Intesis ME-AC-KNX-1-V2 ME AC Interface

ME AC Interface ME-AC-KNX-1-V2

Intesis · Order number ME-AC-KNX-1-V2 · Communication › Interfaces › Mitsubishi Electric Air Conditioning Interfaces

Download .knxprod MEACKNX1V2 T05V10 1.0 · 89 KB

Product

ManufacturerIntesis
Product nameME AC Interface
Order numberME-AC-KNX-1-V2
HardwareME AC Interface
MediumTwisted Pair
Bus current (mA)6
Rail mountedNo
RegistrationCertified
Languageses-ES, en-US
Catalog entryM-0077_H-Y08M09-1_HP-0005-10-4640_CI-ME.2DAC.2DKNX.2D1.2DV2-2
Fingerprint4640
SHA-256d803e85b52dc47dbd3a7e8fa98bb188c90b06cc0dffb3d0bc11d0e95906ac58f
First seen2026-11-25
Markets69 markets

Application program: MEACKNX1V2 T05V10 1.0

Application number$0005
Version1.0
Mask versionMV-0025 (2.5)
KNX Data SecureNo
Minimum ETS version4.0
Parameters78
Group objects101
Group objects (101)
NoNameFunctionSizeDPTFlags
0Control_ On/Off [DPT_1.001]0-Off;1-On1 Bit1.1 switchCWT
1Control_ Mode [DPT_20.105]0-Aut;1-Hea;3-Coo;9-Fan;14-Dry1 Byte20.105 HVAC control modeCWT
2Control_ Mode Cool/Heat [DPT_1.100]0-Cool;1-Heat1 Bit1.100 heating/coolingCWT
3Control_ Mode Auto [DPT_1.002]1-Set AUTO mode1 Bit1.2 booleanCWT
4Control_ Mode Heat [DPT_1.002]1-Set HEAT mode1 Bit1.2 booleanCWT
5Control_ Mode Cool [DPT_1.002]1-Set COOL mode1 Bit1.2 booleanCWT
6Control_ Mode Fan [DPT_1.002]1-Set FAN mode1 Bit1.2 booleanCWT
7Control_ Mode Dry [DPT_1.002]1-Set DRY mode1 Bit1.2 booleanCWT
8Control_ Mode -/+ [DPT_1.007]0-Decrease;1-Increase1 Bit1.7 stepCW
8Control_ Mode +/- [DPT_1.008]0-Up;1-Down1 Bit1.8 up/downCW
9Control_ Fan Speed / 3 Speeds [DPT_5.010]Speed values: 1,2,31 Byte5.10 counter pulses (0..255)CWT
9Control_ Fan Speed / 2 Speeds [DPT_5.010]Speed values: 1,21 Byte5.10 counter pulses (0..255)CWT
9Control_ Fan Speed / 4 Speeds [DPT_5.010]Speed values: 1,2,3,41 Byte5.10 counter pulses (0..255)CWT
10Control_ Fan Speed / 3 Speeds [DPT_5.001]Thresholds: 50% and 83%1 Byte5.1 percentage (0..100%)CWT
10Control_ Fan Speed / 4 Speeds [DPT_5.001] Thresholds:38%, 63% and 88%1 Byte5.1 percentage (0..100%)CWT
10Control_ Fan Speed / 2 Speeds [DPT_5.001]Thresholds: 75%1 Byte5.1 percentage (0..100%)CWT
11Control_ Fan Speed Man/Auto [DPT_1.002]0-Manual;1-Auto1 Bit1.2 booleanCWT
12Control_ Fan Speed 1 [DPT_1.002]1-Set Fan Speed 11 Bit1.2 booleanCWT
13Control_ Fan Speed 2 [DPT_1.002]1-Set Fan Speed 21 Bit1.2 booleanCWT
14Control_ Fan Speed 3 [DPT_1.002]1-Set Fan Speed 31 Bit1.2 booleanCWT
15Control_ Fan Speed 4 [DPT_1.002]1-Set Fan Speed 41 Bit1.2 booleanCWT
16Control_ Fan Speed -/+ [DPT_1.007]0-Decrease;1-Increase1 Bit1.7 stepCW
16Control_ Fan Speed +/- [DPT_1.008]0-Up;1-Down1 Bit1.8 up/downCW
