Ekinex S.p.A. EK-HH1-TP Actuator-controller for mixing group

Actuator-controller for mixing group EK-HH1-TP

Ekinex S.p.A. · Order number EK-HH1-TP · Heating, cooling and ventilation

Actuator-controller for mixing group

Download .knxprod APEKHH1TP 0.2 · 120 KB

Product

ManufacturerEkinex S.p.A.
Product nameActuator-controller for mixing group
Order numberEK-HH1-TP
HardwareActuator-controller for mixing valve
MediumTwisted Pair
Bus current (mA)12
Rail mountedYes
Width (mm)144
RegistrationCertified · 2017-04-25
Languagesen-US, de-DE, fr-FR, it-IT
Catalog entryM-00B6_H-000033-1_HP-4848-02-763F_CI-EK.2DHH1.2DTP-1
Fingerprint763F
SHA-25659720082bd3e41a5dc1e6fa8558ebfc4c62b7e39a0d4fdb342646b2fdc131c7f
First seen2026-11-25
Markets69 markets

Application program: APEKHH1TP 0.2

Application number$4848
Version0.2
Mask versionMV-0705 (7.5)
KNX Data SecureNo
Minimum ETS version4.0
Parameters294
Group objects226
Group objects (226)
NoNameFunctionSizeDPTFlags
0Technical alarm1 Bit1.5 alarmCRT
1Communication alarm1 Bit1.5 alarmCRT
2Thermal generator lock1 Bit1.5 alarmCW
3Power off alarm1 Bit1.5 alarmCRT
4Temperature control alarm1 Bit1.5 alarmCRT
5Too high delivery T alarm (heating)1 Bit1.5 alarmCRT
6Too low delivery T alarm (cooling)1 Bit1.5 alarmCRT
7Alarm text14 Bytes16.0 Character String (ASCII)CRT
8Test mode activated1 Bit1.3 enableCRT
9Disable front keyboard1 Bit1.2 booleanCW
10Heating/cooling changeover in1 Bit1.100 heating/coolingCW
11Heating/cooling changeover out1 Bit1.100 heating/coolingCRT
12Current delivery setpoint2 Bytes9.1 temperature (°C)CRT
13Delivery setpoint offset2 Bytes9.2 temperature difference (K)CW
14Controller output1 Byte5.1 percentage (0..100%)CRT
15Percentage controller output manual control1 Byte5.1 percentage (0..100%)CW
16Automatic/manual controller output from bus1 Bit1.3 enableCRWTU
17T dew point max2 Bytes9.1 temperature (°C)CRT
18T delivery (from input 1)2 Bytes9.1 temperature (°C)CRT
19Threshold temperature 1 sensor (from input 1) - Switch1 Bit1.1 switchCRT
20Threshold temperature 2 sensor (from input 1) - Switch1 Bit1.1 switchCRT
21T return (from input 2)2 Bytes9.1 temperature (°C)CRT
21T generic (from input 2)2 Bytes9.1 temperature (°C)CRT
22Threshold temperature 1 sensor (from input 2) - Switch1 Bit1.1 switchCRT
23Threshold temperature 2 sensor (from input 2) - Switch1 Bit1.1 switchCRT
24T outside (from input 3)2 Bytes9.1 temperature (°C)CRT
24T generic (from input 3)2 Bytes9.1 temperature (°C)CRT
25Threshold temperature 1 sensor (from input 3) - Switch1 Bit1.1 switchCRT
26Threshold temperature 2 sensor (from input 3) - Switch1 Bit1.1 switchCRT
27T generic (from input 4)2 Bytes9.1 temperature (°C)CRT
27Flow request contact state (from input 4)1 Bit1.1 switchCRT
27Anticondensation sensor state (from input 4)1 Bit1.1 switchCRT
27Generic contact state (from input 4)1 Bit1.1 switchCRT
28Threshold temperature 1 sensor (from input 4) - Switch1 Bit1.1 switchCRT
29Threshold temperature 2 sensor (from input 4) - Switch1 Bit1.1 switchCRT
30T generic (from input 5)2 Bytes9.1 temperature (°C)CRT
30Cooling/heating state (from input 5)1 Bit1.1 switchCRT
30Anticondensation sensor state (from input 5)1 Bit1.1 switchCRT
30Generic contact state (from input 5)1 Bit1.1 switchCRT
31Threshold temperature 1 sensor (from input 5) - Switch1 Bit1.1 switchCRT
