| 1 | Control_ On/Off [DPT_1.001] | 0-Off;1-On | 1 Bit | 1.1 switch | CWT |
| 2 | Control_ Mode [DPT_20.105] | 0-Aut;1-Hea;3-Coo;9-Fan;14-Dry | 1 Byte | 20.105 HVAC control mode | CWT |
| 3 | Control_ Mode Cool/Heat [DPT_1.100] | 0-Cool;1-Heat | 1 Bit | 1.100 heating/cooling | CWT |
| 4 | Control_ Mode Cool & On [DPT_5.001] | 0%-Off;0.1%-100%-On+Cool | 1 Byte | 5.1 percentage (0..100%) | CWT |
| 5 | Control_ Mode Heat & On [DPT_5.001 | 0%-Off;0.1%-100%-On+Heat | 1 Byte | 5.1 percentage (0..100%) | CWT |
| 6 | Control_ Mode Auto [DPT_1.002] | 1-Set AUTO mode | 1 Bit | 1.2 boolean | CWT |
| 7 | Control_ Mode Heat [DPT_1.002] | 1-Set HEAT mode | 1 Bit | 1.2 boolean | CWT |
| 8 | Control_ Mode Cool [DPT_1.002] | 1-Set COOL mode | 1 Bit | 1.2 boolean | CWT |
| 9 | Control_ Mode Fan [DPT_1.002] | 1-Set FAN mode | 1 Bit | 1.2 boolean | CWT |
| 10 | Control_ Mode Dry [DPT_1.002] | 1-Set DRY mode | 1 Bit | 1.2 boolean | CWT |
| 11 | Control_ Mode -/+ [DPT_1.007] | 0-Decrease;1-Increase | 1 Bit | 1.7 step | CW |
| 11 | Control_ Mode +/- [DPT_1.008] | 0-Up;1-Down | 1 Bit | 1.8 up/down | CW |
| 12 | Control_ Fan Speed [DPT_5.001] | Thresholds: 100*(n+0'5)/N % | 1 Byte | 5.1 percentage (0..100%) | CWT |
| 12 | Control_ Fan Speed [DPT_5.010] | Speed values: 1,2,3,... | 1 Byte | 5.10 counter pulses (0..255) | CWT |
| 13 | Control_ Fan Speed Man/Auto [DPT_1.002] | 0-Manual;1-Auto | 1 Bit | 1.2 boolean | CWT |
| 14 | Control_ Fan Speed 1 [DPT_1.002] | 1-Set Fan Speed 1 | 1 Bit | 1.2 boolean | CWT |
| 15 | Control_ Fan Speed 2 [DPT_1.002] | 1-Set Fan Speed 2 | 1 Bit | 1.2 boolean | CWT |
| 16 | Control_ Fan Speed 3 [DPT_1.002] | 1-Set Fan Speed 3 | 1 Bit | 1.2 boolean | CWT |
| 17 | Control_ Fan Speed 4 [DPT_1.002] | 1-Set Fan Speed 4 | 1 Bit | 1.2 boolean | CWT |
| 18 | Control_ Fan Speed 5 [DPT_1.002] | 1-Set Fan Speed 5 | 1 Bit | 1.2 boolean | CWT |
| 19 | Control_ Fan Speed 6 [DPT_1.002] | 1-Set Fan Speed 6 | 1 Bit | 1.2 boolean | CWT |
| 20 | Control_ Fan Speed 7 [DPT_1.002] | 1-Set Fan Speed 7 | 1 Bit | 1.2 boolean | CWT |
| 21 | Control_ Fan Speed -/+ [DPT_1.007] | 0-Decrease;1-Increase | 1 Bit | 1.7 step | CW |
| 21 | Control_ Fan Speed +/- [DPT_1.008] | 0-Up;1-Down | 1 Bit | 1.8 up/down | CW |
| 22 | Control_ Vanes U-D [DPT_5.010] | Position values: 1,2,3,... | 1 Byte | 5.10 counter pulses (0..255) | CWT |
| 22 | Control_ Vanes U-D [DPT_5.001] | Thresholds: 100*(n+0'5)/N % | 1 Byte | 5.1 percentage (0..100%) | CWT |
