Intesis PA-AC-KNX-1i PA AC interface, 4 binary inputs

PA AC interface, 4 binary inputs PA-AC-KNX-1i

Intesis · Order number PA-AC-KNX-1i · Communication › Interfaces › Panasonic Air Conditioning Interfaces

Download .knxprod 0106 PAACKNX1i T0CV15 1.5 · 143 KB

Product

ManufacturerIntesis
Product namePA AC interface, 4 binary inputs
Order numberPA-AC-KNX-1i
HardwarePA AC Interface
MediumTwisted Pair
Bus current (mA)6
Rail mountedNo
RegistrationCertified
Languageses-ES, en-US
Catalog entryM-0077_H-PA.2DAC.2DKNX.2D1i-1_HP-000C-15-6F09_CI-PA.2DAC.2DKNX.2D1i-1
Fingerprint6F09
SHA-25694d6d7e3dac2eb7fc62a73296f43bb9349b3e57459c8c83faf392c8407a3d95f
First seen2026-11-25
Markets69 markets

Application program: 0106 PAACKNX1i T0CV15 1.5

Application number$000C
Version1.5
Mask versionMV-0025 (2.5)
KNX Data SecureNo
Minimum ETS version4.0
Parameters320
Group objects177
Group objects (177)
NoNameFunctionSizeDPTFlags
0Control_ On/Off [DPT_1.001 - 1bit]0-Off;1-On1 Bit1.1 switchCWT
1Control_ Powerful [DPT_1.002 - 1bit]1-Set POWERFUL1 Bit1.2 booleanCWT
2Control_ Quiet [DPT_1.002 - 1bit]1-Set QUIET1 Bit1.2 booleanCWT
3Control_ Mode [DPT_20.105 - 1byte]0-Aut;1-Hea;3-Coo;9-Fan;14-Dry1 ByteCWT
4Control_ Mode Cool/Heat [DPT_1.100 - 1bit]0-Cool;1-Heat1 BitCWT
5Control_ Mode Cool & On [DPT_5.001 - 1byte]0%-Off;0.1%-100%-On+Cool1 Byte5.1 percentage (0..100%)CWT
6Control_ Mode Heat & On [DPT_5.001 - 1byte]0%-Off;0.1%-100%-On+Heat1 Byte5.1 percentage (0..100%)CWT
7Control_ Mode Auto [DPT_1.002 - 1bit]1-Set AUTO mode1 Bit1.2 booleanCWT
8Control_ Mode Heat [DPT_1.002 - 1bit]1-Set HEAT mode1 Bit1.2 booleanCWT
9Control_ Mode Cool [DPT_1.002 - 1bit]1-Set COOL mode1 Bit1.2 booleanCWT
10Control_ Mode Fan [DPT_1.002 - 1bit]1-Set FAN mode1 Bit1.2 booleanCWT
11Control_ Mode Dry [DPT_1.002 - 1bit]1-Set DRY mode1 Bit1.2 booleanCWT
12Control_ Mode -/+ [DPT_1.007 - 1bit]0-Decrease;1-Increase1 BitCW
12Control_ Mode +/- [DPT_1.008 - 1bit]0-Up;1-Down1 Bit1.8 up/downCW
13Control_ Fan Speed / 5 Speeds [DPT_5.001 - 1byte]Thresholds:30%,50%,70% and 90%1 Byte5.1 percentage (0..100%)CWT
13Control_ Fan Speed / 5 Speeds [DPT_5.010 - 1byte] Speed values: 1,2,3,4,51 Byte5.10 counter pulses (0..255)CWT
14Control_ Fan Speed Man/Auto [DPT_1.002 - 1bit]0-Manual;1-Auto1 Bit1.2 booleanCWT
15Control_ Fan Speed 1 [DPT_1.002 - 1bit]1-Set Fan Speed 11 Bit1.2 booleanCWT
16Control_ Fan Speed 2 [DPT_1.002 - 1bit]1-Set Fan Speed 21 Bit1.2 booleanCWT
17Control_ Fan Speed 3 [DPT_1.002 - 1bit]1-Set Fan Speed 31 Bit1.2 booleanCWT
18Control_ Fan Speed 4 [DPT_1.002 - 1bit]1-Set Fan Speed 41 Bit1.2 booleanCWT
19Control_ Fan Speed 5 [DPT_1.002 - 1bit]1-Set Fan Speed 51 Bit1.2 booleanCWT
20Control_ Fan Speed -/+ [DPT_1.007 - 1bit]0-Decrease;1-Increase1 BitCW
20Control_ Fan Speed +/- [DPT_1.008 - 1bit]0-Up;1-Down1 Bit1.8 up/downCW
21Control_ Vanes U-D / 5 Pos [DPT_5.001 - 1byte]Thresholds:30%,50%,70% and 90%1 Byte5.1 percentage (0..100%)CWT
21Control_ Vanes U-D / 5 Pos [DPT_5.010 - 1byte]Position values: 1,2,3,4,51 Byte5.10 counter pulses (0..255)CWT
22Control_ Vanes U-D Man/Auto [DPT_1.002 - 1bit]0-Manual;1-Auto1 Bit1.2 booleanCWT
23Control_ Vanes U-D Pos 1 [DPT_1.002 - 1bit]1-Set Position 11 Bit1.2 booleanCWT
24Control_ Vanes U-D Pos 2 [DPT_1.002 - 1bit]1-Set Position 21 Bit1.2 booleanCWT
