| 1 | [In1] Disable channel (via bus) | 1= Disable, 0 = Enable | 1 Bit | 1.3 enable | CW |
| 1 | [In1] Disable temperature functionality (via bus) | 1 = Disable, 0 = Enable | 1 Bit | 1.3 enable | CW |
| 2 | [In1] Switch Telegram | 1 = On, 0 = Off | 1 Bit | 1.1 switch | CT |
| 2 | [In1] Stop / Step Telegram | 0 = Step Up, 1 = Step Down | 1 Bit | 1.7 step | CT |
| 2 | [In1] Bit value on operation | Bit value | 1 Bit | 1.11 state | CT |
| 2 | [In1] 2 Bits value on operation | 2 Bits value | 2 Bit | 2.1 switch control | CT |
| 2 | [In1] Scene control 8 Bits | Scene control | 1 Byte | 18.1 scene control | CT |
| 2 | [In1] 2 Bytes signed value on operation | 2 Bytes signed value | 2 Bytes | 8.1 pulses difference | CT |
| 2 | [In1] 2 Bytes floating value on operation | 2 Bytes floating value | 2 Bytes | 9.1 temperature (°C) | CT |
| 2 | [In1] Byte value on operation | Byte value | 1 Byte | 5.10 counter pulses (0..255) | CT |
| 2 | [In1] 4 Bytes value on operation | 4 Bytes value | 4 Bytes | 12.1 counter pulses (unsigned) | CT |
| 2 | [In1] Temperature value Output | Temperature value | 2 Bytes | 9.1 temperature (°C) | CT |
| 2 | [In1] Counter direction | 0 = Up, 1 = Down | 1 Bit | 1.8 up/down | CW |
| 2 | [In1] Scene 1 Bit | 0 = Scene 1, 1 = Scene 2 | 1 Bit | 1.11 state | CT |
| 2 | [In1] 2 Bytes value on operation | 2 Bytes value | 2 Bytes | 7.1 pulses | CT |
| 3 | [In1] Switch Long Telegram | 1 = On, 0 = Off | 1 Bit | 1.1 switch | CT |
| 3 | [In1] Reset Counter (via bus) | 0 = No action, 1 = Reset | 1 Bit | 1.15 reset | CW |
| 3 | [In1] Switch 2 Telegram | 1 = On, 0 = Off | 1 Bit | 1.1 switch | CT |
| 3 | [In1] Scene save | 0 = No action, 1 = Save Scene | 1 Bit | 1.3 enable | CW |
| 3 | [In1] 4 Bytes value on Long operation | 4 Bytes value | 4 Bytes | 12.1 counter pulses (unsigned) | CT |
| 3 | [In1] 2 Bytes floating value on Long operation | 2 Bytes floating value | 2 Bytes | 9.1 temperature (°C) | CT |
| 3 | [In1] 2 Bytes signed value on Long operation | 2 Bytes signed value | 2 Bytes | 8.1 pulses difference | CT |
| 3 | [In1] Bit value on Long operation | Bit value | 1 Bit | 1.11 state | CT |
| 3 | [In1] 2 Bits value on Long operation | 2 Bits value | 2 Bit | 2.1 switch control | CT |
| 3 | [In1] Sensor not connected | 0 = Sensor Ok, 1 = Sensor not connected | 1 Bit | 1.11 state | CT |
| 3 | [In1] Byte value on Long operation | Byte value | 1 Byte | 5.10 counter pulses (0..255) | CT |
| 3 | [In1] 2 Bytes value on Long operation | 2 Bytes value | 2 Bytes | 7.1 pulses | CT |
| 3 | [In1] Dimming control Telegram | Dimming control | 4 Bit | 3.7 dimming control | CT |
| 3 | [In1] Move Telegram | 0 = Up, 1 = Down | 1 Bit | 1.8 up/down | CT |
| 4 | [In1] Info Switch (via bus) | 1 = On, 0 = Off | 1 Bit | 1.1 switch | CW |
| 4 | [In1] Request Counter (via bus) | 1 = Trigger | 1 Bit | 1.17 trigger | CW |
| 4 | [In1] Over-Heating Output | 1 = Over-Heating, 0 = No Over-Heating | 1 Bit | 1.5 alarm | CT |
| 4 | [In1] Switch 3 Telegram | 1 = On, 0 = Off | 1 Bit | 1.1 switch | CT |
| 5 | [In1] Info Switch Long (via bus) | 1 = On, 0 = Off | 1 Bit | 1.1 switch | CW |
| 5 | [In1] Counter 32 Bits | Counter (0-4.294.967.295) | 4 Bytes | 13.1 counter pulses (signed) | CRT |
| 5 | [In1] Over-Cooling Output | 1 = Over-Cooling, 0 = No Over-Cooling | 1 Bit | 1.5 alarm | CT |
| 5 | [In1] Counter 8 Bits | Counter (0-255) | 1 Byte | 5.10 counter pulses (0..255) | CRT |
| 5 | [In1] Counter 16 Bits | Counter (0-65535) | 2 Bytes | 7.1 pulses | CRT |
| 5 | [In1] Switch 4 Telegram | 1 = On, 0 = Off | 1 Bit | 1.1 switch | CT |
| 6 | [In1] Switch 5 Telegram | 1 = On, 0 = Off | 1 Bit | 1.1 switch | CT |
| 7 | [In1] Increase/Decrease (via bus) | 0 = Up, 1 = Down | 1 Bit | 1.8 up/down | CW |
| 7 | [In1] Scene save | 0 = Scene 1, 1 = Scene 2 | 1 Bit | 1.3 enable | CT |
| 8 | [In2] Disable channel (via bus) | 1 = Disable, 0 = Enable | 1 Bit | 1.3 enable | CW |