| 23 | Control_ Vanes U-D Man/Auto [DPT_1.002] | 0-Manual;1-Auto | 1 Bit | 1.2 boolean | CWT |
| 24 | Control_ Vanes U-D Pos 1 [DPT_1.002] | 1-Set Position 1 | 1 Bit | 1.2 boolean | CWT |
| 25 | Control_ Vanes U-D Pos 2 [DPT_1.002] | 1-Set Position 2 | 1 Bit | 1.2 boolean | CWT |
| 26 | Control_ Vanes U-D Pos 3 [DPT_1.002] | 1-Set Position 3 | 1 Bit | 1.2 boolean | CWT |
| 27 | Control_ Vanes U-D Pos 4 [DPT_1.002] | 1-Set Position 4 | 1 Bit | 1.2 boolean | CWT |
| 28 | Control_ Vanes U-D Pos 5 [DPT_1.002] | 1-Set Position 5 | 1 Bit | 1.2 boolean | CWT |
| 29 | Control_ Vanes U-D Pos 6 [DPT_1.002] | 1-Set Position 6 | 1 Bit | 1.2 boolean | CWT |
| 30 | Control_ Vanes U-D Pos 7 [DPT_1.002] | 1-Set Position 7 | 1 Bit | 1.2 boolean | CWT |
| 31 | Control_ Vanes U-D Pos 8 [DPT_1.002] | 1-Set Position 8 | 1 Bit | 1.2 boolean | CWT |
| 32 | Control_ Vanes U-D Swing [DPT_1.002] | 0-Stop;1-Swing | 1 Bit | 1.2 boolean | CWT |
| 33 | Control_ Vanes U-D Swirl [DPT_1.002] | 0-Stop;1-Swirl | 1 Bit | 1.2 boolean | CWT |
| 34 | Control_ Vanes U-D Wide [DPT_1.002] | 0-Stop;1-Wide | 1 Bit | 1.2 boolean | CWT |
| 35 | Control_ Vanes U-D -/+ [DPT_1.007] | 0-Decrease;1-Increase | 1 Bit | 1.7 step | CW |
| 35 | Control_ Vanes U-D +/- [DPT_1.008] | 0-Up;1-Down | 1 Bit | 1.8 up/down | CW |
| 36 | Control_ Vanes U-D Move Pos [DPT_1.017] | 0,1-Move Position | 1 Bit | 1.17 trigger | CWT |
| 37 | Control_ Vanes L-R [DPT_5.010] | Position values: 1,2,3,... | 1 Byte | 5.10 counter pulses (0..255) | CWT |
| 37 | Control_ Vanes L-R [DPT_5.001] | Thresholds: 100*(n+0'5)/N % | 1 Byte | 5.1 percentage (0..100%) | CWT |
| 38 | Control_ Vanes L-R Man/Auto [DPT_1.002] | 0-Manual;1-Auto | 1 Bit | 1.2 boolean | CWT |
| 39 | Control_ Vanes L-R Pos 1 [DPT_1.002] | 1-Set Position 1 | 1 Bit | 1.2 boolean | CWT |
| 40 | Control_ Vanes L-R Pos 2 [DPT_1.002] | 1-Set Position 2 | 1 Bit | 1.2 boolean | CWT |
| 41 | Control_ Vanes L-R Pos 3 [DPT_1.002] | 1-Set Position 3 | 1 Bit | 1.2 boolean | CWT |
| 42 | Control_ Vanes L-R Pos 4 [DPT_1.002] | 1-Set Position 4 | 1 Bit | 1.2 boolean | CWT |
| 43 | Control_ Vanes L-R Pos 5 [DPT_1.002] | 1-Set Position 5 | 1 Bit | 1.2 boolean | CWT |
| 44 | Control_ Vanes L-R Pos 6 [DPT_1.002] | 1-Set Position 6 | 1 Bit | 1.2 boolean | CWT |
| 45 | Control_ Vanes L-R Pos 7 [DPT_1.002] | 1-Set Position 7 | 1 Bit | 1.2 boolean | CWT |