25Control_ Vanes U-D Pos 3 [DPT_1.002 - 1bit]1-Set Position 31 Bit1.2 booleanCWT
26Control_ Vanes U-D Pos 4 [DPT_1.002 - 1bit]1-Set Position 41 Bit1.2 booleanCWT
27Control_ Vanes U-D Pos 5 [DPT_1.002 - 1bit]1-Set Position 51 Bit1.2 booleanCWT
28Control_ Vanes U-D +/- [DPT_1.008 - 1bit]0-Up;1-Down1 Bit1.8 up/downCW
28Control_ Vanes U-D -/+ [DPT_1.007 - 1bit]0-Decrease;1-Increase1 BitCW
29Control_ Vanes L-R / 5 Pos [DPT_5.001 - 1byte]Thresholds:30%,50%,70% and 90%1 Byte5.1 percentage (0..100%)CWT
29Control_ Vanes L-R / 5 Pos [DPT_5.010 - 1byte]Position values 1,2,3,4,51 Byte5.10 counter pulses (0..255)CWT
30Control_ Vanes L-R Man/Auto [DPT_1.002 - 1bit]0-Manual;1-Auto1 Bit1.2 booleanCWT
31Control_ Vanes L-R Pos 1 [DPT_1.002 - 1bit]1-Set Position 11 Bit1.2 booleanCWT
32Control_ Vanes L-R Pos 2 [DPT_1.002 - 1bit]1-Set Position 21 Bit1.2 booleanCWT
33Control_ Vanes L-R Pos 3 [DPT_1.002 - 1bit]1-Set Position 31 Bit1.2 booleanCWT
34Control_ Vanes L-R Pos 4 [DPT_1.002 - 1bit]1-Set Position 41 Bit1.2 booleanCWT
35Control_ Vanes L-R Pos 5 [DPT_1.002 - 1bit]1-Set Position 51 Bit1.2 booleanCWT
36Control_ Vanes L-R -/+ [DPT_1.007 - 1bit]0-Decrease;1-Increase1 BitCW
36Control_ Vanes L-R +/- [DPT_1.008 - 1bit]0-Up;1-Down1 Bit1.8 up/downCW
37Control_ Setpoint Temp [DPT_9.001 - 2byte]ºC2 Bytes9.1 temperature (°C)CWT
38Control_ Setpoint Temp -/+ [DPT_1.007 - 1bit]0-Decrease;1-Increase1 BitCW
38Control_ Setpoint Temp +/- [DPT_1.008 - 1bit]0-Up;1-Down1 Bit1.8 up/downCW
39Control_ Ambient Temp [DPT_9.001 - 2byte]ºC2 Bytes9.1 temperature (°C)CWT
40Control_ Today [DPT_11.001 - 3byte]Today's date3 Bytes11.1 dateCWT
41Control_ Reset Energy Counter [DPT_1.015 - 1bit]1-Reset counter1 BitCWT
42Control_ Switch Off Timeout [DPT_1.010 - 1bit]0-Stop;1-Start1 Bit1.10 start/stopCWT
42Control_ Window Contact Status [DPT_1.009 - 1bit]0-Open;1-Closed1 Bit1.9 open/closeCWT
43Control_ Occupancy [DPT_1.018 - 1bit]0-Not Occupied;1-Occupied1 BitCWT
44Control_ Sleep Timeout [DPT_1.010 - 1bit]0-Stop;1-Start1 Bit1.10 start/stopCWT
45Control_ Lock Remote Control [DPT_1.002 - 1bit]0-Unlock;1-Lock1 Bit1.2 booleanCWT
46Control_ Lock Control Objects [DPT_1.002 - 1bit]0-Unlock;1-Lock1 Bit1.2 booleanCWT
47Control_ Power Mode [DPT_1.010 - 1bit]0-Stop;1-Start1 Bit1.10 start/stopCWT
48Control_ Econo Mode [DPT_1.010 - 1bit]0-Stop;1-Start1 Bit1.10 start/stopCWT
49Control_ Additional Heat [DPT_1.010 - 1bit]0-Stop;1-Start1 Bit1.10 start/stopCWT
50Control_ Additional Cool [DPT_1.010 - 1bit]0-Stop;1-Start1 Bit1.10 start/stopCWT
51Control_ Execute Scene [DPT_17.001 - 1byte]0..4-Exec1-51 ByteCWT
51Control_ Save/Exec Scene [DPT_18.001 - 1byte]0..4-Exec1-5;128..132-Save1-51 ByteCWT
52Control_ Store Scene 1 [DPT_1.002 - 1bit]1-Store Scene 11 Bit1.2 booleanCW
53Control_ Store Scene 2 [DPT_1.002 - 1bit]1-Store Scene 21 Bit1.2 booleanCW
54Control_ Store Scene 3 [DPT_1.002 - 1bit]1-Store Scene 31 Bit1.2 booleanCW
55Control_ Store Scene 4 [DPT_1.002 - 1bit]1-Store Scene 41 Bit1.2 booleanCW
56Control_ Store Scene 5 [DPT_1.002 - 1bit]1-Store Scene 51 Bit1.2 booleanCW
57Control_ Execute Scene 1 [DPT_1.002 - 1bit]1-Execute Scene 11 Bit1.2 booleanCWT
58Control_ Execute Scene 2 [DPT_1.002 - 1bit]1-Execute Scene 21 Bit1.2 booleanCWT
59Control_ Execute Scene 3 [DPT_1.002 - 1bit]1-Execute Scene 31 Bit1.2 booleanCWT
60Control_ Execute Scene 4 [DPT_1.002 - 1bit]1-Execute Scene 41 Bit1.2 booleanCWT