| 8 | [In2] Disable temperature functionality (via bus) | 1 = Disable, 0 = Enable | 1 Bit | 1.3 enable | CW |
| 9 | [In2] Switch Telegram | 1 = On, 0 = Off | 1 Bit | 1.1 switch | CT |
| 9 | [In2] 4 Bytes value on operation | 4 Bytes value | 4 Bytes | 12.1 counter pulses (unsigned) | CT |
| 9 | [In2] 2 Bytes signed value on operation | 2 Bytes signed value | 2 Bytes | 8.1 pulses difference | CT |
| 9 | [In2] Temperature value Output | Temperature value | 2 Bytes | 9.1 temperature (°C) | CT |
| 9 | [In2] Stop / Step Telegram | 0 = Step Up, 1 = Step Down | 1 Bit | 1.7 step | CT |
| 9 | [In2] 2 Bits value on operation | 2 Bits value | 2 Bit | 2.1 switch control | CT |
| 9 | [In2] 2 Bytes value on operation | 2 Bytes value | 2 Bytes | 7.1 pulses | CT |
| 9 | [In2] Bit value on operation | Bit value | 1 Bit | 1.11 state | CT |
| 9 | [In2] Counter direction (via bus) | 0 = Up, 1 = Down | 1 Bit | 1.8 up/down | CW |
| 9 | [In2] Byte value on operation | Byte value | 1 Byte | 5.10 counter pulses (0..255) | CT |
| 9 | [In2] 2 Bytes floating value on operation | 2 Bytes floating value | 2 Bytes | 9.1 temperature (°C) | CT |
| 9 | [In2] Scene 1 Bit | 0 = Scene 1, 1 = Scene 2 | 1 Bit | 1.11 state | CT |
| 9 | [In2] Scene control 8 Bits | Scene control | 1 Byte | 18.1 scene control | CT |
| 10 | [In2] Switch Long Telegram | 1 = On, 0 = Off | 1 Bit | 1.1 switch | CT |
| 10 | [In2] Scene save | 0 = No action, 1 = Store Scene | 1 Bit | 1.3 enable | CW |
| 10 | [In2] Switch 2 Telegram | 1 = On, 0 = Off | 1 Bit | 1.1 switch | CT |
| 10 | [In2] Bit value on Long operation | Bit value | 1 Bit | 1.11 state | CT |
| 10 | [In2] Reset Counter (via bus) | 0 = No action, 1 = Reset | 1 Bit | 1.15 reset | CW |
| 10 | [In2] Move Telegram | 0 = Up, 1 = Down | 1 Bit | 1.8 up/down | CT |
| 10 | [In2] 2 Bytes floating value on Long operation | 2 Bytes floating value | 2 Bytes | 9.1 temperature (°C) | CT |
| 10 | [In2] 2 Bytes signed value on Long operation | 2 Bytes signed value | 2 Bytes | 8.1 pulses difference | CT |
| 10 | [In2] 4 Bytes value on Long operation | 4 Bytes value | 4 Bytes | 12.1 counter pulses (unsigned) | CT |
| 10 | [In2] 2 Bits value on Long operation | 2 Bits value | 2 Bit | 2.1 switch control | CT |
| 10 | [In2] Sensor not connected Output | 0 = Sensor Ok, 1 = Sensor not connected | 1 Bit | 1.11 state | CT |
| 10 | [In2] Byte value on Long operation | Byte value | 1 Byte | 5.10 counter pulses (0..255) | CT |
| 10 | [In2] 2 Bytes value on Long operation | 2 Bytes value | 2 Bytes | 7.1 pulses | CT |
| 10 | [In2] Dimming control Telegram | Dimming control | 4 Bit | 3.7 dimming control | CT |
| 11 | [In2] Info switch (via bus) | 1 = On, 0 = Off | 1 Bit | 1.1 switch | CW |
| 11 | [In2] Switch 3 Telegram | 1 = On, 0 = Off | 1 Bit | 1.1 switch | CT |
| 11 | [In2] Request Counter (via bus) | 1 = Trigger | 1 Bit | 1.17 trigger | CW |
| 11 | [In2] Over-Heating Output | 1 = Over-Heating, 0 = No Over-Heating | 1 Bit | 1.5 alarm | CT |
| 12 | [In2] Info switch Long (via bus) | 1 = On, 0 = Off | 1 Bit | 1.1 switch | CW |
| 12 | [In2] Counter 16 Bits | Counter (0-65535) | 2 Bytes | 7.1 pulses | CRT |
| 12 | [In2] Switch 4 Telegram | 1 = On, 0 = Off | 1 Bit | 1.1 switch | CT |
| 12 | [In2] Over-Cooling Output | 1 = Over-Cooling, 0 = No Over-Cooling | 1 Bit | 1.5 alarm | CT |
| 12 | [In2] Counter 8 Bits | Counter (0-255) | 1 Byte | 5.10 counter pulses (0..255) | CRT |
| 12 | [In2] Counter 32 Bits | Counter (0-4.294.967.295) | 4 Bytes | 13.1 counter pulses (signed) | CRT |
| 13 | [In2] Switch 5 Telegram | 1 = On, 0 = Off | 1 Bit | 1.1 switch | CT |
| 14 | [In2] Scene save | 0 = Scene 1, 1 = Scene 2 | 1 Bit | 1.3 enable | CT |
| 14 | [In2] Increase/Decrease (via bus) | 0 = Up, 1 = Down | 1 Bit | 1.8 up/down | CW |
| 15 | [In3] Disable channel (via bus) | 1 = Disable, 0 = Enable | 1 Bit | 1.3 enable | CW |
