KNX Database
Ekinex S.p.A. EK-CG2-TP Universal interface 4 DI / NTC

Universal interface 4 DI / NTC EK-CG2-TP

Ekinex S.p.A. · Order number EK-CG2-TP · Heating, cooling and ventilation

Universal interface 4 DI / NTC

Download .knxprod APEKCG2TP 0.1 · 279 KB

Product

ManufacturerEkinex S.p.A.
Product nameUniversal interface 4 DI / NTC
Order numberEK-CG2-TP
HardwareInterfaccia universale 4 DI / NTC
MediumTwisted Pair
Bus current (mA)10
Rail mountedNo
RegistrationCertified · 2017-10-23
Languagesen-US, de-DE, fr-FR, it-IT
Catalog entryM-00B6_H-00B60000002D-1_HP-4347-01-0029_CI-EK.2DCG2.2DTP-2
Fingerprint0029
SHA-2564f27d1922d17eec3eaa0cc6ec4aee9ec3902de2f52b4ea6bcd61e8c0683d92f8
First seen2026-11-25
Markets69 markets

Application program: APEKCG2TP 0.1

Application number$4347
Version0.1
Mask versionMV-07B0 (System B)
KNX Data SecureNo
Minimum ETS version4.0
Parameters1621
Group objects621
Group objects (621)
NoNameFunctionSizeDPTFlags
1Technical alarm1 Bit1.5 alarmCW
2Input 1 - Lock command1 Bit1.3 enableCWU
2Inputs 1 and 2 - Lock command1 Bit1.3 enableCWU
3Input 1 - Switching status 1-bit object 11 Bit1.1 switchCWTU
3Input 1 - Switching status 2-bits object 12 Bit2.1 switch controlCWTU
3Input 1 - Switching status 1-unsigned byte object 11 Byte5.1 percentage (0..100%)CWTU
3Input 1 - Switching status 1-signed byte object 11 Byte6.1 percentage (-128..127%)CWTU
3Input 1 - Switching status 2-unsigned bytes object 12 Bytes7.1 pulsesCWTU
3Input 1 - Switching status 2-signed bytes object 12 Bytes8.1 pulses differenceCWTU
3Input 1 - Switching status 2-bytes floating value object 12 Bytes9.1 temperature (°C)CWTU
4Input 1 - Switching status 1-bit object 21 Bit1.1 switchCWTU
4Input 1 - Switching status 2-bits object 22 Bit2.1 switch controlCWTU
4Input 1 - Switching status 1-unsigned byte object 21 Byte5.1 percentage (0..100%)CWTU
4Input 1 - Switching status 1-signed byte object 21 Byte6.1 percentage (-128..127%)CWTU
4Input 1 - Switching status 2-unsigned bytes object 22 Bytes7.1 pulsesCWTU
4Input 1 - Switching status 2-signed bytes object 22 Bytes8.1 pulses differenceCWTU
4Input 1 - Switching status 2-bytes floating value object 22 Bytes9.1 temperature (°C)CWTU
5Input 1 - Switching status 1-bit object 31 Bit1.1 switchCWTU
5Input 1 - Switching status 2-bits object 32 Bit2.1 switch controlCWTU
5Input 1 - Switching status 1-unsigned byte object 31 Byte5.1 percentage (0..100%)CWTU
5Input 1 - Switching status 1-signed byte object 31 Byte6.1 percentage (-128..127%)CWTU
5Input 1 - Switching status 2-unsigned bytes object 32 Bytes7.1 pulsesCWTU
5Input 1 - Switching status 2-signed bytes object 32 Bytes8.1 pulses differenceCWTU
5Input 1 - Switching status 2-bytes floating value object 32 Bytes9.1 temperature (°C)CWTU
6Input 1 - Switching status 1-bit object 41 Bit1.1 switchCWTU
6Input 1 - Switching status 2-bits object 42 Bit2.1 switch controlCWTU
6Input 1 - Switching status 1-unsigned byte object 41 Byte5.1 percentage (0..100%)CWTU
6Input 1 - Switching status 1-signed byte object 41 Byte6.1 percentage (-128..127%)CWTU
6Input 1 - Switching status 2-unsigned bytes object 42 Bytes7.1 pulsesCWTU
6Input 1 - Switching status 2-signed bytes object 42 Bytes8.1 pulses differenceCWTU
6Input 1 - Switching status 2-bytes floating value object 42 Bytes9.1 temperature (°C)CWTU
7Input 1 - Switching status 1-bit object 51 Bit1.1 switchCWTU
7Input 1 - Switching status 2-bits object 52 Bit2.1 switch controlCWTU
7Input 1 - Switching status 1-unsigned byte object 51 Byte5.1 percentage (0..100%)CWTU
7Input 1 - Switching status 1-signed byte object 51 Byte6.1 percentage (-128..127%)CWTU
7Input 1 - Switching status 2-unsigned bytes object 52 Bytes7.1 pulsesCWTU
7Input 1 - Switching status 2-signed bytes object 52 Bytes8.1 pulses differenceCWTU
7Input 1 - Switching status 2-bytes floating value object 52 Bytes9.1 temperature (°C)CWTU
8Input 1 - Switching status 1-bit object 61 Bit1.1 switchCWTU
8Input 1 - Switching status 2-bits object 62 Bit2.1 switch controlCWTU
8Input 1 - Switching status 1-unsigned byte object 61 Byte5.1 percentage (0..100%)CWTU
8Input 1 - Switching status 1-signed byte object 61 Byte6.1 percentage (-128..127%)CWTU
8Input 1 - Switching status 2-unsigned bytes object 62 Bytes7.1 pulsesCWTU
8Input 1 - Switching status 2-signed bytes object 62 Bytes8.1 pulses differenceCWTU
8Input 1 - Switching status 2-bytes floating value object 62 Bytes9.1 temperature (°C)CWTU
9Input 1 - Switching status 1-bit object 71 Bit1.1 switchCWTU
9Input 1 - Switching status 2-bits object 72 Bit2.1 switch controlCWTU
9Input 1 - Switching status 1-unsigned byte object 71 Byte5.1 percentage (0..100%)CWTU
9Input 1 - Switching status 1-signed byte object 71 Byte6.1 percentage (-128..127%)CWTU
9Input 1 - Switching status 2-unsigned bytes object 72 Bytes7.1 pulsesCWTU
9Input 1 - Switching status 2-signed bytes object 72 Bytes8.1 pulses differenceCWTU
9Input 1 - Switching status 2-bytes floating value object 72 Bytes9.1 temperature (°C)CWTU
10Input 1 - Switching status 1-bit object 81 Bit1.1 switchCWTU
10Input 1 - Switching status 2-bits object 82 Bit2.1 switch controlCWTU
10Input 1 - Switching status 1-unsigned byte object 81 Byte5.1 percentage (0..100%)CWTU
10Input 1 - Switching status 1-signed byte object 81 Byte6.1 percentage (-128..127%)CWTU
10Input 1 - Switching status 2-unsigned bytes object 82 Bytes7.1 pulsesCWTU
10Input 1 - Switching status 2-signed bytes object 82 Bytes8.1 pulses differenceCWTU
10Input 1 - Switching status 2-bytes floating value object 82 Bytes9.1 temperature (°C)CWTU
11Input 1 - Switching command1 Bit1.1 switchCWTU
11Input 1 - Dedicated stop command1 Bit1.17 triggerCT
11Inputs 1 and 2 - Switching command1 Bit1.1 switchCWTU
11Inputs 1 and 2 - Dedicated stop command1 Bit1.17 triggerCT
12Inputs 1 and 2 - Dimming up / down / stop command4 Bit3.7 dimming controlCT
12Input 1 - Dimming up / down / stop command4 Bit3.7 dimming controlCT
14Input 1 - Stop-step up / down command1 Bit1.7 stepCT
14Inputs 1 and 2 - Stop-step up / down command1 Bit1.7 stepCT
15Inputs 1 and 2 - Move up / down command1 Bit1.8 up/downCT
15Input 1 - Move up / down command1 Bit1.8 up/downCT
16Input 1 - Scene number1 Byte17.1 scene numberCT
16Input 1 - Counter value 1 byte1 Byte5.10 counter pulses (0..255)CRT
16Input 1 - Counter value 2 bytes2 Bytes7.1 pulsesCRT
16Input 1 - Counter value 4 bytes4 Bytes12.1 counter pulses (unsigned)CRT
17Input 1 - Counter reset command1 Bit1.15 resetCW
18Input 1 - Counter runout1 Bit1.5 alarmCRWT
19Input 2 - Lock command1 Bit1.3 enableCWU
20Input 2 - Switching status 1-bit object 11 Bit1.1 switchCWTU
20Input 2 - Switching status 2-bits object 12 Bit2.1 switch controlCWTU
20Input 2 - Switching status 1-unsigned byte object 11 Byte5.1 percentage (0..100%)CWTU
