Multi driver led dimmer RE KNX XXX
Dinuy · Order number RE KNX XXX · KNX-RF Devices › Actuators › Dimming Actuators
Download .knxprod Switching_Dimming_Actuator 1.1 · 127 KB
Product
| Manufacturer | Dinuy |
|---|---|
| Product name | Multi driver led dimmer |
| Order number | RE KNX XXX |
| Product text | Switching or Dimming KNX-RF Actuator |
| Hardware | Multidriver dimmer RF transciver |
| Medium | KNX RF |
| Rail mounted | No |
| Device kind | RFRetransmitter |
| Registration | Certified · 2017-12-21 |
| Languages | es-ES, en-GB, en-US |
| Catalog entry | M-009A_H-SN2017.2E06.2E12-1_HP-FF41-11-DA31_CI-RE.20KNX.20XXX-1 |
| Fingerprint | DA31 |
| SHA-256 | 75685378f1d399993c1afb8aaeeaee7001a7b6855801518779bdd0dc5b38ca89 |
| First seen | 2026-11-25 |
| Markets | 68 markets |
Application program: Switching_Dimming_Actuator 1.1
| Application number | $FF41 |
|---|---|
| Version | 1.1 |
| Mask version | MV-27B0 (RF System B) |
| KNX Data Secure | No |
| Minimum ETS version | 5.0 |
| Parameters | 78 |
| Group objects | 37 |
Group objects (37)
| No | Name | Function | Size | DPT | Flags |
|---|---|---|---|---|---|
| 1 | Switch On-Off Input | Switch | 1 Bit | 1.1 switch | CW |
| 2 | Dimming Up-Down Input | Relative Set Value control | 4 Bit | 3.7 dimming control | CW |
| 3 | Absolute Set value control Input | Dimming Value | 1 Byte | 5.1 percentage (0..100%) | CW |
| 4 | Scene Numbered Input | Scene Numbered | 1 Byte | 18.1 scene control | CW |
| 5 | Forced Input | Forced | 2 Bit | 2.1 switch control | CW |
| 6 | Timed Start-Stop Input | Timed Start-Stop | 1 Bit | 1.1 switch | CW |
| 7 | Dimmer Block Input | Dimmer Block | 1 Bit | 1.2 boolean | CW |
| 8 | Dimming Speed (from 1% to 100%) | Dimming Speed | 2 Bytes | 7.4 time (100 ms) | CW |
| 9 | Info Switch On-Off Output | Info Switch On-Off | 1 Bit | 1.1 switch | CT |
| 10 | Info Actual Dimming Value Output | Info Dimming Value | 1 Byte | 5.1 percentage (0..100%) | CT |
| 11 | Switch On-Off Output Short operation | Switch | 1 Bit | 1.1 switch | CRWTU |
| 11 | Scene Numbered Output | Scene Numbered Output | 1 Byte | 18.1 scene control | CRWTU |
| 11 | 1 bit value Output | 1 bit value Output | 1 Bit | 1.1 switch | CRWTU |
| 11 | 2 bit value Output | 2 bit value Output | 2 Bit | 2.3 enable control | CRWTU |
| 11 | 1 Byte value Output | 1 Byte value Output | 1 Byte | 5.1 percentage (0..100%) | CRWTU |
| 11 | 2 Byte value Output | 2 Byte value Output | 2 Bytes | 7.2 time (ms) | CRWTU |
| 11 | 4 Byte value Output | 4 Byte value Output | 4 Bytes | 12.1 counter pulses (unsigned) | CRWTU |
| 12 | Switch On-Off Output Long operation | Switch | 1 Bit | 1.1 switch | CRWTU |
| 12 | Dimming Up-Down Output | Relative Set Value control Output | 4 Bit | 3.7 dimming control | CRWTU |
| 12 | 1 bit value Output long | 1 bit value Output long operation | 1 Bit | 1.1 switch | CRWTU |
| 12 | 2 bit value Output long | 2 bit value Output long | 2 Bit | 2.3 enable control | CRWTU |
