Easy room temperature Easy controller with LCD EK-ER2-TP
Ekinex S.p.A. · Order number EK-ER2-TP · Heating, cooling and ventilation
Easy room temperature controller with LCD
Download .knxprod APEKER2TP 0.1 · 169 KB
Product
| Manufacturer | Ekinex S.p.A. |
|---|---|
| Product name | Easy room temperature Easy controller with LCD |
| Order number | EK-ER2-TP |
| Product text | Easy room temperature controller with LCD |
| Hardware | Easy room temperature controller with LCD |
| Medium | Twisted Pair |
| Bus current (mA) | 12 |
| Rail mounted | No |
| Registration | Certified · 2019-03-01 |
| Languages | en-US, de-DE, fr-FR, it-IT |
| Catalog entry | M-00B6_H-00B600000038-1_HP-4552-01-73B0_CI-EK.2DER2.2DTP-2 |
| Fingerprint | 73B0 |
| SHA-256 | 6956001a04aba11ad210a1b5b6ebb48b606ba2bb4af114b3cb3f289c33a61ebb |
| First seen | 2026-11-25 |
| Markets | 69 markets |
Application program: APEKER2TP 0.1
| Application number | $4552 |
|---|---|
| Version | 0.1 |
| Mask version | MV-0705 (7.5) |
| KNX Data Secure | No |
| Minimum ETS version | 4.0 |
| Parameters | 474 |
| Group objects | 143 |
Group objects (143)
| No | Name | Function | Size | DPT | Flags |
|---|---|---|---|---|---|
| 0 | Technical alarm | 1 Bit | 1.5 alarm | CW | |
| 1 | Brightness value | 2 Bytes | 9.4 lux (Lux) | CRT | |
| 2 | Leds intensity percentage | 1 Byte | 5.1 percentage (0..100%) | CW | |
| 3 | Temperature value | 2 Bytes | 9.1 temperature (°C) | CRT | |
| 4 | Light threshold 1 - Switch | 1 Bit | 1.1 switch | CRT | |
| 5 | Light threshold 2 - Switch | 1 Bit | 1.1 switch | CRT | |
| 6 | Rocker 1 - Led first color A | 1 Bit | 1.1 switch | CRWTU | |
| 7 | Rocker 1 - Led second color A | 1 Bit | 1.1 switch | CRWTU | |
| 8 | Rocker 1 - Led first color B | 1 Bit | 1.1 switch | CRWTU | |
| 9 | Rocker 1 - Led second color B | 1 Bit | 1.1 switch | CRWTU | |
| 10 | Rocker 2 - Led first color A | 1 Bit | 1.1 switch | CRWTU | |
| 11 | Rocker 2 - Led second color A | 1 Bit | 1.1 switch | CRWTU | |
| 12 | Rocker 2 - Led first color B | 1 Bit | 1.1 switch | CRWTU | |
| 13 | Rocker 2 - Led second color B | 1 Bit | 1.1 switch | CRWTU | |
| 16 | Temperature threshold 1 - Switch | 1 Bit | 1.1 switch | CRT | |
| 17 | Temperature threshold 2 - Switch | 1 Bit | 1.1 switch | CRT | |
| 20 | Temperature value sensor (from input 1) | 2 Bytes | 9.1 temperature (°C) | CRT | |
| 20 | Coil battery temperature sensor (from input 1) | 2 Bytes | 9.1 temperature (°C) | CRT | |
| 20 | Room temperature sensor (from input 1) | 2 Bytes | 9.1 temperature (°C) | CRT | |
| 20 | Antistratification temperature sensor (from input 1) | 2 Bytes | 9.1 temperature (°C) | CRT | |
| 20 | Floor surface temperature sensor (from input 1) | 2 Bytes | 9.1 temperature (°C) | CRT | |
| 20 | Outdoor temperature sensor (from input 1) | 2 Bytes | 9.1 temperature (°C) | CRT | |
| 21 | Temperature threshold 1 sensor 1 - Switch | 1 Bit | 1.1 switch | CRT | |
| 22 | Temperature threshold 2 sensor 1 - Switch | 1 Bit | 1.1 switch | CRT | |
| 23 | Temperature value sensor (from input 2) | 2 Bytes | 9.1 temperature (°C) | CRT | |
