Room temperature controller 71 Serie EK-E72-TP
Ekinex S.p.A. · Order number EK-E72-TP · Heating, cooling and ventilation
Room temperature controller 71 Serie
Download .knxprod APEKE73TP 0.3 · 136 KB
Product
| Manufacturer | Ekinex S.p.A. |
|---|---|
| Product name | Room temperature controller 71 Serie |
| Order number | EK-E72-TP |
| Product text | EK-E72-TP - Room temperature controller 71 Serie |
| Hardware | Room temperature controller 71 Serie |
| Medium | Twisted Pair |
| Bus current (mA) | 13 |
| Rail mounted | No |
| Registration | Certified · 2016-02-12 |
| Languages | en-US, de-DE, fr-FR, it-IT |
| Catalog entry | M-00B6_H-000024-1_HP-4537-03-DE59_CI-EK.2DE72.2DTP-2 |
| Fingerprint | DE59 |
| SHA-256 | fab59135c68f876a3651345ab4712c32f4714a4360ce19f9866a9f682c3e50d2 |
| First seen | 2026-11-25 |
| Markets | 69 markets |
Application program: APEKE73TP 0.3
| Application number | $4537 |
|---|---|
| Version | 0.3 |
| Mask version | MV-0705 (7.5) |
| KNX Data Secure | No |
| Minimum ETS version | 4.0 |
| Parameters | 418 |
| Group objects | 122 |
Group objects (122)
| No | Name | Function | Size | DPT | Flags |
|---|---|---|---|---|---|
| 0 | Technical alarm | 1 Bit | 1.5 alarm | CW | |
| 1 | Temperature value | 2 Bytes | 9.1 temperature (°C) | CRT | |
| 2 | Temperature threshold 1 - Switch | 1 Bit | 1.1 switch | CRT | |
| 3 | Temperature threshold 2 - Switch | 1 Bit | 1.1 switch | CRT | |
| 4 | Brightness value (from bus) | 2 Bytes | 9.4 lux (Lux) | CWTU | |
| 5 | Room temperature (from bus) | 2 Bytes | 9.1 temperature (°C) | CWTU | |
| 6 | Humidity (2 bytes, from bus) | 2 Bytes | 9.7 humidity (%) | CWTU | |
| 7 | Humidity (1 byte, from bus) | 1 Byte | 5.1 percentage (0..100%) | CWTU | |
| 8 | Antistratification temperature (from bus) | 2 Bytes | 9.1 temperature (°C) | CWTU | |
| 9 | Outdoor temperature (from bus) | 2 Bytes | 9.1 temperature (°C) | CWTU | |
| 10 | Coil temperature (from bus) | 2 Bytes | 9.1 temperature (°C) | CWTU | |
| 11 | Floor temperature (from bus) | 2 Bytes | 9.1 temperature (°C) | CWTU | |
| 12 | Flow temperature (from bus) | 2 Bytes | 9.1 temperature (°C) | CWTU | |
| 13 | Windows contact sensor 1 (from bus) | 1 Bit | 1.19 window/door | CWTU | |
| 14 | Windows contact sensor 2 (from bus) | 1 Bit | 1.19 window/door | CWTU | |
| 15 | Presence sensor 1 (from bus) | 1 Bit | 1.18 occupancy | CWTU | |
| 16 | Presence sensor 2 (from bus) | 1 Bit | 1.18 occupancy | CWTU | |
| 17 | Contact of card holder (from bus) | 1 Bit | 1.18 occupancy | CWTU | |
| 18 | Anticondensation (from bus) | 1 Bit | 1.1 switch | CWTU | |
| 19 | Weighted temperature | 2 Bytes | 9.1 temperature (°C) | CRT | |
| 20 | Heating/cooling status out | 1 Bit | 1.100 heating/cooling | CRT | |
| 21 | Heating/cooling status in | 1 Bit | 1.100 heating/cooling | CW | |
| 22 | HVAC mode in | 1 Byte | 20.102 HVAC mode | CW | |
| 23 | HVAC forced mode in | 1 Byte | 20.102 HVAC mode | CW | |
| 24 | HVAC mode out | 1 Byte | 20.102 HVAC mode | CRT | |
| 25 | HVAC manual mode | 1 Byte | 20.102 HVAC mode | CWTU | |
| 26 | Chrono active status | 1 Bit | 1.11 state | CRT | |
| 27 | Actual setpoint | 2 Bytes | 9.1 temperature (°C) | CRT | |