61Control_ Execute Scene 5 [DPT_1.002 - 1bit]1-Execute Scene 51 Bit1.2 booleanCWT
62Control_ Disable Input 1 [DPT_1.003 - 1bit]0-Disable;1-Enable1 Bit1.3 enableCWT
62Control_ Disable Input 1 [DPT_1.002 - 1bit]0-False;1-True1 Bit1.2 booleanCWT
63Control_ Disable Input 2 [DPT_1.002 - 1bit]0-False;1-True1 Bit1.2 booleanCWT
63Control_ Disable Input 2 [DPT_1.003 - 1bit]0-Disable;1-Enable1 Bit1.3 enableCWT
64Control_ Disable Input 3 [DPT_1.002 - 1bit]0-False;1-True1 Bit1.2 booleanCWT
64Control_ Disable Input 3 [DPT_1.003 - 1bit]0-Disable;1-Enable1 Bit1.3 enableCWT
65Control_ Disable Input 4 [DPT_1.002 - 1bit]0-False;1-True1 Bit1.2 booleanCWT
65Control_ Disable Input 4 [DPT_1.003 - 1bit]0-Disable;1-Enable1 Bit1.3 enableCWT
66Status_ On/Off [DPT_1.001 - 1bit]0-Off;1-On1 Bit1.1 switchCRT
67Status_ Powerful [DPT_1.002 - 1bit]1-POWERFUL is active1 Bit1.2 booleanCRT
68Status_ Quiet [DPT_1.002 - 1bit]1-QUIET is active1 Bit1.2 booleanCRT
69Status_ Mode [DPT_20.105 - 1byte]0-Aut;1-Hea;3-Coo;9-Fan;14-Dry1 ByteCRT
70Status_ Mode Cool/Heat [DPT_1.100 - 1bit]0-Cool;1-Heat1 BitCRT
71Status_ Mode Auto [DPT_1.002 - 1bit]1-AUTO mode is active1 Bit1.2 booleanCRT
72Status_ Mode Heat [DPT_1.002 - 1bit]1-HEAT mode is active1 Bit1.2 booleanCRT
73Status_ Mode Cool [DPT_1.002 - 1bit]1-COOL mode is active1 Bit1.2 booleanCRT
74Status_ Mode Fan [DPT_1.002 - 1bit]1-FAN mode is active1 Bit1.2 booleanCRT
75Status_ Mode Dry [DPT_1.002 - 1bit]1-DRY mode is active1 Bit1.2 booleanCRT
76Status_ Mode Text [DPT_16.001 - 14byte]ASCII String14 Bytes16.1 Character String (ISO 8859-1)CRT
77Status_ Fan Speed / 5 Speeds [DPT_5.001 - 1byte]20%, 40%, 60%, 80% and 100%1 Byte5.1 percentage (0..100%)CRT
77Status_ Fan Speed / 5 Speeds [DPT_5.010 - 1byte]Speed Values: 1,2,3,4,51 Byte5.10 counter pulses (0..255)CRT
78Status_ Fan Speed Man/Auto [DPT_1.002 - 1bit]0-Manual;1-Auto1 Bit1.2 booleanCRT
79Status_ Fan Speed 1 [DPT_1.002 - 1bit]1-Fan in Speed 11 Bit1.2 booleanCRT
80Status_ Fan Speed 2 [DPT_1.002 - 1bit]1-Fan in Speed 21 Bit1.2 booleanCRT
81Status_ Fan Speed 3 [DPT_1.002 - 1bit]1-Fan in Speed 31 Bit1.2 booleanCRT
82Status_ Fan Speed 4 [DPT_1.002 - 1bit]1-Fan in Speed 41 Bit1.2 booleanCRT
83Status_ Fan Speed 5 [DPT_1.002 - 1bit]1-Fan in Speed 51 Bit1.2 booleanCRT
84Status_ Fan Speed Text [DPT_16.001 - 14byte]ASCII String14 Bytes16.1 Character String (ISO 8859-1)CRT
85Status_ Vanes U-D / 5 Pos [DPT_5.001 - 1byte]20%, 40%, 60%, 80% and 100%1 Byte5.1 percentage (0..100%)CRT
85Status_ Vanes U-D / 5 Pos [DPT_5.010 - 1byte]Position values 1,2,3,4,51 Byte5.10 counter pulses (0..255)CRT
86Status_ Vanes U-D Man/Auto [DPT_1.002 - 1bit]0-Manual;1-Auto1 Bit1.2 booleanCRT
87Status_ Vanes U-D Pos 1 [DPT_1.002 - 1bit]1-Vanes in Position 11 Bit1.2 booleanCRT
88Status_ Vanes U-D Pos 2 [DPT_1.002 - 1bit]1-Vanes in Position 21 Bit1.2 booleanCRT
89Status_ Vanes U-D Pos 3 [DPT_1.002 - 1bit]1-Vanes in Position 31 Bit1.2 booleanCRT
90Status_ Vanes U-D Pos 4 [DPT_1.002 - 1bit]1-Vanes in Position 41 Bit1.2 booleanCRT
91Status_ Vanes U-D Pos 5 [DPT_1.002 - 1bit]1-Vanes in Position 51 Bit1.2 booleanCRT
92Status_ Vanes U-D Text [DPT_16.001 - 14byte]ASCII String14 Bytes16.1 Character String (ISO 8859-1)CRT
93Status_ Vanes L-R / 5 Pos [DPT_5.001 - 1byte]20%, 40%, 60%, 80% and 100%1 Byte5.1 percentage (0..100%)CRT