| 15 | [In3] Disable Temperature functionality (via bus) | 1 = Disable, 0 = Enable | 1 Bit | 1.3 enable | CW |
| 16 | [In3] Switch Telegram | 1 = On, 0 = Off | 1 Bit | 1.1 switch | CT |
| 16 | [In3] Scene control 8 Bits | Scene control | 1 Byte | 18.1 scene control | CT |
| 16 | [In3] Temperature value Output | Temperature value | 2 Bytes | 9.1 temperature (°C) | CT |
| 16 | [In3] 2 Bytes floating value on operation | 2 Bytes floating value | 2 Bytes | 9.1 temperature (°C) | CT |
| 16 | [In3] Byte value on operation | Byte value | 1 Byte | 5.10 counter pulses (0..255) | CT |
| 16 | [In3] Counter direction (via bus) | 0 = Up, 1 = Down | 1 Bit | 1.8 up/down | CW |
| 16 | [In3] Bit value on operation | Bit value | 1 Bit | 1.11 state | CT |
| 16 | [In3] 2 Bytes value on operation | 2 Bytes value | 2 Bytes | 7.1 pulses | CT |
| 16 | [In3] 2 Bits value on operation | 2 Bits value | 2 Bit | 2.1 switch control | T |
| 16 | [In3] Stop / Step Telegram | 0 = Step Up, 1 = Step Down | 1 Bit | 1.7 step | CT |
| 16 | [In3] 2 Bytes signed value on operation | 2 Bytes signed value | 2 Bytes | 8.1 pulses difference | CT |
| 16 | [In3] Scene 1 Bit | 0 = Scene 1, 1 = Scene 2 | 1 Bit | 1.11 state | CT |
| 16 | [In3] 4 Bytes value on operation | 4 Bytes value | 4 Bytes | 12.1 counter pulses (unsigned) | CT |
| 17 | [In3] 2 Bytes floating value on Long operation | 2 Bytes floating value | 2 Bytes | 9.1 temperature (°C) | CT |
| 17 | [In3] Switch 2 Telegram | 1 = On, 0 = Off | 1 Bit | 1.1 switch | CT |
| 17 | [In3] 2 Bytes signed value on Long operation | 2 Bytes signed value | 2 Bytes | 8.1 pulses difference | CT |
| 17 | [In3] Scene save | 0 = No action, 1 = Store save | 1 Bit | 1.3 enable | CW |
| 17 | [In3] Move Telegram | 0 = Up, 1 = Down | 1 Bit | 1.8 up/down | CT |
| 17 | [In3] Reset Counter (via bus) | 0 = No action, 1 = Reset | 1 Bit | 1.15 reset | CW |
| 17 | [In3] 2 Bits value on Long operation | 2 Bits value | 2 Bit | 2.1 switch control | CT |
| 17 | [In3] Sensor not connected Output | 0 = Sensor Ok, 1 = Sensor not connected | 1 Bit | 1.11 state | CT |
| 17 | [In3] Byte value on Long operation | Byte value | 1 Byte | 5.10 counter pulses (0..255) | CT |
| 17 | [In3] 2 Bytes value on Long operation | 2 Bytes value | 2 Bytes | 7.1 pulses | CT |
| 17 | [In3] Dimming control Telegram | Dimming control | 4 Bit | 3.7 dimming control | CT |
| 17 | [In3] Switch Long Telegram | 1 = On, 0 = Off | 1 Bit | 1.1 switch | CT |
| 17 | [In3] Bit value on Long operation | Bit value | 1 Bit | 1.11 state | CT |
| 17 | [In3] 4 Bytes value on Long operation | 4 Bytes value | 4 Bytes | 12.1 counter pulses (unsigned) | CT |
| 18 | [In3] Request counter (via bus) | 1 = Trigger | 1 Bit | 1.17 trigger | CW |
| 18 | [In3] Over-Heating Output | 1 = Over-Heating, 0 = No Over-Heating | 1 Bit | 1.5 alarm | CT |
| 18 | [In3] Switch 3 Telegram | 1 = On, 0 = Off | 1 Bit | 1.1 switch | CT |
| 18 | [In3] Info switch (via bus) | 1 = On, 0 = Off | 1 Bit | 1.1 switch | CW |
| 19 | [In3] Switch 4 Telegram | 1 = On, 0 = Off | 1 Bit | 1.1 switch | CT |
| 19 | [In3] Over-Cooling Output | 1 = Over-Cooling, 0 = No Over-Cooling | 1 Bit | 1.5 alarm | CT |
| 19 | [In3] Counter 8 Bits | Counter (0-255) | 1 Byte | 5.10 counter pulses (0..255) | CRT |
| 19 | [In3] Counter 32 Bits | Counter (0-4.294.967.295) | 4 Bytes | 13.1 counter pulses (signed) | CRT |
| 19 | [In3] Info switch Long (via bus) | 1 = On, 0 = Off | 1 Bit | 1.1 switch | CW |
| 19 | [In3] Counter 16 Bits | Counter (0-65535) | 2 Bytes | 7.1 pulses | CRT |
| 20 | [In3] Switch 5 Telegram | 1 = On, 0 = Off | 1 Bit | 1.1 switch | CT |
| 21 | [In3] Increase/Decrease (via bus) | 0 = Up, 1 = Down | 1 Bit | 1.8 up/down | CW |
| 21 | [In3] Scene save | 0 = Scene 1, 1 = Scene 2 | 1 Bit | 1.3 enable | CT |
| 22 | [In4] Disable channel (via bus) | 1 = Disable, 0 = Enable | 1 Bit | 1.3 enable | CW |