| 28 | Manual setpoint | 2 Bytes | 9.1 temperature (°C) | CW | |
| 29 | Comfort setpoint (heating) | 2 Bytes | 9.1 temperature (°C) | CRWTU | |
| 30 | Comfort setpoint (cooling) | 2 Bytes | 9.1 temperature (°C) | CRWTU | |
| 31 | Standby setpoint (heating) | 2 Bytes | 9.1 temperature (°C) | CRWTU | |
| 32 | Standby setpoint (cooling) | 2 Bytes | 9.1 temperature (°C) | CRWTU | |
| 33 | Economy setpoint (heating) | 2 Bytes | 9.1 temperature (°C) | CRWTU | |
| 34 | Economy setpoint (cooling) | 2 Bytes | 9.1 temperature (°C) | CRWTU | |
| 35 | Building protection setpoint (heating) | 2 Bytes | 9.1 temperature (°C) | CRWTU | |
| 36 | Building protection setpoint (cooling) | 2 Bytes | 9.1 temperature (°C) | CRWTU | |
| 37 | Temperature setpoint change lock | 1 Bit | 1.3 enable | CW | |
| 38 | Heating out command | 1 Byte | 5.1 percentage (0..100%) | CRT | |
| 38 | Heating out command | 1 Bit | 1.1 switch | CRT | |
| 38 | Heating and cooling out command | 1 Bit | 1.1 switch | CRT | |
| 38 | Heating and cooling out command | 1 Byte | 5.1 percentage (0..100%) | CRT | |
| 39 | Cooling out command | 1 Byte | 5.1 percentage (0..100%) | CRT | |
| 39 | Cooling out command | 1 Bit | 1.1 switch | CRT | |
| 40 | Auxiliary heating output command | 1 Bit | 1.1 switch | CRT | |
| 40 | Auxiliary heating and cooling output command | 1 Bit | 1.1 switch | CRT | |
| 41 | Auxiliary cooling output command | 1 Bit | 1.1 switch | CRT | |
| 42 | Auxiliary heating disable | 1 Bit | 1.3 enable | CW | |
| 43 | Auxiliary cooling disable | 1 Bit | 1.3 enable | CW | |
| 44 | Fan continuous speed | 1 Byte | 5.1 percentage (0..100%) | CRT | |
| 45 | Fan speed 1 | 1 Bit | 1.1 switch | CRT | |
| 46 | Fan speed 2 | 1 Bit | 1.1 switch | CRT | |
| 47 | Fan speed 3 | 1 Bit | 1.1 switch | CRT | |
| 48 | Fan control disable | 1 Bit | 1.2 boolean | CW | |
| 49 | Manual mode lock | 1 Bit | 1.3 enable | CW | |
| 50 | Manual/forced setpoint active status | 1 Bit | 1.11 state | CRWTU | |
| 51 | Fan manual speed | 1 Byte | 5.10 counter pulses (0..255) | CRWTU | |
| 52 | Fan speed | 1 Byte | 5.10 counter pulses (0..255) | CRT | |
| 53 | Fan manual active status | 1 Bit | 1.11 state | CRWTU | |
| 54 | HVAC scene number | 1 Byte | 17.1 scene number | CW | |
| 55 | Comfort state | 1 Bit | 1.6 binary value | CRT | |
| 56 | Dew-point temperature | 2 Bytes | 9.1 temperature (°C) | CRT | |
| 57 | Perceived temperature | 2 Bytes | 9.1 temperature (°C) | CRT | |
| 58 | Relative humidity setpoint for dehumidification | 2 Bytes | 9.7 humidity (%) | CRWTU | |
| 59 | Relative humidity setpoint for humidification | 2 Bytes | 9.7 humidity (%) | CRWTU | |
| 60 | Dehumidification command | 1 Bit | 1.1 switch | CRT | |
| 61 | Dehumidification integration control | 1 Bit | 1.1 switch | CRT | |
| 62 | Dehumidification integration control | 1 Bit | 1.1 switch | CRT | |
| 63 | Dehumidification control disable | 1 Bit | 1.2 boolean | CW | |
| 64 | Humidification command | 1 Bit | 1.1 switch | CRT | |
| 65 | Humidification control disable | 1 Bit | 1.2 boolean | CW | |
| 66 | Anticondensation alarm | 1 Bit | 1.5 alarm | CRT | |
| 67 | Leds intensity percentage | 1 Byte | 5.1 percentage (0..100%) | CW | |
| 68 | Thermal generator lock | 1 Bit | 1.5 alarm | CW | |
