| 0 | Technical alarm | | 1 Bit | 1.5 alarm | CRT |
| 1 | Communication alarm | | 1 Bit | 1.5 alarm | CRT |
| 2 | Thermal generator lock | | 1 Bit | 1.5 alarm | CW |
| 3 | Power off alarm | | 1 Bit | 1.5 alarm | CRT |
| 4 | Temperature control alarm | | 1 Bit | 1.5 alarm | CRT |
| 5 | Too high delivery T alarm (heating) | | 1 Bit | 1.5 alarm | CRT |
| 6 | Too low delivery T alarm (cooling) | | 1 Bit | 1.5 alarm | CRT |
| 7 | Alarm text | | 14 Bytes | 16.0 Character String (ASCII) | CRT |
| 8 | Test mode activated | | 1 Bit | 1.3 enable | CRT |
| 9 | Disable front keyboard | | 1 Bit | 1.2 boolean | CW |
| 10 | Heating/cooling changeover in | | 1 Bit | 1.100 heating/cooling | CW |
| 11 | Heating/cooling changeover out | | 1 Bit | 1.100 heating/cooling | CRT |
| 12 | Current delivery setpoint | | 2 Bytes | 9.1 temperature (°C) | CRT |
| 13 | Delivery setpoint offset | | 2 Bytes | 9.2 temperature difference (K) | CW |
| 14 | Controller output | | 1 Byte | 5.1 percentage (0..100%) | CRT |
| 15 | Percentage controller output manual control | | 1 Byte | 5.1 percentage (0..100%) | CW |
| 16 | Automatic/manual controller output from bus | | 1 Bit | 1.3 enable | CRWTU |
| 17 | T dew point max | | 2 Bytes | 9.1 temperature (°C) | CRT |
| 18 | T delivery (from input 1) | | 2 Bytes | 9.1 temperature (°C) | CRT |
| 19 | Threshold temperature 1 sensor (from input 1) - Switch | | 1 Bit | 1.1 switch | CRT |
| 20 | Threshold temperature 2 sensor (from input 1) - Switch | | 1 Bit | 1.1 switch | CRT |
| 21 | T return (from input 2) | | 2 Bytes | 9.1 temperature (°C) | CRT |
| 21 | T generic (from input 2) | | 2 Bytes | 9.1 temperature (°C) | CRT |
| 22 | Threshold temperature 1 sensor (from input 2) - Switch | | 1 Bit | 1.1 switch | CRT |
| 23 | Threshold temperature 2 sensor (from input 2) - Switch | | 1 Bit | 1.1 switch | CRT |
| 24 | T outside (from input 3) | | 2 Bytes | 9.1 temperature (°C) | CRT |
| 24 | T generic (from input 3) | | 2 Bytes | 9.1 temperature (°C) | CRT |
| 25 | Threshold temperature 1 sensor (from input 3) - Switch | | 1 Bit | 1.1 switch | CRT |
| 26 | Threshold temperature 2 sensor (from input 3) - Switch | | 1 Bit | 1.1 switch | CRT |
| 27 | T generic (from input 4) | | 2 Bytes | 9.1 temperature (°C) | CRT |
| 27 | Flow request contact state (from input 4) | | 1 Bit | 1.1 switch | CRT |
| 27 | Anticondensation sensor state (from input 4) | | 1 Bit | 1.1 switch | CRT |
| 27 | Generic contact state (from input 4) | | 1 Bit | 1.1 switch | CRT |
| 28 | Threshold temperature 1 sensor (from input 4) - Switch | | 1 Bit | 1.1 switch | CRT |
| 29 | Threshold temperature 2 sensor (from input 4) - Switch | | 1 Bit | 1.1 switch | CRT |
| 30 | T generic (from input 5) | | 2 Bytes | 9.1 temperature (°C) | CRT |
