KNX Database
Dinuy SE K5X 005 Temperature sensor

Temperature sensor SE K5X 005

Dinuy · Order number SE K5X 005 · KNX-RF Devices › Sensors › Temperature Sensor with Probe

Download .knxprod DINUY Temperature sensor 0.0 · 122 KB

Product

ManufacturerDinuy
Product nameTemperature sensor
Order numberSE K5X 005
HardwareTemperature sensor
MediumKNX RF
Rail mountedNo
RegistrationCertified · 2018-07-09
Languageses-ES
Catalog entryM-009A_H-009ASEK5X005270418-0_HP-2000-00-C4D8_CI-SE.20K5X.20005-1
FingerprintC4D8
SHA-256d550d6bad3371a326fda94b711990193ff5299e91509fe959ee3f427e8f854cd
First seen2026-11-25
Markets68 markets

Application program: DINUY Temperature sensor 0.0

Application number$2000
Version0.0
Mask versionMV-27B0 (RF System B)
KNX Data SecureNo
Minimum ETS version5.0
Parameters51
Group objects30
Group objects (30)
NoNameFunctionSizeDPTFlags
1Disable temperature send1=Disable; 0=Enable1 Bit1.3 enableCW
2Output temperature valueTemperature value2 Bytes9.1 temperature (°C)CT
3Output sensor not connected0=Sensor OK; 1=Sensor not connected1 Bit1.11 stateCT
4Output Over-Heating1=Over-Heating; 0=No Over-Heating1 Bit1.5 alarmCT
5Output Over-Cooling1=Over-Cooling; 0=No Over-Cooling1 Bit1.5 alarmCT
10Thermostat On/Off status1 = On; 0 = Off1 Bit1.1 switchCT
11Thermostat On/Off1 = On; 0 = Off1 Bit1.1 switchCW
12Set-point Input Set-point2 Bytes9.1 temperature (°C)CW
12Comfort set-point InputComfort set-point2 Bytes9.1 temperature (°C)CW
13Set-point informationSet-point actual2 Bytes9.1 temperature (°C)CT
25OutputOutput (% Proportional- Integral)1 Byte5.1 percentage (0..100%)CT
25OutputOutput (PWM Proportional- Integral)1 Bit1.1 switchCT
25OutputOutput (2 points with hysteresis)1 Bit1.1 switchCT
25Output HeatingOutput (% Proportional- Integral)1 Byte5.1 percentage (0..100%)CT
25Output HeatingOutput (PWM Proportional- Integral)1 Bit1.1 switchCT
25Output HeatingOutput (2 point with hysteresis)1 Bit1.1 switchCT
26Output CoolingOutput (% Proportional- Integral)1 Byte5.1 percentage (0..100%)CT
26Output CoolingOutput (PWM Proportional- Integral)1 Bit1.1 switchCT
26Output CoolingOutput (2 points with hysteresis)1 Bit1.1 switchCT
27Special mode Info2-byte mode Info2 Bytes22.101 RHCC statusCT
28Special mode input 1byte1-byte mode HVAC mode1 Byte20.102 HVAC modeCW
29Window alarm0 = No alarm; 1 = Alarm1 Bit1.5 alarmCW
30Special mode Economic0 = Off; 1 = On1 Bit1.1 switchCW
31Special mode Stand-by0 = Off; 1 = On1 Bit1.1 switchCW
32Special mode Comfort0 = Off; 1 = On1 Bit1.1 switchCW
33Special mode Protection0 = Off; 1 = On1 Bit1.1 switchCW
34Heating or Cooling mode0 = Cooling; 1 = Heating1 Bit1.1 switchCW
35Heating or Cooling mode status0 = Cooling; 1 = Heating1 Bit1.1 switchCT
36Temperature Sensor 1Input Temperature Sensor 12 Bytes9.1 temperature (°C)CW
37Temperature Sensor 2Input Temperature Sensor 22 Bytes9.1 temperature (°C)CW
Parameters (44)
ParameterTypeDefault
Base time to send Temperaturelist1 Min
Factor time to send Temperature (Total time = Base x Factor) (0 = Disable send)unsignedInt 0…2555
Temperature variation to sendunsignedInt 5…2005
Protection AlarmslistNo protection
Over-Heating Temperaturelist45
Over-Cooling Temperaturelist-30
HysteresisunsignedInt 0…500
"Temperature send" enabled after bus recovery voltage?listYes
Temperature sensor calibration valuelist0
Enable Thermostat functionalitylistEnabled
ModelistCooling and Heating Thermostat
Set-point modelistAbsolute Set-point mode
Initial comfort set-point after bus recovery voltageunsignedInt 5…4524
Enable window protectionlistEnable
Thermostat always on?listNo
State after bus recovery voltagelistOn
Enable turn on Thermostat when special commands arrive?listEnable
Send Thermostat mode after bus recovery voltage?listYes
Enable automatic mode change?listEnable
Thermostat type after bus recovery voltage?listHeating Thermostat
Control objectlistOnly one object for Heating and Cooling
Mode after bus recovery voltagelistComfort
Enable 1bit mode objects?listSwitch mode
Reference temperature sourcelistOne source
Remember set-point input after bus recovery voltage?listYes
Comfort mode set-pointunsignedInt 5…4524
Offset for Stand-by set-point modelist-30
Offset for Economic set-point modelist-50
Set-point for protection from FreezingunsignedInt 0…158
Offset for Stand-by set-point modeunsignedInt 0…10030
Offset for Economic set-point modeunsignedInt 0…10050
Over-Temperature protection set-pointunsignedInt 30…4540
Regulation modelistTwo points with Hysteresis control
Upper HysteresisunsignedInt 5…4510
Lower HysteresisunsignedInt 5…4510
Forwarding period (0 = Disable)unsignedInt 0…2550
PWM typelistPWM (1 bit)
PI cycle timeunsignedInt 0…25515
Proportional bandunsignedInt 0…155
Attenuation factorunsignedInt 0…9931
Maximum Integral component (%)unsignedInt 0…9921
Upper hysteresisunsignedInt 5…4510
Lower hysteresisunsignedInt 5…4510
Initial set-point afer bus recovery voltageunsignedInt 5…4524

Version history

ApplicationApp noFingerprintFirst seenSizeFile
DINUY Temperature sensor 0.0 latest$2000C4D82026-11-25122 KBDownload

About this file

This is the official ETS product database for the Dinuy Temperature sensor (SE K5X 005), published by the manufacturer in the KNX online catalog. To use it, open ETS, go to Catalogs → Import and choose the downloaded .knxprod file. The device then appears in your catalog and can be added to a project. Older versions are kept so existing projects can be matched to the application program they were commissioned with.