17Control_ Vanes U-D / 5 Pos [DPT_5.010]Position values: 1,2,3,4,51 Byte5.10 counter pulses (0..255)CWT
17Control_ Vanes U-D / 4 Pos [DPT_5.010]Position values: 1,2,3,41 Byte5.10 counter pulses (0..255)CWT
18Control_ Vanes U-D / 5 Pos [DPT_5.001]Thresholds:30%,50%,70% y 90%1 Byte5.1 percentage (0..100%)CWT
18Control_ Vanes U-D / 4 Pos [DPT_5.001]Thresholds: 38%,63% and 88%1 Byte5.1 percentage (0..100%)CWT
19Control_ Vanes U-D Man/Auto [DPT_1.002]0-Manual;1-Auto1 Bit1.2 booleanCWT
20Control_ Vanes U-D Pos 1 [DPT_1.002]1-Set Position 11 Bit1.2 booleanCWT
21Control_ Vanes U-D Pos 2 [DPT_1.002]1-Set Position 21 Bit1.2 booleanCWT
22Control_ Vanes U-D Pos 3 [DPT_1.002]1-Set Position 31 Bit1.2 booleanCWT
23Control_ Vanes U-D Pos 4 [DPT_1.002]1-Set Position 41 Bit1.2 booleanCWT
24Control_ Vanes U-D Pos 5 [DPT_1.002]1-Set Position 51 Bit1.2 booleanCWT
25Control_ Vanes U-D Swing [DPT_1.002]0-Off;1-Swing1 Bit1.2 booleanCWT
26Control_ Vanes U-D +/- [DPT_1.008]0-Up;1-Down1 Bit1.8 up/downCWT
26Control_ Vanes U-D -/+ [DPT_1.007]0-Decrease;1-Increase1 Bit1.7 stepCWT
27Control_ Setpoint Temperature [DPT_9.001](ºC)2 Bytes9.1 temperature (°C)CWT
28Control_ Setpoint Temperature -/+ [DPT_1.007]0-Decrease;1-Increase1 Bit1.7 stepCW
28Control_ Setpoint Temperature +/- [DPT_1.008]0-Up;1-Down1 Bit1.8 up/downCW
29Control_ Ambient Temperature [DPT_9.001](ºC)2 Bytes9.1 temperature (°C)CWT
30Control_ Operation Hour Counter [DPT_7.001]Number of operating hours2 Bytes7.7 time (h)CWT
31Control_ Operation Second Counter [DPT_13.100]Number of operating seconds4 Bytes13.100 time lag (s)CWT
32Control_ Window Contact Status [DPT_1.009]0-Open;1-Closed1 Bit1.9 open/closeCWT
33Control_ Lock Remote Control [DPT_1.002]0-Unlocked;1-Locked1 Bit1.2 booleanCWT
34Control_ Lock Control Objects [DPT_1.002]0-Unlocked;1-Locked1 Bit1.2 booleanCWT
35Control_ Store/Execute Scene [DPT_18.001]0..4-Exec1-5;128..132-Save1-51 Byte18.1 scene controlCWT
36Control_ Store Scene 1 [DPT_1.002]1-Store Scene 11 Bit1.2 booleanCW
37Control_ Store Scene 2 [DPT_1.002]1-Store Scene 21 Bit1.2 booleanCW
38Control_ Store Scene 3 [DPT_1.002]1-Store Scene 31 Bit1.2 booleanCW
39Control_ Store Scene 4 [DPT_1.002]1-Store Scene 41 Bit1.2 booleanCW
40Control_ Store Scene 5 [DPT_1.002]1-Store Scene 51 Bit1.2 booleanCW
41Control_ Execute Scene 1 [DPT_1.002]1-Execute Scene 11 Bit1.2 booleanCWT
42Control_ Execute Scene 2 [DPT_1.002]1-Execute Scene 21 Bit1.2 booleanCWT
43Control_ Execute Scene 3 [DPT_1.002]1-Execute Scene 31 Bit1.2 booleanCWT
44Control_ Execute Scene 4 [DPT_1.002]1-Execute Scene 41 Bit1.2 booleanCWT
45Control_ Execute Scene 5 [DPT_1.002]1-Execute Scene 51 Bit1.2 booleanCWT