| 30 | Cooling/heating state (from input 5) | | 1 Bit | 1.1 switch | CRT |
| 30 | Anticondensation sensor state (from input 5) | | 1 Bit | 1.1 switch | CRT |
| 30 | Generic contact state (from input 5) | | 1 Bit | 1.1 switch | CRT |
| 31 | Threshold temperature 1 sensor (from input 5) - Switch | | 1 Bit | 1.1 switch | CRT |
| 32 | Threshold temperature 2 sensor (from input 5) - Switch | | 1 Bit | 1.1 switch | CRT |
| 33 | T outside from bus | | 2 Bytes | 9.1 temperature (°C) | CWTU |
| 34 | Circulator output DO1 state | | 1 Bit | 1.1 switch | CRT |
| 35 | DO2 output state | | 1 Bit | 1.1 switch | CRT |
| 36 | DO3 output state | | 1 Bit | 1.1 switch | CRT |
| 37 | Disable circulator output DO1 from bus | | 1 Bit | 1.1 switch | CW |
| 38 | Disable output DO2 from bus | | 1 Bit | 1.1 switch | CW |
| 39 | Disable output DO3 from bus | | 1 Bit | 1.1 switch | CW |
| 40 | Disable output TR1/TR2 from bus | | 1 Bit | 1.1 switch | CW |
| 41 | Disable output 0-10V from bus | | 1 Bit | 1.3 enable | CW |
| 42 | DO2 output control from bus | | 1 Bit | 1.1 switch | CW |
| 43 | DO3 output control from bus | | 1 Bit | 1.1 switch | CW |
| 44 | TR1 control from bus | | 1 Bit | 1.1 switch | CW |
| 45 | TR2 control from bus | | 1 Bit | 1.1 switch | CW |
| 46 | 0-10V output control from bus | | 1 Byte | 5.1 percentage (0..100%) | CW |
| 47 | Fixed point delivery setpoint (heating) | | 2 Bytes | 9.1 temperature (°C) | CRWTU |
| 47 | Project delivery setpoint (heating) | | 2 Bytes | 9.1 temperature (°C) | CRWTU |
| 48 | Min delivery setpoint (heating) | | 2 Bytes | 9.1 temperature (°C) | CRWTU |
| 49 | Max delivery setpoint (heating) | | 2 Bytes | 9.1 temperature (°C) | CRWTU |
| 50 | T outside T1 (heating) | | 2 Bytes | 9.1 temperature (°C) | CRWTU |
| 51 | T outside T0 (heating) | | 2 Bytes | 9.1 temperature (°C) | CRWTU |
| 52 | Project ΔT (heating) | | 2 Bytes | 9.1 temperature (°C) | CRWTU |
| 53 | Setpoint change (heating) | | 2 Bytes | 9.1 temperature (°C) | CRWTU |
| 54 | Fixed point delivery setpoint (cooling) | | 2 Bytes | 9.1 temperature (°C) | CRWTU |
| 54 | Project delivery setpoint (cooling) | | 2 Bytes | 9.1 temperature (°C) | CRWTU |
| 55 | Min delivery setpoint (cooling) | | 2 Bytes | 9.1 temperature (°C) | CRWTU |
| 56 | Max delivery setpoint (cooling) | | 2 Bytes | 9.1 temperature (°C) | CRWTU |
| 57 | T outside T2 (cooling) | | 2 Bytes | 9.1 temperature (°C) | CRWTU |
| 58 | T outside T3 (cooling) | | 2 Bytes | 9.1 temperature (°C) | CRWTU |
| 59 | Safety value (cooling) | | 2 Bytes | 9.1 temperature (°C) | CRWTU |
| 60 | not used | | 1 Byte | | CRT |
| 61 | not used | | 1 Byte | | CRT |
| 62 | not used | | 1 Byte | | CRT |
| 63 | not used | | 1 Byte | | CRT |