32Threshold temperature 2 sensor (from input 5) - Switch1 Bit1.1 switchCRT
33T outside from bus2 Bytes9.1 temperature (°C)CWTU
34Circulator output DO1 state1 Bit1.1 switchCRT
35DO2 output state1 Bit1.1 switchCRT
36DO3 output state1 Bit1.1 switchCRT
37Disable circulator output DO1 from bus1 Bit1.1 switchCW
38Disable output DO2 from bus1 Bit1.1 switchCW
39Disable output DO3 from bus1 Bit1.1 switchCW
40Disable output TR1/TR2 from bus1 Bit1.1 switchCW
41Disable output 0-10V from bus1 Bit1.3 enableCW
42DO2 output control from bus1 Bit1.1 switchCW
43DO3 output control from bus1 Bit1.1 switchCW
44TR1 control from bus1 Bit1.1 switchCW
45TR2 control from bus1 Bit1.1 switchCW
460-10V output control from bus1 Byte5.1 percentage (0..100%)CW
47Fixed point delivery setpoint (heating)2 Bytes9.1 temperature (°C)CRWTU
47Project delivery setpoint (heating)2 Bytes9.1 temperature (°C)CRWTU
48Min delivery setpoint (heating)2 Bytes9.1 temperature (°C)CRWTU
49Max delivery setpoint (heating)2 Bytes9.1 temperature (°C)CRWTU
50T outside T1 (heating)2 Bytes9.1 temperature (°C)CRWTU
51T outside T0 (heating)2 Bytes9.1 temperature (°C)CRWTU
52Project ΔT (heating)2 Bytes9.1 temperature (°C)CRWTU
53Setpoint change (heating)2 Bytes9.1 temperature (°C)CRWTU
54Fixed point delivery setpoint (cooling)2 Bytes9.1 temperature (°C)CRWTU
54Project delivery setpoint (cooling)2 Bytes9.1 temperature (°C)CRWTU
55Min delivery setpoint (cooling)2 Bytes9.1 temperature (°C)CRWTU
56Max delivery setpoint (cooling)2 Bytes9.1 temperature (°C)CRWTU
57T outside T2 (cooling)2 Bytes9.1 temperature (°C)CRWTU
58T outside T3 (cooling)2 Bytes9.1 temperature (°C)CRWTU
59Safety value (cooling)2 Bytes9.1 temperature (°C)CRWTU
60not used1 ByteCRT
61not used1 ByteCRT
62not used1 ByteCRT
63not used1 ByteCRT
64not used1 ByteCRT
65not used1 ByteCRT
66not used1 ByteCRT
67not used1 ByteCRT
68not used1 ByteCRT
69not used1 ByteCRT
70Zone 1 - Command state1 Bit1.1 switchCWTU
71Zone 1 - T set current2 Bytes9.1 temperature (°C)CWTU
72Zone 1 - T room2 Bytes9.1 temperature (°C)CWTU
73Zone 1 - RH room (2 bytes)2 Bytes9.7 humidity (%)CWTU
73Zone 1 - Relative humidity (1 byte)1 Byte5.1 percentage (0..100%)CWTU
73Zone 1 - T dew point room2 Bytes9.1 temperature (°C)CWTU
74Zone 1 - T dew point room2 Bytes9.1 temperature (°C)CRT
75Zone 2 - Command state1 Bit1.1 switchCWTU
76Zone 2 - T set current2 Bytes9.1 temperature (°C)CWTU
77Zone 2 - T room2 Bytes9.1 temperature (°C)CWTU
78Zone 2 - T dew point room2 Bytes9.1 temperature (°C)CWTU
78Zone 2 - Relative humidity (1 byte)1 Byte5.1 percentage (0..100%)CWTU
78Zone 2 - RH room (2 bytes)2 Bytes9.7 humidity (%)CWTU
79Zone 2 - T dew point room2 Bytes9.1 temperature (°C)CRT
80Zone 3 - Command state1 Bit1.1 switchCWTU
81Zone 3 - T set current2 Bytes9.1 temperature (°C)CWTU
82Zone 3 - T room2 Bytes9.1 temperature (°C)CWTU
83Zone 3 - T dew point room2 Bytes9.1 temperature (°C)CWTU
83Zone 3 - Relative humidity (1 byte)1 Byte5.1 percentage (0..100%)CWTU
83Zone 3 - RH room (2 bytes)2 Bytes9.7 humidity (%)CWTU
84Zone 3 - T dew point room2 Bytes9.1 temperature (°C)CRT
85Zone 4 - Command state1 Bit1.1 switchCWTU
86Zone 4 - T set current2 Bytes9.1 temperature (°C)CWTU
87Zone 4 - T room2 Bytes9.1 temperature (°C)CWTU
88Zone 4 - T dew point room2 Bytes9.1 temperature (°C)CWTU