| 23 | Coil battery temperature sensor (from input 2) | 2 Bytes | 9.1 temperature (°C) | CRT | |
| 23 | Room temperature sensor (from input 2) | 2 Bytes | 9.1 temperature (°C) | CRT | |
| 23 | Antistratification temperature sensor (from input 2) | 2 Bytes | 9.1 temperature (°C) | CRT | |
| 23 | Floor surface temperature sensor (from input 2) | 2 Bytes | 9.1 temperature (°C) | CRT | |
| 23 | Outdoor temperature sensor (from input 2) | 2 Bytes | 9.1 temperature (°C) | CRT | |
| 24 | Temperature threshold 1 sensor 2 - Switch | 1 Bit | 1.1 switch | CRT | |
| 25 | Temperature threshold 2 sensor 2 - Switch | 1 Bit | 1.1 switch | CRT | |
| 26 | Window contact sensor (from input 1) | 1 Bit | 1.19 window/door | CRT | |
| 27 | Window contact sensor (from input 2) | 1 Bit | 1.19 window/door | CRT | |
| 28 | Anticondensation sensor (from input 1) | 1 Bit | 1.5 alarm | CRT | |
| 29 | Anticondensation sensor (from input 2) | 1 Bit | 1.5 alarm | CRT | |
| 30 | Card holder contact sensor (from input 1) | 1 Bit | 1.18 occupancy | CRT | |
| 31 | Card holder contact sensor (from input 2) | 1 Bit | 1.18 occupancy | CRT | |
| 32 | Presence sensor 1 (from bus) | 1 Bit | 1.18 occupancy | CW | |
| 33 | Presence sensor 2 (from bus) | 1 Bit | 1.18 occupancy | CW | |
| 34 | Room temperature (from bus) | 2 Bytes | 9.1 temperature (°C) | CW | |
| 37 | Antistratification temperature (from bus) | 2 Bytes | 9.1 temperature (°C) | CW | |
| 38 | Outdoor temperature (from bus) | 2 Bytes | 9.1 temperature (°C) | CW | |
| 40 | Coil temperature (from bus) | 2 Bytes | 9.1 temperature (°C) | CW | |
| 41 | Floor temperature (from bus) | 2 Bytes | 9.1 temperature (°C) | CW | |
| 43 | Windows contact sensor 1 (from bus) | 1 Bit | 1.19 window/door | CW | |
| 44 | Windows contact sensor 2 (from bus) | 1 Bit | 1.19 window/door | CW | |
| 45 | Contact of card holder (from bus) | 1 Bit | 1.18 occupancy | CW | |
| 46 | Anticondensation (from bus) | 1 Bit | 1.1 switch | CW | |
| 47 | Weighted temperature | 2 Bytes | 9.1 temperature (°C) | CRT | |
| 48 | Heating/cooling status out | 1 Bit | 1.100 heating/cooling | CRT | |
| 49 | Heating/cooling status in | 1 Bit | 1.100 heating/cooling | CW | |
| 50 | HVAC mode in | 1 Byte | 20.102 HVAC mode | CW | |
| 51 | HVAC forced mode in | 1 Byte | 20.102 HVAC mode | CW | |
| 52 | Actual setpoint | 2 Bytes | 9.1 temperature (°C) | CRT | |
| 53 | HVAC manual mode | 1 Byte | 20.102 HVAC mode | CWTU | |
| 54 | Thermostat off status | 1 Bit | 1.11 state | CRT | |
| 55 | Manual setpoint | 2 Bytes | 9.1 temperature (°C) | CW | |
| 56 | Thermostat off command | 1 Bit | 1.11 state | CRWTU | |
| 57 | Setpoint (heating) | 2 Bytes | 9.1 temperature (°C) | CRWTU | |
| 57 | Setpoint | 2 Bytes | 9.1 temperature (°C) | CRWTU | |
| 58 | Setpoint (cooling) | 2 Bytes | 9.1 temperature (°C) | CRWTU | |
| 59 | Standby setpoint (heating) | 2 Bytes | 9.1 temperature (°C) | CRWTU | |
| 60 | Standby setpoint (cooling) | 2 Bytes | 9.1 temperature (°C) | CRWTU | |
| 61 | Economy setpoint (heating) | 2 Bytes | 9.1 temperature (°C) | CRWTU | |
| 62 | Economy setpoint (cooling) | 2 Bytes | 9.1 temperature (°C) | CRWTU | |