20Input 2 - Switching status 1-signed byte object 11 Byte6.1 percentage (-128..127%)CWTU
20Input 2 - Switching status 2-unsigned bytes object 12 Bytes7.1 pulsesCWTU
20Input 2 - Switching status 2-signed bytes object 12 Bytes8.1 pulses differenceCWTU
20Input 2 - Switching status 2-bytes floating value object 12 Bytes9.1 temperature (°C)CWTU
21Input 2 - Switching status 1-bit object 21 Bit1.1 switchCWTU
21Input 2 - Switching status 2-bits object 22 Bit2.1 switch controlCWTU
21Input 2 - Switching status 1-unsigned byte object 21 Byte5.1 percentage (0..100%)CWTU
21Input 2 - Switching status 1-signed byte object 21 Byte6.1 percentage (-128..127%)CWTU
21Input 2 - Switching status 2-unsigned bytes object 22 Bytes7.1 pulsesCWTU
21Input 2 - Switching status 2-signed bytes object 22 Bytes8.1 pulses differenceCWTU
21Input 2 - Switching status 2-bytes floating value object 22 Bytes9.1 temperature (°C)CWTU
22Input 2 - Switching status 1-bit object 31 Bit1.1 switchCWTU
22Input 2 - Switching status 2-bits object 32 Bit2.1 switch controlCWTU
22Input 2 - Switching status 1-unsigned byte object 31 Byte5.1 percentage (0..100%)CWTU
22Input 2 - Switching status 1-signed byte object 31 Byte6.1 percentage (-128..127%)CWTU
22Input 2 - Switching status 2-unsigned bytes object 32 Bytes7.1 pulsesCWTU
22Input 2 - Switching status 2-signed bytes object 32 Bytes8.1 pulses differenceCWTU
22Input 2 - Switching status 2-bytes floating value object 32 Bytes9.1 temperature (°C)CWTU
23Input 2 - Switching status 1-bit object 41 Bit1.1 switchCWTU
23Input 2 - Switching status 2-bits object 42 Bit2.1 switch controlCWTU
23Input 2 - Switching status 1-unsigned byte object 41 Byte5.1 percentage (0..100%)CWTU
23Input 2 - Switching status 1-signed byte object 41 Byte6.1 percentage (-128..127%)CWTU
23Input 2 - Switching status 2-unsigned bytes object 42 Bytes7.1 pulsesCWTU
23Input 2 - Switching status 2-signed bytes object 42 Bytes8.1 pulses differenceCWTU
23Input 2 - Switching status 2-bytes floating value object 42 Bytes9.1 temperature (°C)CWTU
24Input 2 - Switching status 1-bit object 51 Bit1.1 switchCWTU
24Input 2 - Switching status 2-bits object 52 Bit2.1 switch controlCWTU
24Input 2 - Switching status 1-unsigned byte object 51 Byte5.1 percentage (0..100%)CWTU
24Input 2 - Switching status 1-signed byte object 51 Byte6.1 percentage (-128..127%)CWTU
24Input 2 - Switching status 2-unsigned bytes object 52 Bytes7.1 pulsesCWTU
24Input 2 - Switching status 2-signed bytes object 52 Bytes8.1 pulses differenceCWTU
24Input 2 - Switching status 2-bytes floating value object 52 Bytes9.1 temperature (°C)CWTU
25Input 2 - Switching status 1-bit object 61 Bit1.1 switchCWTU
25Input 2 - Switching status 2-bits object 62 Bit2.1 switch controlCWTU
25Input 2 - Switching status 1-unsigned byte object 61 Byte5.1 percentage (0..100%)CWTU
25Input 2 - Switching status 1-signed byte object 61 Byte6.1 percentage (-128..127%)CWTU
25Input 2 - Switching status 2-unsigned bytes object 62 Bytes7.1 pulsesCWTU
25Input 2 - Switching status 2-signed bytes object 62 Bytes8.1 pulses differenceCWTU
25Input 2 - Switching status 2-bytes floating value object 62 Bytes9.1 temperature (°C)CWTU
26Input 2 - Switching status 1-bit object 71 Bit1.1 switchCWTU
26Input 2 - Switching status 2-bits object 72 Bit2.1 switch controlCWTU
26Input 2 - Switching status 1-unsigned byte object 71 Byte5.1 percentage (0..100%)CWTU
26Input 2 - Switching status 1-signed byte object 71 Byte6.1 percentage (-128..127%)CWTU
26Input 2 - Switching status 2-unsigned bytes object 72 Bytes7.1 pulsesCWTU
26Input 2 - Switching status 2-signed bytes object 72 Bytes8.1 pulses differenceCWTU
26Input 2 - Switching status 2-bytes floating value object 72 Bytes9.1 temperature (°C)CWTU
27Input 2 - Switching status 1-bit object 81 Bit1.1 switchCWTU
27Input 2 - Switching status 2-bits object 82 Bit2.1 switch controlCWTU
27Input 2 - Switching status 1-unsigned byte object 81 Byte5.1 percentage (0..100%)CWTU
27Input 2 - Switching status 1-signed byte object 81 Byte6.1 percentage (-128..127%)CWTU
27Input 2 - Switching status 2-unsigned bytes object 82 Bytes7.1 pulsesCWTU
27Input 2 - Switching status 2-signed bytes object 82 Bytes8.1 pulses differenceCWTU
27Input 2 - Switching status 2-bytes floating value object 82 Bytes9.1 temperature (°C)CWTU
28Input 2 - Switching command1 Bit1.1 switchCWTU
28Input 2 - Dedicated stop command1 Bit1.17 triggerCT
29Input 2 - Dimming up / down / stop command4 Bit3.7 dimming controlCT
31Input 2 - Stop-step up / down command1 Bit1.7 stepCT
32Input 2 - Move up / down command1 Bit1.8 up/downCT
33Input 2 - Scene number1 Byte17.1 scene numberCT
33Input 2 - Counter value 2 bytes2 Bytes7.1 pulsesCRT
33Input 2 - Counter value 1 byte1 Byte5.10 counter pulses (0..255)CRT
33Input 2 - Counter value 4 bytes4 Bytes12.1 counter pulses (unsigned)CRT
34Input 2 - Counter reset command1 Bit1.15 resetCW
35Input 2 - Counter runout1 Bit1.5 alarmCRWT
36Input 3 - Lock command1 Bit1.3 enableCWU
36Inputs 3 and 4 - Lock command1 Bit1.3 enableCWU
37Input 3 - Switching status 1-bit object 11 Bit1.1 switchCWTU
37Input 3 - Switching status 2-bits object 12 Bit2.1 switch controlCWTU
37Input 3 - Switching status 1-unsigned byte object 11 Byte5.1 percentage (0..100%)CWTU
37Input 3 - Switching status 1-signed byte object 11 Byte6.1 percentage (-128..127%)CWTU
37Input 3 - Switching status 2-unsigned bytes object 12 Bytes7.1 pulsesCWTU
37Input 3 - Switching status 2-signed bytes object 12 Bytes8.1 pulses differenceCWTU
37Input 3 - Switching status 2-bytes floating value object 12 Bytes9.1 temperature (°C)CWTU
38Input 3 - Switching status 1-bit object 21 Bit1.1 switchCWTU
38Input 3 - Switching status 2-bits object 22 Bit2.1 switch controlCWTU
38Input 3 - Switching status 1-unsigned byte object 21 Byte5.1 percentage (0..100%)CWTU
38Input 3 - Switching status 1-signed byte object 21 Byte6.1 percentage (-128..127%)CWTU
38Input 3 - Switching status 2-unsigned bytes object 22 Bytes7.1 pulsesCWTU
38Input 3 - Switching status 2-signed bytes object 22 Bytes8.1 pulses differenceCWTU
38Input 3 - Switching status 2-bytes floating value object 22 Bytes9.1 temperature (°C)CWTU
39Input 3 - Switching status 1-bit object 31 Bit1.1 switchCWTU
39Input 3 - Switching status 2-bits object 32 Bit2.1 switch controlCWTU
39Input 3 - Switching status 1-unsigned byte object 31 Byte5.1 percentage (0..100%)CWTU
39Input 3 - Switching status 1-signed byte object 31 Byte6.1 percentage (-128..127%)CWTU
39Input 3 - Switching status 2-unsigned bytes object 32 Bytes7.1 pulsesCWTU
39Input 3 - Switching status 2-signed bytes object 32 Bytes8.1 pulses differenceCWTU
39Input 3 - Switching status 2-bytes floating value object 32 Bytes9.1 temperature (°C)CWTU
40Input 3 - Switching status 1-bit object 41 Bit1.1 switchCWTU