46Status_ On/Off [DPT_1.001]0-Off;1-On1 Bit1.1 switchCRT
47Status_ Mode [DPT_20.105]0-Aut;1-Hea;3-Coo;9-Fan;14-Dry1 Byte20.105 HVAC control modeCRT
48Status_ Mode Cool/Heat [DPT_1.100]0-Cool;1-Heat1 Bit1.100 heating/coolingCRT
49Status_ Mode Auto [DPT_1.002]1-AUTO mode is active1 Bit1.2 booleanCRT
50Status_ Mode Heat [DPT_1.002]1-HEAT mode is active1 Bit1.2 booleanCRT
51Status_ Mode Cool [DPT_1.002]1-COOL mode is active1 Bit1.2 booleanCRT
52Status_ Mode Fan [DPT_1.002]1-FAN mode is active1 Bit1.2 booleanCRT
53Status_ Mode Dry [DPT_1.002]1-DRY mode is active1 Bit1.2 booleanCRT
54Status_ Mode Text [DPT_16.001]ASCII String14 Bytes16.1 Character String (ISO 8859-1)CRT
55Status_ Fan Speed / 3 Speeds [DPT_5.010]Speed Values: 1,2,31 Byte5.10 counter pulses (0..255)CRT
55Status_ Fan Speed / 2 Speeds [DPT_5.010]Speed Values: 1,21 Byte5.10 counter pulses (0..255)CRT
55Status_ Fan Speed / 4 Speeds [DPT_5.010]Speed Values: 1,2,3,41 Byte5.10 counter pulses (0..255)CRT
56Status_ Fan Speed / 2 Speeds [DPT_5.001]50% and 100%1 Byte5.1 percentage (0..100%)CRT
56Status_ Fan Speed / 4 Speeds [DPT_5.001]25%, 50%, 75% and 100%1 Byte5.1 percentage (0..100%)CRT
56Status_ Fan Speed / 3 Speeds [DPT_5.001]33%, 67% and 100%1 Byte5.1 percentage (0..100%)CRT
57Status_ Fan Speed Man/Auto [DPT_1.002]0-Manual;1-Auto1 Bit1.2 booleanCRT
58Status_ Fan Speed 1 [DPT_1.002]1-Fan in speed 11 Bit1.2 booleanCRT
59Status_ Fan Speed 2 [DPT_1.002]1-Fan in speed 21 Bit1.2 booleanCRT
60Status_ Fan Speed 3 [DPT_1.002]1-Fan in speed 31 Bit1.2 booleanCRT
61Status_ Fan Speed 4 [DPT_1.002]1-Fan in speed 41 Bit1.2 booleanCRT
62Status_ Fan Speed Text [DPT_16.001]ASCII String14 Bytes16.1 Character String (ISO 8859-1)CRT
63Status_ Vanes U-D / 5 pos [DPT_5.010]Position values: 1,2,3,4,51 Byte5.10 counter pulses (0..255)CRT
63Status_ Vanes U-D / 4 pos [DPT_5.010]Position values: 1,2,3,41 Byte5.10 counter pulses (0..255)CRT
64Status_ Vanes U-D / 5 pos [DPT_5.001]20%, 40, 60%, 80% and 100%1 Byte5.1 percentage (0..100%)CRT
64Status_ Vanes U-D / 4 pos [DPT_5.001]25%, 50, 75%, and 100%1 Byte5.1 percentage (0..100%)CRT
65Status_ Vanes U-D Man/Auto [DPT_1.002]0-Manual;1-Auto1 Bit1.2 booleanCRT
66Status_ Vanes U-D Pos 1 [DPT_1.002]1-Vanes in Position 11 Bit1.2 booleanCRT
67Status_ Vanes U-D Pos 2 [DPT_1.002]1-Vanes in Position 21 Bit1.2 booleanCRT
68Status_ Vanes U-D Pos 3 [DPT_1.002]1-Vanes in Position 31 Bit1.2 booleanCRT
69Status_ Vanes U-D Pos 4 [DPT_1.002]1-Vanes in Position 41 Bit1.2 booleanCRT
70Status_ Vanes U-D Pos 5 [DPT_1.002]1-Vanes in Position 51 Bit1.2 booleanCRT
71Status_ Vanes U-D Swing [DPT_1.002]0-Off;1-Swing1 Bit1.2 booleanCRT