| 63 | Building protection setpoint (heating) | 2 Bytes | 9.1 temperature (°C) | CRWTU | |
| 64 | Building protection setpoint (cooling) | 2 Bytes | 9.1 temperature (°C) | CRWTU | |
| 65 | Heating out command | 1 Byte | 5.1 percentage (0..100%) | CRT | |
| 65 | Heating out command | 1 Bit | 1.1 switch | CRT | |
| 65 | Heating and cooling out command | 1 Bit | 1.1 switch | CRT | |
| 65 | Heating and cooling out command | 1 Byte | 5.1 percentage (0..100%) | CRT | |
| 66 | Cooling out command | 1 Byte | 5.1 percentage (0..100%) | CRT | |
| 66 | Cooling out command | 1 Bit | 1.1 switch | CRT | |
| 67 | Auxiliary heating output command | 1 Bit | 1.1 switch | CRT | |
| 67 | Auxiliary heating and cooling output command | 1 Bit | 1.1 switch | CRT | |
| 68 | Auxiliary cooling output command | 1 Bit | 1.1 switch | CRT | |
| 69 | Auxiliary heating enable | 1 Bit | 1.3 enable | CW | |
| 70 | Auxiliary cooling enable | 1 Bit | 1.3 enable | CW | |
| 71 | Fan continuous speed | 1 Byte | 5.1 percentage (0..100%) | CRT | |
| 72 | Fan speed 1 | 1 Bit | 1.1 switch | CRT | |
| 73 | Fan speed 2 | 1 Bit | 1.1 switch | CRT | |
| 74 | Fan speed 3 | 1 Bit | 1.1 switch | CRT | |
| 75 | Fan control disable | 1 Bit | 1.2 boolean | CW | |
| 76 | Fan manual speed | 1 Byte | 5.10 counter pulses (0..255) | CRWU | |
| 77 | Fan speed | 1 Byte | 5.10 counter pulses (0..255) | CRT | |
| 78 | Fan manual active status | 1 Bit | 1.11 state | CRWT | |
| 79 | HVAC scene number | 1 Byte | 17.1 scene number | CW | |
| 83 | HVAC mode out | 1 Byte | 20.102 HVAC mode | CRT | |
| 90 | Temperature setpoint change lock | 1 Bit | 1.3 enable | CW | |
| 91 | Manual mode lock | 1 Bit | 1.3 enable | CW | |
| 92 | Anticondensation alarm | 1 Bit | 1.5 alarm | CRT | |
| 93 | Rockers lock | 1 Bit | 1.2 boolean | CW | |
| 94 | Thermal generator lock | 1 Bit | 1.5 alarm | CW | |
| 95 | Alarm 1 (from bus) | 1 Bit | 1.5 alarm | CW | |
| 96 | Alarm 2 (from bus) | 1 Bit | 1.5 alarm | CW | |
| 97 | Alarm 3 (from bus) | 1 Bit | 1.5 alarm | CW | |
| 98 | Alarm 4 (from bus) | 1 Bit | 1.5 alarm | CW | |
| 99 | Dehumidification Setpoint | 2 Bytes | 9.7 humidity (%) | CRWTU | |
| 100 | Humidification Setpoint | 2 Bytes | 9.7 humidity (%) | CRWTU | |
| 101 | Building protection HVAC mode active | 1 Bit | 1.11 state | CRT | |
| 102 | Fan manual speed percentage | 1 Byte | 5.1 percentage (0..100%) | CRT | |
| 103 | Fan manual speed off status | 1 Bit | 1.11 state | CRT | |
| 104 | Logic function 1 - Input 1 | 1 Bit | 1.1 switch | CWTU | |
| 105 | Logic function 1 - Input 2 | 1 Bit | 1.1 switch | CWTU | |
| 106 | Logic function 1 - Input 3 | 1 Bit | 1.1 switch | CWTU | |
| 107 | Logic function 1 - Input 4 | 1 Bit | 1.1 switch | CWTU | |
| 108 | Logic function 1 - Output | 1 Bit | 1.1 switch | CRT | |
| 109 | Logic function 2 - Input 1 | 1 Bit | 1.1 switch | CWTU | |
| 110 | Logic function 2 - Input 2 | 1 Bit | 1.1 switch | CWTU | |
| 111 | Logic function 2 - Input 3 | 1 Bit | 1.1 switch | CWTU | |
| 112 | Logic function 2 - Input 4 | 1 Bit | 1.1 switch | CWTU | |
| 113 | Logic function 2 - Output | 1 Bit | 1.1 switch | CRT | |
| 114 | Logic function 3 - Input 1 | 1 Bit | 1.1 switch | CWTU | |