93Status_ Vanes L-R / 5 Pos [DPT_5.010 - 1byte]Position values 1,2,3,4,51 Byte5.10 counter pulses (0..255)CRT
94Status_ Vanes L-R Man/Auto [DPT_1.002 - 1bit]0-Manual;1-Auto1 Bit1.2 booleanCRT
95Status_ Vanes L-R Pos 1 [DPT_1.002 - 1bit]1-Vanes in Position 11 Bit1.2 booleanCRT
96Status_ Vanes L-R Pos 2 [DPT_1.002 - 1bit]1-Vanes in Position 21 Bit1.2 booleanCRT
97Status_ Vanes L-R Pos 3 [DPT_1.002 - 1bit]1-Vanes in Position 31 Bit1.2 booleanCRT
98Status_ Vanes L-R Pos 4 [DPT_1.002 - 1bit]1-Vanes in Position 41 Bit1.2 booleanCRT
99Status_ Vanes L-R Pos 5 [DPT_1.002 - 1bit]1-Vanes in Position 51 Bit1.2 booleanCRT
100Status_ Vanes L-R Text [DPT_16.001 - 14byte]ASCII String14 Bytes16.1 Character String (ISO 8859-1)CRT
101Status_ AC Setpoint Temp [DPT_9.001 - 2byte]ºC2 Bytes9.1 temperature (°C)CRT
102Status_ AC Return Path Temp [DPT_9.001 - 2byte]ºC2 Bytes9.1 temperature (°C)CRT
103Status_ Outdoor Temp [DPT_9.001 - 2byte]ºC2 Bytes9.1 temperature (°C)CRT
104Status_ Error/Alarm [DPT_1.005 - 1bit]0-No alarm;1-Alarm1 BitCRT
105Status_ Error Code [2byte]0-No error /Any other see man.2 BytesCRT
106Status_ Error Text Code [DPT_16.001 - 14byte]3 char PA Error;Empty-None14 Bytes16.1 Character String (ISO 8859-1)CRT
107Status_ Power Consumption [DPT_14.056 - 4byte]W4 Bytes14.56 power (W)CRT
108Status_ Today Energy [DPT_13.010 - 4byte]Wh4 BytesCRT
109Status_ Yesterday Energy [DPT_13.010 - 4byte]Wh4 BytesCRT
110Status_ Total Energy [DPT_13.010 - 4byte]Wh4 BytesCRT
111Status_ Today [DPT_11.001 - 3byte]Today's date3 Bytes11.1 dateCRT
112Status_ Lock Remote Control [DPT_1.002 - 1bit]0-Unlocked;1-Locked1 Bit1.2 booleanCRT
113Status_ Lock Control Objects [DPT_1.002 - 1bit]0-Unlocked;1-Locked1 Bit1.2 booleanCRT
114Status_ Power Mode [DPT_1.001 - 1bit]0-Off;1-On1 Bit1.1 switchCRT
115Status_ Econo Mode [DPT_1.001 - 1bit]0-Off;1-On1 Bit1.1 switchCRT
116Status_ Additional Heat [DPT_1.001 - 1bit]0-Off;1-On1 Bit1.1 switchCRT
117Status_ Additional Cool [DPT_1.001 - 1bit]0-Off;1-On1 Bit1.1 switchCRT
118Status_ Operation Hour Counter [DPT_7.001 - 2byte]Number of operating hours2 Bytes7.1 pulsesCRT
119Status_ Current Scene [DPT_17.001 - 1byte]0..4-Scene X+1;63-No Scene1 ByteCRT
120Status_ In1 - Switching [DPT_1.001 - 1bit]0-Off;1-On1 Bit1.1 switchCRT
120Status_ In1 - Dimming - On/Off [DPT_1.001 - 1bit]0-Off;1-On1 Bit1.1 switchCRT
120Status_ In1 - Shut/Blind - Step [DPT_1.007 - 1bit]0-Step Up;1-Step Down1 BitCRT
121Status_ In1 - Dimming - Step(%) [DPT_3.007 - 4bit]Dimming step4 Bit3.7 dimming controlCRT
121Status_ In1 - Shut/Blind - Move [DPT_1.008 - 1bit]0-Move Up;1-Move Down1 Bit1.8 up/downCRT
121Status_ In1 - Value [DPT_12.001 - 4byte]4-byte unsigned value4 Bytes12.1 counter pulses (unsigned)CRT
121Status_ In1 - Value [DPT_5.010 - 1byte]1-byte unsigned value1 Byte5.10 counter pulses (0..255)CRT
121Status_ In1 - Value [DPT_8.001 - 2byte]2-byte signed value2 Bytes8.1 pulses differenceCRT
121Status_ In1 - Value [DPT_9.001 - 2byte]Temperature (ºC)2 Bytes9.1 temperature (°C)CRT
121Status_ In1 - Value [DPT_7.001 - 2byte]2-byte unsigned value2 Bytes7.1 pulsesCRT
122Status_ In2 - Switching [DPT_1.001 - 1bit]0-Off;1-On1 Bit1.1 switchCRT
122Status_ In2 - Dimming - On/Off [DPT_1.001 - 1bit]0-Off;1-On1 Bit1.1 switchCRT
122Status_ In2 - Shut/Blind - Step [DPT_1.007 - 1bit]0-Step Up;1-Step Down1 BitCRT