72Status_ Vanes U-D Text [DPT_16.001]ASCII String14 Bytes16.1 Character String (ISO 8859-1)CRT
73Status_ AC Setpoint Temperature [DPT_9.001](ºC)2 Bytes9.1 temperature (°C)CRT
74Status_ AC Return Temperature [DPT_9.001](ºC)2 Bytes9.1 temperature (°C)CRT
75Status_ Error/Alarm [DPT_1.005]0-No alarm;1-Alarm1 Bit1.5 alarmCRT
76Status_ Error Code [2byte]AC Unit Error Code2 BytesDPT.8CRT
77Status_ Operation Hour Counter [DPT_7.001]Number of operating hours2 Bytes7.7 time (h)CRT
78Status_ Operation Second Counter [DPT_13.100]Number of operating seconds4 Bytes13.100 time lag (s)CRT
79Status_ Lock Remote Control [DPT_1.002]0-Unlocked;1-Locked1 Bit1.2 booleanCRT
80Status_ Lock Control Objects [DPT_1.002]0-Unlocked;1-Locked1 Bit1.2 booleanCRT
81Status_ Current Scene [DPT_17.001]0..4-Scene X+1;63-No Scene1 Byte17.1 scene numberCRT
82Legacy_ Mode [1byte]0-Aut;1-Hea,2-Dry,3-Fan;4-Coo1 ByteDPT.5CRWT
83Legacy_ Fan Speed [1byte]0 - Auto; 1..4 - speed 1..41 ByteDPT.5CRWT
84Legacy_ Vanes [1byte]0-Auto; 1..5-pos1..5; 6-Swing1 ByteDPT.5CRWT
Parameters (65)
ParameterTypeDefault
Download latest database entry for this product and its User Manual from:texthttp://www.intesisbox.com
Send READs for Control_ objects on bus recovery (T & U flags must be active)listNo
> Delay before sending READs (sec)unsignedInt 0…3010
Enable "Lock Remote Control" objectslistNo
Enable "Lock Control Objects" objectslistNo
Enable func "Operating Hours Counter"listNo
Enable object "Error Code [2byte]"listNo
Indoor unit has FAN mode (see docum. for your indoor unit)listYes
Enable "Mode Cool/Heat" objects (for Control and Status)listNo
Enable use of +/- object for ModelistNo
> DPT type for +/- Mode Objectlist0-Decrease / 1-Increase [DPT_1.007]
Enable use of bit-type Mode objects (for Control)listNo
Enable use of bit-type Mode objects (for Status)listNo
Enable use of Text object for ModelistNo
ASCII strings shown in comm object "Status_ Mode Text"text<< 14-byte string values >>
> String when mode is AUTOtextAUTO
> String when mode is HEATtextHEAT
> String when mode is COOLtextCOOL
> String when mode is FANtextFAN
> String when mode is DRYtextDRY
Enable use of Legacy_ object for Mode (compatible with old vers of XXACKNX1)listNo
Fan is accessible in Indoor unit (see docum. for your indoor unit)listYes
Available fanspeeds in Indoor Unit (see docum. for your indoor unit)unsignedInt 2…43
Indoor unit has AUTO fan speed (see docum. for your indoor unit)listNo
Enable use of +/- object for Fan SpeedlistNo
> DPT type for +/- Fan Speed objectlist0-Decrease / 1-Increase [DPT_1.007]
Enable "Fan Speed Man/Auto" objects (for Control and Status)listNo
Enable use of bit-type Fan Speed objects (for Control)listNo