| 46 | Control_ Vanes L-R Pos 8 [DPT_1.002] | 1-Set Position 8 | 1 Bit | 1.2 boolean | CWT |
| 47 | Control_ Vanes L-R Swing [DPT_1.002] | 0-Stop;1-Swing | 1 Bit | 1.2 boolean | CWT |
| 48 | Control_ Vanes L-R Swirl [DPT_1.002] | 0-Stop;1-Swirl | 1 Bit | 1.2 boolean | CWT |
| 49 | Control_ Vanes L-R Wide [DPT_1.002] | 0-Stop;1-Wide | 1 Bit | 1.2 boolean | CWT |
| 50 | Control_ Vanes L-R -/+ [DPT_1.007] | 0-Decrease;1-Increase | 1 Bit | 1.7 step | CW |
| 50 | Control_ Vanes L-R +/- [DPT_1.008] | 0-Up;1-Down | 1 Bit | 1.8 up/down | CW |
| 51 | Control_ Vanes L-R Move Pos [DPT_1.017] | 0,1-Move Position | 1 Bit | 1.17 trigger | CWT |
| 52 | Control_ Setpoint Temperature [DPT_9.001] | ºC | 2 Bytes | 9.1 temperature (°C) | CWT |
| 53 | Control_ Setpoint Temp -/+ [DPT_1.007] | 0-Decrease;1-Increase | 1 Bit | 1.7 step | CW |
| 53 | Control_ Setpoint Temp +/- [DPT_1.008] | 0-Up;1-Down | 1 Bit | 1.8 up/down | CW |
| 54 | Control_ Ambient Temperature [DPT_9.001] | ºC | 2 Bytes | 9.1 temperature (°C) | CWT |
| 55 | Control_ Window Contact Input [DPT_1.009] | 0-Open;1-Closed | 1 Bit | 1.9 open/close | CWT |
| 55 | Control_ Window Contact Input [DPT_1.019] | 0-Closed;1-Open | 1 Bit | 1.19 window/door | CWT |
| 56 | Control_ Occupancy Input [DPT_1.018] | 0-Not Occupied;1-Occupied | 1 Bit | 1.18 occupancy | CWT |
| 57 | Control_ Sleep Timeout [DPT_1.010] | 0-Stop;1-Start | 1 Bit | 1.10 start/stop | CWT |
| 58 | Control_ Lock Remote Control [DPT_1.002] | 0-Unlock;1-Lock | 1 Bit | 1.2 boolean | CWT |
| 59 | Control_ Lock Control Objects [DPT_1.002] | 0-Unlock;1-Lock | 1 Bit | 1.2 boolean | CWT |
| 60 | Control_ Operating Hour Counter [DPT_7.007] | Number of operating hours | 2 Bytes | 7.7 time (h) | CWT |
| 61 | Control_ Operating Second Counter [DPT_13.100] | Number of operating seconds | 4 Bytes | 13.100 time lag (s) | CWT |
| 62 | Control_ Execute Scene [DPT_17.001] | 0..4-Exec1-5 | 1 Byte | 17.1 scene number | CWT |
| 62 | Control_ Save/Execute Scene [DPT_18.001] | 0..4-Exec1-5;128..132-Save1-5 | 1 Byte | 18.1 scene control | CWT |
| 63 | Control_ Save Scene 1 [DPT_1.002] | 1-Save Scene 1 | 1 Bit | 1.2 boolean | CWT |
| 64 | Control_ Save Scene 2 [DPT_1.002] | 1-Save Scene 2 | 1 Bit | 1.2 boolean | CWT |
| 65 | Control_ Save Scene 3 [DPT_1.002] | 1-Save Scene 3 | 1 Bit | 1.2 boolean | CWT |
| 66 | Control_ Save Scene 4 [DPT_1.002] | 1-Save Scene 4 | 1 Bit | 1.2 boolean | CWT |
