SCN-RTR60S.01 Room Temperature Controller Smart 60 CH SCN-RTR60S.01
MDT technologies GmbH · Order number SCN-RTR60S.01 · Temperature Controller › Room temperature controller Smart
Download .knxprod Room temperature controller Smart 55/63 1.4 · 278 KB
Product
| Manufacturer | MDT technologies GmbH |
|---|---|
| Product name | SCN-RTR60S.01 Room Temperature Controller Smart 60 CH |
| Order number | SCN-RTR60S.01 |
| Hardware | Raumtemperaturregler Smart 55 |
| Medium | Twisted Pair |
| Bus current (mA) | 5 |
| Rail mounted | No |
| Registration | Certified · 2021-08-05 |
| Languages | de-DE, en-US, es-ES, fr-FR, it-IT |
| Catalog entry | M-0083_H-170-1_HP-005C-14-B9A9_CI-SCN.2DRTR60S.2E01-1 |
| Fingerprint | B9A9 |
| SHA-256 | 0ec51e2c71fa61798d89502c75a08f0989d4ea9cdc07fb7498c28f32a096db0c |
| First seen | 2026-11-25 |
| Markets | 69 markets |
Application program: Room temperature controller Smart 55/63 1.4
| Application number | $005C |
|---|---|
| Version | 1.4 |
| Mask version | MV-0705 (7.5) |
| KNX Data Secure | No |
| Minimum ETS version | 5.0 |
| Parameters | 595 |
| Group objects | 334 |
Group objects (334)
| No | Name | Function | Size | DPT | Flags |
|---|---|---|---|---|---|
| 0 | Setpoint setting | Set setpoint | 2 Bytes | 9.1 temperature (°C) | CW |
| 0 | Setpoint setting | Set setpoint | 2 Bytes | 9.1 temperature (°C) | CRT |
| 1 | Combination object | Set setpoint | 8 Bytes | 275.100 Temperature setpoint setting for 4 HVAC Modes | CW |
| 1 | Comfort | Set setpoint | 2 Bytes | 9.1 temperature (°C) | CW |
| 1 | Combination object (Heating) | Set setpoint | 8 Bytes | 275.100 Temperature setpoint setting for 4 HVAC Modes | CW |
| 1 | (Basic) Comfort setpoint | Set setpoint | 2 Bytes | 9.1 temperature (°C) | CW |
| 2 | Standby | Set setpoint | 2 Bytes | 9.1 temperature (°C) | CW |
| 3 | Night | Set setpoint | 2 Bytes | 9.1 temperature (°C) | CW |
| 4 | Frost protection | Set setpoint | 2 Bytes | 9.1 temperature (°C) | CW |
| 4 | Heating protection | Set setpoint | 2 Bytes | 9.1 temperature (°C) | CW |
| 5 | Combination object (Cooling) | Set setpoint | 8 Bytes | 275.100 Temperature setpoint setting for 4 HVAC Modes | CW |
| 6 | Current setpoint | Send setpoint | 2 Bytes | 9.1 temperature (°C) | CRT |
| 6 | Current setpoint | Receive setpoint | 2 Bytes | 9.1 temperature (°C) | CWTU |
| 7 | Manual setpoint shift | Increase / decrease (2Byte) | 2 Bytes | 9.2 temperature difference (K) | CW |
| 7 | Manual setpoint shift | Increase / decrease (2Byte) | 2 Bytes | 9.2 temperature difference (K) | CRT |
| 7 | Manual setpoint shift | Increase / decrease (1Byte) | 1 Byte | 6.10 counter pulses (-128..127) | CRT |
| 8 | Manual setpoint shift | Increase / decrease (1Byte) | 1 Byte | 6.10 counter pulses (-128..127) | CW |
| 8 | Manual setpoint shift | Increase / decrease (1=+ / 0=-) | 1 Bit | 1.7 step | CW |
| 8 | Manual setpoint shift | Increase / decrease (1=+ / 0=-) | 1 Bit | 1.7 step | CT |
| 9 | Setpoint shift | Send status | 2 Bytes | 9.2 temperature difference (K) | CRT |