88Zone 4 - Relative humidity (1 byte)1 Byte5.1 percentage (0..100%)CWTU
88Zone 4 - RH room (2 bytes)2 Bytes9.7 humidity (%)CWTU
89Zone 4 - T dew point room2 Bytes9.1 temperature (°C)CRT
90Zone 5 - Command state1 Bit1.1 switchCWTU
91Zone 5 - T set current2 Bytes9.1 temperature (°C)CWTU
92Zone 5 - T room2 Bytes9.1 temperature (°C)CWTU
93Zone 5 - T dew point room2 Bytes9.1 temperature (°C)CWTU
93Zone 5 - Relative humidity (1 byte)1 Byte5.1 percentage (0..100%)CWTU
93Zone 5 - RH room (2 bytes)2 Bytes9.7 humidity (%)CWTU
94Zone 5 - T dew point room2 Bytes9.1 temperature (°C)CRT
95Zone 6 - Command state1 Bit1.1 switchCWTU
96Zone 6 - T set current2 Bytes9.1 temperature (°C)CWTU
97Zone 6 - T room2 Bytes9.1 temperature (°C)CWTU
98Zone 6 - T dew point room2 Bytes9.1 temperature (°C)CWTU
98Zone 6 - Relative humidity (1 byte)1 Byte5.1 percentage (0..100%)CWTU
98Zone 6 - RH room (2 bytes)2 Bytes9.7 humidity (%)CWTU
99Zone 6 - T dew point room2 Bytes9.1 temperature (°C)CRT
100Zone 7 - Command state1 Bit1.1 switchCWTU
101Zone 7 - T set current2 Bytes9.1 temperature (°C)CWTU
102Zone 7 - T room2 Bytes9.1 temperature (°C)CWTU
103Zone 7 - T dew point room2 Bytes9.1 temperature (°C)CWTU
103Zone 7 - Relative humidity (1 byte)1 Byte5.1 percentage (0..100%)CWTU
103Zone 7 - RH room (2 bytes)2 Bytes9.7 humidity (%)CWTU
104Zone 7 - T dew point room2 Bytes9.1 temperature (°C)CRT
105Zone 8 - Command state1 Bit1.1 switchCWTU
106Zone 8 - T set current2 Bytes9.1 temperature (°C)CWTU
107Zone 8 - T room2 Bytes9.1 temperature (°C)CWTU
108Zone 8 - T dew point room2 Bytes9.1 temperature (°C)CWTU
108Zone 8 - Relative humidity (1 byte)1 Byte5.1 percentage (0..100%)CWTU
108Zone 8 - RH room (2 bytes)2 Bytes9.7 humidity (%)CWTU
109Zone 8 - T dew point room2 Bytes9.1 temperature (°C)CRT
110Zone 9 - Command state1 Bit1.1 switchCWTU
111Zone 9 - T set current2 Bytes9.1 temperature (°C)CWTU
112Zone 9 - T room2 Bytes9.1 temperature (°C)CWTU
113Zone 9 - T dew point room2 Bytes9.1 temperature (°C)CWTU
113Zone 9 - Relative humidity (1 byte)1 Byte5.1 percentage (0..100%)CWTU
113Zone 9 - RH room (2 bytes)2 Bytes9.7 humidity (%)CWTU
114Zone 9 - T dew point room2 Bytes9.1 temperature (°C)CRT
115Zone 10 - Command state1 Bit1.1 switchCWTU
116Zone 10 - T set current2 Bytes9.1 temperature (°C)CWTU
117Zone 10 - T room2 Bytes9.1 temperature (°C)CWTU
118Zone 10 - T dew point room2 Bytes9.1 temperature (°C)CWTU
118Zone 10 - Relative humidity (1 byte)1 Byte5.1 percentage (0..100%)CWTU
118Zone 10 - RH room (2 bytes)2 Bytes9.7 humidity (%)CWTU
119Zone 10 - T dew point room2 Bytes9.1 temperature (°C)CRT
120Zone 11 - Command state1 Bit1.1 switchCWTU
121Zone 11 - T set current2 Bytes9.1 temperature (°C)CWTU
122Zone 11 - T room2 Bytes9.1 temperature (°C)CWTU
123Zone 11 - Relative humidity (1 byte)1 Byte5.1 percentage (0..100%)CWTU
123Zone 11 - T dew point room2 Bytes9.1 temperature (°C)CWTU
123Zone 11 - RH room (2 bytes)2 Bytes9.7 humidity (%)CWTU
124Zone 11 - T dew point room2 Bytes9.1 temperature (°C)CRT
125Zone 12 - Command state1 Bit1.1 switchCWTU
126Zone 12 - T set current2 Bytes9.1 temperature (°C)CWTU
127Zone 12 - T room2 Bytes9.1 temperature (°C)CWTU
128Zone 12 - T dew point room2 Bytes9.1 temperature (°C)CWTU
128Zone 12 - Relative humidity (1 byte)1 Byte5.1 percentage (0..100%)CWTU
128Zone 12 - RH room (2 bytes)2 Bytes9.7 humidity (%)CWTU