40Input 3 - Switching status 2-bits object 42 Bit2.1 switch controlCWTU
40Input 3 - Switching status 1-unsigned byte object 41 Byte5.1 percentage (0..100%)CWTU
40Input 3 - Switching status 1-signed byte object 41 Byte6.1 percentage (-128..127%)CWTU
40Input 3 - Switching status 2-unsigned bytes object 42 Bytes7.1 pulsesCWTU
40Input 3 - Switching status 2-signed bytes object 42 Bytes8.1 pulses differenceCWTU
40Input 3 - Switching status 2-bytes floating value object 42 Bytes9.1 temperature (°C)CWTU
41Input 3 - Switching status 1-bit object 51 Bit1.1 switchCWTU
41Input 3 - Switching status 2-bits object 52 Bit2.1 switch controlCWTU
41Input 3 - Switching status 1-unsigned byte object 51 Byte5.1 percentage (0..100%)CWTU
41Input 3 - Switching status 1-signed byte object 51 Byte6.1 percentage (-128..127%)CWTU
41Input 3 - Switching status 2-unsigned bytes object 52 Bytes7.1 pulsesCWTU
41Input 3 - Switching status 2-signed bytes object 52 Bytes8.1 pulses differenceCWTU
41Input 3 - Switching status 2-bytes floating value object 52 Bytes9.1 temperature (°C)CWTU
42Input 3 - Switching status 1-bit object 61 Bit1.1 switchCWTU
42Input 3 - Switching status 2-bits object 62 Bit2.1 switch controlCWTU
42Input 3 - Switching status 1-unsigned byte object 61 Byte5.1 percentage (0..100%)CWTU
42Input 3 - Switching status 1-signed byte object 61 Byte6.1 percentage (-128..127%)CWTU
42Input 3 - Switching status 2-unsigned bytes object 62 Bytes7.1 pulsesCWTU
42Input 3 - Switching status 2-signed bytes object 62 Bytes8.1 pulses differenceCWTU
42Input 3 - Switching status 2-bytes floating value object 62 Bytes9.1 temperature (°C)CWTU
43Input 3 - Switching status 1-bit object 71 Bit1.1 switchCWTU
43Input 3 - Switching status 2-bits object 72 Bit2.1 switch controlCWTU
43Input 3 - Switching status 1-unsigned byte object 71 Byte5.1 percentage (0..100%)CWTU
43Input 3 - Switching status 1-signed byte object 71 Byte6.1 percentage (-128..127%)CWTU
43Input 3 - Switching status 2-unsigned bytes object 72 Bytes7.1 pulsesCWTU
43Input 3 - Switching status 2-signed bytes object 72 Bytes8.1 pulses differenceCWTU
43Input 3 - Switching status 2-bytes floating value object 72 Bytes9.1 temperature (°C)CWTU
44Input 3 - Switching status 1-bit object 81 Bit1.1 switchCWTU
44Input 3 - Switching status 2-bits object 82 Bit2.1 switch controlCWTU
44Input 3 - Switching status 1-unsigned byte object 81 Byte5.1 percentage (0..100%)CWTU
44Input 3 - Switching status 1-signed byte object 81 Byte6.1 percentage (-128..127%)CWTU
44Input 3 - Switching status 2-unsigned bytes object 82 Bytes7.1 pulsesCWTU
44Input 3 - Switching status 2-signed bytes object 82 Bytes8.1 pulses differenceCWTU
44Input 3 - Switching status 2-bytes floating value object 82 Bytes9.1 temperature (°C)CWTU
45Input 3 - Switching command1 Bit1.1 switchCWTU
45Input 3 - Dedicated stop command1 Bit1.17 triggerCT
45Inputs 3 and 4 - Switching command1 Bit1.1 switchCWTU
45Inputs 3 and 4 - Dedicated stop command1 Bit1.17 triggerCT
46Input 3 - Dimming up / down / stop command4 Bit3.7 dimming controlCT
46Inputs 3 and 4 - Dimming up / down / stop command4 Bit3.7 dimming controlCT
48Input 3 - Stop-step up / down command1 Bit1.7 stepCT
48Inputs 3 and 4 - Stop-step up / down command1 Bit1.7 stepCT
49Input 3 - Move up / down command1 Bit1.8 up/downCT
49Inputs 3 and 4 - Move up / down command1 Bit1.8 up/downCT
50Input 3 - Scene number1 Byte17.1 scene numberCT
50Input 3 - Counter value 2 bytes2 Bytes7.1 pulsesCRT
50Input 3 - Counter value 1 byte1 Byte5.10 counter pulses (0..255)CRT
50Input 3 - Counter value 4 bytes4 Bytes12.1 counter pulses (unsigned)CRT
51Input 3 - Counter reset command1 Bit1.15 resetCW
52Input 3 - Counter runout1 Bit1.5 alarmCRWT
53Input 4 - Lock command1 Bit1.3 enableCWU
54Input 4 - Switching status 1-bit object 11 Bit1.1 switchCWTU
54Input 4 - Switching status 2-bits object 12 Bit2.1 switch controlCWTU
54Input 4 - Switching status 1-unsigned byte object 11 Byte5.1 percentage (0..100%)CWTU
54Input 4 - Switching status 1-signed byte object 11 Byte6.1 percentage (-128..127%)CWTU
54Input 4 - Switching status 2-unsigned bytes object 12 Bytes7.1 pulsesCWTU
54Input 4 - Switching status 2-signed bytes object 12 Bytes8.1 pulses differenceCWTU
54Input 4 - Switching status 2-bytes floating value object 12 Bytes9.1 temperature (°C)CWTU
55Input 4 - Switching status 1-bit object 21 Bit1.1 switchCWTU
55Input 4 - Switching status 2-bits object 22 Bit2.1 switch controlCWTU
55Input 4 - Switching status 1-unsigned byte object 21 Byte5.1 percentage (0..100%)CWTU
55Input 4 - Switching status 1-signed byte object 21 Byte6.1 percentage (-128..127%)CWTU
55Input 4 - Switching status 2-unsigned bytes object 22 Bytes7.1 pulsesCWTU
55Input 4 - Switching status 2-signed bytes object 22 Bytes8.1 pulses differenceCWTU
55Input 4 - Switching status 2-bytes floating value object 22 Bytes9.1 temperature (°C)CWTU
56Input 4 - Switching status 1-bit object 31 Bit1.1 switchCWTU
56Input 4 - Switching status 2-bits object 32 Bit2.1 switch controlCWTU
56Input 4 - Switching status 1-unsigned byte object 31 Byte5.1 percentage (0..100%)CWTU
56Input 4 - Switching status 1-signed byte object 31 Byte6.1 percentage (-128..127%)CWTU
56Input 4 - Switching status 2-unsigned bytes object 32 Bytes7.1 pulsesCWTU
56Input 4 - Switching status 2-signed bytes object 32 Bytes8.1 pulses differenceCWTU
56Input 4 - Switching status 2-bytes floating value object 32 Bytes9.1 temperature (°C)CWTU
57Input 4 - Switching status 1-bit object 41 Bit1.1 switchCWTU
57Input 4 - Switching status 2-bits object 42 Bit2.1 switch controlCWTU
57Input 4 - Switching status 1-unsigned byte object 41 Byte5.1 percentage (0..100%)CWTU
57Input 4 - Switching status 1-signed byte object 41 Byte6.1 percentage (-128..127%)CWTU
57Input 4 - Switching status 2-unsigned bytes object 42 Bytes7.1 pulsesCWTU
57Input 4 - Switching status 2-signed bytes object 42 Bytes8.1 pulses differenceCWTU
57Input 4 - Switching status 2-bytes floating value object 42 Bytes9.1 temperature (°C)CWTU
58Input 4 - Switching status 1-bit object 51 Bit1.1 switchCWTU
58Input 4 - Switching status 2-bits object 52 Bit2.1 switch controlCWTU
58Input 4 - Switching status 1-unsigned byte object 51 Byte5.1 percentage (0..100%)CWTU
58Input 4 - Switching status 1-signed byte object 51 Byte6.1 percentage (-128..127%)CWTU
58Input 4 - Switching status 2-unsigned bytes object 52 Bytes7.1 pulsesCWTU
58Input 4 - Switching status 2-signed bytes object 52 Bytes8.1 pulses differenceCWTU
58Input 4 - Switching status 2-bytes floating value object 52 Bytes9.1 temperature (°C)CWTU
59Input 4 - Switching status 1-bit object 61 Bit1.1 switchCWTU
59Input 4 - Switching status 2-bits object 62 Bit2.1 switch controlCWTU
59Input 4 - Switching status 1-unsigned byte object 61 Byte5.1 percentage (0..100%)CWTU