| 115 | Logic function 3 - Input 2 | 1 Bit | 1.1 switch | CWTU | |
| 116 | Logic function 3 - Input 3 | 1 Bit | 1.1 switch | CWTU | |
| 117 | Logic function 3 - Input 4 | 1 Bit | 1.1 switch | CWTU | |
| 118 | Logic function 3 - Output | 1 Bit | 1.1 switch | CRT | |
| 119 | Logic function 4 - Input 1 | 1 Bit | 1.1 switch | CWTU | |
| 120 | Logic function 4 - Input 2 | 1 Bit | 1.1 switch | CWTU | |
| 121 | Logic function 4 - Input 3 | 1 Bit | 1.1 switch | CWTU | |
| 122 | Logic function 4 - Input 4 | 1 Bit | 1.1 switch | CWTU | |
| 123 | Logic function 4 - Output | 1 Bit | 1.1 switch | CRT | |
| 124 | Logic function 5 - Input 1 | 1 Bit | 1.1 switch | CWTU | |
| 125 | Logic function 5 - Input 2 | 1 Bit | 1.1 switch | CWTU | |
| 126 | Logic function 5 - Input 3 | 1 Bit | 1.1 switch | CWTU | |
| 127 | Logic function 5 - Input 4 | 1 Bit | 1.1 switch | CWTU | |
| 128 | Logic function 5 - Output | 1 Bit | 1.1 switch | CRT | |
| 129 | Logic function 6 - Input 1 | 1 Bit | 1.1 switch | CWTU | |
| 130 | Logic function 6 - Input 2 | 1 Bit | 1.1 switch | CWTU | |
| 131 | Logic function 6 - Input 3 | 1 Bit | 1.1 switch | CWTU | |
| 132 | Logic function 6 - Input 4 | 1 Bit | 1.1 switch | CWTU | |
| 133 | Logic function 6 - Output | 1 Bit | 1.1 switch | CRT | |
| 134 | Logic function 7 - Input 1 | 1 Bit | 1.1 switch | CWTU | |
| 135 | Logic function 7 - Input 2 | 1 Bit | 1.1 switch | CWTU | |
| 136 | Logic function 7 - Input 3 | 1 Bit | 1.1 switch | CWTU | |
| 137 | Logic function 7 - Input 4 | 1 Bit | 1.1 switch | CWTU | |
| 138 | Logic function 7 - Output | 1 Bit | 1.1 switch | CRT | |
| 139 | Logic function 8 - Input 1 | 1 Bit | 1.1 switch | CWTU | |
| 140 | Logic function 8 - Input 2 | 1 Bit | 1.1 switch | CWTU | |
| 141 | Logic function 8 - Input 3 | 1 Bit | 1.1 switch | CWTU | |
| 142 | Logic function 8 - Input 4 | 1 Bit | 1.1 switch | CWTU | |
| 143 | Logic function 8 - Output | 1 Bit | 1.1 switch | CRT |
Parameters (204)
| Parameter | Type | Default |
|---|---|---|
| Light sensor | list | disabled |
| Temperature sensor | list | enabled |
| Input 1 | list | disabled |
| Led intensity correlation | list | none |
| Minimum change of value to send [Lux] | float 0…670760 | 50 |
| Cyclic sending interval | list | no sending |
| Minimum change of value to send [K] | float 0…5 | 0.5 |
| Delay after bus voltage recovery | time | 400 |
| Leds intensity from bus | list | no |
| Leds intensity | list | 50% |
| Led first color 1A | list | when contact closed |
| Blinking | list | no |
| Signal from bus | list | not inverted |
| Always | list | off |
| Off delay | time | 20 |
| Blinking period / type | list | 1 s on, 1 s off |
| Led second color 1A | list | when contact closed |
| Led second color 1B | list | when contact closed |
| Led first color 1B | list | when contact closed |
| Led first color 2A | list | when contact closed |
| Led second color 2A | list | when contact closed |
| Led first color 2B | list | when contact closed |
| Led second color 2B | list | when contact closed |
| Value [Lux] | float 0…670760 | 500 |
| Hysteresis | list | 50 lux |