| 64 | not used | | 1 Byte | | CRT |
| 65 | not used | | 1 Byte | | CRT |
| 66 | not used | | 1 Byte | | CRT |
| 67 | not used | | 1 Byte | | CRT |
| 68 | not used | | 1 Byte | | CRT |
| 69 | not used | | 1 Byte | | CRT |
| 70 | Zone 1 - Command state | | 1 Bit | 1.1 switch | CWTU |
| 71 | Zone 1 - T set current | | 2 Bytes | 9.1 temperature (°C) | CWTU |
| 72 | Zone 1 - T room | | 2 Bytes | 9.1 temperature (°C) | CWTU |
| 73 | Zone 1 - RH room (2 bytes) | | 2 Bytes | 9.7 humidity (%) | CWTU |
| 73 | Zone 1 - Relative humidity (1 byte) | | 1 Byte | 5.1 percentage (0..100%) | CWTU |
| 73 | Zone 1 - T dew point room | | 2 Bytes | 9.1 temperature (°C) | CWTU |
| 74 | Zone 1 - T dew point room | | 2 Bytes | 9.1 temperature (°C) | CRT |
| 75 | Zone 2 - Command state | | 1 Bit | 1.1 switch | CWTU |
| 76 | Zone 2 - T set current | | 2 Bytes | 9.1 temperature (°C) | CWTU |
| 77 | Zone 2 - T room | | 2 Bytes | 9.1 temperature (°C) | CWTU |
| 78 | Zone 2 - T dew point room | | 2 Bytes | 9.1 temperature (°C) | CWTU |
| 78 | Zone 2 - Relative humidity (1 byte) | | 1 Byte | 5.1 percentage (0..100%) | CWTU |
| 78 | Zone 2 - RH room (2 bytes) | | 2 Bytes | 9.7 humidity (%) | CWTU |
| 79 | Zone 2 - T dew point room | | 2 Bytes | 9.1 temperature (°C) | CRT |
| 80 | Zone 3 - Command state | | 1 Bit | 1.1 switch | CWTU |
| 81 | Zone 3 - T set current | | 2 Bytes | 9.1 temperature (°C) | CWTU |
| 82 | Zone 3 - T room | | 2 Bytes | 9.1 temperature (°C) | CWTU |
| 83 | Zone 3 - T dew point room | | 2 Bytes | 9.1 temperature (°C) | CWTU |
| 83 | Zone 3 - Relative humidity (1 byte) | | 1 Byte | 5.1 percentage (0..100%) | CWTU |
| 83 | Zone 3 - RH room (2 bytes) | | 2 Bytes | 9.7 humidity (%) | CWTU |
| 84 | Zone 3 - T dew point room | | 2 Bytes | 9.1 temperature (°C) | CRT |
| 85 | Zone 4 - Command state | | 1 Bit | 1.1 switch | CWTU |
| 86 | Zone 4 - T set current | | 2 Bytes | 9.1 temperature (°C) | CWTU |
| 87 | Zone 4 - T room | | 2 Bytes | 9.1 temperature (°C) | CWTU |
| 88 | Zone 4 - T dew point room | | 2 Bytes | 9.1 temperature (°C) | CWTU |
| 88 | Zone 4 - Relative humidity (1 byte) | | 1 Byte | 5.1 percentage (0..100%) | CWTU |
| 88 | Zone 4 - RH room (2 bytes) | | 2 Bytes | 9.7 humidity (%) | CWTU |
| 89 | Zone 4 - T dew point room | | 2 Bytes | 9.1 temperature (°C) | CRT |
| 90 | Zone 5 - Command state | | 1 Bit | 1.1 switch | CWTU |
| 91 | Zone 5 - T set current | | 2 Bytes | 9.1 temperature (°C) | CWTU |
| 92 | Zone 5 - T room | | 2 Bytes | 9.1 temperature (°C) | CWTU |
| 93 | Zone 5 - T dew point room | | 2 Bytes | 9.1 temperature (°C) | CWTU |
| 93 | Zone 5 - Relative humidity (1 byte) | | 1 Byte | 5.1 percentage (0..100%) | CWTU |
| 93 | Zone 5 - RH room (2 bytes) | | 2 Bytes | 9.7 humidity (%) | CWTU |