123Status_ In2 - Dimming - Step(%) [DPT_3.007 - 4bit]Dimming step4 Bit3.7 dimming controlCRT
123Status_ In2 - Value [DPT_7.001 - 2byte]2-byte unsigned value2 Bytes7.1 pulsesCRT
123Status_ In2 - Value [DPT_5.010 - 1byte]1-byte unsigned value1 Byte5.10 counter pulses (0..255)CRT
123Status_ In2 - Shut/Blind - Move [DPT_1.008 - 1bit]0-Move Up;1-Move Down1 Bit1.8 up/downCRT
123Status_ In2 - Value [DPT_12.001 - 4byte]4-byte unsigned value4 Bytes12.1 counter pulses (unsigned)CRT
123Status_ In2 - Value [DPT_9.001 - 2byte]Temperature (ºC)2 Bytes9.1 temperature (°C)CRT
123Status_ In2 - Value [DPT_8.001 - 2byte]2-byte signed value2 Bytes8.1 pulses differenceCRT
124Status_ In3 - Switching [DPT_1.001 - 1bit]0-Off;1-On1 Bit1.1 switchCRT
124Status_ In3 - Dimming - On/Off [DPT_1.001 - 1bit]0-Off;1-On1 Bit1.1 switchCRT
124Status_ In3 - Shut/Blind - Step [DPT_1.007 - 1bit]0-Step Up;1-Step Down1 BitCRT
125Status_ In3 - Dimming - Step(%) [DPT_3.007 - 4bit]Dimming step4 Bit3.7 dimming controlCRT
125Status_ In3 - Value [DPT_12.001 - 4byte]4-byte unsigned value4 Bytes12.1 counter pulses (unsigned)CRT
125Status_ In3 - Value [DPT_9.001 - 2byte]Temperature (ºC)2 Bytes9.1 temperature (°C)CRT
125Status_ In3 - Value [DPT_8.001 - 2byte]2-byte signed value2 Bytes8.1 pulses differenceCRT
125Status_ In3 - Value [DPT_7.001 - 2byte]2-byte unsigned value2 Bytes7.1 pulsesCRT
125Status_ In3 - Value [DPT_5.010 - 1byte]1-byte unsigned value1 Byte5.10 counter pulses (0..255)CRT
125Status_ In3 - Shut/Blind - Move [DPT_1.008 - 1bit]0-Move Up;1-Move Down1 Bit1.8 up/downCRT
126Status_ In4 - Switching [DPT_1.001 - 1bit]0-Off;1-On1 Bit1.1 switchCRT
126Status_ In4 - Dimming - On/Off [DPT_1.001 - 1bit]0-Off;1-On1 Bit1.1 switchCRT
126Status_ In4 - Shut/Blind - Step [DPT_1.007 - 1bit]0-Step Up;1-Step Down1 BitCRT
127Status_ In4 - Dimming - Step(%) [DPT_3.007 - 4bit]Dimming step4 Bit3.7 dimming controlCRT
127Status_ In4 - Value [DPT_12.001 - 4byte]4-byte unsigned value4 Bytes12.1 counter pulses (unsigned)CRT
127Status_ In4 - Value [DPT_9.001 - 2byte]Temperature (ºC)2 Bytes9.1 temperature (°C)CRT
127Status_ In4 - Value [DPT_8.001 - 2byte]2-byte signed value2 Bytes8.1 pulses differenceCRT
127Status_ In4 - Value [DPT_7.001 - 2byte]2-byte unsigned value2 Bytes7.1 pulsesCRT
127Status_ In4 - Value [DPT_5.010 - 1byte]1-byte unsigned value1 Byte5.10 counter pulses (0..255)CRT
127Status_ In4 - Shut/Blind - Move [DPT_1.008 - 1bit]0-Move Up;1-Move Down1 Bit1.8 up/downCRT
Parameters (197)
ParameterTypeDefault
Download latest database entry for this product and its User Manual from:texthttp://www.intesis.com
Send READs for Control_ objects on bus recovery (T & U flags must be active)listNo
> Delay before sending READs (sec)unsignedInt 0…3010
Scene to load on bus recovery / startup (needs to define vals for that scene)list(none)
Enable object "Error Code [2byte]"listNo
Disallow control from remote controllerlistNo
> Enable "Lock Remote Control" objslistNo
Enable func "Lock Control Objects"listNo
Enable func "Operating Hours Counter"listNo
When mode is AUTO Status_ objs report actual operating status (HEAT/COOL/..)listNo
Enable "Mode Cool/Heat" objects (for Control and Status)listNo
Enable PID-Compat. Scaling Mode ObjectslistNo
Enable use of +/- object for ModelistNo
> DPT type for +/- Mode Objectlist0-Decrease / 1-Increase [DPT_1.007]