| Threshold 1 | list | not active |
| Threshold 2 | list | not active |
| Sensor value multiplier (1 ÷ 255) x 0.1 | unsignedInt 1…255 | 10 |
| Temperature offset | list | 0.0 °C |
| Technical alarm | list | disabled |
| Input 2 | list | disabled |
| Contact type | list | NO (normally open) |
| Relative humidity sensor | list | disabled |
| Value [°C] | float 0…50 | 45 |
| Value [°C] | float 0…50 | 7 |
| Hysteresis | list | 0.4 K |
| Value [%] | unsignedInt 0…100 | 65 |
| Hysteresis [%] | list | 3.0% |
| Minimum change of value to send [%] | unsignedInt 0…10 | 2 |
| Temperature displayed unit | list | Celsius |
| Default displayed information | list | actual temperature |
| Time to return to default display | list | 2 s |
| Button function level | list | system integrator |
| Time to exit change with saving | list | 3 s |
| Debounce time | time | 20 |
| Digital sensors timeout | time | 300 |
| Room temperature | list | disabled |
| Relative humidity | list | disabled |
| Antistratification temperature | list | disabled |
| Outdoor temperature | list | disabled |
| Air quality | list | disabled |
| Coil temperature | list | disabled |
| Floor surface temperature | list | disabled |
| Flow temperature | list | disabled |
| Window contact 1 | list | disabled |
| Window contact 2 | list | disabled |
| Presence sensor 1 | list | disabled |
| Presence sensor 2 | list | disabled |
| Card holder contact | list | disabled |
| Humidity CO dimension | list | 2 bytes |
| Main source for temperature value | list | internal sensor |
| Additional source temperature value | list | internal sensor |
| Relative weight | list | 50% / 50% |
| Filter type | list | medium |
| Main source for temperature value | list | input |
| Additional source temperature value | list | input |
| Additional source temperature value | list | from bus |
| Thermostat function | list | heating |
| Anticondensation | list | disabled |
| Heating - cooling switch over | list | from bus |
| Heating - cooling cyclic sending interval | list | no sending |
| Max manual temperature change | list | ±3 °C |
| Max setpoint temperature change | list | ±9 °C |
| Setpoint cyclic sending interval | list | no sending |
| Scenes | list | disabled |
| Temperature setpoint [°C] | float 2…50 | 21 |
| Standby temperature setpoint [°C] | float 10…50 | 18 |
| Economy temp. setpoint [°C] | float 10…50 | 16 |
| Building protection temp. setpoint [°C] | float 2…10 | 7 |
| Control type | list | 2 points hysteresis |
| Command Communication Object | list | separated |
| Hysteresis | list | 0.3 K |
| PWM cycle time | time | 15 |
| Proportional band [0.1K] | unsignedInt 5…100 | 40 |
| Integral time [min] | unsignedInt 0…255 | 90 |
| Valve protection function | list | disabled |
| Frequency | list | once a week |
| Time interval | list | 10 s |
| Floor temperature limitation | list | disabled |
| Temperature limit [°C] | float 20…40 | 29 |
| Auxiliary heating | list | disabled |
| Communication object | list | separated |
| Offset from setpoint | list | 0.6 K |
| Disabled from bus | list | no |
| Ventilation for auxiliary heating | list | disabled |