| 22 | [In4] Disable Temperature functionality (via bus) | 1 = Disable, 0 = Enable | 1 Bit | 1.3 enable | CW |
| 23 | [In4] Switch Telegram | 1 = On, 0 = Off | 1 Bit | 1.1 switch | CT |
| 23 | [In4] 2 Bytes floating value on operation | 2 Bytes floating value | 2 Bytes | 9.1 temperature (°C) | CT |
| 23 | [In4] Scene 1 Bit | 0 = Scene 1, 1 = Scene 2 | 1 Bit | 1.11 state | CT |
| 23 | [In4] Counter direction (via bus) | 0 = Up, 1 = Down | 1 Bit | 1.8 up/down | CW |
| 23 | [In4] 4 Bytes value on operation | 4 Bytes value | 4 Bytes | 12.1 counter pulses (unsigned) | CT |
| 23 | [In4] Temperature value Output | Temperature value | 2 Bytes | 9.1 temperature (°C) | CT |
| 23 | [In4] 2 Bytes value on operation | 2 Bytes value | 2 Bytes | 7.1 pulses | CT |
| 23 | [In4] 2 Bits value on operation | 2 Bits value | 2 Bit | 2.1 switch control | CT |
| 23 | [In4] Stop / Step Telegram | 0 = Step Up, 1 = Step Down | 1 Bit | 1.7 step | CT |
| 23 | [In4] 2 Bytes signed value on operation | 2 Bytes signed value | 2 Bytes | 8.1 pulses difference | CT |
| 23 | [In4] Bit value on operation | Bit value | 1 Bit | 1.11 state | CT |
| 23 | [In4] Byte value on operation | Byte value | 1 Byte | 5.10 counter pulses (0..255) | CT |
| 23 | [In4] Scene control 8 Bits | Scene control | 1 Byte | 18.1 scene control | CT |
| 24 | [In4] 4 Bytes value on Long operation | 4 Bytes value | 4 Bytes | 12.1 counter pulses (unsigned) | CT |
| 24 | [In4] 2 Bytes floating value on Long operation | 2 Bytes floating value | 2 Bytes | 9.1 temperature (°C) | CT |
| 24 | [In4] Move Telegram | 0 = Up, 1 = Down | 1 Bit | 1.8 up/down | CT |
| 24 | [In4] 2 Bytes signed value on Long operation | 2 Bytes signed value | 2 Bytes | 8.1 pulses difference | CT |
| 24 | [In4] Reset Counter (via bus) | 0 = No action, 1 = Reset | 1 Bit | 1.15 reset | CW |
| 24 | [In4] 2 Bits value on Long operation | 2 Bits value | 2 Bit | 2.1 switch control | CT |
| 24 | [In4] Sensor not connected Output | 0 = Sensor Ok, 1 = Sensor not connected | 1 Bit | 1.11 state | CT |
| 24 | [In4] Byte value on Long operation | Byte value | 1 Byte | 5.10 counter pulses (0..255) | CT |
| 24 | [In4] 2 Bytes value on Long operation | 2 Bytes value | 2 Bytes | 7.1 pulses | CT |
| 24 | [In4] Dimming control Telegram | Dimming control | 4 Bit | 3.7 dimming control | CT |
| 24 | [In4] Switch Long Telegram | 1 = On, 0 = Off | 1 Bit | 1.1 switch | CT |
| 24 | [In4] Bit value on Long operation | Bit value | 1 Bit | 1.11 state | CT |
| 24 | [In4] Switch 2 Telegram | 1 = On, 0 = Off | 1 Bit | 1.1 switch | CT |
| 24 | [In4] Scene save | 0 = No action, 1 = Save Scene | 1 Bit | 1.3 enable | CW |
| 25 | [In4] Switch 3 Telegram | 1 = On, 0 = Off | 1 Bit | 1.1 switch | CT |
| 25 | [In4] Info Switch (via bus) | 1 = On, 0 = Off | 1 Bit | 1.1 switch | CW |
| 25 | [In4] Over-Heating Output | 1 = Over-Heating, 0 = No Over-Heating | 1 Bit | 1.5 alarm | CT |
| 25 | [In4] Request Counter (via bus) | 1 = Trigger | 1 Bit | 1.17 trigger | CW |
| 26 | [In4] Counter 32 bits | Counter (0-4.294.967.295) | 4 Bytes | 13.1 counter pulses (signed) | CRT |
| 26 | [In4] Over-Cooling Output | 1 = Over-Cooling, 0 = No Over-Cooling | 1 Bit | 1.5 alarm | CT |
| 26 | [In4] Counter 8 Bits | Counter (0-255) | 1 Byte | 5.10 counter pulses (0..255) | CRT |
| 26 | [In4] Info Switch Long (via bus) | 1 = On, 0 = Off | 1 Bit | 1.1 switch | CW |
| 26 | [In4] Switch 4 Telegram | 1 = On, 0 = Off | 1 Bit | 1.1 switch | CT |
| 26 | [In4] Counter 16 Bits | Counter (0-65535) | 2 Bytes | 7.1 pulses | CRT |
| 27 | [In4] Switch 5 Telegram | 1 = On, 0 = Off | 1 Bit | 1.1 switch | CT |
| 28 | [In4] Scene save | 0 = Scene 1, 1 = Scene 2 | 1 Bit | 1.3 enable | CT |
| 28 | [In4] Increase/Decrease (via bus) | 0 = Up, 1 = Down | 1 Bit | 1.8 up/down | CW |
| 30 | [Out1] Switch Status | 1 = On, 0= Off | 1 Bit | 1.1 switch | CT |