| 12 | 1 Byte value Output long operation | 1 Byte value Output long operation | 1 Byte | 5.1 percentage (0..100%) | CRWTU |
| 12 | 2 Byte value Output long operation | 2 Byte value Output long operation | 2 Bytes | 7.2 time (ms) | CRWTU |
| 12 | 4 Byte value Output long operation | 4 Byte value Output long operation | 4 Bytes | 12.1 counter pulses (unsigned) | CRWTU |
| 13 | INFO_SWITCH_AUX | INFO_SWITCH_AUX | 1 Bit | 1.1 switch | CW |
| 14 | Re-address DALI lamps | Re-address DALI lamps | 1 Bit | 1.10 start/stop | CWT |
| 15 | GODUMMY2 | GODUMMY2 | 4 Bytes | 12.1 counter pulses (unsigned) | CWT |
| 15 | Sequential operation | Sequential Switch On-Off Input | 1 Bit | 1.1 switch | CRWTU |
| 16 | GODUMMY3 | GODUMMY3 | 4 Bytes | 12.1 counter pulses (unsigned) | CWT |
| 16 | Sequential work Info | Sequential Info Switch On-Off Output | 1 Bit | 1.1 switch | CRWTU |
| 17 | GODUMMY4 | GODUMMY4 | 4 Bytes | DPT.12 | CWT |
| 18 | GODUMMY5 | GODUMMY5 | 4 Bytes | DPT.12 | CWT |
| 19 | GODUMMY6 | GODUMMY6 | 4 Bytes | DPT.12 | CWT |
| 20 | GODUMMY7 | GODUMMY7 | 4 Bytes | DPT.12 | CWT |
| 21 | GODUMMY8 | GODUMMY8 | 4 Bytes | DPT.12 | CWT |
| 22 | GODUMMY9 | GODUMMY9 | 4 Bytes | DPT.12 | CWT |
| 23 | GODUMMY10 | GODUMMY10 | 4 Bytes | DPT.12 | CWT |
Parameters (74)
| Parameter | Type | Default |
|---|---|---|
| Staircase Time Delay (Sec) | unsignedInt 1…65535 | 40 |
| Staircase Pre-warning (Sec) | unsignedInt 0…240 | 2 |
| Dimmer Type | list | Phase-cut LED Dimmer |
| Minimum Brightness (%) | unsignedInt 1…50 | 3 |
| Maximum Brightness (%) | unsignedInt 3…100 | 90 |
| Soft Turn-On Time ( x 0,1 Sec) | unsignedInt 1…65535 | 3 |
| Soft Turn-Off Time ( x 0,1 Sec) | unsignedInt 1…65535 | 3 |
| Switch-On Mode | list | Switch-On at last turn-off brightness |
| Switch-On Brightness Value (%) | unsignedInt 3…100 | 90 |
| Ripple filter state | list | Filter No Active |
| Action after Power Supply fault | list | OFF |
| Brightness after Power Supply fault (%) | unsignedInt 3…100 | 100 |
| Switch-On Ramp Time (Sec) | unsignedInt 1…65535 | 1 |
| ON Time (Sec) | unsignedInt 1…65535 | 1 |
| Switch-Off Ramp Time (Sec) | unsignedInt 1…65535 | 1 |
| OFF Time (Sec) | unsignedInt 1…65535 | 1 |
| Number of Scenes | list | One Scene |
| Scene Number 1 | list | Scene 2 |
| Scene Number 2 | list | Scene 2 |
| Scene Number 3 | list | Scene 2 |
| Scene Number 4 | list | Scene 2 |
| Scene Number 5 | list | Scene 2 |
| Default Brightness (%) Scene 1 | unsignedInt 0…99 | 3 |
| Default Brightness (%) Scene 2 | unsignedInt 0…99 | 3 |
| Default Brightness (%) Scene 3 | unsignedInt 0…99 | 3 |
| Default Brightness (%) Scene 4 | unsignedInt 0…99 | 3 |
| Default Brightness (%) Scene 5 | unsignedInt 0…99 | 3 |
| Dimming Curve (1-5) | list | Curve 2 |
| Dimming Mode | list | Trailing-edge Dimming |
| Min Switch Off Voltage | list | 1.2 Volt |
| PWM Frequency | list | 400 Hz |
| Dimming Speed (from 0% to 100% x 0,1Sec) | unsignedInt 1…65535 | 1 |
| Enable RF Retransmitter mode? | list | Disable |