| 9 | Setpoint shift | Receive status | 2 Bytes | 9.2 temperature difference (K) | CWTU |
| 10 | Control value Heating | Send control value | 1 Byte | 5.1 percentage (0..100%) | CRT |
| 10 | Control value Heating | Send control value | 1 Bit | 1.1 switch | CRT |
| 10 | Control value Heating/Cooling | Send control value | 1 Byte | 5.1 percentage (0..100%) | CRT |
| 10 | Control value Heating/Cooling | Send control value | 1 Bit | 1.1 switch | CRT |
| 11 | Control value Cooling | Send control value | 1 Byte | 5.1 percentage (0..100%) | CRT |
| 11 | Control value Cooling | Send control value | 1 Bit | 1.1 switch | CRT |
| 12 | Control value Heating | Send status | 1 Byte | 5.1 percentage (0..100%) | CRT |
| 12 | Control value Heating/Cooling | Send status | 1 Byte | 5.1 percentage (0..100%) | CRT |
| 12 | Control value Heating/Cooling | Receive status | 1 Byte | 5.1 percentage (0..100%) | CWTU |
| 12 | Control value Heating | Receive status | 1 Byte | 5.1 percentage (0..100%) | CWTU |
| 13 | Control value Cooling | Send status | 1 Byte | 5.1 percentage (0..100%) | CRT |
| 13 | Control value Cooling | Receive status | 1 Byte | 5.1 percentage (0..100%) | CWTU |
| 14 | Control value additional Heating | Send control value | 1 Bit | 1.1 switch | CT |
| 15 | Mode selection | Select mode | 1 Byte | 20.102 HVAC mode | CW |
| 15 | Mode selection | Send mode | 1 Byte | 20.102 HVAC mode | CT |
| 16 | Comfort mode | Comfort extension | 1 Bit | 1.10 start/stop | CW |
| 17 | Comfort mode | Switch mode | 1 Bit | 1.1 switch | CW |
| 18 | Night mode | Switch mode | 1 Bit | 1.1 switch | CW |
| 19 | Mode Frost protection | Switch mode | 1 Bit | 1.1 switch | CW |
| 19 | Mode Heating protection | Switch mode | 1 Bit | 1.1 switch | CW |
| 19 | Frost/Heat protection mode | Switch mode | 1 Bit | 1.1 switch | CW |
| 20 | DPT_HVAC Mode | Send controller status | 1 Byte | 20.102 HVAC mode | CRT |
| 20 | DPT_HVAC Status | Send controller status | 1 Byte | CRT | |
| 20 | DPT_HVAC Status | Receive controller status | 1 Byte | CWTU | |
| 20 | DPT_HVAC Mode | Receive controller status | 1 Byte | 20.102 HVAC mode | CWTU |
| 21 | RHCC Status | Send controller status | 2 Bytes | 22.101 RHCC status | CRT |
| 21 | DPT_HVAC Status | Send controller status | 1 Byte | CRT | |
| 21 | DPT_HVAC Mode | Send controller status | 1 Byte | 20.102 HVAC mode | CRT |
| 21 | DPT_RTC combination status | Send controller status | 2 Bytes | 22.103 combined status RTC | CRT |
| 21 | DPT_RTSM combination status | Send controller status | 1 Byte | 21.107 combined status RTSM | CRT |
| 22 | Frost alarm | Send alarm | 1 Bit | 1.5 alarm | CRT |
| 23 | Heat alarm | Send alarm | 1 Bit | 1.5 alarm | CRT |
| 24 | Flow temperature Heating | Receive measured value | 2 Bytes | 9.1 temperature (°C) | CWT |
| 25 | Surface temperature Cooling | Receive measured value | 2 Bytes | 9.1 temperature (°C) | CWT |
| 25 | Dew point alarm | Receive alarm | 1 Bit | 1.5 alarm | CWT |
