Temperature sensor SE K5X 005
Dinuy · Order number SE K5X 005 · KNX-RF Devices › Sensors › Temperature Sensor with Probe
Download .knxprod DINUY Temperature sensor 0.0 · 122 KB
Product
| Manufacturer | Dinuy |
|---|---|
| Product name | Temperature sensor |
| Order number | SE K5X 005 |
| Hardware | Temperature sensor |
| Medium | KNX RF |
| Rail mounted | No |
| Registration | Certified · 2018-07-09 |
| Languages | es-ES |
| Catalog entry | M-009A_H-009ASEK5X005270418-0_HP-2000-00-C4D8_CI-SE.20K5X.20005-1 |
| Fingerprint | C4D8 |
| SHA-256 | d550d6bad3371a326fda94b711990193ff5299e91509fe959ee3f427e8f854cd |
| First seen | 2026-11-25 |
| Markets | 68 markets |
Application program: DINUY Temperature sensor 0.0
| Application number | $2000 |
|---|---|
| Version | 0.0 |
| Mask version | MV-27B0 (RF System B) |
| KNX Data Secure | No |
| Minimum ETS version | 5.0 |
| Parameters | 51 |
| Group objects | 30 |
Group objects (30)
| No | Name | Function | Size | DPT | Flags |
|---|---|---|---|---|---|
| 1 | Disable temperature send | 1=Disable; 0=Enable | 1 Bit | 1.3 enable | CW |
| 2 | Output temperature value | Temperature value | 2 Bytes | 9.1 temperature (°C) | CT |
| 3 | Output sensor not connected | 0=Sensor OK; 1=Sensor not connected | 1 Bit | 1.11 state | CT |
| 4 | Output Over-Heating | 1=Over-Heating; 0=No Over-Heating | 1 Bit | 1.5 alarm | CT |
| 5 | Output Over-Cooling | 1=Over-Cooling; 0=No Over-Cooling | 1 Bit | 1.5 alarm | CT |
| 10 | Thermostat On/Off status | 1 = On; 0 = Off | 1 Bit | 1.1 switch | CT |
| 11 | Thermostat On/Off | 1 = On; 0 = Off | 1 Bit | 1.1 switch | CW |
| 12 | Set-point Input | Set-point | 2 Bytes | 9.1 temperature (°C) | CW |
| 12 | Comfort set-point Input | Comfort set-point | 2 Bytes | 9.1 temperature (°C) | CW |
| 13 | Set-point information | Set-point actual | 2 Bytes | 9.1 temperature (°C) | CT |
| 25 | Output | Output (% Proportional- Integral) | 1 Byte | 5.1 percentage (0..100%) | CT |
| 25 | Output | Output (PWM Proportional- Integral) | 1 Bit | 1.1 switch | CT |
| 25 | Output | Output (2 points with hysteresis) | 1 Bit | 1.1 switch | CT |
| 25 | Output Heating | Output (% Proportional- Integral) | 1 Byte | 5.1 percentage (0..100%) | CT |
| 25 | Output Heating | Output (PWM Proportional- Integral) | 1 Bit | 1.1 switch | CT |
| 25 | Output Heating | Output (2 point with hysteresis) | 1 Bit | 1.1 switch | CT |
| 26 | Output Cooling | Output (% Proportional- Integral) | 1 Byte | 5.1 percentage (0..100%) | CT |
| 26 | Output Cooling | Output (PWM Proportional- Integral) | 1 Bit | 1.1 switch | CT |
| 26 | Output Cooling | Output (2 points with hysteresis) | 1 Bit | 1.1 switch | CT |
| 27 | Special mode Info | 2-byte mode Info | 2 Bytes | 22.101 RHCC status | CT |
| 28 | Special mode input 1byte | 1-byte mode HVAC mode | 1 Byte | 20.102 HVAC mode | CW |
| 29 | Window alarm | 0 = No alarm; 1 = Alarm | 1 Bit | 1.5 alarm | CW |
| 30 | Special mode Economic | 0 = Off; 1 = On | 1 Bit | 1.1 switch | CW |
| 31 | Special mode Stand-by | 0 = Off; 1 = On | 1 Bit | 1.1 switch | CW |
| 32 | Special mode Comfort | 0 = Off; 1 = On | 1 Bit | 1.1 switch | CW |
| 33 | Special mode Protection | 0 = Off; 1 = On | 1 Bit | 1.1 switch | CW |
| 34 | Heating or Cooling mode | 0 = Cooling; 1 = Heating | 1 Bit | 1.1 switch | CW |
| 35 | Heating or Cooling mode status | 0 = Cooling; 1 = Heating | 1 Bit | 1.1 switch | CT |
| 36 | Temperature Sensor 1 | Input Temperature Sensor 1 | 2 Bytes | 9.1 temperature (°C) | CW |
| 37 | Temperature Sensor 2 | Input Temperature Sensor 2 | 2 Bytes | 9.1 temperature (°C) | CW |
Parameters (44)
| Parameter | Type | Default |
|---|---|---|