| 67 | Control_ Save Scene 5 [DPT_1.002] | 1-Save Scene 5 | 1 Bit | 1.2 boolean | CWT |
| 68 | Control_ Execute Scene 1 [DPT_1.002] | 1-Execute Scene 1 | 1 Bit | 1.2 boolean | CWT |
| 69 | Control_ Execute Scene 2 [DPT_1.002] | 1-Execute Scene 2 | 1 Bit | 1.2 boolean | CWT |
| 70 | Control_ Execute Scene 3 [DPT_1.002] | 1-Execute Scene 3 | 1 Bit | 1.2 boolean | CWT |
| 71 | Control_ Execute Scene 4 [DPT_1.002] | 1-Execute Scene 4 | 1 Bit | 1.2 boolean | CWT |
| 72 | Control_ Execute Scene 5 [DPT_1.002] | 1-Execute Scene 5 | 1 Bit | 1.2 boolean | CWT |
| 73 | Control_ Disable Input 1 [DPT_1.002] | 0-False;1-True | 1 Bit | 1.2 boolean | CWT |
| 73 | Control_ Disable Input 1 [DPT_1.003] | 0-Disable;1-Enable | 1 Bit | 1.3 enable | CWT |
| 74 | Control_ Disable Input 2 [DPT_1.002] | 0-False;1-True | 1 Bit | 1.2 boolean | CWT |
| 74 | Control_ Disable Input 2 [DPT_1.003] | 0-Disable;1-Enable | 1 Bit | 1.3 enable | CWT |
| 75 | Status_ On/Off [DPT_1.001] | 0-Off;1-On | 1 Bit | 1.1 switch | CRT |
| 76 | Status_ Mode [DPT_20.105] | 0-Aut;1-Hea;3-Coo;9-Fan;14-Dry | 1 Byte | 20.105 HVAC control mode | CRT |
| 77 | Status_ Mode Cool/Heat [DPT_1.100] | 0-Cool;1-Heat | 1 Bit | 1.100 heating/cooling | CRT |
| 78 | Status_ Mode Auto [DPT_1.002] | 1-AUTO mode is active | 1 Bit | 1.2 boolean | CRT |
| 79 | Status_ Mode Heat [DPT_1.002] | 1-HEAT mode is active | 1 Bit | 1.2 boolean | CRT |
| 80 | Status_ Mode Cool [DPT_1.002] | 1-COOL mode is active | 1 Bit | 1.2 boolean | CRT |
| 81 | Status_ Mode Fan [DPT_1.002] | 1-FAN mode is active | 1 Bit | 1.2 boolean | CRT |
| 82 | Status_ Mode Dry [DPT_1.002] | 1-DRY mode is active | 1 Bit | 1.2 boolean | CRT |
| 83 | Status_ Mode Text [DPT_16.001] | ASCII String | 14 Bytes | 16.1 Character String (ISO 8859-1) | CRT |
| 84 | Status_ Fan Speed [DPT_5.001] | 100*n/N % | 1 Byte | 5.1 percentage (0..100%) | CRT |
| 84 | Status_ Fan Speed [DPT_5.010] | Speed values: 1,2,3,... | 1 Byte | 5.10 counter pulses (0..255) | CRT |
| 85 | Status_ Fan Speed Man/Auto [DPT_1.002] | 0-Manual;1-Auto | 1 Bit | 1.2 boolean | CRT |
| 86 | Status_ Fan Speed 1 [DPT_1.002] | 1-Fan in Speed 1 | 1 Bit | 1.2 boolean | CRT |
| 87 | Status_ Fan Speed 2 [DPT_1.002] | 1-Fan in Speed 2 | 1 Bit | 1.2 boolean | CRT |
| 88 | Status_ Fan Speed 3 [DPT_1.002] | 1-Fan in Speed 3 | 1 Bit | 1.2 boolean | CRT |
| 89 | Status_ Fan Speed 4 [DPT_1.002] | 1-Fan in Speed 4 | 1 Bit | 1.2 boolean | CRT |