| Auxiliary Pushbutton function | list | Switch |
| Debounce Time | list | 20 mSec. |
| Distinction between Short/Long action | list | YES |
| Number of objects for Short/Long operation | list | 2 |
| Contact Type | list | Normally CLOSED |
| Long action after | list | 0,4 Sec. |
| Long action | list | Off |
| Short action | list | Off |
| Dimming Functionality? | list | Only Dimming |
| Action after Short operation | list | Off |
| Action after Long operation | list | Dim Brighter |
| Scene Number | list | Scene 2 |
| Action after Short operation | list | Ignore |
| Action after Long operation | list | Ignore |
| Value type after Short operation | list | 1 bit |
| Value type after Long operation | list | 1 bit |
| Bit value | list | 1 |
| 2 Bits value | list | 1 |
| 1 Byte value | unsignedInt 0…255 | 1 |
| 2 Byte value | unsignedInt 0…65535 | 1 |
| 4 Byte value | unsignedInt 0…4294967295 | 1 |
| Action after Closing the contact | list | Off |
| Action after Opening the contact | list | Off |
| OFF value (0-100%) | unsignedInt 0…99 | 0 |
| Dimming Speed (from 0% to 100%) x 0,1Sec | list | 2 |
| Switch-On Ramp Time (Sec) | list | 0,7 |
| Switch-Off Ramp Time (Sec) | list | 0,7 |
| Soft Turn-On Time (Sec) | list | 0,7 |
| Soft Turn-Off Time (Sec) | list | 0,7 |
| Dimming Value Fade Time ( x Sec) | list | 0,7 |
| DUMMY10 | unsignedInt 0…255 | 1 |
| Dimming Value Fade Time ( x 0,1 Sec) | unsignedInt 1…65535 | 10 |
| Action after operation | list | Dim Brighter |
| Value type after operation | list | 1 bit |
| RASTRO_ETS | unsignedInt 0…255 | 10 |
| Default state Scene 1 | list | OFF |
| Default state Scene 2 | list | OFF |
| Default state Scene 3 | list | OFF |
| Default state Scene 4 | list | OFF |
| Default state Scene 5 | list | OFF |
| Contact polarity? | list | Switch-On when Object is 1 |
Version history
| Application | App no | Fingerprint | First seen | Size | File |
|---|---|---|---|---|---|
| Switching_Dimming_Actuator 1.1 latest | $FF41 | DA31 | 2026-11-25 | 127 KB | Download |
About this file
This is the official ETS product database for the Dinuy Multi driver led dimmer (RE KNX XXX), published by the manufacturer in the KNX online catalog. To use it, open ETS, go to Catalogs → Import and choose the downloaded .knxprod file. The device then appears in your catalog and can be added to a project. Older versions are kept so existing projects can be matched to the application program they were commissioned with.
More from Dinuy
- KNX RF/TP Coupler Secure CO K5X 003 CO K5X 003
- Movement Detector DMK5X 001-230
- KNX-RF Pushbutton Interface EMK5X002
- 4-channel Universal Interface EMK5X004
- 2-channel switching actuator/blind actuator PE K5X 002
- Actuator RF 1ch Blind / 2ch Switch - 4 Inputs PEK5X001
- DINUY RF 3-channel LED Strip Dimmer_4input ch RE K5X RGB
- Temperature sensor SE K5X 005
- KNX-RF Multi-Sensor SE K5X 0XX
- KNX RF/TP Coupler CO K5X 002
- KNX IP Interface Secure CO KNT IPI CO KNT IPI
- KNX IP Router Secure CO KNT IPR CO KNT IPR