| 31 | [Out1] Switch On/Off | 1 = On, 0= Off | 1 Bit | 1.1 switch | CW |
| 32 | [Out1] Forced positioning 1 bit | 1 = Forced, 0 = No Forced | 1 Bit | 1.3 enable | CW |
| 32 | [Out1] Forced positioning 2 Bits | 2 Bits value | 2 Bit | 2.1 switch control | CW |
| 34 | [Out1] Change Threshold value | 1 Byte value | 1 Byte | 5.10 counter pulses (0..255) | CW |
| 34 | [Out1] Change Threshold value | 2 Bytes value | 2 Bytes | 7.1 pulses | CW |
| 35 | [Out1] Threshold input | 1 Byte value | 1 Byte | 5.10 counter pulses (0..255) | CW |
| 35 | [Out1] Threshold Input | 2 Bytes value | 2 Bytes | 7.1 pulses | CW |
| 37 | [Out1] Logical connection 1 | 1 = True, 0 = False | 1 Bit | 1.2 boolean | CW |
| 38 | [Out1] Logical connection 2 | 1 = True, 0 = False | 1 Bit | 1.2 boolean | CW |
| 39 | [Out1] Scene | Scene control | 1 Byte | 18.1 scene control | CW |
| 40 | [Out1] Set Preset 1/2 | Telegram 0 --> Set Preset 1, Telegram 1 --> Set Preset 2 | 1 Bit | 1.1 switch | CW |
| 41 | [Out1] Call Preset 1/2 | Telegram 0 --> Call Preset 1, Telegram 1 --> Call Preset 2 | 1 Bit | 1.3 enable | CW |
| 42 | [Out1] Timed switch | 1 = Timed On | 1 Bit | 1.10 start/stop | CW |
| 43 | [Out1] Stair lighting Warning | 1 = Warning, 0 = No warning | 1 Bit | 1.1 switch | CT |
| 44 | [Out1] Duration of staircase light (sec) | 2 Bytes value | 2 Bytes | 7.5 time (s) | CW |
| 45 | [Out1] Permanent ON | 1 = On, 0 = Off | 1 Bit | 1.1 switch | CW |
| 46 | [Out1] Disable Time function | 1 = Disable, 0 = Enable | 1 Bit | 1.3 enable | CW |
| 50 | [Out2] Switch Status | 1 = On, 0 = Off | 1 Bit | 1.1 switch | CT |
| 51 | [Out2] Switch On/Off | 1 = On, 0= Off | 1 Bit | 1.1 switch | CW |
| 52 | [Out2] Forced positioning 2 bit | 2 Bit value | 2 Bit | 2.1 switch control | CW |
| 52 | [Out2] Forced positioning 1 Bit | 1 = Forced, 0 = No Forced | 1 Bit | 1.1 switch | CW |
| 54 | [Out2] Change Threshold value | 1 Byte value | 1 Byte | 5.10 counter pulses (0..255) | CW |
| 54 | [Out2] Change Threshold value | 2 Bytes value | 2 Bytes | 7.1 pulses | CW |
| 55 | [Out2] Threshold input | 1 Byte value | 1 Byte | 5.10 counter pulses (0..255) | CW |
| 55 | [Out2] Threshold input | 2 Bytes value | 2 Bytes | 7.1 pulses | CW |
| 57 | [Out2] Logical connection 1 | 1 = True, 0 = False | 1 Bit | 1.2 boolean | CW |
| 58 | [Out2] Logical connection 2 | 1 = True, 0 = False | 1 Bit | 1.2 boolean | CW |
| 59 | [Out2] Scene | Scene control | 1 Byte | 18.1 scene control | CW |
| 60 | [Out2] Set Preset 1/2 | Telegram 0 --> Set Preset 1, Telegram 1 --> Set Preset 2 | 1 Bit | 1.1 switch | CW |
| 61 | [Out2] Call Preset 1/2 | Telegram 0 --> Call Preset 1, Telegram 1 --> Call Preset 2 | 1 Bit | 1.3 enable | CW |
| 62 | [Out2] Timed switch | 1= Timed On | 1 Bit | 1.10 start/stop | CW |
| 63 | [Out2] Stair lighting Warning | 1 = Warning, 0 = No warning | 1 Bit | 1.1 switch | CT |
| 64 | [Out2] Duration of staircase light (sec) | 2 Bytes value | 2 Bytes | 7.5 time (s) | CW |
| 65 | [Out2] Permanent ON | 1 = On, 0 = Off | 1 Bit | 1.1 switch | CW |
| 66 | [Out2] Disable Time function | 1 = Disable, 0 = Enable | 1 Bit | 1.3 enable | CW |
| 70 | [Out] Blind Move Up/Down | 0 = Up, 1 = Down | 1 Bit | 1.8 up/down | CW |
| 70 | [Out] Roller Move Up/Down | 0 = Up, 1 = Down | 1 Bit | 1.8 up/down | CW |
| 70 | [Out] Louver Move Up/Down | 0 = Up, 1 = Down | 1 Bit | 1.8 up/down | CW |
| 71 | [Out] Blind Stop / Step Up/Down | 0 = Step Up, 1 = Step Down | 1 Bit | 1.7 step | CW |
| 71 | [Out] Roller Stop / Step Up/Down | 0 = Step Up, 1 = Step Down | 1 Bit | 1.7 step | CW |
| 71 | [Out] Louver Stop / Step Up/Down | 0 = Step Up, 1 = Step Down | 1 Bit | 1.7 step | CW |
| 72 | [Out] Forced input | 2 Bits control | 2 Bit | 2.1 switch control | CW |
| 73 | [Out] Wind alarm input 1 | 1 = Alarm, 0 = No alarm | 1 Bit | 1.5 alarm | CW |
| 74 | [Out] Wind alarm input 2 | 1 = Alarm, 0 = No alarm | 1 Bit | 1.5 alarm | CW |