59Input 4 - Switching status 1-signed byte object 61 Byte6.1 percentage (-128..127%)CWTU
59Input 4 - Switching status 2-unsigned bytes object 62 Bytes7.1 pulsesCWTU
59Input 4 - Switching status 2-signed bytes object 62 Bytes8.1 pulses differenceCWTU
59Input 4 - Switching status 2-bytes floating value object 62 Bytes9.1 temperature (°C)CWTU
60Input 4 - Switching status 1-bit object 71 Bit1.1 switchCWTU
60Input 4 - Switching status 2-bits object 72 Bit2.1 switch controlCWTU
60Input 4 - Switching status 1-unsigned byte object 71 Byte5.1 percentage (0..100%)CWTU
60Input 4 - Switching status 1-signed byte object 71 Byte6.1 percentage (-128..127%)CWTU
60Input 4 - Switching status 2-unsigned bytes object 72 Bytes7.1 pulsesCWTU
60Input 4 - Switching status 2-signed bytes object 72 Bytes8.1 pulses differenceCWTU
60Input 4 - Switching status 2-bytes floating value object 72 Bytes9.1 temperature (°C)CWTU
61Input 4 - Switching status 1-bit object 81 Bit1.1 switchCWTU
61Input 4 - Switching status 2-bits object 82 Bit2.1 switch controlCWTU
61Input 4 - Switching status 1-unsigned byte object 81 Byte5.1 percentage (0..100%)CWTU
61Input 4 - Switching status 1-signed byte object 81 Byte6.1 percentage (-128..127%)CWTU
61Input 4 - Switching status 2-unsigned bytes object 82 Bytes7.1 pulsesCWTU
61Input 4 - Switching status 2-signed bytes object 82 Bytes8.1 pulses differenceCWTU
61Input 4 - Switching status 2-bytes floating value object 82 Bytes9.1 temperature (°C)CWTU
62Input 4 - Switching command1 Bit1.1 switchCWTU
62Input 4 - Dedicated stop command1 Bit1.17 triggerCT
63Input 4 - Dimming up / down / stop command4 Bit3.7 dimming controlCT
65Input 4 - Stop-step up / down command1 Bit1.7 stepCT
66Input 4 - Move up / down command1 Bit1.8 up/downCT
67Input 4 - Scene number1 Byte17.1 scene numberCT
67Input 4 - Counter value 2 bytes2 Bytes7.1 pulsesCRT
67Input 4 - Counter value 1 byte1 Byte5.10 counter pulses (0..255)CRT
67Input 4 - Counter value 4 bytes4 Bytes12.1 counter pulses (unsigned)CRT
68Input 4 - Counter reset command1 Bit1.15 resetCW
69Input 4 - Counter runout1 Bit1.5 alarmCRWT
70Led L1 - Command1 Bit1.1 switchCRWTU
71Led L2 - Command1 Bit1.1 switchCRWTU
72Led L3 - Command1 Bit1.1 switchCRWTU
73Led L4 - Command1 Bit1.1 switchCRWTU
74Logic function 1 - Input 11 Bit1.1 switchCWTU
75Logic function 1 - Input 21 Bit1.1 switchCWTU
76Logic function 1 - Input 31 Bit1.1 switchCWTU
77Logic function 1 - Input 41 Bit1.1 switchCWTU
78Logic function 1 - Output1 Bit1.1 switchCRT
79Logic function 2 - Input 11 Bit1.1 switchCWTU
80Logic function 2 - Input 21 Bit1.1 switchCWTU
81Logic function 2 - Input 31 Bit1.1 switchCWTU
82Logic function 2 - Input 41 Bit1.1 switchCWTU
83Logic function 2 - Output1 Bit1.1 switchCRT
84Logic function 3 - Input 11 Bit1.1 switchCWTU
85Logic function 3 - Input 21 Bit1.1 switchCWTU
86Logic function 3 - Input 31 Bit1.1 switchCWTU
87Logic function 3 - Input 41 Bit1.1 switchCWTU
88Logic function 3 - Output1 Bit1.1 switchCRT
89Logic function 4 - Input 11 Bit1.1 switchCWTU
90Logic function 4 - Input 21 Bit1.1 switchCWTU
91Logic function 4 - Input 31 Bit1.1 switchCWTU
92Logic function 4 - Input 41 Bit1.1 switchCWTU
93Logic function 4 - Output1 Bit1.1 switchCRT
94Input 1 - Temperature value2 Bytes9.1 temperature (°C)CRT
95Input 1 - Temperature threshold 1 - Switch1 Bit1.1 switchCRT
96Input 1 - Temperature threshold 2 - Switch1 Bit1.1 switchCRT
97Thermostat 1 - Room temperature (from bus)2 Bytes9.1 temperature (°C)CWTU
98Thermostat 1 - Humidity (2 bytes, from bus)2 Bytes9.7 humidity (%)CWTU
99Thermostat 1 - Humidity (1 byte, from bus)1 Byte5.1 percentage (0..100%)CWTU
100Thermostat 1 - Antistratification temperature (from bus)2 Bytes9.1 temperature (°C)CWTU
101Thermostat 1 - Outdoor temperature (from bus)2 Bytes9.1 temperature (°C)CWTU
102Thermostat 1 - Coil temperature (from bus)2 Bytes9.1 temperature (°C)CWTU
103Thermostat 1 - Floor temperature (from bus)2 Bytes9.1 temperature (°C)CWTU
104Thermostat 1 - Flow temperature (from bus)2 Bytes9.1 temperature (°C)CWTU
105Thermostat 1 - Windows contact sensor 1 (from bus)1 Bit1.19 window/doorCWTU
106Thermostat 1 - Windows contact sensor 2 (from bus)1 Bit1.19 window/doorCWTU
107Thermostat 1 - Presence sensor 1 (from bus)1 Bit1.18 occupancyCWTU
108Thermostat 1 - Presence sensor 2 (from bus)1 Bit1.18 occupancyCWTU
109Thermostat 1 - Card holder contact (from bus)1 Bit1.18 occupancyCWTU
110Thermostat 1 - Anticondensation (from bus)1 Bit1.1 switchCWTU
111Thermostat 1 - Weighted temperature2 Bytes9.1 temperature (°C)CRT
112Thermostat 1 - Heating/cooling status out1 Bit1.100 heating/coolingCRT
113Thermostat 1 - Heating/cooling status in1 Bit1.100 heating/coolingCW
114Thermostat 1 - HVAC mode in1 Byte20.102 HVAC modeCW
115Thermostat 1 - HVAC forced mode in1 Byte20.102 HVAC modeCW
116Thermostat 1 - HVAC mode out1 Byte20.102 HVAC modeCRT
117Thermostat 1 - HVAC manual mode1 Byte20.102 HVAC modeCWTU
118Thermostat 1 - Chrono active status1 Bit1.11 stateCRT
119Thermostat 1 - Actual setpoint2 Bytes9.1 temperature (°C)CRT
120Thermostat 1 - Manual setpoint2 Bytes9.1 temperature (°C)CW
121Thermostat 1 - Comfort setpoint (heating)2 Bytes9.1 temperature (°C)CRWTU
121Thermostat 1 - Input setpoint2 Bytes9.1 temperature (°C)CRWTU
122Thermostat 1 - Comfort setpoint (cooling)2 Bytes9.1 temperature (°C)CRWTU
123Thermostat 1 - Standby setpoint (heating)2 Bytes9.1 temperature (°C)CRWTU
123Thermostat 1 - Standby offset (heating)2 Bytes9.2 temperature difference (K)CRWTU
124Thermostat 1 - Standby setpoint (cooling)2 Bytes9.1 temperature (°C)CRWTU
124Thermostat 1 - Standby offset (cooling)2 Bytes9.2 temperature difference (K)CRWTU
125Thermostat 1 - Economy setpoint (heating)2 Bytes9.1 temperature (°C)CRWTU
125Thermostat 1 - Economy offset (heating)2 Bytes9.2 temperature difference (K)CRWTU
126Thermostat 1 - Economy setpoint (cooling)2 Bytes9.1 temperature (°C)CRWTU
126Thermostat 1 - Economy offset (cooling)2 Bytes9.2 temperature difference (K)CRWTU
127Thermostat 1 - Building protection setpoint (heating)2 Bytes9.1 temperature (°C)CRWTU
128Thermostat 1 - Building protection setpoint (cooling)2 Bytes9.1 temperature (°C)CRWTU
129Thermostat 1 - Room temperature controller status1 Bit1.3 enableCRT
130Thermostat 1 - Heating out command1 Byte5.1 percentage (0..100%)CRT
130Thermostat 1 - Heating out command1 Bit1.1 switchCRT
130Thermostat 1 - Heating and cooling out command1 Bit1.1 switchCRT
130Thermostat 1 - Heating and cooling out command1 Byte5.1 percentage (0..100%)CRT
131Thermostat 1 - Cooling out command1 Byte5.1 percentage (0..100%)CRT
131Thermostat 1 - Cooling out command1 Bit1.1 switchCRT
132Thermostat 1 - Auxiliary heating output command1 Bit1.1 switchCRT
132Thermostat 1 - Auxiliary heating and cooling output command1 Bit1.1 switchCRT