| Temperature setpoint [°C] | float 2…50 | 23 |
| Standby temperature setpoint [°C] | float 10…50 | 26 |
| Economy temp. setpoint [°C] | float 10…50 | 28 |
| Building protection temp. setpoint [°C] | float 30…50 | 36 |
| Cooling type | list | fancoils |
| Auxiliary cooling | list | disabled |
| Anticondensation with probe | list | disabled |
| Active anticondensation | list | disabled |
| Min. change of value to send [%] | unsignedInt 0…100 | 10 |
| Anticondensation hysteresis range | list | 0.5 K |
| Control type | list | 1 speed |
| Threshold first speed [0.1K] | unsignedInt 0…255 | 0 |
| Threshold second speed [0.1K] | unsignedInt 0…255 | 10 |
| Threshold third speed [0.1K] | unsignedInt 0…255 | 20 |
| Manual operation | list | not depending on the temperature |
| Hot start | list | no |
| Use coil battery temperature sensor for dehumidification | list | no |
| Speed control hysteresis | list | 0.3 K |
| Speed proportional band [0.1K] | unsignedInt 5…100 | 30 |
| Min. change of value to send [%] | unsignedInt 2…40 | 10 |
| Min. temp. to start ventilation [°C] | unsignedInt 28…40 | 28 |
| Min. temp. to start dehumidif. [°C] | unsignedInt 0…255 | 10 |
| Relative humidity setpoint [%] | unsignedInt 0…100 | 65 |
| Relative humidity setpoint [%] | list | 0.6% |
| Max. temp. diff. to disable dehum. [°C] | float 0…50 | 0.5 |
| Forced speed | list | 1 speed |
| Forced speed | unsignedInt 0…100 | 20 |
| Antistratification function | list | disabled |
| Antistratification temp. differential | list | 2.00 [K/m] |
| Hysteresis | list | 0.5 K |
| Disable ventilation from bus | list | no |
| Fan start delay | list | 0 s |
| Fan stop delay | list | 0 s |
| Download overwrite | list | disabled |
| Scene 1 | list | disabled |
| Scene 2 | list | disabled |
| Scene 3 | list | disabled |
| Scene 4 | list | disabled |
| Scene 5 | list | disabled |
| Scene 6 | list | disabled |
| Scene 7 | list | disabled |
| Scene 8 | list | disabled |
| Learning mode | list | disabled |
| HVAC mode | list | comfort |
| Scene number | unsignedInt 1…64 | 1 |
| Activation delay | time | 0 |
| Windows contacts function | list | disabled |
| Presence sensors function | list | disabled |
| Presence sensors use | list | comfort extension |
| Thermostat modes | list | comfort - standby |
| Wait time to off mode | time | 60 |
| Absence time to switch HVAC mode | time | 60 |
| Signal | list | not inverted |
| Device operation as | list | stand-alone |
| Main source for temperature value | list | input 1 |
| Additional source temperature value | list | input 1 |
| Additional source temperature value | list | input 2 |
| Actual temperature | list | always enabled |
| Temperature setpoint | list | enabled |
| Relative humidity | list | enabled |
| Relative humidity setpoint | list | enabled |
| Perceived temperature | list | enabled |
| Outdoor temperature | list | enabled |
| Air quality | list | enabled |
| Card holder function | list | disabled |
| On card insertion switch to | list | on |
| On card removal switch to | list | off |
| Activation delay on card insertion | time | 0 |
| Activation delay on card removal | time | 0 |