| 75 | [Out] Wind alarm input 3 | 1 = Alarm, 0 = No alarm | 1 Bit | 1.5 alarm | CW |
| 76 | [Out] Rain alarm input | 1 = Alarm, 0 = No alarm | 1 Bit | 1.5 alarm | CW |
| 77 | [Out] Frost alarm input | 1 = Alarm, 0 = No alarm | 1 Bit | 1.5 alarm | CW |
| 78 | [Out] Scene input | Scene control | 1 Byte | 18.1 scene control | CW |
| 79 | [Out] Info Movement | 0 = Up, 1 = Down | 1 Bit | 1.8 up/down | CT |
| 80 | [Out] Blind position input | 0h = 0%, 80h = 50%, FFh = 100% | 1 Byte | 5.1 percentage (0..100%) | CW |
| 80 | [Out] Louver position Input | 0h = 0%, 80h = 50%, FFh = 100% | 1 Byte | 5.1 percentage (0..100%) | CW |
| 80 | [Out] Roller position Input | 0h = 0%, 80h = 50%, FFh = 100% | 1 Byte | 5.1 percentage (0..100%) | CW |
| 81 | [Out] Slats position input | 0h = 0%, 80h = 50%, FFh = 100% | 1 Byte | 5.1 percentage (0..100%) | CW |
| 82 | [Out] Blind position Info | 0h = 0%, 80h = 50%, FFh = 100% | 1 Byte | 5.1 percentage (0..100%) | CT |
| 82 | [Out] Roller position Info | 0h = 0%, 80h = 50%, FFh = 100% | 1 Byte | 5.1 percentage (0..100%) | CT |
| 82 | [Out] Louver position Info | 0h = 0%, 80h = 50%, FFh = 100% | 1 Byte | 5.1 percentage (0..100%) | CT |
| 83 | [Out] Slats position Info | 0h = 0%, 80h = 50%, FFh = 100% | 1 Byte | 5.1 percentage (0..100%) | CT |
| 84 | [Out] Lux level input | Lux value | 2 Bytes | 9.4 lux (Lux) | CW |
| 84 | [Out] Solar protection Input | 1 = On, 0 = Off | 1 Bit | 1.1 switch | CW |
| 85 | [Out] Solar protection position input | 0h = 0%, 80h = 50%, FFh = 100% | 1 Byte | 5.1 percentage (0..100%) | CW |
| 90 | [T1] On/Off status Info | 1 = On; 0 = Off | 1 Bit | 1.1 switch | CT |
| 91 | [T1] On/Off Input | 1= On; 0= Off | 1 Bit | 1.1 switch | CW |
| 92 | [T1] Set-point Information | Current Set-point | 2 Bytes | 9.1 temperature (°C) | CT |
| 93 | [T1] Set-point Input | Set-point | 2 Bytes | 9.1 temperature (°C) | CW |
| 93 | [T1] Comfort Set-point Input | Comfort Set-point | 2 Bytes | 9.1 temperature (°C) | CW |
| 94 | [T1] Output | Output (PWM Proportional - Integral) | 1 Bit | 1.1 switch | CT |
| 94 | [T1] Output | Output (% Proportional - Integral) | 1 Byte | 5.1 percentage (0..100%) | CT |
| 94 | [T1] Output Heating | Output (PWM Proportional - Integral) | 1 Bit | 1.1 switch | CT |
| 94 | [T1] Output Heating | Output (2 points with Hysteresis) | 1 Bit | 1.1 switch | CT |
| 94 | [T1] Output Heating | Output (% Proportional - Integral) | 1 Byte | 5.1 percentage (0..100%) | CT |
| 94 | [T1] Output | Output (2 points with Hysteresis) | 1 Bit | 1.1 switch | CT |
| 95 | [T1] Output Cooling | Output (% Proportional - Integral) | 1 Byte | 5.1 percentage (0..100%) | CT |
| 95 | [T1] Output Cooling | Output (2 points with Hysteresis) | 1 Bit | 1.1 switch | CT |
| 95 | [T1] Output Cooling | Output (PWM Proportional - Integral) | 1 Bit | 1.1 switch | CT |
| 96 | [T1] Temperature Sensor 1 | Input Temperature Sensor 1 | 2 Bytes | 9.1 temperature (°C) | CW |
| 97 | [T1] Temperature Sensor 2 | Input Temperature Sensor 2 | 2 Bytes | 9.1 temperature (°C) | CW |
| 98 | [T1] Special mode Info | 2 Bytes mode Info | 2 Bytes | 22.101 RHCC status | CT |
| 99 | [T1] Special mode Input 1 Byte | 1 Byte mode HVAC | 1 Byte | 20.102 HVAC mode | CW |
| 100 | [T1] Special mode Economic | 0=Off; 1=On | 1 Bit | 1.1 switch | CW |
| 101 | [T1] Special mode Stand-by | 0=Off; 1=On | 1 Bit | 1.1 switch | CW |
| 102 | [T1] Special mode Protection | 0=Off; 1=On | 1 Bit | 1.1 switch | CW |
| 103 | [T1] Special mode Comfort | 0=Off; 1=On | 1 Bit | 1.1 switch | CW |
| 104 | [T1] Heating or Cooling mode Status | 0=Cooling; 1=Heating | 1 Bit | 1.1 switch | CT |
| 105 | [T1] Heating or Cooling mode | 0=Cooling; 1=Heating | 1 Bit | 1.1 switch | CW |
| 106 | [T1] Window alarm 1 Input | 0=No alarm; 1=Alarm | 1 Bit | 1.5 alarm | CW |
| 107 | [T1] Window alarm 2 Input | 0=No alarm; 1=Alarm | 1 Bit | 1.5 alarm | CW |