Enable use of bit-type Fan Speed objects (for Status)listNo
Enable use of Text object for Fan SpeedlistNo
ASCII strings shown in comm object "Status_ Fan Speed Text"text<< 14-byte string values >>
> String when fan speed is AUTOtextAUTO
> String when fan speed is 1textSPEED 1
> String when fan speed is 2textSPEED 2
> String when fan speed is 3textSPEED 3
> String when fan speed is 4textSPEED 4
Enable use of Legacy_ object for Fan (compatible with old vers of XXACKNX1)listNo
Indoor unit has U-D Vanes (see docum. for your indoor unit)listNo
Available positions in Indoor Unit (see docum. for your indoor unit)unsignedInt 4…55
Indoor unit has AUTO Vanes U-D (see docum. for your indoor unit)listNo
Enable "Vanes U-D Swing" objects (for Control and Status)listNo
Enable "Vanes U-D Man/Auto" objects (for Control and Status)listNo
Enable use of +/- object for Vanes U-DlistNo
> DPT type for +/- Vanes U-D objectlist0-Decrease / 1-Increase [DPT_1.007]
Enable use of bit-type Vanes U-D objects (for Control)listNo
Enable use of bit-type Vanes U-D objects (for Status)listNo
Enable use of Text object for Vanes U-DlistNo
ASCII strings shown in comm object "Status_ Vanes U-D Text"text<< 14-byte string values >>
> String when vanes U-D in AUTOtextU-D AUTO
> String when vanes U-D in POS 1textU-D POS 1
> String when vanes U-D in POS 2textU-D POS 2
> String when vanes U-D in POS 3textU-D POS 3
> String when vanes U-D in POS 4textU-D POS 4
> String when vanes U-D in POS 5textU-D POS 5
> String when vanes U-D in SWINGtextU-D SWING
Enable use of Legacy_ object for Vanes (compatible with old vers of XXACKNX1)listNo
Enable use of +/- obj for Setpoint TemplistNo
> DPT type for +/- Setp Temp objectlist0-Decrease / 1-Increase [DPT_1.007]
Ambient temp. ref. is provided from KNX (carefully read User Guide if enabled)listNo
Enable use of sceneslistNo
Enable use of bit objects for storing sceneslistNo
Enable use of bit objects for scene executionlistNo
Enable use of Open Window functionlistNo
> AC switch-off timeout (min)unsignedInt 0…3010
> Reload last On/Off val once window is ClosedlistNo

Version history

ApplicationApp noFingerprintFirst seenSizeFile
MEACKNX1V2 T05V10 1.0 latest$000546402026-11-2589 KBDownload

About this file

This is the official ETS product database for the Intesis ME AC Interface (ME-AC-KNX-1-V2), published by the manufacturer in the KNX online catalog. To use it, open ETS, go to Catalogs → Import and choose the downloaded .knxprod file. The device then appears in your catalog and can be added to a project. Older versions are kept so existing projects can be matched to the application program they were commissioned with.