| 94 | Zone 5 - T dew point room | | 2 Bytes | 9.1 temperature (°C) | CRT |
| 95 | Zone 6 - Command state | | 1 Bit | 1.1 switch | CWTU |
| 96 | Zone 6 - T set current | | 2 Bytes | 9.1 temperature (°C) | CWTU |
| 97 | Zone 6 - T room | | 2 Bytes | 9.1 temperature (°C) | CWTU |
| 98 | Zone 6 - T dew point room | | 2 Bytes | 9.1 temperature (°C) | CWTU |
| 98 | Zone 6 - Relative humidity (1 byte) | | 1 Byte | 5.1 percentage (0..100%) | CWTU |
| 98 | Zone 6 - RH room (2 bytes) | | 2 Bytes | 9.7 humidity (%) | CWTU |
| 99 | Zone 6 - T dew point room | | 2 Bytes | 9.1 temperature (°C) | CRT |
| 100 | Zone 7 - Command state | | 1 Bit | 1.1 switch | CWTU |
| 101 | Zone 7 - T set current | | 2 Bytes | 9.1 temperature (°C) | CWTU |
| 102 | Zone 7 - T room | | 2 Bytes | 9.1 temperature (°C) | CWTU |
| 103 | Zone 7 - T dew point room | | 2 Bytes | 9.1 temperature (°C) | CWTU |
| 103 | Zone 7 - Relative humidity (1 byte) | | 1 Byte | 5.1 percentage (0..100%) | CWTU |
| 103 | Zone 7 - RH room (2 bytes) | | 2 Bytes | 9.7 humidity (%) | CWTU |
| 104 | Zone 7 - T dew point room | | 2 Bytes | 9.1 temperature (°C) | CRT |
| 105 | Zone 8 - Command state | | 1 Bit | 1.1 switch | CWTU |
| 106 | Zone 8 - T set current | | 2 Bytes | 9.1 temperature (°C) | CWTU |
| 107 | Zone 8 - T room | | 2 Bytes | 9.1 temperature (°C) | CWTU |
| 108 | Zone 8 - T dew point room | | 2 Bytes | 9.1 temperature (°C) | CWTU |
| 108 | Zone 8 - Relative humidity (1 byte) | | 1 Byte | 5.1 percentage (0..100%) | CWTU |
| 108 | Zone 8 - RH room (2 bytes) | | 2 Bytes | 9.7 humidity (%) | CWTU |
| 109 | Zone 8 - T dew point room | | 2 Bytes | 9.1 temperature (°C) | CRT |
| 110 | Zone 9 - Command state | | 1 Bit | 1.1 switch | CWTU |
| 111 | Zone 9 - T set current | | 2 Bytes | 9.1 temperature (°C) | CWTU |
| 112 | Zone 9 - T room | | 2 Bytes | 9.1 temperature (°C) | CWTU |
| 113 | Zone 9 - T dew point room | | 2 Bytes | 9.1 temperature (°C) | CWTU |
| 113 | Zone 9 - Relative humidity (1 byte) | | 1 Byte | 5.1 percentage (0..100%) | CWTU |
| 113 | Zone 9 - RH room (2 bytes) | | 2 Bytes | 9.7 humidity (%) | CWTU |
| 114 | Zone 9 - T dew point room | | 2 Bytes | 9.1 temperature (°C) | CRT |
| 115 | Zone 10 - Command state | | 1 Bit | 1.1 switch | CWTU |
| 116 | Zone 10 - T set current | | 2 Bytes | 9.1 temperature (°C) | CWTU |
| 117 | Zone 10 - T room | | 2 Bytes | 9.1 temperature (°C) | CWTU |
| 118 | Zone 10 - T dew point room | | 2 Bytes | 9.1 temperature (°C) | CWTU |
| 118 | Zone 10 - Relative humidity (1 byte) | | 1 Byte | 5.1 percentage (0..100%) | CWTU |
| 118 | Zone 10 - RH room (2 bytes) | | 2 Bytes | 9.7 humidity (%) | CWTU |
| 119 | Zone 10 - T dew point room | | 2 Bytes | 9.1 temperature (°C) | CRT |