| 90 | Status_ Fan Speed 5 [DPT_1.002] | 1-Fan in Speed 5 | 1 Bit | 1.2 boolean | CRT |
| 91 | Status_ Fan Speed 6 [DPT_1.002] | 1-Fan in Speed 6 | 1 Bit | 1.2 boolean | CRT |
| 92 | Status_ Fan Speed 7 [DPT_1.002] | 1-Fan in Speed 7 | 1 Bit | 1.2 boolean | CRT |
| 93 | Status_ Fan Speed Text [DPT_16.001] | ASCII String | 14 Bytes | 16.1 Character String (ISO 8859-1) | CRT |
| 94 | Status_ Vanes U-D [DPT_5.010] | Position values: 1,2,3,... | 1 Byte | 5.10 counter pulses (0..255) | CRT |
| 94 | Status_ Vanes U-D [DPT_5.001] | 100*n/N % | 1 Byte | 5.1 percentage (0..100%) | CRT |
| 95 | Status_ Vanes U-D Man/Auto [DPT_1.002] | 0-Manual;1-Auto | 1 Bit | 1.2 boolean | CRT |
| 96 | Status_ Vanes U-D Pos 1 [DPT_1.002] | 1-Vanes in Position 1 | 1 Bit | 1.2 boolean | CRT |
| 97 | Status_ Vanes U-D Pos 2 [DPT_1.002] | 1-Vanes in Position 2 | 1 Bit | 1.2 boolean | CRT |
| 98 | Status_ Vanes U-D Pos 3 [DPT_1.002] | 1-Vanes in Position 3 | 1 Bit | 1.2 boolean | CRT |
| 99 | Status_ Vanes U-D Pos 4 [DPT_1.002] | 1-Vanes in Position 4 | 1 Bit | 1.2 boolean | CRT |
| 100 | Status_ Vanes U-D Pos 5 [DPT_1.002] | 1-Vanes in Position 5 | 1 Bit | 1.2 boolean | CRT |
| 101 | Status_ Vanes U-D Pos 6 [DPT_1.002] | 1-Vanes in Position 6 | 1 Bit | 1.2 boolean | CRT |
| 102 | Status_ Vanes U-D Pos 7 [DPT_1.002] | 1-Vanes in Position 7 | 1 Bit | 1.2 boolean | CRT |
| 103 | Status_ Vanes U-D Pos 8 [DPT_1.002] | 1-Vanes in Position 8 | 1 Bit | 1.2 boolean | CRT |
| 104 | Status_ Vanes U-D Swing [DPT_1.002] | 0-Stop;1-Swing | 1 Bit | 1.2 boolean | CRT |
| 105 | Status_ Vanes U-D Swirl [DPT_1.002] | 0-Stop;1-Swirl | 1 Bit | 1.2 boolean | CRT |
| 106 | Status_ Vanes U-D Wide [DPT_1.002] | 0-Stop;1-Wide | 1 Bit | 1.2 boolean | CRT |
| 107 | Status_ Vanes U-D Text [DPT_16.001] | ASCII String | 14 Bytes | 16.1 Character String (ISO 8859-1) | CRT |
| 108 | Status_ Vanes L-R [DPT_5.010] | Position values: 1,2,3,... | 1 Byte | 5.10 counter pulses (0..255) | CRT |
| 108 | Status_ Vanes L-R [DPT_5.001] | 100*n/N % | 1 Byte | 5.1 percentage (0..100%) | CRT |
| 109 | Status_ Vanes L-R Man/Auto [DPT_1.002] | 0-Manual;1-Auto | 1 Bit | 1.2 boolean | CRT |
| 110 | Status_ Vanes L-R Pos 1 [DPT_1.002] | 1-Vanes in Position 1 | 1 Bit | 1.2 boolean | CRT |
| 111 | Status_ Vanes L-R Pos 2 [DPT_1.002] | 1-Vanes in Position 2 | 1 Bit | 1.2 boolean | CRT |
| 112 | Status_ Vanes L-R Pos 3 [DPT_1.002] | 1-Vanes in Position 3 | 1 Bit | 1.2 boolean | CRT |