Enable use of bit-type Mode objects (for control)listNo
Enable use of bit-type Mode objects (for status)listNo
Enable use of Text object for ModelistNo
ASCII strings shown in comm object "Status_ Mode Text"text<< 14-byte string values >>
> String when mode is AUTOtextAUTO
> String when mode is HEATtextHEAT
> String when mode is COOLtextCOOL
> String when mode is FANtextFAN
> String when mode is DRYtextDRY
Enable use of "POWERFUL" mode (AC feature)listNo
Enable use of "QUIET" mode (AC feature)listNo
Enable use of POWER modelistNo
> Action time for this mode (minutes)unsignedInt 1…18030
> Setpoint delta increase (HEAT) or decrease (COOL) (ºC)list2.0 ºC
> Fan Speed for this modelistFAN SPEED 5
Enable use of ECONOMY modelistNo
> Setpoint delta decrease (HEAT) or increase (COOL) (ºC)list2.0 ºC
> Fan Speed for this modelistFAN SPEED 1
Enable use of Sleep functionlistNo
> Sleep function switch-off timeout (minutes)unsignedInt 0…18060
Enable use of ADDITIONAL HEATING modelistNo
> Fan Speed for this modelistFAN SPEED AUTO
Enable use of ADDITIONAL COOLING modelistNo
Enable "Fan Speed Man/Auto" objects for Control and StatuslistNo
Available fanspeeds in Indoor Unit (see docum. for your indoor unit)unsignedInt 2…75
DPT object type for Fan SpeedlistScaling [DPT_5.001]
Enable use of +/- object for Fan SpeedlistNo
> DPT type for +/- Fan Speed objectlist0-Decrease / 1-Increase [DPT_1.007]
> Does +/- sequence include fan speed AUTO?listNo
> Rollover Speed at upper/lower limit (when controlling with +/- obj)listYes
Enable use of bit-type Fan Speed objects (for Control)listNo
Enable use of bit-type Fan Speed objects (for Status)listNo
Enable use of Text object for Fan SpeedlistNo
ASCII strings shown in comm object "Status_ Fan Speed Text"text<< 14-byte string values >>
> String when fan speed is AUTOtextAUTO
> String when fan speed is 1textSPEED 1
> String when fan speed is 2textSPEED 2
> String when fan speed is 3textSPEED 3
> String when fan speed is 4textSPEED 4
> String when fan speed is 5textSPEED 5
Indoor unit has Up-Down Vanes (see docum. for your indoor unit)listYes
Enable "Vanes U-D Man/Auto" objects (for Control and Status)listNo
DPT object type for Vanes Up-DownlistScaling [DPT_5.001]
Enable use of +/- object for Vanes U-DlistNo
> DPT type for +/- Vanes U-D objectlist0-Decrease / 1-Increase [DPT_1.007]
> Does +/- sequence include vanes Up-Down AUTO?listNo
> Rollover Vanes at upper/lower limit (when controlling with +/- obj)listYes
Enable use of bit-type Vanes U-D objects (for Control)listNo
Enable use of bit-type Vanes U-D objects (for Status)listNo
Enable use of Text object for Vanes U-DlistNo
ASCII strings shown in comm object "Status_ Vanes U-D Text"text<< 14-byte string values >>
> String when vanes U-D in AUTOtextU-D AUTO
> String when vanes U-D in POS 1textU-D POS 1
> String when vanes U-D in POS 2textU-D POS 2
> String when vanes U-D in POS 3textU-D POS 3
> String when vanes U-D in POS 4textU-D POS 4
> String when vanes U-D in POS 5textU-D POS 5
Indoor unit has Left-Right Vanes (see docum. for your indoor unit)listYes
Enable "Vanes L-R Man/Auto" objects (for Control and Status)listNo
DPT object type for Vanes Left-RightlistScaling [DPT_5.001]
Enable use of +/- object for Vanes L-RlistNo
> DPT type for +/- Vanes L-R objectlist0-Decrease / 1-Increase [DPT_1.007]