| 120 | Zone 11 - Command state | | 1 Bit | 1.1 switch | CWTU |
| 121 | Zone 11 - T set current | | 2 Bytes | 9.1 temperature (°C) | CWTU |
| 122 | Zone 11 - T room | | 2 Bytes | 9.1 temperature (°C) | CWTU |
| 123 | Zone 11 - Relative humidity (1 byte) | | 1 Byte | 5.1 percentage (0..100%) | CWTU |
| 123 | Zone 11 - T dew point room | | 2 Bytes | 9.1 temperature (°C) | CWTU |
| 123 | Zone 11 - RH room (2 bytes) | | 2 Bytes | 9.7 humidity (%) | CWTU |
| 124 | Zone 11 - T dew point room | | 2 Bytes | 9.1 temperature (°C) | CRT |
| 125 | Zone 12 - Command state | | 1 Bit | 1.1 switch | CWTU |
| 126 | Zone 12 - T set current | | 2 Bytes | 9.1 temperature (°C) | CWTU |
| 127 | Zone 12 - T room | | 2 Bytes | 9.1 temperature (°C) | CWTU |
| 128 | Zone 12 - T dew point room | | 2 Bytes | 9.1 temperature (°C) | CWTU |
| 128 | Zone 12 - Relative humidity (1 byte) | | 1 Byte | 5.1 percentage (0..100%) | CWTU |
| 128 | Zone 12 - RH room (2 bytes) | | 2 Bytes | 9.7 humidity (%) | CWTU |
| 129 | Zone 12 - T dew point room | | 2 Bytes | 9.1 temperature (°C) | CRT |
| 130 | Zone 13 - Command state | | 1 Bit | 1.1 switch | CWTU |
| 131 | Zone 13 - T set current | | 2 Bytes | 9.1 temperature (°C) | CWTU |
| 132 | Zone 13 - T room | | 2 Bytes | 9.1 temperature (°C) | CWTU |
| 133 | Zone 13 - T dew point room | | 2 Bytes | 9.1 temperature (°C) | CWTU |
| 133 | Zone 13 - Relative humidity (1 byte) | | 1 Byte | 5.1 percentage (0..100%) | CWTU |
| 133 | Zone 13 - RH room (2 bytes) | | 2 Bytes | 9.7 humidity (%) | CWTU |
| 134 | Zone 13 - T dew point room | | 2 Bytes | 9.1 temperature (°C) | CRT |
| 135 | Zone 14 - Command state | | 1 Bit | 1.1 switch | CWTU |
| 136 | Zone 14 - T set current | | 2 Bytes | 9.1 temperature (°C) | CWTU |
| 137 | Zone 14 - T room | | 2 Bytes | 9.1 temperature (°C) | CWTU |
| 138 | Zone 14 - T dew point room | | 2 Bytes | 9.1 temperature (°C) | CWTU |
| 138 | Zone 14 - Relative humidity (1 byte) | | 1 Byte | 5.1 percentage (0..100%) | CWTU |
| 138 | Zone 14 - RH room (2 bytes) | | 2 Bytes | 9.7 humidity (%) | CWTU |
| 139 | Zone 14 - T dew point room | | 2 Bytes | 9.1 temperature (°C) | CRT |
| 140 | Zone 15 - Command state | | 1 Bit | 1.1 switch | CWTU |
| 141 | Zone 15 - T set current | | 2 Bytes | 9.1 temperature (°C) | CWTU |
| 142 | Zone 15 - T room | | 2 Bytes | 9.1 temperature (°C) | CWTU |
| 143 | Zone 15 - T dew point room | | 2 Bytes | 9.1 temperature (°C) | CWTU |
| 143 | Zone 15 - Relative humidity (1 byte) | | 1 Byte | 5.1 percentage (0..100%) | CWTU |
| 143 | Zone 15 - RH room (2 bytes) | | 2 Bytes | 9.7 humidity (%) | CWTU |
| 144 | Zone 15 - T dew point room | | 2 Bytes | 9.1 temperature (°C) | CRT |
| 145 | Zone 16 - Command state | | 1 Bit | 1.1 switch | CWTU |