133Thermostat 1 - Auxiliary cooling output command1 Bit1.1 switchCRT
134Thermostat 1 - Auxiliary heating disable1 Bit1.3 enableCW
135Thermostat 1 - Auxiliary cooling disable1 Bit1.3 enableCW
136Thermostat 1 - Fan continuous speed1 Byte5.1 percentage (0..100%)CRT
137Thermostat 1 - Fan speed 11 Bit1.1 switchCRT
138Thermostat 1 - Fan speed 21 Bit1.1 switchCRT
139Thermostat 1 - Fan speed 31 Bit1.1 switchCRT
140Thermostat 1 - Fan control disable1 Bit1.2 booleanCW
141Thermostat 1 - Alarm text14 Bytes16.0 Character String (ASCII)CRT
142Thermostat 1 - Manual setpoint active status1 Bit1.11 stateCRWTU
143Thermostat 1 - Fan manual speed1 Byte5.10 counter pulses (0..255)CRWTU
144Thermostat 1 - Fan speed1 Byte5.10 counter pulses (0..255)CRT
145Thermostat 1 - Fan manual active status1 Bit1.11 stateCRWTU
146Thermostat 1 - Room temperature control alarm1 Bit1.5 alarmCRT
147Thermostat 1 - Disable room temperature controller1 Bit1.1 switchCW
148Thermostat 1 - Dew-point temperature2 Bytes9.1 temperature (°C)CRT
149Thermostat 1 - Relative humidity setpoint for dehumidification2 Bytes9.7 humidity (%)CRWTU
150Thermostat 1 - Relative humidity setpoint for humidification2 Bytes9.7 humidity (%)CRWTU
151Thermostat 1 - Dehumidification command1 Bit1.1 switchCRT
152Thermostat 1 - Dehumidification integration control1 Bit1.1 switchCRT
153Thermostat 1 - Dehumidification integration control1 Bit1.1 switchCRT
154Thermostat 1 - Dehumidification control disable1 Bit1.2 booleanCW
155Thermostat 1 - Humidification command1 Bit1.1 switchCRT
156Thermostat 1 - Humidification control disable1 Bit1.2 booleanCW
157Thermostat 1 - Anticondensation alarm1 Bit1.5 alarmCRT
158Thermostat 1 - Thermal generator lock1 Bit1.5 alarmCW
159Thermostat 1 - Building protection HVAC mode active1 Bit1.11 stateCRT
160Thermostat 1 - Fan manual speed percentage1 Byte5.1 percentage (0..100%)CRT
161Thermostat 1 - Fan manual speed off status1 Bit1.11 stateCRT
162Input 2 - Temperature value2 Bytes9.1 temperature (°C)CRT
163Input 2 - Temperature threshold 1 - Switch1 Bit1.1 switchCRT
164Input 2 - Temperature threshold 2 - Switch1 Bit1.1 switchCRT
165Thermostat 2 - Room temperature (from bus)2 Bytes9.1 temperature (°C)CWTU
166Thermostat 2 - Humidity (2 bytes, from bus)2 Bytes9.7 humidity (%)CWTU
167Thermostat 2 - Humidity (1 byte, from bus)1 Byte5.1 percentage (0..100%)CWTU
168Thermostat 2 - Antistratification temperature (from bus)2 Bytes9.1 temperature (°C)CWTU
169Thermostat 2 - Outdoor temperature (from bus)2 Bytes9.1 temperature (°C)CWTU
170Thermostat 2 - Coil temperature (from bus)2 Bytes9.1 temperature (°C)CWTU
171Thermostat 2 - Floor temperature (from bus)2 Bytes9.1 temperature (°C)CWTU
172Thermostat 2 - Flow temperature (from bus)2 Bytes9.1 temperature (°C)CWTU
173Thermostat 2 - Windows contact sensor 1 (from bus)1 Bit1.19 window/doorCWTU
174Thermostat 2 - Windows contact sensor 2 (from bus)1 Bit1.19 window/doorCWTU
175Thermostat 2 - Presence sensor 1 (from bus)1 Bit1.18 occupancyCWTU
176Thermostat 2 - Presence sensor 2 (from bus)1 Bit1.18 occupancyCWTU
177Thermostat 2 - Contact of card holder (from bus)1 Bit1.18 occupancyCWTU
178Thermostat 2 - Anticondensation (from bus)1 Bit1.1 switchCWTU
179Thermostat 2 - Weighted temperature2 Bytes9.1 temperature (°C)CRT
180Thermostat 2 - Heating/cooling status out1 Bit1.100 heating/coolingCRT
181Thermostat 2 - Heating/cooling status in1 Bit1.100 heating/coolingCW
182Thermostat 2 - HVAC mode in1 Byte20.102 HVAC modeCW
183Thermostat 2 - HVAC forced mode in1 Byte20.102 HVAC modeCW
184Thermostat 2 - HVAC mode out1 Byte20.102 HVAC modeCRT
185Thermostat 2 - HVAC manual mode1 Byte20.102 HVAC modeCWTU
186Thermostat 2 - Chrono active status1 Bit1.11 stateCRT
187Thermostat 2 - Actual setpoint2 Bytes9.1 temperature (°C)CRT
188Thermostat 2 - Manual setpoint2 Bytes9.1 temperature (°C)CW
189Thermostat 2 - Input setpoint2 Bytes9.1 temperature (°C)CRWTU
189Thermostat 2 - Comfort setpoint (heating)2 Bytes9.1 temperature (°C)CRWTU
190Thermostat 2 - Comfort setpoint (cooling)2 Bytes9.1 temperature (°C)CRWTU
191Thermostat 2 - Standby setpoint (heating)2 Bytes9.1 temperature (°C)CRWTU
191Thermostat 2 - Standby offset (heating)2 Bytes9.2 temperature difference (K)CRWTU
192Thermostat 2 - Standby setpoint (cooling)2 Bytes9.1 temperature (°C)CRWTU
192Thermostat 2 - Standby offset (cooling)2 Bytes9.2 temperature difference (K)CRWTU
193Thermostat 2 - Economy setpoint (heating)2 Bytes9.1 temperature (°C)CRWTU
193Thermostat 2 - Economy offset (heating)2 Bytes9.2 temperature difference (K)CRWTU
194Thermostat 2 - Economy setpoint (cooling)2 Bytes9.1 temperature (°C)CRWTU
194Thermostat 2 - Economy offset (cooling)2 Bytes9.2 temperature difference (K)CRWTU
195Thermostat 2 - Building protection setpoint (heating)2 Bytes9.1 temperature (°C)CRWTU
196Thermostat 2 - Building protection setpoint (cooling)2 Bytes9.1 temperature (°C)CRWTU
197Thermostat 2 - Room temperature controller status1 Bit1.3 enableCRT
198Thermostat 2 - Heating and cooling out command1 Byte5.1 percentage (0..100%)CRT
198Thermostat 2 - Heating out command1 Byte5.1 percentage (0..100%)CRT
198Thermostat 2 - Heating and cooling out command1 Bit1.1 switchCRT
198Thermostat 2 - Heating out command1 Bit1.1 switchCRT
199Thermostat 2 - Cooling out command1 Byte5.1 percentage (0..100%)CRT
199Thermostat 2 - Cooling out command1 Bit1.1 switchCRT
200Thermostat 2 - Auxiliary heating and cooling output command1 Bit1.1 switchCRT
200Thermostat 2 - Auxiliary heating output command1 Bit1.1 switchCRT
201Thermostat 2 - Auxiliary cooling output command1 Bit1.1 switchCRT
202Thermostat 2 - Auxiliary heating disable1 Bit1.3 enableCW
203Thermostat 2 - Auxiliary cooling disable1 Bit1.3 enableCW
204Thermostat 2 - Fan continuous speed1 Byte5.1 percentage (0..100%)CRT
205Thermostat 2 - Fan speed 11 Bit1.1 switchCRT
206Thermostat 2 - Fan speed 21 Bit1.1 switchCRT
207Thermostat 2 - Fan speed 31 Bit1.1 switchCRT
208Thermostat 2 - Fan control disable1 Bit1.2 booleanCW
209Thermostat 2 - Alarm text14 Bytes16.0 Character String (ASCII)CRT
210Thermostat 2 - Manual/forced setpoint active status1 Bit1.11 stateCRWTU
211Thermostat 2 - Fan manual speed1 Byte5.10 counter pulses (0..255)CRWTU
212Thermostat 2 - Fan speed1 Byte5.10 counter pulses (0..255)CRT
213Thermostat 2 - Fan manual active status1 Bit1.11 stateCRWTU
214Thermostat 2 - Room temperature control alarm1 Bit1.5 alarmCRT
215Thermostat 2 - Disable room temperature controller1 Bit1.1 switchCW
216Thermostat 2 - Dew-point temperature2 Bytes9.1 temperature (°C)CRT
217Thermostat 2 - Relative humidity setpoint for dehumidification2 Bytes9.7 humidity (%)CRWTU
218Thermostat 2 - Relative humidity setpoint for humidification2 Bytes9.7 humidity (%)CRWTU