129Zone 12 - T dew point room2 Bytes9.1 temperature (°C)CRT
130Zone 13 - Command state1 Bit1.1 switchCWTU
131Zone 13 - T set current2 Bytes9.1 temperature (°C)CWTU
132Zone 13 - T room2 Bytes9.1 temperature (°C)CWTU
133Zone 13 - T dew point room2 Bytes9.1 temperature (°C)CWTU
133Zone 13 - Relative humidity (1 byte)1 Byte5.1 percentage (0..100%)CWTU
133Zone 13 - RH room (2 bytes)2 Bytes9.7 humidity (%)CWTU
134Zone 13 - T dew point room2 Bytes9.1 temperature (°C)CRT
135Zone 14 - Command state1 Bit1.1 switchCWTU
136Zone 14 - T set current2 Bytes9.1 temperature (°C)CWTU
137Zone 14 - T room2 Bytes9.1 temperature (°C)CWTU
138Zone 14 - T dew point room2 Bytes9.1 temperature (°C)CWTU
138Zone 14 - Relative humidity (1 byte)1 Byte5.1 percentage (0..100%)CWTU
138Zone 14 - RH room (2 bytes)2 Bytes9.7 humidity (%)CWTU
139Zone 14 - T dew point room2 Bytes9.1 temperature (°C)CRT
140Zone 15 - Command state1 Bit1.1 switchCWTU
141Zone 15 - T set current2 Bytes9.1 temperature (°C)CWTU
142Zone 15 - T room2 Bytes9.1 temperature (°C)CWTU
143Zone 15 - T dew point room2 Bytes9.1 temperature (°C)CWTU
143Zone 15 - Relative humidity (1 byte)1 Byte5.1 percentage (0..100%)CWTU
143Zone 15 - RH room (2 bytes)2 Bytes9.7 humidity (%)CWTU
144Zone 15 - T dew point room2 Bytes9.1 temperature (°C)CRT
145Zone 16 - Command state1 Bit1.1 switchCWTU
146Zone 16 - T set current2 Bytes9.1 temperature (°C)CWTU
147Zone 16 - T room2 Bytes9.1 temperature (°C)CWTU
148Zone 16 - T dew point room2 Bytes9.1 temperature (°C)CWTU
148Zone 16 - Relative humidity (1 byte)1 Byte5.1 percentage (0..100%)CWTU
148Zone 16 - RH room (2 bytes)2 Bytes9.7 humidity (%)CWTU
149Zone 16 - T dew point room2 Bytes9.1 temperature (°C)CRT
150Logic function 1 - Input 11 Bit1.1 switchCWTU
151Logic function 1 - Input 21 Bit1.1 switchCWTU
152Logic function 1 - Input 31 Bit1.1 switchCWTU
153Logic function 1 - Input 41 Bit1.1 switchCWTU
154Logic function 1 - Input 51 Bit1.1 switchCWTU
155Logic function 1 - Input 61 Bit1.1 switchCWTU
156Logic function 1 - Input 71 Bit1.1 switchCWTU
157Logic function 1 - Input 81 Bit1.1 switchCWTU
158Logic function 1 - Input 91 Bit1.1 switchCWTU
159Logic function 1 - Input 101 Bit1.1 switchCWTU
160Logic function 1 - Input 111 Bit1.1 switchCWTU
161Logic function 1 - Input 121 Bit1.1 switchCWTU
162Logic function 1 - Input 131 Bit1.1 switchCWTU
163Logic function 1 - Input 141 Bit1.1 switchCWTU
164Logic function 1 - Input 151 Bit1.1 switchCWTU
165Logic function 1 - Input 161 Bit1.1 switchCWTU
166Logic function 1 - Output1 Bit1.1 switchCRT
167Logic function 2 - Input 11 Bit1.1 switchCWTU
168Logic function 2 - Input 21 Bit1.1 switchCWTU
169Logic function 2 - Input 31 Bit1.1 switchCWTU
170Logic function 2 - Input 41 Bit1.1 switchCWTU
171Logic function 2 - Input 51 Bit1.1 switchCWTU
172Logic function 2 - Input 61 Bit1.1 switchCWTU
173Logic function 2 - Input 71 Bit1.1 switchCWTU
174Logic function 2 - Input 81 Bit1.1 switchCWTU
175Logic function 2 - Input 91 Bit1.1 switchCWTU
176Logic function 2 - Input 101 Bit1.1 switchCWTU
177Logic function 2 - Input 111 Bit1.1 switchCWTU
178Logic function 2 - Input 121 Bit1.1 switchCWTU
179Logic function 2 - Input 131 Bit1.1 switchCWTU
180Logic function 2 - Input 141 Bit1.1 switchCWTU
181Logic function 2 - Input 151 Bit1.1 switchCWTU
182Logic function 2 - Input 161 Bit1.1 switchCWTU