| 113 | Status_ Vanes L-R Pos 4 [DPT_1.002] | 1-Vanes in Position 4 | 1 Bit | 1.2 boolean | CRT |
| 114 | Status_ Vanes L-R Pos 5 [DPT_1.002] | 1-Vanes in Position 5 | 1 Bit | 1.2 boolean | CRT |
| 115 | Status_ Vanes L-R Pos 6 [DPT_1.002] | 1-Vanes in Position 6 | 1 Bit | 1.2 boolean | CRT |
| 116 | Status_ Vanes L-R Pos 7 [DPT_1.002] | 1-Vanes in Position 7 | 1 Bit | 1.2 boolean | CRT |
| 117 | Status_ Vanes L-R Pos 8 [DPT_1.002] | 1-Vanes in Position 8 | 1 Bit | 1.2 boolean | CRT |
| 118 | Status_ Vanes L-R Swing [DPT_1.002] | 0-Stop;1-Swing | 1 Bit | 1.2 boolean | CRT |
| 119 | Status_ Vanes L-R Swirl [DPT_1.002] | 0-Stop;1-Swirl | 1 Bit | 1.2 boolean | CRT |
| 120 | Status_ Vanes L-R Wide [DPT_1.002] | 0-Stop;1-Wide | 1 Bit | 1.2 boolean | CRT |
| 121 | Status_ Vanes L-R Text [DPT_16.001] | ASCII String | 14 Bytes | 16.1 Character String (ISO 8859-1) | CRT |
| 122 | Status_ AC Setpoint Temperature [DPT_9.001] | ºC | 2 Bytes | 9.1 temperature (°C) | CRT |
| 123 | Status_ IntesisBox Ambient Temperature [DPT_9.001] | ºC | 2 Bytes | 9.1 temperature (°C) | CRT |
| 124 | Status_ IntesisBox Reference Temperature [DPT_9.001] | ºC | 2 Bytes | 9.1 temperature (°C) | CRT |
| 125 | Status_ Error/Alarm [DPT_1.005] | 0-No alarm;1-Alarm | 1 Bit | 1.5 alarm | CRT |
| 126 | Status_ Error Code [2-byte signed value] | Error Code | 2 Bytes | 8.1 pulses difference | CRT |
| 127 | Status_ Error Text [DPT_16.001] | Error Text | 14 Bytes | 16.1 Character String (ISO 8859-1) | CRT |
| 128 | Status_ Window Contact Sensor [DPT_1.009] | 0-Open;1-Closed | 1 Bit | 1.9 open/close | CRT |
| 128 | Status_ Window Contact Sensor [DPT_1.019] | 0-Closed;1-Open | 1 Bit | 1.19 window/door | CRT |
| 129 | Status_ Window Contact Step [1-byte unsigned value] | 0-Closed;1-Open;2-Off | 1 Byte | 5.10 counter pulses (0..255) | CRT |
| 130 | Status_ Occupancy Sensor [DPT_1.018] | 0-Unoccupied;1-Occupied | 1 Bit | 1.18 occupancy | CRT |
| 131 | Status_ Occupancy Mode [DPT_20.003] | 0-Occupied;1-Standby;2-Not occupied | 1 Byte | 20.3 occupied | CRT |
| 132 | Status_ Occupancy Step [1-byte unsigned value] | 0-Occupied;1-Timeout;2-Action1;3-Action2 | 1 Byte | 5.10 counter pulses (0..255) | CRT |
| 133 | Status_ Lock Remote Control [DPT_1.002] | 0-Unlocked;1-Locked | 1 Bit | 1.2 boolean | CRT |
| 134 | Status_ Lock Control Objects [DPT_1.002] | 0-Unlocked;1-Locked | 1 Bit | 1.2 boolean | CRT |