> Does +/- sequence include vanes Left-Right AUTO?listNo
Enable use of bit-type Vanes L-R objects (for Control)listNo
Enable use of bit-type Vanes L-R objects (for Status)listNo
Enable use of Text object for Vanes L-RlistNo
ASCII strings shown in comm object "Status_ Vanes L-R Text"text<< 14-byte string values >>
> String when vanes L-R in AUTOtextL-R AUTO
> String when vanes L-R in POS 1textL-R POS 1
> String when vanes L-R in POS 2textL-R POS 2
> String when vanes L-R in POS 3textL-R POS 3
> String when vanes L-R in POS 4textL-R POS 4
> String when vanes L-R in POS 5textL-R POS 5
Periodic sending of "Status_ AC Setp" (in seconds;0=No periodic sending)unsignedInt 0…2550
Enable use of +/- obj for Setpoint TemplistNo
> DPT type for +/- Setp Temp objectlist0-Decrease / 1-Increase [DPT_1.007]
> [+/-] step sizelist1.0 ºC
Enable limits on Control_ Setpoint objlistNo
> Lower limit (ºC)list16.0 ºC
> Upper limit (ºC)list30.0 ºC
Ambient temp. ref. is provided from KNX (carefully read User Guide if enabled)listNo
Enable use of sceneslistNo
Scenes can be stored from KNX buslistNo
Enable use of bit objects for scene executionlistNo
> Enable use of bit objects for storing scenes (from bus)listNo
Scene 1 presetlistNo
> Scene 1 / Value for On-Offlist(unchanged)
> Scene 1 / Value for Modelist(unchanged)
> Scene 1 / Value for Fan Speedlist(unchanged)
> Scene 1 / Value for Vanes U-D (if available)list(unchanged)
> Scene 1 / Value for Vanes L-R (if available)list(unchanged)
> Scene 1 / Value for Setpoint Templist(unchanged)
> Scene 1 / Value for Remote Locklist(unchanged)
Scene 2 presetlistNo
> Scene 2 / Value for On-Offlist(unchanged)
> Scene 2 / Value for Modelist(unchanged)
> Scene 2 / Value for Fan Speedlist(unchanged)
> Scene 2 / Value for Vanes U-D (if available)list(unchanged)
> Scene 2 / Value for Vanes L-R (if available)list(unchanged)
> Scene 2 / Value for Setpoint Templist(unchanged)
> Scene 2 / Value for Remote Locklist(unchanged)
Scene 3 presetlistNo
> Scene 3 / Value for On-Offlist(unchanged)
> Scene 3 / Value for Modelist(unchanged)
> Scene 3 / Value for Fan Speedlist(unchanged)
> Scene 3 / Value for Vanes U-D (if available)list(unchanged)
> Scene 3 / Value for Vanes L-R (if available)list(unchanged)
> Scene 3 / Value for Setpoint Templist(unchanged)
> Scene 3 / Value for Remote Locklist(unchanged)
Scene 4 presetlistNo
> Scene 4 / Value for On-Offlist(unchanged)
> Scene 4 / Value for Modelist(unchanged)
> Scene 4 / Value for Fan Speedlist(unchanged)
> Scene 4 / Value for Vanes U-D (if available)list(unchanged)
> Scene 4 / Value for Vanes L-R (if available)list(unchanged)
> Scene 4 / Value for Setpoint Templist(unchanged)
> Scene 4 / Value for Remote Locklist(unchanged)
Scene 5 presetlistNo
> Scene 5 / Value for On-Offlist(unchanged)
> Scene 5 / Value for Modelist(unchanged)
> Scene 5 / Value for Fan Speedlist(unchanged)
> Scene 5 / Value for Vanes U-D (if available)list(unchanged)
> Scene 5 / Value for Vanes L-R (if available)list(unchanged)
> Scene 5 / Value for Setpoint Templist(unchanged)
> Scene 5 / Value for Remote Locklist(unchanged)
Enable use of Open Window / Switch off timeout functionlistNo
> AC switch-off timeout (min)unsignedInt 0…3010
> DPT for Window / Switch-off timeoutlist0-Stop / 1-Start Timeout [DPT_1.010]