183Logic function 2 - Output1 Bit1.1 switchCRT
Parameters (160)
ParameterTypeDefault
Manual operationslistenabled
Disable from buslistno
Delay after bus voltage recoverytime500
Restore auto mode timetime900
Systemlistheating
Mode switching (heating/cooling)listfrom bus
Activation delay [s]unsignedInt 0…255180
Binary input prioritylistno
Access passwordunsignedInt 0…99999999
Power loss alarmlistdisabled
Access passwordlistdisabled
Logic functionlistdisabled
Logic operationlistOR
Output cyclic transmission intervallistno sending
Logic object 1listdisabled
Logic object 2listdisabled
Logic object 3listdisabled
Logic object 4listdisabled
Logic object 1 negatedlistno
Logic object 2 negatedlistno
Logic object 3 negatedlistno
Logic object 4 negatedlistno
Logic object 1 read at startuplistno
Logic object 2 read at startuplistno
Logic object 3 read at startuplistno
Logic object 4 read at startuplistno
Logic object 1 default valuelistnone
Logic object 2 default valuelistnone
Logic object 3 default valuelistnone
Logic object 4 default valuelistnone
Logical functionslistdisabled
Activation of mixing grouplistfrom binary input
Logic object 5listdisabled
Logic object 6listdisabled
Logic object 7listdisabled
Logic object 8listdisabled
Logic object 9listdisabled
Logic object 10listdisabled
Logic object 11listdisabled
Logic object 12listdisabled
Logic object 13listdisabled
Logic object 14listdisabled
Logic object 15listdisabled
Logic object 16listdisabled
Logic object 5 negatedlistno
Logic object 6 negatedlistno
Logic object 7 negatedlistno
Logic object 8 negatedlistno
Logic object 9 negatedlistno
Logic object 10 negatedlistno
Logic object 11 negatedlistno
Logic object 12 negatedlistno
Logic object 13 negatedlistno
Logic object 14 negatedlistno
Logic object 15 negatedlistno
Logic object 16 negatedlistno
Logic object 5 read at startuplistno
Logic object 6 read at startuplistno
Logic object 7 read at startuplistno
Logic object 8 read at startuplistno
Logic object 9 read at startuplistno
Logic object 10 read at startuplistno
Logic object 11 read at startuplistno
Logic object 12 read at startuplistno
Logic object 13 read at startuplistno
Logic object 14 read at startuplistno
Logic object 15 read at startuplistno
Logic object 16 read at startuplistno
Logic object 5 default valuelistnone
Logic object 6 default valuelistnone
Logic object 7 default valuelistnone
Logic object 8 default valuelistnone
Logic object 9 default valuelistnone
Logic object 10 default valuelistnone
Logic object 11 default valuelistnone
Logic object 12 default valuelistnone
Logic object 13 default valuelistnone
Logic object 14 default valuelistnone
Logic object 15 default valuelistnone
Logic object 16 default valuelistnone
Delay after bus voltage recoverytime400
DO2 physical output controllistno
Disable output from buslistno
Signal from buslistnot inverted
DO3 physical output controllistno
Input 1list[AI] delivery temperature sensor
Filter typelistmedium
Contact typelistNO (normally open)
Debounce timetime20
Correction of measured temperaturelist0.0 °C
Min change of value to send [K]list0.4 K
Cyclic sending intervallistno sending
Threshold 1listnot active
Threshold 2listnot active
Cyclic sending interval for thresholdslistno sending
Value [°C]float 0…507
Value [°C]float 0…5045
Hysteresislist0.2 K
Input 2listdisabled