219Thermostat 2 - Dehumidification command1 Bit1.1 switchCRT
220Thermostat 2 - Dehumidification integration control1 Bit1.1 switchCRT
221Thermostat 2 - Dehumidification integration control1 Bit1.1 switchCRT
222Thermostat 2 - Dehumidification control disable1 Bit1.2 booleanCW
223Thermostat 2 - Humidification command1 Bit1.1 switchCRT
224Thermostat 2 - Humidification control disable1 Bit1.2 booleanCW
225Thermostat 2 - Anticondensation alarm1 Bit1.5 alarmCRT
226Thermostat 2 - Thermal generator lock1 Bit1.5 alarmCW
227Thermostat 2 - Building protection HVAC mode active1 Bit1.11 stateCRT
228Thermostat 2 - Fan manual speed percentage1 Byte5.1 percentage (0..100%)CRT
229Thermostat 2 - Fan manual speed off status1 Bit1.11 stateCRT
230Input 3 - Temperature value2 Bytes9.1 temperature (°C)CRT
231Input 3 - Temperature threshold 1 - Switch1 Bit1.1 switchCRT
232Input 3 - Temperature threshold 2 - Switch1 Bit1.1 switchCRT
233Thermostat 3 - Room temperature (from bus)2 Bytes9.1 temperature (°C)CWTU
234Thermostat 3 - Humidity (2 bytes, from bus)2 Bytes9.7 humidity (%)CWTU
235Thermostat 3 - Humidity (1 byte, from bus)1 Byte5.1 percentage (0..100%)CWTU
236Thermostat 3 - Antistratification temperature (from bus)2 Bytes9.1 temperature (°C)CWTU
237Thermostat 3 - Outdoor temperature (from bus)2 Bytes9.1 temperature (°C)CWTU
238Thermostat 3 - Coil temperature (from bus)2 Bytes9.1 temperature (°C)CWTU
239Thermostat 3 - Floor temperature (from bus)2 Bytes9.1 temperature (°C)CWTU
240Thermostat 3 - Flow temperature (from bus)2 Bytes9.1 temperature (°C)CWTU
241Thermostat 3 - Windows contact sensor 1 (from bus)1 Bit1.19 window/doorCWTU
242Thermostat 3 - Windows contact sensor 2 (from bus)1 Bit1.19 window/doorCWTU
243Thermostat 3 - Presence sensor 1 (from bus)1 Bit1.18 occupancyCWTU
244Thermostat 3 - Presence sensor 2 (from bus)1 Bit1.18 occupancyCWTU
245Thermostat 3 - Contact of card holder (from bus)1 Bit1.18 occupancyCWTU
246Thermostat 3 - Anticondensation (from bus)1 Bit1.1 switchCWTU
247Thermostat 3 - Weighted temperature2 Bytes9.1 temperature (°C)CRT
248Thermostat 3 - Heating/cooling status out1 Bit1.100 heating/coolingCRT
249Thermostat 3 - Heating/cooling status in1 Bit1.100 heating/coolingCW
250Thermostat 3 - HVAC mode in1 Byte20.102 HVAC modeCW
251Thermostat 3 - HVAC forced mode in1 Byte20.102 HVAC modeCW
252Thermostat 3 - HVAC mode out1 Byte20.102 HVAC modeCRT
253Thermostat 3 - HVAC manual mode1 Byte20.102 HVAC modeCWTU
254Thermostat 3 - Chrono active status1 Bit1.11 stateCRT
255Thermostat 3 - Actual setpoint2 Bytes9.1 temperature (°C)CRT
256Thermostat 3 - Manual setpoint2 Bytes9.1 temperature (°C)CW
257Thermostat 3 - Input setpoint2 Bytes9.1 temperature (°C)CRWTU
257Thermostat 3 - Comfort setpoint (heating)2 Bytes9.1 temperature (°C)CRWTU
258Thermostat 3 - Comfort setpoint (cooling)2 Bytes9.1 temperature (°C)CRWTU
259Thermostat 3 - Standby setpoint (heating)2 Bytes9.1 temperature (°C)CRWTU
259Thermostat 3 - Standby offset (heating)2 Bytes9.2 temperature difference (K)CRWTU
260Thermostat 3 - Standby setpoint (cooling)2 Bytes9.1 temperature (°C)CRWTU
260Thermostat 3 - Standby offset (cooling)2 Bytes9.2 temperature difference (K)CRWTU
261Thermostat 3 - Economy setpoint (heating)2 Bytes9.1 temperature (°C)CRWTU
261Thermostat 3 - Economy offset (heating)2 Bytes9.2 temperature difference (K)CRWTU
262Thermostat 3 - Economy setpoint (cooling)2 Bytes9.1 temperature (°C)CRWTU
262Thermostat 3 - Economy offset (cooling)2 Bytes9.2 temperature difference (K)CRWTU
263Thermostat 3 - Building protection setpoint (heating)2 Bytes9.1 temperature (°C)CRWTU
264Thermostat 3 - Building protection setpoint (cooling)2 Bytes9.1 temperature (°C)CRWTU
265Thermostat 3 - Room temperature controller status1 Bit1.3 enableCRT
266Thermostat 3 - Heating and cooling out command1 Byte5.1 percentage (0..100%)CRT
266Thermostat 3 - Heating out command1 Byte5.1 percentage (0..100%)CRT
266Thermostat 3 - Heating and cooling out command1 Bit1.1 switchCRT
266Thermostat 3 - Heating out command1 Bit1.1 switchCRT
267Thermostat 3 - Cooling out command1 Byte5.1 percentage (0..100%)CRT
267Thermostat 3 - Cooling out command1 Bit1.1 switchCRT
268Thermostat 3 - Auxiliary heating and cooling output command1 Bit1.1 switchCRT
268Thermostat 3 - Auxiliary heating output command1 Bit1.1 switchCRT
269Thermostat 3 - Auxiliary cooling output command1 Bit1.1 switchCRT
270Thermostat 3 - Auxiliary heating disable1 Bit1.3 enableCW
271Thermostat 3 - Auxiliary cooling disable1 Bit1.3 enableCW
272Thermostat 3 - Fan continuous speed1 Byte5.1 percentage (0..100%)CRT
273Thermostat 3 - Fan speed 11 Bit1.1 switchCRT
274Thermostat 3 - Fan speed 21 Bit1.1 switchCRT
275Thermostat 3 - Fan speed 31 Bit1.1 switchCRT
276Thermostat 3 - Fan control disable1 Bit1.2 booleanCW
277Thermostat 3 - Alarm text14 Bytes16.0 Character String (ASCII)CRT
278Thermostat 3 - Manual/forced setpoint active status1 Bit1.11 stateCRWTU
279Thermostat 3 - Fan manual speed1 Byte5.10 counter pulses (0..255)CRWTU
280Thermostat 3 - Fan speed1 Byte5.10 counter pulses (0..255)CRT
281Thermostat 3 - Fan manual active status1 Bit1.11 stateCRWTU
282Thermostat 3 - Room temperature control alarm1 Bit1.5 alarmCRT
283Thermostat 3 - Disable room temperature controller1 Bit1.1 switchCW
284Thermostat 3 - Dew-point temperature2 Bytes9.1 temperature (°C)CRT
285Thermostat 3 - Relative humidity setpoint for dehumidification2 Bytes9.7 humidity (%)CRWTU
286Thermostat 3 - Relative humidity setpoint for humidification2 Bytes9.7 humidity (%)CRWTU
287Thermostat 3 - Dehumidification command1 Bit1.1 switchCRT
288Thermostat 3 - Dehumidification integration control1 Bit1.1 switchCRT
289Thermostat 3 - Dehumidification integration control1 Bit1.1 switchCRT
290Thermostat 3 - Dehumidification control disable1 Bit1.2 booleanCW
291Thermostat 3 - Humidification command1 Bit1.1 switchCRT
292Thermostat 3 - Humidification control disable1 Bit1.2 booleanCW
293Thermostat 3 - Anticondensation alarm1 Bit1.5 alarmCRT
294Thermostat 3 - Thermal generator lock1 Bit1.5 alarmCW
295Thermostat 3 - Building protection HVAC mode active1 Bit1.11 stateCRT
296Thermostat 3 - Fan manual speed percentage1 Byte5.1 percentage (0..100%)CRT
297Thermostat 3 - Fan manual speed off status1 Bit1.11 stateCRT
298Input 4 - Temperature value2 Bytes9.1 temperature (°C)CRT
299Input 4 - Temperature threshold 1 - Switch1 Bit1.1 switchCRT
300Input 4 - Temperature threshold 2 - Switch1 Bit1.1 switchCRT
301Thermostat 4 - Room temperature (from bus)2 Bytes9.1 temperature (°C)CWTU
302Thermostat 4 - Humidity (2 bytes, from bus)2 Bytes9.7 humidity (%)CWTU
303Thermostat 4 - Humidity (1 byte, from bus)1 Byte5.1 percentage (0..100%)CWTU
304Thermostat 4 - Antistratification temperature (from bus)2 Bytes9.1 temperature (°C)CWTU
305Thermostat 4 - Outdoor temperature (from bus)2 Bytes9.1 temperature (°C)CWTU
