRT |
| 57 | Status_ Zone1 Actual (Pool) Temperature [DPT_9.001 - 2byte] | ºC | 2 Bytes | 9.1 temperature (°C) | CRT |
| 58 | Status_ Zone1 Min Setpoint Temperature [DPT_9.001 - 2byte] | ºC | 2 Bytes | 9.1 temperature (°C) | CRT |
| 59 | Status_ Zone1 Max Setpoint Temperature [DPT_9.001 - 2byte] | ºC | 2 Bytes | 9.1 temperature (°C) | CRT |
| 60 | Status_ Zone1 Room Temperature Setting Mode [DPT_1.002 - 1bit] | 1- Active | 1 Bit | 1.2 boolean | CRT |
| 61 | Status_ Zone1 Compensation Curve Water Temp Setting Mode [DPT_1.002 - 1bit] | 1- Active | 1 Bit | 1.2 boolean | CRT |
| 62 | Status_ Zone1 Direct Water Temp Setting Mode [DPT_1.002 - 1bit] | 1- Active | 1 Bit | 1.2 boolean | CRT |
| 63 | Status_ Zone1 Pool Temperature Setting Mode [DPT_1.002 - 1bit] | 1- Active | 1 Bit | 1.2 boolean | CRT |
| 64 | Status_ Zone2 Setup Room [DPT_1.002 - 1bit] | 1- Active | 1 Bit | 1.2 boolean | CRT |
| 65 | Status_ Zone2 Setup Pool [DPT_1.002 - 1bit] | 1- Active | 1 Bit | 1.2 boolean | CRT |
| 66 | Status_ Zone2 Water Temperature Sensor [DPT_1.002 - 1bit] | 1- Active | 1 Bit | 1.2 boolean | CRT |
| 67 | Status_ Zone2 Room Temperature External Sensor [DPT_1.002 - 1bit] | 1- Active | 1 Bit | 1.2 boolean | CRT |
| 68 | Status_ Zone2 Room Temperature Internal Sensor [DPT_1.002 - 1bit] | 1- Active | 1 Bit | 1.2 boolean | CRT |
| 69 | Status_ Zone2 Room Temperature Thermistor Sensor [DPT_1.002 - 1bit] | 1- Active | 1 Bit | 1.2 boolean | CRT |
| 70 | Status_ Zone2 Pool Temperature Sensor [DPT_1.002 - 1bit] | 1- Active | 1 Bit | 1.2 boolean | CRT |
| 71 | Status_ Zone2 Setpoint Temperature [DPT_9.001 - 2byte] | ºC | 2 Bytes | 9.1 temperature (°C) | CRT |
| 72 | Status_ Zone2 Actual (Water Outlet/Room) Temperature [DPT_9.001 - 2byte] | ºC | 2 Bytes | 9.1 temperature (°C) | CRT |
| 73 | Status_ Zone2 Actual (Pool) Temperature [DPT_9.001 - 2byte] | ºC | 2 Bytes | 9.1 temperature (°C) | CRT |
| 74 | Status_ Zone2 Min Setpoint Temperature [DPT_9.001 - 2byte] | ºC | 2 Bytes | 9.1 temperature (°C) | CRT |
| 75 | Status_ Zone2 Max Setpoint Temperature [DPT_9.001 - 2byte] | ºC | 2 Bytes | 9.1 temperature (°C) | CRT |
| 76 | Status_ Zone2 Room Temperature Setting Mode [DPT_1.002 - 1bit] | 1- Active | 1 Bit | 1.2 boolean | CRT |
| 77 | Status_ Zone2 Compensation Curve Water Temp Setting Mode [DPT_1.002 - 1bit] | 1- Active | 1 Bit | 1.2 boolean | CRT |
| 78 | Status_ Zone2 Direct Water Temp Setting Mode [DPT_1.002 - 1bit] | 1- Active | 1 Bit | 1.2 boolean | CRT |
| 79 | Status_ Zone2 Pool Temperature Setting Mode [DPT_1.002 - 1bit] | 1- Active | 1 Bit | 1.2 boolean | CRT |