| Backlight intensity | list | 50% |
| Automatic backlight dimming | list | disabled |
| Energy saving | list | disabled |
| Visualization type | list | full |
| Time before energy saving mode | list | 10 s |
| Backlight when in energy saving mode | list | 25% |
| Behaviour on button press | list | backlight only |
| Ventilation for auxiliary cooling | list | disabled |
| Heating type | list | radiators |
| Heating type | list | fancoils |
| End of manual operation | list | till first telegram from bus |
| Duration of comfort extension | list | not allowed |
| Analog sensors timeout | time | 300 |
| Flow temperature (project) | list | 14 °C |
| Min control value [%] | unsignedInt 0…30 | 15 |
| Max control value [%] | unsignedInt 70…100 | 85 |
| Transmission delay after mode change | time | 400 |
| Hysteresis position | list | below |
| Hysteresis position | list | above |
| Exit manual mode on setpoint from bus | list | no |
| Logic functions | list | disabled |
| Logic function | list | disabled |
| Logic operation | list | OR |
| Output cyclic transmission interval | list | no sending |
| Logic object 1 | list | disabled |
| Logic object 2 | list | disabled |
| Logic object 3 | list | disabled |
| Logic object 4 | list | disabled |
| Logic object 1 negated | list | no |
| Logic object 2 negated | list | no |
| Logic object 3 negated | list | no |
| Logic object 4 negated | list | no |
| Logic object 1 read at startup | list | no |
| Logic object 2 read at startup | list | no |
| Logic object 3 read at startup | list | no |
| Logic object 4 read at startup | list | no |
| Logic object 1 default value | list | none |
| Logic object 2 default value | list | none |
| Logic object 3 default value | list | none |
| Logic object 4 default value | list | none |
Version history
| Application | App no | Fingerprint | First seen | Size | File |
|---|---|---|---|---|---|
| APEKER2TP 0.1 latest | $4552 | 73B0 | 2026-11-25 | 169 KB | Download |
About this file
This is the official ETS product database for the Ekinex S.p.A. Easy room temperature Easy controller with LCD (EK-ER2-TP), published by the manufacturer in the KNX online catalog. To use it, open ETS, go to Catalogs → Import and choose the downloaded .knxprod file. The device then appears in your catalog and can be added to a project. Older versions are kept so existing projects can be matched to the application program they were commissioned with.
More from Ekinex S.p.A.
- Universal interface 4 DI + 4 DI / NTC EK-CA1-TP
- Universal interface 4 DI / 2 relais 5A EK-CE2-TP
- Universal interface 4 DI / NTC EK-CG2-TP
- Room temperature controller 71 Serie EK-E72-TP
- Room temperature controller 71 Serie - EASY EK-E73-EASY
- Room temperature controller 71 Serie EK-E73-TP
- Touch & See with integrated pushbutton 2 channels EK-EF2-TP
- Easy room temperature controller with LCD EK-EM2-TP-E
- Full room temperature controller with LCD EK-EM2-TP-F
- Room temperature controller with LCD EK-EP2-TP
- Room temperature controller with LCD and relative humidity sensor EK-EQ2-TP
- Multisensor T, RH and CO2eq with controller EK-ES2-TP