306Thermostat 4 - Coil temperature (from bus)2 Bytes9.1 temperature (°C)CWTU
307Thermostat 4 - Floor temperature (from bus)2 Bytes9.1 temperature (°C)CWTU
308Thermostat 4 - Flow temperature (from bus)2 Bytes9.1 temperature (°C)CWTU
309Thermostat 4 - Windows contact sensor 1 (from bus)1 Bit1.19 window/doorCWTU
310Thermostat 4 - Windows contact sensor 2 (from bus)1 Bit1.19 window/doorCWTU
311Thermostat 4 - Presence sensor 1 (from bus)1 Bit1.18 occupancyCWTU
312Thermostat 4 - Presence sensor 2 (from bus)1 Bit1.18 occupancyCWTU
313Thermostat 4 - Contact of card holder (from bus)1 Bit1.18 occupancyCWTU
314Thermostat 4 - Anticondensation (from bus)1 Bit1.1 switchCWTU
315Thermostat 4 - Weighted temperature2 Bytes9.1 temperature (°C)CRT
316Thermostat 4 - Heating/cooling status out1 Bit1.100 heating/coolingCRT
317Thermostat 4 - Heating/cooling status in1 Bit1.100 heating/coolingCW
318Thermostat 4 - HVAC mode in1 Byte20.102 HVAC modeCW
319Thermostat 4 - HVAC forced mode in1 Byte20.102 HVAC modeCW
320Thermostat 4 - HVAC mode out1 Byte20.102 HVAC modeCRT
321Thermostat 4 - HVAC manual mode1 Byte20.102 HVAC modeCWTU
322Thermostat 4 - Chrono active status1 Bit1.11 stateCRT
323Thermostat 4 - Actual setpoint2 Bytes9.1 temperature (°C)CRT
324Thermostat 4 - Manual setpoint2 Bytes9.1 temperature (°C)CW
325Thermostat 4 - Input setpoint2 Bytes9.1 temperature (°C)CRWTU
325Thermostat 4 - Comfort setpoint (heating)2 Bytes9.1 temperature (°C)CRWTU
326Thermostat 4 - Comfort setpoint (cooling)2 Bytes9.1 temperature (°C)CRWTU
327Thermostat 4 - Standby setpoint (heating)2 Bytes9.1 temperature (°C)CRWTU
327Thermostat 4 - Standby offset (heating)2 Bytes9.2 temperature difference (K)CRWTU
328Thermostat 4 - Standby setpoint (cooling)2 Bytes9.1 temperature (°C)CRWTU
328Thermostat 4 - Standby offset (cooling)2 Bytes9.2 temperature difference (K)CRWTU
329Thermostat 4 - Economy setpoint (heating)2 Bytes9.1 temperature (°C)CRWTU
329Thermostat 4 - Economy offset (heating)2 Bytes9.2 temperature difference (K)CRWTU
330Thermostat 4 - Economy setpoint (cooling)2 Bytes9.1 temperature (°C)CRWTU
330Thermostat 4 - Economy offset (cooling)2 Bytes9.2 temperature difference (K)CRWTU
331Thermostat 4 - Building protection setpoint (heating)2 Bytes9.1 temperature (°C)CRWTU
332Thermostat 4 - Building protection setpoint (cooling)2 Bytes9.1 temperature (°C)CRWTU
333Thermostat 4 - Room temperature controller status1 Bit1.3 enableCRT
334Thermostat 4 - Heating and cooling out command1 Byte5.1 percentage (0..100%)CRT
334Thermostat 4 - Heating out command1 Byte5.1 percentage (0..100%)CRT
334Thermostat 4 - Heating and cooling out command1 Bit1.1 switchCRT
334Thermostat 4 - Heating out command1 Bit1.1 switchCRT
335Thermostat 4 - Cooling out command1 Byte5.1 percentage (0..100%)CRT
335Thermostat 4 - Cooling out command1 Bit1.1 switchCRT
336Thermostat 4 - Auxiliary heating and cooling output command1 Bit1.1 switchCRT
336Thermostat 4 - Auxiliary heating output command1 Bit1.1 switchCRT
337Thermostat 4 - Auxiliary cooling output command1 Bit1.1 switchCRT
338Thermostat 4 - Auxiliary heating disable1 Bit1.3 enableCW
339Thermostat 4 - Auxiliary cooling disable1 Bit1.3 enableCW
340Thermostat 4 - Fan continuous speed1 Byte5.1 percentage (0..100%)CRT
341Thermostat 4 - Fan speed 11 Bit1.1 switchCRT
342Thermostat 4 - Fan speed 21 Bit1.1 switchCRT
343Thermostat 4 - Fan speed 31 Bit1.1 switchCRT
344Thermostat 4 - Fan control disable1 Bit1.2 booleanCW
345Thermostat 4 - Alarm text14 Bytes16.0 Character String (ASCII)CRT
346Thermostat 4 - Manual/forced setpoint active status1 Bit1.11 stateCRWTU
347Thermostat 4 - Fan manual speed1 Byte5.10 counter pulses (0..255)CRWTU
348Thermostat 4 - Fan speed1 Byte5.10 counter pulses (0..255)CRT
349Thermostat 4 - Fan manual active status1 Bit1.11 stateCRWTU
350Thermostat 4 - Room temperature control alarm1 Bit1.5 alarmCRT
351Thermostat 4 - Disable room temperature controller1 Bit1.1 switchCW
352Thermostat 4 - Dew-point temperature2 Bytes9.1 temperature (°C)CRT
353Thermostat 4 - Relative humidity setpoint for dehumidification2 Bytes9.7 humidity (%)CRWTU
354Thermostat 4 - Relative humidity setpoint for humidification2 Bytes9.7 humidity (%)CRWTU
355Thermostat 4 - Dehumidification command1 Bit1.1 switchCRT
356Thermostat 4 - Dehumidification integration control1 Bit1.1 switchCRT
357Thermostat 4 - Dehumidification integration control1 Bit1.1 switchCRT
358Thermostat 4 - Dehumidification control disable1 Bit1.2 booleanCW
359Thermostat 4 - Humidification command1 Bit1.1 switchCRT
360Thermostat 4 - Humidification control disable1 Bit1.2 booleanCW
361Thermostat 4 - Anticondensation alarm1 Bit1.5 alarmCRT
362Thermostat 4 - Thermal generator lock1 Bit1.5 alarmCW
363Thermostat 4 - Building protection HVAC mode active1 Bit1.11 stateCRT
364Thermostat 4 - Fan manual speed percentage1 Byte5.1 percentage (0..100%)CRT
365Thermostat 4 - Fan manual speed off status1 Bit1.11 stateCRT
Parameters (232)
ParameterTypeDefault
Signallistnot inverted
Cyclic reading eachlistno reading
Hysteresis positionlistbelow
Hysteresis positionlistabove
Delay for alarm signallist5 min
Thermostat functionlistheating
Heating - cooling cyclic sending intervallistno sending
Heating/cooling changeoverlistfrom bus
Analog sensors timeouttime300
Dehumidification functionlistdisabled
Humidification functionlistdisabled
Flow temperature (project)list14 °C
Digital sensors timeouttime300
Room temperaturelistdisabled
Relative humiditylistdisabled
Antistratification temperaturelistdisabled
Outdoor temperaturelistdisabled
Coil temperaturelistdisabled
Floor surface temperaturelistdisabled
Flow temperaturelistdisabled
Window contact 1listdisabled
Window contact 2listdisabled
Presence sensor 1listdisabled
Presence sensor 2listdisabled
Card holder contactlistdisabled
Humidity CO dimensionlist2 bytes
Cyclic sending intervallistno sending
Minimum change of value to send [K]float 0…50.5
Anticondensationlistdisabled
Relative weightlist50% / 50%
Setpoint cyclic sending intervallistno sending
Comfort temperature setpoint [°C]float 10…5021
Standby temperature offset [0.1 K]signedInt -50…-10-30
Economy temperature offset [0.1 K]signedInt -80…-10-50
Building protection temperature [°C]float 2…107
Control typelist2 points hysteresis
Command Communication Objectlistseparated
Hysteresislist0.3 K
PWM cycle timetime15
Proportional band [0.1K]unsignedInt 5…10040
Integral time [min]unsignedInt 0…25590
Valve protection functionlistdisabled
Frequencylistonce a week
Time intervallist10 s
Floor temperature limitationlistdisabled
Temperature limit [°C]float 20…4029
Auxiliary heatinglistdisabled
Communication objectlistseparated
Offset from setpointlist0.6 K
Disabled from buslistno
Cooling typelistfloor radiant panels