| 69 | Alarm 1 (from bus) | 1 Bit | 1.5 alarm | CW | |
| 70 | Alarm 2 (from bus) | 1 Bit | 1.5 alarm | CW | |
| 71 | Alarm 3 (from bus) | 1 Bit | 1.5 alarm | CW | |
| 72 | Alarm 4 (from bus) | 1 Bit | 1.5 alarm | CW | |
| 73 | Rockers lock | 1 Bit | 1.2 boolean | CW | |
| 74 | Building protection HVAC mode active | 1 Bit | 1.11 state | CRT | |
| 75 | Fan manual speed percentage | 1 Byte | 5.1 percentage (0..100%) | CRT | |
| 76 | Fan manual speed off status | 1 Bit | 1.11 state | CRT | |
| 77 | Logic function 1 - Input 1 | 1 Bit | 1.1 switch | CWTU | |
| 78 | Logic function 1 - Input 2 | 1 Bit | 1.1 switch | CWTU | |
| 79 | Logic function 1 - Input 3 | 1 Bit | 1.1 switch | CWTU | |
| 80 | Logic function 1 - Input 4 | 1 Bit | 1.1 switch | CWTU | |
| 81 | Logic function 1 - Output | 1 Bit | 1.1 switch | CRT | |
| 82 | Logic function 2 - Input 1 | 1 Bit | 1.1 switch | CWTU | |
| 83 | Logic function 2 - Input 2 | 1 Bit | 1.1 switch | CWTU | |
| 84 | Logic function 2 - Input 3 | 1 Bit | 1.1 switch | CWTU | |
| 85 | Logic function 2 - Input 4 | 1 Bit | 1.1 switch | CWTU | |
| 86 | Logic function 2 - Output | 1 Bit | 1.1 switch | CRT | |
| 87 | Logic function 3 - Input 1 | 1 Bit | 1.1 switch | CWTU | |
| 88 | Logic function 3 - Input 2 | 1 Bit | 1.1 switch | CWTU | |
| 89 | Logic function 3 - Input 3 | 1 Bit | 1.1 switch | CWTU | |
| 90 | Logic function 3 - Input 4 | 1 Bit | 1.1 switch | CWTU | |
| 91 | Logic function 3 - Output | 1 Bit | 1.1 switch | CRT | |
| 92 | Logic function 4 - Input 1 | 1 Bit | 1.1 switch | CWTU | |
| 93 | Logic function 4 - Input 2 | 1 Bit | 1.1 switch | CWTU | |
| 94 | Logic function 4 - Input 3 | 1 Bit | 1.1 switch | CWTU | |
| 95 | Logic function 4 - Input 4 | 1 Bit | 1.1 switch | CWTU | |
| 96 | Logic function 4 - Output | 1 Bit | 1.1 switch | CRT | |
| 97 | Logic function 5 - Input 1 | 1 Bit | 1.1 switch | CWTU | |
| 98 | Logic function 5 - Input 2 | 1 Bit | 1.1 switch | CWTU | |
| 99 | Logic function 5 - Input 3 | 1 Bit | 1.1 switch | CWTU | |
| 100 | Logic function 5 - Input 4 | 1 Bit | 1.1 switch | CWTU | |
| 101 | Logic function 5 - Output | 1 Bit | 1.1 switch | CRT | |
| 102 | Logic function 6 - Input 1 | 1 Bit | 1.1 switch | CWTU | |
| 103 | Logic function 6 - Input 2 | 1 Bit | 1.1 switch | CWTU | |
| 104 | Logic function 6 - Input 3 | 1 Bit | 1.1 switch | CWTU | |
| 105 | Logic function 6 - Input 4 | 1 Bit | 1.1 switch | CWTU | |
| 106 | Logic function 6 - Output | 1 Bit | 1.1 switch | CRT | |
| 107 | Logic function 7 - Input 1 | 1 Bit | 1.1 switch | CWTU | |
| 108 | Logic function 7 - Input 2 | 1 Bit | 1.1 switch | CWTU | |
| 109 | Logic function 7 - Input 3 | 1 Bit | 1.1 switch | CWTU | |
| 110 | Logic function 7 - Input 4 | 1 Bit | 1.1 switch | CWTU | |
| 111 | Logic function 7 - Output | 1 Bit | 1.1 switch | CRT | |
| 112 | Logic function 8 - Input 1 | 1 Bit | 1.1 switch | CWTU | |
| 113 | Logic function 8 - Input 2 | 1 Bit | 1.1 switch | CWTU | |
| 114 | Logic function 8 - Input 3 | 1 Bit | 1.1 switch | CWTU | |
| 115 | Logic function 8 - Input 4 | 1 Bit | 1.1 switch | CWTU | |
| 116 | Logic function 8 - Output | 1 Bit | 1.1 switch | CRT |
Parameters (183)
| Parameter | Type | Default |