> Reload last On/Off val once window is ClosedlistNo
Enable use of Occupancy functionlistNo
> Timeout to apply action (minutes)unsignedInt 0…18020
> Action after timeout elapsedlistSwitch-Off AC
> Temp delta decrease (HEAT) or increase (COOL) (ºC)list2.0 ºC
> Enable secondary timeoutlistNo
> Timeout to apply action (min)unsignedInt 1…18020
> Action after timeout elapsedlistSwitch-Off AC
> Temp delta dec (HEAT) or inc (COOL) (ºC)list2.0 ºC
Enable object "Error Text Code [14byte]" (3 ASCII-char Error Code)listYes
Indoor unit has HEAT mode (see docum. for your indoor unit)listYes
> Disallow On/Off operation while window is OpenlistNo
> Disallow On/Off operation while timeout is elapsedlistNo
> Reload last On/Off val once timeout is stoppedlistNo
> Disallow On/Off operation while not OccupiedlistNo
> Reload last On/Off value when OccupiedlistNo
> Debounce timelist50 ms
> Contact typelistNO: Normally Open
> Disabling functionlistNo
> FunctionlistSwitching
> Sending delay after bus recovery (seconds)unsignedInt 0…25510
> Send telegram after bus recoverylistNo action
Indoor unit has FAN mode (see docum. for your indoor unit)listYes
> Value on raising edge (contact activated)listNo action
> Value on falling edge (contact deactivated)listNo action
> Period for cyclical sending (seconds)unsignedInt 1…6553510
> Cyclical sendinglistNever
> Scene when contact is activated (needs to be defined)listScene 1
> Setpoint temp for this mode (ºC)list20.0 ºC
> Setpoint temp for this mode (ºC)list30.0 ºC
Enable use of Input 1listNo
Enable use of Input 2listNo
Enable use of Input 3listNo
Enable use of Input 4listNo
> Reset Input when enablinglistNo
> Mode for short (long) operationlistToggle: On/Off (increase/decrease)
> Increasing steplist+ 25 %
> Decreasing steplist- 25 %
> Short/long operation limit (x100ms)unsignedInt 1…25510
> Cycl. send. period in long oper. (x100ms)(0-No cyclical send.)unsignedInt 0…2550
> OperationlistToggle (Up/Down)
> MethodlistStep-Move-Step
> Vanes adjustment time (x100ms)unsignedInt 1…25510
> DPT to be sentlistDPT 5.010 (1byte)
> Value on raising edge (when contact activated)unsignedInt 0…2550
> Value on raising edge (when contact activated)unsignedInt 0…655350
> Value on raising edge (when contact activated)signedInt -32768…327670
> Value on rais. edge (x0.1ºC) (when contact activated)signedInt -2730…3276250
> Value on raising edge (when contact activated)unsignedInt 0…42949672950
Enable use of Power ConsumptionlistNo
> Power threshold to update (W)unsignedInt 0…25550
> Power update timeout (s)unsignedInt 0…25530
> Energy update timeout (min)unsignedInt 0…2551
Etherea AC modellistCS-xyyMKE or CS-xyyNKE
Power consumption is not available for current AC model:textCS-xyyMKE or CS-xyyNKE

Version history

ApplicationApp noFingerprintFirst seenSizeFile
0106 PAACKNX1i T0CV15 1.5 latest$000C6F092026-11-25143 KBDownload

About this file

This is the official ETS product database for the Intesis PA AC interface, 4 binary inputs (PA-AC-KNX-1i), published by the manufacturer in the KNX online catalog. To use it, open ETS, go to Catalogs → Import and choose the downloaded .knxprod file. The device then appears in your catalog and can be added to a project. Older versions are kept so existing projects can be matched to the application program they were commissioned with.