| Light sensor | list | disabled |
| Temperature sensor | list | enabled |
| Rocker 1 | list | independent or single |
| Rocker 2 | list | copy parameters from rocker 1 |
| Input 1 | list | disabled |
| Led intensity correlation | list | none |
| Minimum change of value to send [Lux] | float 0…670760 | 50 |
| Cyclic sending interval | list | no sending |
| Minimum change of value to send [K] | float 0…5 | 0.5 |
| Delay after bus voltage recovery | time | 400 |
| Function A | list | enabled |
| Long press time | time | 300 |
| Lock function | list | disabled |
| Invert lock device signal | list | not inverted |
| Lock after bus recovery | list | no |
| Type | list | send values or sequences |
| Number of Communication Objects | unsignedInt 1…8 | 1 |
| Event | list | activation / release |
| Behaviour at locking | list | none |
| Behaviour at unlocking | list | none |
| Send cyclically | list | none |
| Cyclic sending interval | list | 5 min |
| Send delay | time | 0 |
| Communication object dimension | list | 1 bit value |
| Reaction to activation | list | toggle |
| Reaction to release | list | off |
| Reaction to short press | list | toggle |
| Reaction to long press | list | off |
| Reaction to activation | list | enable on / down |
| Reaction to release | list | disable |
| Reaction to short press | list | enable on / down |
| Reaction to long press | list | disable |
| Reaction to activation | list | send value 1 |
| Reaction to release | list | none |
| Reaction to short press | list | send value 1 |
| Reaction to long press | list | none |
| Value 1 | unsignedInt 0…255 | 0 |
| Value 2 | unsignedInt 0…255 | 0 |
| Value 1 | signedInt -128…127 | 0 |
| Value 2 | signedInt -128…127 | 0 |
| Value 1 | unsignedInt 0…65535 | 0 |
| Value 2 | unsignedInt 0…65535 | 0 |
| Value 1 | signedInt -32768…32767 | 0 |
| Value 2 | signedInt -32768…32767 | 0 |
| Value 1 | float -671088.64…670760.96 | 0 |
| Value 2 | float -671088.64…670760.96 | 0 |
| Reaction to activation | list | on |
| Reaction to short press | list | on |
| Toggle mode | list | enabled |
| Short / long action | list | off / darker |
| Up / down action | list | up |
| Venetian blind mode | list | disabled |
| Learning mode | list | disabled |
| Scene activation | list | send first scene only |
| First scene number | unsignedInt 1…64 | 1 |
| Second scene number | unsignedInt 1…64 | 2 |
| Function B | list | copy parameters from function A |
| Type | list | dimming |
| 1A and 1B use | list | A increases, B decreases |
| 1A and 1B use | list | A up, B down |
| Leds intensity from bus | list | no |
| Leds intensity | list | 50 % |
| Led first color 1A | list | when contact closed |
| Blinking | list | no |
| Signal from bus | list | not inverted |
| Always | list | off |
| Off delay | time | 20 |
| Blinking period / type | list | 1 s on, 1 s off |
| 1A and 1B use | list | A on, B off |
| Led second color 1A | list | when contact closed |
| Led second color 1B | list | when contact closed |
| Led first color 1B | list | when contact closed |
| 2A and 2B use | list | A on, B off |
| 2A and 2B use | list | A increases, B decreases |
| 2A and 2B use | list | A up, B down |
| Led first color 2A | list | when contact closed |
| Led second color 2A | list | when contact closed |
| Led first color 2B | list | when contact closed |
| Led second color 2B | list | when contact closed |
| Value [Lux] | float 0…670760 | 500 |
| Hysteresis | list | 50 lux |
| Threshold 1 | list | not active |
| Threshold 2 | list | not active |
| Sensor value multiplier (1 ÷ 255) x 0.1 | unsignedInt 1…255 | 10 |
| Reaction to long press | list | darker |
| Temperature offset | list | 0.0 °C |
| Technical alarm | list | disabled |
| Value 1 | unsignedInt 0…100 | 0 |
| Value 2 | unsignedInt 0…100 | 0 |
| Input 2 | list | disabled |
| Contact type | list | NO (normally open) |
| Relative humidity sensor | list | disabled |
| Value [°C] | float 0…50 | 45 |
| Value [°C] | float 0…50 | 7 |
| Hysteresis | list | 0.4 K |
| Value [%] | unsignedInt 0…100 | 65 |
| Hysteresis [%] | list | 3.0 % |
| Minimum change of value to send [%] | unsignedInt 0…10 | 2 |
| Temperature displayed unit | list | Celsius |
| Default displayed information | list | actual temperature |
| Time to return to default display | list | 5 s |
| Button function level | list | system integrator |
| Time to exit change without saving | list | 10 s |
| Debounce time | time | 20 |
| Digital sensors timeout | time | 300 |
| Room temperature | list | disabled |
| Relative humidity | list | disabled |
| Antistratification temperature | list | disabled |
| Outdoor temperature | list | disabled |
| Air quality | list | disabled |
| Coil temperature | list | disabled |
| Floor surface temperature | list | disabled |
| Flow temperature | list | disabled |
| Window contact 1 | list | disabled |
| Window contact 2 | list | disabled |
| Presence sensor 1 | list | disabled |
| Presence sensor 2 | list | disabled |
| Card holder contact | list | disabled |
| Humidity CO dimension | list | 2 bytes |
| Main source for temperature value | list | internal sensor |
| Additional source temperature value | list | internal sensor |
| Relative weight | list | 50% / 50% |
| Filter type | list | medium |
| Main source for temperature value | list | input |
| Additional source temperature value | list | input |
| Additional source temperature value | list | from bus |