|---|---|---|
| Temperature sensor | list | enabled |
| Minimum change of value to send [K] | float 0…5 | 0.5 |
| Cyclic sending interval | list | no sending |
| Delay after bus voltage recovery | time | 400 |
| Leds intensity from bus | list | no |
| Leds intensity | list | 3 |
| Temperature offset | list | 0.0 °C |
| Technical alarm | list | disabled |
| Threshold 2 | list | not active |
| Threshold 1 | list | not active |
| Value [°C] | float 0…50 | 45 |
| Value [°C] | float 0…50 | 7 |
| Hysteresis | list | 0.4 K |
| Temperature displayed unit | list | Celsius |
| Default displayed information | list | actual temperature |
| Time to return to default display | list | 5 s |
| Button function level | list | system integrator |
| Time to exit change without saving | list | 10 s |
| Digital sensors timeout | time | 300 |
| Room temperature | list | disabled |
| Relative humidity | list | disabled |
| Antistratification temperature | list | disabled |
| Outdoor temperature | list | disabled |
| Light sensor | list | disabled |
| Coil temperature | list | disabled |
| Floor surface temperature | list | disabled |
| Flow temperature | list | disabled |
| Window contact 1 | list | disabled |
| Window contact 2 | list | disabled |
| Presence sensor 1 | list | disabled |
| Presence sensor 2 | list | disabled |
| Card holder contact | list | disabled |
| Humidity CO dimension | list | 2 bytes |
| Relative weight | list | 50% / 50% |
| Filter type | list | medium |
| Anticondensation | list | disabled |
| Max manual temperature change | list | ±3 °C |
| Max setpoint temperature change | list | ±9 °C |
| Setpoint cyclic sending interval | list | no sending |
| Scenes | list | disabled |
| Comfort temp. setpoint [°C] | float 10…50 | 21 |
| Standby temperature setpoint [°C] | float 10…50 | 18 |
| Economy temp. setpoint [°C] | float 10…50 | 16 |
| Building protection temp. setpoint [°C] | float 2…10 | 7 |
| Control type | list | 2 points hysteresis |
| Command Communication Object | list | separated |
| Hysteresis | list | 0.3 K |
| PWM cycle time | time | 15 |
| Proportional band [0.1K] | unsignedInt 5…100 | 40 |
| Integral time [min] | unsignedInt 0…255 | 90 |
| Valve protection function | list | disabled |
| Frequency | list | once a week |
| Time interval | list | 10 s |
| Floor temperature limitation | list | disabled |
| Temperature limit [°C] | float 20…40 | 29 |
| Auxiliary heating | list | disabled |
| Communication object | list | separated |
| Offset from setpoint | list | 0.6 K |
| Disabled from bus | list | no |
| Ventilation for auxiliary heating | list | disabled |
| Comfort temp. setpoint [°C] | float 10…50 | 23 |
| Standby temperature setpoint [°C] | float 10…50 | 26 |
| Economy temp. setpoint [°C] | float 10…50 | 28 |
| Building protection temp. setpoint [°C] | float 30…50 | 36 |
| Cooling type | list | fancoils |
| Auxiliary cooling | list | disabled |
| Anticondensation with probe | list | disabled |
| Active anticondensation | list | disabled |
| Min. change of value to send [%] | unsignedInt 0…100 | 10 |
| Anticondensation hysteresis range | list | 0.5 K |
| Control type | list | 1 speed |
| Threshold first speed [0.1K] | unsignedInt 0…255 | 0 |