Input 3listdisabled
Input 4list[DI] flow request contact
Input 4listdisabled
Input 5list[DI] heating/cooling changeover contact
Input 5listdisabled
Outside temperaturelistdisabled
Reading at startlistno
Cyclic reading intervallistno reading
Zone numberunsignedInt 1…161
Analog sensors timeouttime300
Cyclic sending interval calculated T dew pointlistno sending
Control typelistfixed point
Fixed point delivery setpoint [0.1 °C]unsignedInt 200…600350
Min delivery setpoint [0.1 °C]unsignedInt 200…400300
Max delivery setpoint [0.1 °C]unsignedInt 300…600400
Outside temperature T1, compensation start [0.1 °C]unsignedInt 100…250180
Outside temperature T0, project [0.1 °C]signedInt -200…1000
Project delivery setpoint [0.1 °C]unsignedInt 200…600300
ΔT delivery/return (project value) [0.1 K]signedInt 10…10060
Setpoint change range [0.1 °C]signedInt 10…15080
Enable overtemperature alarmlistno
Enable low temperature reportinglistno
Overtemperature alarm setpoint [0.1 °C]unsignedInt 400…700450
Low temperature indicating setpoint [0.1 °C]unsignedInt 100…400200
Cyclic sending interval for current delivery setpointlistno sending
Min change of actual delivery setpoint value to sendlist0.2 K
System inertia [%]unsignedInt 15…10060
Fixed point delivery setpoint [0.1 °C]unsignedInt 70…250160
Project delivery setpoint [0.1 °C]unsignedInt 70…250160
Min delivery setpoint [0.1 °C]unsignedInt 70…250160
Max delivery setpoint [0.1 °C]unsignedInt 150…300200
Outside temperature T2, compensation start [0.1 °C]unsignedInt 200…400250
Outside temperature T3, project [0.1 °C]unsignedInt 200…400350
Cyclic sending interval max T dewpointlistno sending
Enable undertemperature alarmlistno
Undertemperature alarm setpoint [0.1 °C]unsignedInt 90…200130
Enable high temperature reportinglistno
High temperature indicating setpoint [0.1 °C]unsignedInt 200…300250
Safety value [0.1 °C]signedInt -50…5015
Circulator locklistno
Set mixing valve to bypasslistno
Min change of max T dewpoint value to sendlist0.4 K
Enable anticondensation alarmlistno
Servomotor for mixing valvelist3 point floating
Servomotor opening time [s]unsignedInt 0…255145
Proportional band [0.1 K]unsignedInt 5…500150
Integral time [s]signedInt 1…1500600
Dead band [0.1 K]unsignedInt 0…102
Enable valve protection functionlistno
Frequencylistonce a week
Time intervallist10 s
Enable manual modelistno
Disable mixing valve from buslistno
Disable circulator from buslistno
Enable valve position feedbacklistno
Min change of value to sendlist3%
Activate internal dewpoint processinglistno
Relative humidity Communication Objectlist2 bytes (DPT 9.007)
Display languagelistenglish
Output sendinglistboth values
Output updatelistat value change

Version history

ApplicationApp noFingerprintFirst seenSizeFile
APEKHH1TP 0.2 latest$4848763F2026-11-25120 KBDownload

About this file

This is the official ETS product database for the Ekinex S.p.A. Actuator-controller for mixing group (EK-HH1-TP), published by the manufacturer in the KNX online catalog. To use it, open ETS, go to Catalogs → Import and choose the downloaded .knxprod file. The device then appears in your catalog and can be added to a project. Older versions are kept so existing projects can be matched to the application program they were commissioned with.

More from Ekinex S.p.A.

All Ekinex S.p.A. products