| Thermostat function | list | heating |
| Anticondensation | list | disabled |
| Heating - cooling switch over | list | from bus |
| Heating - cooling cyclic sending interval | list | no sending |
| Max manual temperature change | list | ±3 °C |
| Max setpoint temperature change | list | ±9 °C |
| Setpoint cyclic sending interval | list | no sending |
| Scenes | list | disabled |
| Comfort temp. setpoint [°C] | float 10…50 | 21 |
| Standby temperature setpoint [°C] | float 10…50 | 18 |
| Economy temp. setpoint [°C] | float 10…50 | 16 |
| Building protection temp. setpoint [°C] | float 2…10 | 7 |
| Control type | list | 2 points hysteresis |
| Command Communication Object | list | separated |
| Hysteresis | list | 0.3 K |
| PWM cycle time | time | 15 |
| Proportional band [0.1K] | unsignedInt 5…100 | 40 |
| Integral time [min] | unsignedInt 0…255 | 90 |
| Valve protection function | list | disabled |
| Frequency | list | once a week |
| Time interval | list | 10 s |
| Floor temperature limitation | list | disabled |
| Temperature limit [°C] | float 20…40 | 29 |
| Auxiliary heating | list | disabled |
| Communication object | list | separated |
| Offset from setpoint | list | 0.6 K |
| Disabled from bus | list | no |
| Ventilation for auxiliary heating | list | disabled |
| Comfort temp. setpoint [°C] | float 10…50 | 23 |
| Standby temperature setpoint [°C] | float 10…50 | 26 |
| Economy temp. setpoint [°C] | float 10…50 | 28 |
| Building protection temp. setpoint [°C] | float 30…50 | 36 |
| Cooling type | list | fancoils |
| Auxiliary cooling | list | disabled |
| Anticondensation with probe | list | disabled |
| Active anticondensation | list | disabled |
| Min. change of value to send [%] | unsignedInt 0…100 | 10 |
| Anticondensation hysteresis range | list | 0.5 K |
| Control type | list | 1 speed |
| Threshold first speed [0.1K] | unsignedInt 0…255 | 0 |
| Threshold second speed [0.1K] | unsignedInt 0…255 | 10 |
| Threshold third speed [0.1K] | unsignedInt 0…255 | 20 |
| Manual operation | list | not depending on the temperature |
| Hot start | list | no |
| Use coil battery temperature sensor for dehumidification | list | no |
| Speed control hysteresis | list | 0.3 K |
| Speed proportional band [0.1K] | unsignedInt 5…100 | 30 |
| Min. change of value to send [%] | unsignedInt 2…40 | 10 |
| Min. temp. to start ventilation [°C] | unsignedInt 28…40 | 28 |
| Min. temp. to start dehumidif. [°C] | unsignedInt 0…255 | 10 |
| Relative humidity setpoint [%] | unsignedInt 0…100 | 65 |
| Relative humidity setpoint [%] | list | 0.6 % |
| Max. temp. diff. to disable dehum. [°C] | float 0…50 | 0.5 |
| Forced speed | list | 1 speed |
| Forced speed | unsignedInt 0…100 | 20 |
| Antistratification function | list | disabled |
| Antistratification temp. differential | list | 2.00 [K/m] |
| Hysteresis | list | 0.5 K |
| Disable ventilation from bus | list | no |
| Fan start delay | list | 0 s |
| Fan stop delay | list | 0 s |
| Download overwrite | list | disabled |
| Scene 1 | list | disabled |
| Scene 2 | list | disabled |
| Scene 3 | list | disabled |
| Scene 4 | list | disabled |
| Scene 5 | list | disabled |
| Scene 6 | list | disabled |
| Scene 7 | list | disabled |
| Scene 8 | list | disabled |
| HVAC mode | list | comfort |
| Scene number | unsignedInt 1…64 | 1 |
| Activation delay | time | 0 |
| Windows contacts function | list | disabled |
| Presence sensors function | list | disabled |
| Presence sensors use | list | comfort extension |
| Thermostat modes | list | comfort - standby |
| Wait time to building protection mode | time | 60 |
| Absence time to switch HVAC mode | time | 60 |
| Signal | list | not inverted |
| Device operation as | list | stand-alone |
| Use rockers as | list | thermostat predefined functions |
| Main source for temperature value | list | input 1 |
| Additional source temperature value | list | input 1 |
| Additional source temperature value | list | input 2 |
| Actual temperature | list | always enabled |
| Temperature setpoint | list | enabled |
| Relative humidity | list | enabled |
| Relative humidity setpoint | list | enabled |
| Perceived temperature | list | enabled |
| Outdoor temperature | list | enabled |
| Air quality | list | enabled |
| Card holder function | list | disabled |
| On card insertion switch HVAC mode to | list | comfort |
| On card removal switch HVAC mode to | list | standby |
| Activation delay on card insertion | time | 0 |
| Activation delay on card removal | time | 0 |
| Backlight intensity | list | 50 % |
| Automatic backlight dimming | list | disabled |
| Energy saving | list | disabled |
| Visualization type | list | full |
| Time before energy saving mode | list | 10 s |
| Backlight when in energy saving mode | list | 25 % |
| Behaviour on button press | list | backlight only |
| Ventilation for auxiliary cooling | list | disabled |
| Heating type | list | radiators |
| Heating type | list | fancoils |
| End of manual operation | list | till first telegram from bus |
| Duration of comfort extension | list | not allowed |
| Analog sensors timeout | time | 300 |
| Flow temperature (project) | list | 14 °C |
| Min control value [%] | unsignedInt 0…30 | 15 |
| Max control value [%] | unsignedInt 70…100 | 85 |
| Transmission delay after mode change | time | 400 |
| Hysteresis position | list | below |
| Hysteresis position | list | above |