| Threshold second speed [0.1K] | unsignedInt 0…255 | 10 |
| Threshold third speed [0.1K] | unsignedInt 0…255 | 20 |
| Manual operation | list | not depending on the temperature |
| Hot start | list | no |
| Use coil battery temperature sensor for dehumidification | list | no |
| Speed control hysteresis | list | 0.3 K |
| Speed proportional band [0.1K] | unsignedInt 5…100 | 30 |
| Min. change of value to send [%] | unsignedInt 2…40 | 10 |
| Min. temp. to start ventilation [°C] | unsignedInt 28…40 | 28 |
| Min. temp. to start dehumidif. [°C] | unsignedInt 0…255 | 10 |
| Relative humidity setpoint [%] | unsignedInt 0…100 | 65 |
| Relative humidity setpoint [%] | list | 0.6 % |
| Max. temp. diff. to disable dehum. [°C] | float 0…50 | 0.5 |
| Forced speed | list | 1 speed |
| Forced speed | unsignedInt 0…100 | 20 |
| Antistratification function | list | disabled |
| Antistratification temp. differential | list | 2.00 [K/m] |
| Hysteresis | list | 0.5 K |
| Disable ventilation from bus | list | no |
| Signal from bus | list | not inverted |
| Fan start delay | list | 0 s |
| Fan stop delay | list | 0 s |
| Download overwrite | list | disabled |
| Scene 1 | list | disabled |
| Scene 2 | list | disabled |
| Scene 3 | list | disabled |
| Scene 4 | list | disabled |
| Scene 5 | list | disabled |
| Scene 6 | list | disabled |
| Scene 7 | list | disabled |
| Scene 8 | list | disabled |
| Learning mode | list | disabled |
| HVAC mode | list | comfort |
| Scene number | unsignedInt 1…64 | 1 |
| Activation delay | time | 0 |
| Minimum temperature [°C] | float 10…50 | 20 |
| Maximum temperature [°C] | float 10…50 | 26 |
| Minimum relative humidity [%] | unsignedInt 0…100 | 30 |
| Maximum relative humidity [%] | unsignedInt 0…100 | 65 |
| Maximum absolute humidity [g/kg x 0,1] | unsignedInt 50…200 | 115 |
| Dew-point temperature | list | disabled |
| Perceived temperature | list | disabled |
| Min. change of value to send [K] | list | 0.2 K |
| Min. change of value to send | list | 0.2 K |
| Windows contacts function | list | disabled |
| Presence sensors function | list | disabled |
| Presence sensors use | list | comfort extension |
| Thermostat modes | list | comfort - standby |
| Wait time to building protection mode | time | 60 |
| Absence time to switch HVAC mode | time | 60 |
| Signal | list | not inverted |
| Device operation as | list | stand-alone |
| Actual temperature | list | always enabled |
| Temperature setpoint | list | enabled |
| Relative humidity | list | enabled |
| Relative humidity setpoint | list | enabled |
| Outdoor temperature | list | enabled |
| Card holder function | list | disabled |
| On card insertion switch HVAC mode to | list | comfort |
| On card removal switch HVAC mode to | list | standby |
| Activation delay on card insertion | time | 0 |
| Activation delay on card removal | time | 0 |
| Backlight intensity | list | 50 % |
| Automatic backlight dimming | list | disabled |
| Energy saving | list | disabled |
| Visualization type | list | full |
| Time before energy saving mode | list | 10 s |
| Backlight when in energy saving mode | list | 25 % |
| Behaviour on button press | list | backlight only |