| 146 | Zone 16 - T set current | | 2 Bytes | 9.1 temperature (°C) | CWTU |
| 147 | Zone 16 - T room | | 2 Bytes | 9.1 temperature (°C) | CWTU |
| 148 | Zone 16 - T dew point room | | 2 Bytes | 9.1 temperature (°C) | CWTU |
| 148 | Zone 16 - Relative humidity (1 byte) | | 1 Byte | 5.1 percentage (0..100%) | CWTU |
| 148 | Zone 16 - RH room (2 bytes) | | 2 Bytes | 9.7 humidity (%) | CWTU |
| 149 | Zone 16 - T dew point room | | 2 Bytes | 9.1 temperature (°C) | CRT |
| 150 | Logic function 1 - Input 1 | | 1 Bit | 1.1 switch | CWTU |
| 151 | Logic function 1 - Input 2 | | 1 Bit | 1.1 switch | CWTU |
| 152 | Logic function 1 - Input 3 | | 1 Bit | 1.1 switch | CWTU |
| 153 | Logic function 1 - Input 4 | | 1 Bit | 1.1 switch | CWTU |
| 154 | Logic function 1 - Input 5 | | 1 Bit | 1.1 switch | CWTU |
| 155 | Logic function 1 - Input 6 | | 1 Bit | 1.1 switch | CWTU |
| 156 | Logic function 1 - Input 7 | | 1 Bit | 1.1 switch | CWTU |
| 157 | Logic function 1 - Input 8 | | 1 Bit | 1.1 switch | CWTU |
| 158 | Logic function 1 - Input 9 | | 1 Bit | 1.1 switch | CWTU |
| 159 | Logic function 1 - Input 10 | | 1 Bit | 1.1 switch | CWTU |
| 160 | Logic function 1 - Input 11 | | 1 Bit | 1.1 switch | CWTU |
| 161 | Logic function 1 - Input 12 | | 1 Bit | 1.1 switch | CWTU |
| 162 | Logic function 1 - Input 13 | | 1 Bit | 1.1 switch | CWTU |
| 163 | Logic function 1 - Input 14 | | 1 Bit | 1.1 switch | CWTU |
| 164 | Logic function 1 - Input 15 | | 1 Bit | 1.1 switch | CWTU |
| 165 | Logic function 1 - Input 16 | | 1 Bit | 1.1 switch | CWTU |
| 166 | Logic function 1 - Output | | 1 Bit | 1.1 switch | CRT |
| 167 | Logic function 2 - Input 1 | | 1 Bit | 1.1 switch | CWTU |
| 168 | Logic function 2 - Input 2 | | 1 Bit | 1.1 switch | CWTU |
| 169 | Logic function 2 - Input 3 | | 1 Bit | 1.1 switch | CWTU |
| 170 | Logic function 2 - Input 4 | | 1 Bit | 1.1 switch | CWTU |
| 171 | Logic function 2 - Input 5 | | 1 Bit | 1.1 switch | CWTU |
| 172 | Logic function 2 - Input 6 | | 1 Bit | 1.1 switch | CWTU |
| 173 | Logic function 2 - Input 7 | | 1 Bit | 1.1 switch | CWTU |
| 174 | Logic function 2 - Input 8 | | 1 Bit | 1.1 switch | CWTU |
| 175 | Logic function 2 - Input 9 | | 1 Bit | 1.1 switch | CWTU |
| 176 | Logic function 2 - Input 10 | | 1 Bit | 1.1 switch | CWTU |
| 177 | Logic function 2 - Input 11 | | 1 Bit | 1.1 switch | CWTU |
| 178 | Logic function 2 - Input 12 | | 1 Bit | 1.1 switch | CWTU |
| 179 | Logic function 2 - Input 13 | | 1 Bit | 1.1 switch | CWTU |
| 180 | Logic function 2 - Input 14 | | 1 Bit | 1.1 switch | CWTU |
| 181 | Logic function 2 - Input 15 | | 1 Bit | 1.1 switch | CWTU |
| 182 | Logic function 2 - Input 16 | | 1 Bit | 1.1 switch | CWTU |
| 183 | Logic function 2 - Output | | 1 Bit | 1.1 switch | CRT |