| 108 | [T1] Window alarm 3 Input | 0=No alarm; 1=Alarm | 1 Bit | 1.5 alarm | CW |
| 109 | [T1] Window alarm 4 Input | 0=No alarm; 1=Alarm | 1 Bit | 1.5 alarm | CW |
| 110 | [T2] On/Off status Info | 1 = On; 0 = Off | 1 Bit | 1.1 switch | CT |
| 111 | [T2] On/Off Input | 1 = On; 0 = Off | 1 Bit | 1.1 switch | CW |
| 112 | [T2] Set-point Information | Current Set-point | 2 Bytes | 9.1 temperature (°C) | CT |
| 113 | [T2] Set-point Input | Set-point | 2 Bytes | 9.1 temperature (°C) | CW |
| 113 | [T2] Comfort Set-point Input | Comfort Set-point | 2 Bytes | 9.1 temperature (°C) | CW |
| 114 | [T2] Output Heating | Output (PWM Proportional - Integral) | 1 Bit | 1.1 switch | CT |
| 114 | [T2] Output | Output (PWM Proportional - Integral) | 1 Bit | 1.1 switch | CT |
| 114 | [T2] Output | Output (2 points with Hysteresis) | 1 Bit | 1.1 switch | CT |
| 114 | [T2] Output | Output (% Proportional - Integral) | 1 Byte | 5.10 counter pulses (0..255) | CT |
| 114 | [T2] Output Heating | Output (% Proportional - Integral) | 1 Byte | 5.10 counter pulses (0..255) | CT |
| 114 | [T2] Output Heating | Output (2 points with Hysteresis) | 1 Bit | 1.1 switch | CT |
| 115 | [T2] Output Cooling | Output (PWM Proportional - Integral) | 1 Bit | 1.1 switch | CT |
| 115 | [T2] Output Cooling | Output (% Proportional - Integral) | 1 Byte | 5.10 counter pulses (0..255) | CT |
| 115 | [T2] Output Cooling | Output (2 points with Hysteresis) | 1 Bit | 1.1 switch | CT |
| 116 | [T2] Temperature sensor 1 | Input Temperature Sensor 1 | 2 Bytes | 9.1 temperature (°C) | CW |
| 117 | [T2] Temperature sensor 2 | Input Temperature Sensor 2 | 2 Bytes | 9.1 temperature (°C) | CW |
| 118 | [T2] Special mode Info | 2 Bytes mode Info | 2 Bytes | 22.101 RHCC status | CT |
| 119 | [T2] Special mode Input 1 Byte | 1 Byte mode HVAC | 1 Byte | 20.102 HVAC mode | CW |
| 120 | [T2] Special mode Economic | 0=Off; 1=On | 1 Bit | 1.1 switch | CW |
| 121 | [T2] Special mode Stand-by | 0=Off; 1=On | 1 Bit | 1.1 switch | CW |
| 122 | [T2] Special mode Protection | 0=Off; 1=On | 1 Bit | 1.1 switch | CW |
| 123 | [T2] Special mode Comfort | 0=Off; 1=On | 1 Bit | 1.1 switch | CW |
| 124 | [T2] Heating or Cooling mode Status | 0=Cooling; 1=Heating | 1 Bit | 1.1 switch | CT |
| 125 | [T2] Heating or Cooling mode | 0=Cooling; 1=Heating | 1 Bit | 1.1 switch | CW |
| 126 | [T2] Window alarm 1 Input | 0=No alarm; 1=Alarm | 1 Bit | 1.5 alarm | CW |
| 127 | [T2] Window alarm 2 Input | 0=No alarm; 1=Alarm | 1 Bit | 1.5 alarm | CW |
| 128 | [T2] Window alarm 3 Input | 0=No alarm; 1=Alarm | 1 Bit | 1.5 alarm | CW |
| 129 | [T2] Window alarm 4 Input | 0=No alarm; 1=Alarm | 1 Bit | 1.5 alarm | CW |
| 130 | [T3] On/Off status Info | 1 = On; 0 = Off | 1 Bit | 1.1 switch | CT |
| 131 | [T3] On/Off Input | 1= On; 0= Off | 1 Bit | 1.1 switch | CW |
| 132 | [T3] Set-point Information | Current Set-point | 2 Bytes | 9.1 temperature (°C) | CT |
| 133 | [T3] Set-point Input | Set-point | 2 Bytes | 9.1 temperature (°C) | CW |
| 133 | [T3] Comfort Set-point Input | Comfort Set-point | 2 Bytes | 9.1 temperature (°C) | CW |
| 134 | [T3] Output Heating | Output (PWM Proportional - Integral) | 1 Bit | 1.1 switch | CT |
| 134 | [T3] Output | Output (2 points with Hysteresis) | 1 Bit | 1.1 switch | CT |
| 134 | [T3] Output | Output (PWM Proportional - Integral) | 1 Bit | 1.1 switch | CT |
| 134 | [T3] Output | Output (% Proportional - Integral) | 1 Byte | 5.10 counter pulses (0..255) | CT |
| 134 | [T3] Output Heating | Output (% Proportional - Integral) | 1 Byte | 5.10 counter pulses (0..255) | CT |
| 134 | [T3] Output Heating | Output (2 points with Hysteresis) | 1 Bit | 1.1 switch | CT |
| 135 | [T3] Output Cooling | Output (PWM Proportional - Integral) | 1 Bit | 1.1 switch | CT |
| 135 | [T3] Output Cooling | Output (% Proportional - Integral) | 1 Byte | 5.10 counter pulses (0..255) | CT |