| Ventilation for auxiliary cooling | list | disabled |
| Heating type | list | radiators |
| Heating type | list | fancoils |
| End of manual operation | list | till first telegram from bus |
| Humidity hysteresis | list | 0.8 % |
| Subordinated to temperature control | list | yes |
| Humidity setpoint | unsignedInt 20…80 | 55 |
| Integration | list | no |
| Dehumidification start delay | time | 300 |
| Temperature difference for integration | list | 1.5 °C |
| Hysteresis for integration | list | 0.5 K |
| Disable dehumid. control from bus | list | no |
| Humidity setpoint | unsignedInt 20…80 | 35 |
| Disable humidification control from bus | list | no |
| Duration of comfort extension | list | not allowed |
| Analog sensors timeout | time | 300 |
| Flow temperature (project) | list | 14 °C |
| Min control value [%] | unsignedInt 0…30 | 15 |
| Max control value [%] | unsignedInt 70…100 | 85 |
| Transmission delay after mode change | time | 400 |
| Hysteresis position | list | below |
| Hysteresis position | list | above |
| Delay for alarm signal | list | 5 min |
| Heating - cooling switch over | list | from bus |
| Thermostat function | list | heating |
| Heating - cooling cyclic sending interval | list | no sending |
| Dehumidification function | list | disabled |
| Humidification function | list | disabled |
| Exit manual mode on setpoint from bus | list | no |
| Leds intensity at standby | list | no change |
| Cyclic reading each | list | no reading |
| Logic function | list | disabled |
| Logic operation | list | OR |
| Output cyclic sending interval | list | no sending |
| Logic object 1 | list | disabled |
| Logic object 2 | list | disabled |
| Logic object 3 | list | disabled |
| Logic object 4 | list | disabled |
| Negated | list | no |
| Read at startup | list | no |
| Default value | list | none |
| Logic functions | list | disabled |
Version history
| Application | App no | Fingerprint | First seen | Size | File |
|---|---|---|---|---|---|
| APEKE73TP 0.3 latest | $4537 | DE59 | 2026-11-25 | 136 KB | Download |
About this file
This is the official ETS product database for the Ekinex S.p.A. Room temperature controller 71 Serie (EK-E72-TP), published by the manufacturer in the KNX online catalog. To use it, open ETS, go to Catalogs → Import and choose the downloaded .knxprod file. The device then appears in your catalog and can be added to a project. Older versions are kept so existing projects can be matched to the application program they were commissioned with.
More from Ekinex S.p.A.
- Universal interface 4 DI + 4 DI / NTC EK-CA1-TP
- Universal interface 4 DI / 2 relais 5A EK-CE2-TP
- Universal interface 4 DI / NTC EK-CG2-TP
- Room temperature controller 71 Serie - EASY EK-E73-EASY
- Room temperature controller 71 Serie EK-E73-TP
- Touch & See with integrated pushbutton 2 channels EK-EF2-TP
- Easy room temperature controller with LCD EK-EM2-TP-E
- Full room temperature controller with LCD EK-EM2-TP-F
- Room temperature controller with LCD EK-EP2-TP
- Room temperature controller with LCD and relative humidity sensor EK-EQ2-TP
- Easy room temperature Easy controller with LCD EK-ER2-TP
- Multisensor T, RH and CO2eq with controller EK-ES2-TP