| Base time to send Temperature | list | 1 Min |
| Factor time to send Temperature (Total time = Base x Factor) (0 = Disable send) | unsignedInt 0…255 | 5 |
| Temperature variation to send | unsignedInt 5…200 | 5 |
| Protection Alarms | list | No protection |
| Over-Heating Temperature | list | 45 |
| Over-Cooling Temperature | list | -30 |
| Hysteresis | unsignedInt 0…50 | 0 |
| "Temperature send" enabled after bus recovery voltage? | list | Yes |
| Temperature sensor calibration value | list | 0 |
| Enable Thermostat functionality | list | Enabled |
| Mode | list | Cooling and Heating Thermostat |
| Set-point mode | list | Absolute Set-point mode |
| Initial comfort set-point after bus recovery voltage | unsignedInt 5…45 | 24 |
| Enable window protection | list | Enable |
| Thermostat always on? | list | No |
| State after bus recovery voltage | list | On |
| Enable turn on Thermostat when special commands arrive? | list | Enable |
| Send Thermostat mode after bus recovery voltage? | list | Yes |
| Enable automatic mode change? | list | Enable |
| Thermostat type after bus recovery voltage? | list | Heating Thermostat |
| Control object | list | Only one object for Heating and Cooling |
| Mode after bus recovery voltage | list | Comfort |
| Enable 1bit mode objects? | list | Switch mode |
| Reference temperature source | list | One source |
| Remember set-point input after bus recovery voltage? | list | Yes |
| Comfort mode set-point | unsignedInt 5…45 | 24 |
| Offset for Stand-by set-point mode | list | -30 |
| Offset for Economic set-point mode | list | -50 |
| Set-point for protection from Freezing | unsignedInt 0…15 | 8 |
| Offset for Stand-by set-point mode | unsignedInt 0…100 | 30 |
| Offset for Economic set-point mode | unsignedInt 0…100 | 50 |
| Over-Temperature protection set-point | unsignedInt 30…45 | 40 |
| Regulation mode | list | Two points with Hysteresis control |
| Upper Hysteresis | unsignedInt 5…45 | 10 |
| Lower Hysteresis | unsignedInt 5…45 | 10 |
| Forwarding period (0 = Disable) | unsignedInt 0…255 | 0 |
| PWM type | list | PWM (1 bit) |
| PI cycle time | unsignedInt 0…255 | 15 |
| Proportional band | unsignedInt 0…15 | 5 |
| Attenuation factor | unsignedInt 0…99 | 31 |
| Maximum Integral component (%) | unsignedInt 0…99 | 21 |
| Upper hysteresis | unsignedInt 5…45 | 10 |
| Lower hysteresis | unsignedInt 5…45 | 10 |
| Initial set-point afer bus recovery voltage | unsignedInt 5…45 | 24 |
Version history
| Application | App no | Fingerprint | First seen | Size | File |
|---|---|---|---|---|---|
| DINUY Temperature sensor 0.0 latest | $2000 | C4D8 | 2026-11-25 | 122 KB | Download |
About this file
This is the official ETS product database for the Dinuy Temperature sensor (SE K5X 005), published by the manufacturer in the KNX online catalog. To use it, open ETS, go to Catalogs → Import and choose the downloaded .knxprod file. The device then appears in your catalog and can be added to a project. Older versions are kept so existing projects can be matched to the application program they were commissioned with.
More from Dinuy
- KNX RF/TP Coupler Secure CO K5X 003 CO K5X 003
- Movement Detector DMK5X 001-230
- KNX-RF Pushbutton Interface EMK5X002
- 4-channel Universal Interface EMK5X004
- 2-channel switching actuator/blind actuator PE K5X 002
- Actuator RF 1ch Blind / 2ch Switch - 4 Inputs PEK5X001
- DINUY RF 3-channel LED Strip Dimmer_4input ch RE K5X RGB
- Multi driver led dimmer RE KNX XXX
- KNX-RF Multi-Sensor SE K5X 0XX
- KNX RF/TP Coupler CO K5X 002
- KNX IP Interface Secure CO KNT IPI CO KNT IPI
- KNX IP Router Secure CO KNT IPR CO KNT IPR