| 135 | [T3] Output Cooling | Output (2 points with Hysteresis) | 1 Bit | 1.1 switch | CT |
| 136 | [T3] Temperature Sensor 1 | Input Temperature Sensor 1 | 2 Bytes | 9.1 temperature (°C) | CW |
| 137 | [T3] Temperature Sensor 2 | Input Temperature Sensor 2 | 2 Bytes | 9.1 temperature (°C) | CW |
| 138 | [T3] Special mode Info | 2 Bytes mode Info | 2 Bytes | 22.101 RHCC status | CT |
| 139 | [T3] Special mode Input 1 Byte | 1 Byte mode HVAC | 1 Byte | 20.102 HVAC mode | CW |
| 140 | [T3] Special mode Economic | 0=Off; 1=On | 1 Bit | 1.1 switch | CW |
| 141 | [T3] Special mode Stand-by | 0=Off; 1=On | 1 Bit | 1.1 switch | CW |
| 142 | [T3] Special mode Protection | 0=Off; 1=On | 1 Bit | 1.1 switch | CW |
| 143 | [T3] Special mode Comfort | 0=Off; 1=On | 1 Bit | 1.1 switch | CW |
| 144 | [T3] Heating or Cooling mode Status | 0=Cooling; 1=Heating | 1 Bit | 1.1 switch | CT |
| 145 | [T3] Heating or Cooling mode | 0=Cooling; 1=Heating | 1 Bit | 1.1 switch | CW |
| 146 | [T3] Window alarm 1 Input | 0=No alarm; 1=Alarm | 1 Bit | 1.5 alarm | CW |
| 147 | [T3] Window alarm 2 Input | 0=No alarm; 1=Alarm | 1 Bit | 1.5 alarm | CW |
| 148 | [T3] Window alarm 3 Input | 0=No alarm; 1=Alarm | 1 Bit | 1.5 alarm | CW |
| 149 | [T3] Window alarm 4 Input | 0=No alarm; 1=Alarm | 1 Bit | 1.5 alarm | CW |
| 150 | [T4] On/Off status Info | 1 = On; 0 = Off | 1 Bit | 1.1 switch | CT |
| 151 | [T4] On/Off Input | 1 = On; 0 = Off | 1 Bit | 1.1 switch | CW |
| 152 | [T4] Set-point Information | Current Set-point | 2 Bytes | 9.1 temperature (°C) | CT |
| 153 | [T4] Set-point Input | Set-point | 2 Bytes | 9.1 temperature (°C) | CW |
| 153 | [T4] Comfort Set-point Input | Comfort Set-point | 2 Bytes | 9.1 temperature (°C) | CW |
| 154 | [T4] Output Heating | Output (PWM Proportional - Integral) | 1 Bit | 1.1 switch | CT |
| 154 | [T4] Output | Output (2 points with Hysteresis) | 1 Bit | 1.1 switch | CT |
| 154 | [T4] Output | Output (PWM Proportional - Integral) | 1 Bit | 1.1 switch | CT |
| 154 | [T4] Output | Output (% Proportional - Integral) | 1 Byte | 5.10 counter pulses (0..255) | CT |
| 154 | [T4] Output Heating | Output (% Proportional - Integral) | 1 Byte | 5.10 counter pulses (0..255) | CT |
| 154 | [T4] Output Heating | Output (2 points with Hysteresis) | 1 Bit | 1.1 switch | CT |
| 155 | [T4] Output Cooling | Output (PWM Proportional - Integral) | 1 Bit | 1.1 switch | CT |
| 155 | [T4] Output Cooling | Output (2 points with Hysteresis) | 1 Bit | 1.1 switch | CT |
| 155 | [T4] Output Cooling | Output (% Proportional - Integral) | 1 Byte | 5.10 counter pulses (0..255) | CT |
| 156 | [T4] Temperature Sensor 1 | Input Temperature Sensor 1 | 2 Bytes | 9.1 temperature (°C) | CW |
| 157 | [T4] Temperature Sensor 2 | Input Temperature Sensor 2 | 2 Bytes | 9.1 temperature (°C) | CW |
| 158 | [T4] Special mode Info | 2 Bytes mode Info | 2 Bytes | 22.101 RHCC status | CT |
| 159 | [T4] Special mode Input 1 Byte | 1 Byte mode HVAC | 1 Byte | 20.102 HVAC mode | CW |
| 160 | [T4] Special mode Economic | 0=Off; 1=On | 1 Bit | 1.1 switch | CW |
| 161 | [T4] Special mode Stand-by | 0=Off; 1=On | 1 Bit | 1.1 switch | CW |
| 162 | [T4] Special mode Protection | 0=Off; 1=On | 1 Bit | 1.1 switch | CW |
| 163 | [T4] Special mode Comfort | 0=Off; 1=On | 1 Bit | 1.1 switch | CW |
| 164 | [T4] Heating or Cooling mode Status | 0=Cooling; 1=Heating | 1 Bit | 1.1 switch | CT |
| 165 | [T4] Heating or Cooling mode | 0=Cooling; 1=Heating | 1 Bit | 1.1 switch | CW |
| 166 | [T4] Window alarm 1 Input | 0=No alarm; 1=Alarm | 1 Bit | 1.5 alarm | CW |
| 167 | [T4] Window alarm 2 Input | 0=No alarm; 1=Alarm | 1 Bit | 1.5 alarm | CW |
| 168 | [T4] Window alarm 3 Input | 0=No alarm; 1=Alarm | 1 Bit | 1.5 alarm | CW |
| 169 | [T4] Window alarm 4 Input | 0=No alarm; 1=Alarm | 1 Bit | 1.5 alarm | CW |