| 135 | Status_ Operating Hour Counter [DPT_7.007] | Number of operating hours | 2 Bytes | 7.7 time (h) | CRT |
| 136 | Status_ Operating Second Counter [DPT_13.100] | Number of operating seconds | 4 Bytes | 13.100 time lag (s) | CRT |
| 137 | Status_ Current Scene [DPT_17.001] | 0..4-Scene X+1;63-No Scene | 1 Byte | 17.1 scene number | CRT |
| 138 | Status_ In1 - Switching [DPT_1.001] | 0-Off;1-On | 1 Bit | 1.1 switch | CRT |
| 139 | Status_ In1 - Dimming - On/Off [DPT_1.001] | 0-Off;1-On | 1 Bit | 1.1 switch | CRT |
| 140 | Status_ In1 - Dimming - Step(%) [DPT_3.007] | Dimming step | 4 Bit | 3.7 dimming control | CRT |
| 141 | Status_ In1 - Shut/Blind - Step [DPT_1.007] | 0-Step Up;1-Step Down | 1 Bit | 1.7 step | CRT |
| 142 | Status_ In1 - Shut/Blind - Move [DPT_1.008] | 0-Move Up;1-Move Down | 1 Bit | 1.8 up/down | CRT |
| 143 | Status_ In1 - Value [DPT_5.010] | 1-byte unsigned value | 1 Byte | 5.10 counter pulses (0..255) | CRT |
| 144 | Status_ In1 - Value [DPT_7.001] | 2-byte unsigned value | 2 Bytes | 7.1 pulses | CRT |
| 145 | Status_ In1 - Value [DPT_8.001] | 2-byte signed value | 2 Bytes | 8.1 pulses difference | CRT |
| 146 | Status_ In1 - Value [DPT_9.001] | Temperature (ºC) | 2 Bytes | 9.1 temperature (°C) | CRT |
| 147 | Status_ In1 - Value [DPT_12.001] | 4-byte unsigned value | 4 Bytes | 12.1 counter pulses (unsigned) | CRT |
| 148 | Status_ In2 - Switching [DPT_1.001] | 0-Off;1-On | 1 Bit | 1.1 switch | CRT |
| 149 | Status_ In2 - Dimming - On/Off [DPT_1.001] | 0-Off;1-On | 1 Bit | 1.1 switch | CRT |
| 150 | Status_ In2 - Dimming - Step(%) [DPT_3.007] | Dimming step | 4 Bit | 3.7 dimming control | CRT |
| 151 | Status_ In2 - Shut/Blind - Step [DPT_1.007] | 0-Step Up;1-Step Down | 1 Bit | 1.7 step | CRT |
| 152 | Status_ In2 - Shut/Blind - Move [DPT_1.008] | 0-Move Up;1-Move Down | 1 Bit | 1.8 up/down | CRT |
| 153 | Status_ In2 - Value [DPT_5.010] | 1-byte unsigned value | 1 Byte | 5.10 counter pulses (0..255) | CRT |
| 154 | Status_ In2 - Value [DPT_7.001] | 2-byte unsigned value | 2 Bytes | 7.1 pulses | CRT |
| 155 | Status_ In2 - Value [DPT_8.001] | 2-byte signed value | 2 Bytes | 8.1 pulses difference | CRT |
| 156 | Status_ In2 - Value [DPT_9.001] | Temperature (ºC) | 2 Bytes | 9.1 temperature (°C) | CRT |
| 157 | Status_ In2 - Value [DPT_12.001] | 4-byte unsigned value | 4 Bytes | 12.1 counter pulses (unsigned) | CRT |