Anticondensation with probelistdisabled
Min control value [%]unsignedInt 0…3015
Min. change of value to send [%]unsignedInt 0…10010
Anticondensation hysteresis rangelist0.5 K
Auxiliary coolinglistdisabled
Control typelist1 speed
Threshold first speed [0.1K]unsignedInt 0…2550
Threshold second speed [0.1K]unsignedInt 0…25510
Threshold third speed [0.1K]unsignedInt 0…25520
Manual operationlistnot depending on the temperature
Hot startlistno
Use coil battery temperature sensor for dehumidificationlistno
Speed control hysteresislist0.3 K
Speed proportional band [0.1K]unsignedInt 5…10030
Min. change of value to send [%]unsignedInt 2…4010
Min. temp. to start ventilation [°C]unsignedInt 28…4028
Min. temp. to start dehumidif. [°C]unsignedInt 0…25510
Relative humidity setpoint [%]unsignedInt 0…10065
Relative humidity setpoint [%]list0.6 %
Max. temp. diff. to disable dehum. [°C]float 0…500.5
Forced speedlist1 speed
Forced speedunsignedInt 0…10020
Antistratification functionlistdisabled
Antistratification temp. differentiallist2.00 [K/m]
Hysteresislist0.5 K
Disable ventilation from buslistno
Signal from buslistnot inverted
Fan start delaylist0 s
Fan stop delaylist0 s
Dew-point temperaturelistdisabled
Min. change of value to send [K]list0.2 K
Windows contacts functionlistdisabled
Presence sensors functionlistdisabled
Presence sensors uselistcomfort extension
Thermostat modeslistcomfort - standby
Wait time to building protection modetime60
Absence time to switch HVAC modetime60
Card holder functionlistdisabled
On card insertion switch HVAC mode tolistcomfort
On card removal switch HVAC mode toliststandby
Activation delay on card insertiontime0
Activation delay on card removaltime0
Ventilation for auxiliary coolinglistdisabled
End of manual operationlistat first telegram from bus
Heating typelistradiators
Heating typelistfancoils
Humidity hysteresislist0.8 %
Subordinated to temperature controllistyes
Humidity setpointunsignedInt 20…8055
Integrationlistno
Dehumidification start delaytime300
Temperature difference for integrationlist1.5 °C
Hysteresis for integrationlist0.5 K
Disable dehumid. control from buslistno
Humidity setpointunsignedInt 20…8035
Disable humidification control from buslistno
Max control value [%]unsignedInt 70…10085
Active anticondensationlistdisabled
Transmission delay after mode changetime400
Channel 1listindependent or single
Channel 2listindependent or single
Delay after bus voltage recoverytime400
Input 1listenabled DI
Long press timetime80
Lock functionlistdisabled
Invert lock device signallistnot inverted
Lock after bus recoverylistno
Typelistsend values or sequences
Number of Communication ObjectsunsignedInt 1…81
Eventlistactivation / release
Behavior at lockinglistnone
Behavior at unlockinglistnone
Send cyclicallylistnone
Cyclic sending intervaltime120
Send delaytime0
Communication object dimensionlist1 bit value
Reaction to activationlisttoggle
Reaction to releaselistoff
Reaction to short presslisttoggle
Reaction to long presslistoff
Reaction to activationlistenable on / down
Reaction to releaselistdisable
Reaction to short presslistenable on / down
Reaction to long presslistdisable
Reaction to activationlistsend value 1
Reaction to releaselistnone
Reaction to short presslistsend value 1
Reaction to long presslistnone
Value 1unsignedInt 0…2550
Value 2unsignedInt 0…2550
Value 1signedInt -128…1270
Value 2signedInt -128…1270
Value 1unsignedInt 0…655350
Value 2unsignedInt 0…655350
Value 1signedInt -32768…327670
Value 2signedInt -32768…327670
Value 1float -671088.64…670760.960
Value 2float -671088.64…670760.960
Reaction to activationliston
Reaction to short pressliston
Toggle modelistenabled
Short / long actionlistoff / darker
Up / down actionlistup
Venetian blind modelistdisabled
Learning modelistdisabled
Scene activationlistsend first scene only
First scene numberunsignedInt 1…641
Second scene numberunsignedInt 1…642
Input 2listenabled DI
Typelistdimming
1 and 2 uselistA increases, B decreases
1 and 2 uselistA up, B down
Led L1listwhen contact closed
Blinkinglistno
Alwayslistoff
Off delaytime20
Blinking period / typelist1 s on, 1 s off
1 and 2 uselistA on, B off
Led L2listwhen contact closed
Led L4listwhen contact closed
Led L3listwhen contact closed
Input 3listenabled DI
Input 4listenabled DI
3 and 4 uselistA on, B off
3 and 4 uselistA increases, B decreases
3 and 4 uselistA up, B down
Reaction to long presslistdarker
Value 1unsignedInt 0…1000
Value 2unsignedInt 0…1000
Logic functionlistdisabled
Logic operationlistOR
Output cyclic transmission intervallistno sending
Logic object 1listdisabled
Logic object 2listdisabled
Logic object 3listdisabled
Logic object 4listdisabled
Logic object 1 negatedlistno
Logic object 2 negatedlistno
Logic object 3 negatedlistno
Logic object 4 negatedlistno
Logic object 1 read at startuplistno
Logic object 2 read at startuplistno
Logic object 3 read at startuplistno
Logic object 4 read at startuplistno
Logic object 1 default valuelistnone
Logic object 2 default valuelistnone
Logic object 3 default valuelistnone
Logic object 4 default valuelistnone
Output sendlistboth values
Output updatingliston value change
Technical alarmlistdisabled
Debounce timetime5
Contact typelistNO (normally open)
Led L1listfixed
Led L2listfixed
Led L3listfixed
Led L4listfixed
Counter dimensionlistfrom 0 to 255 (1 byte)
Max valueunsignedInt 0…255255
Max valueunsignedInt 0…6553565535
Max valueunsignedInt 0…42949672954294967295
Setpoint typelistsingle
Ventilation for auxiliary heatinglistdisabled
Threshold 1listnot active
Threshold 2listnot active
Value [°C]float 0…507
Value [°C]float 0…5045
Hysteresislist0.4 K
Temperature offsetlist0.0 °C
Thermostat functionalitieslistdisabled
Filter typelistmedium
Temperature setpoint [°C]float 10…5021
Temperature setpoint [°C]float 10…5023
Standby temperature offset [0.1 K]signedInt 10…5030
Economy temperature offset [0.1 K]signedInt 10…8050
Building protection temperature [°C]float 10…5036
Disable temperature controller from buslistno
Comfort temperature setpoint [°C]float 10…5023
HVAC mode after downloadlistno change
Neutral zone [0.1 K]signedInt 10…8020
Cyclic sendingtime120

Version history

ApplicationApp noFingerprintFirst seenSizeFile
APEKCG2TP 0.1 latest$434700292026-11-25279 KBDownload
APEKCG2TP 0.1$434700292026-11-25279 KBDownload

About this file

This is the official ETS product database for the Ekinex S.p.A. Universal interface 4 DI / NTC (EK-CG2-TP), published by the manufacturer in the KNX online catalog. To use it, open ETS, go to Catalogs → Import and choose the downloaded .knxprod file. The device then appears in your catalog and can be added to a project. Older versions are kept so existing projects can be matched to the application program they were commissioned with.