| 26 | Diagnosis | Status | 14 Bytes | 16.1 Character String (ISO 8859-1) | CRT |
| 27 | Window contact input | 0=closed / 1=open | 1 Bit | 1.19 window/door | CWTU |
| 27 | Window contact input | 1=closed / 0=open | 1 Bit | 1.1 switch | CWTU |
| 28 | Lock object Heating | Lock control value | 1 Bit | 1.3 enable | CRWTU |
| 29 | Lock object Cooling | Lock control value | 1 Bit | 1.3 enable | CRWTU |
| 30 | Dummy | 1 Bit | |||
| 31 | Dummy | 1 Bit | |||
| 32 | Toggle Heating/Cooling | 0=Cooling 1=Heating | 1 Bit | 1.100 cooling/heating | CW |
| 32 | Toggle Heating/Cooling | 0=Cooling 1=Heating | 1 Bit | 1.100 cooling/heating | CRT |
| 33 | Status Heating / Cooling | 0=Cooling 1=Heating | 1 Bit | 1.100 cooling/heating | CRT |
| 33 | Status Heating / Cooling | 0=Cooling 1=Heating | 1 Bit | 1.100 cooling/heating | CWTU |
| 34 | Heating request | Send request | 1 Bit | 1.1 switch | CRT |
| 35 | Cooling request | Send request | 1 Bit | 1.1 switch | CRT |
| 36 | Outside temperature | Receive measured / reference value | 2 Bytes | 9.1 temperature (°C) | CW |
| 36 | Outside temperature | Receive measured value | 2 Bytes | 9.1 temperature (°C) | CW |
| 37 | Ventilation control | Lock | 1 Bit | 1.3 enable | CW |
| 38 | Ventilation control | Level 1 | 1 Bit | 1.1 switch | CRT |
| 38 | Ventilation control | Bit 0 | 1 Bit | 1.2 boolean | CRT |
| 39 | Ventilation control | Level 2 | 1 Bit | 1.1 switch | CRT |
| 39 | Ventilation control | Bit 1 | 1 Bit | 1.2 boolean | CRT |
| 39 | Ventilation control | Level 1+2 | 1 Bit | 1.1 switch | CRT |
| 40 | Ventilation control | Level 3 | 1 Bit | 1.1 switch | CRT |
| 40 | Ventilation control | Bit 2 | 1 Bit | 1.2 boolean | CRT |
| 40 | Ventilation control | Level 1+2+3 | 1 Bit | 1.1 switch | CRT |
| 41 | Ventilation control | Level 4 | 1 Bit | 1.1 switch | CRT |
| 41 | Ventilation control | Level 1+2+3+4 | 1 Bit | 1.1 switch | CRT |
| 42 | Ventilation control | 1Byte status ventilation level | 1 Byte | 5.10 counter pulses (0..255) | CRT |
| 42 | Ventilation control | 1Byte status ventilation level (Extension unit) | 1 Byte | 5.10 counter pulses (0..255) | CWTU |
| 43 | Ventilation control | Control value | 1 Byte | 5.1 percentage (0..100%) | CRT |
| 44 | Ventilation control | Object Priority | 1 Bit | 1.1 switch | CW |
| 45 | Ventilation control | Switch Automatic | 1 Bit | 1.1 switch | CRWT |
| 45 | Ventilation control | Switch automatic mode (Extension unit) | 1 Bit | 1.1 switch | CRT |
| 46 | Ventilation control | Change ventilation levels manually (+/-) | 1 Bit | 1.7 step | CWT |
| 47 | Ventilation control | Manual ventilation control | 1 Byte | 5.100 fan stage (0..255) | CW |
| 47 | Ventilation control | Manual ventilation control (Extension unit) | 1 Byte | 5.100 fan stage (0..255) | CRT |
| 48 | Ventilation control | Status ventilation active | 1 Bit | 1.11 state | CRT |
| 49 | Ventilation control | Status Automatic | 1 Bit | 1.11 state | CRT |
| 49 | Ventilation control | Status automatic (Extension unit) | 1 Bit | 1.11 state | CWTU |
| 50 | Dummy | 1 Bit | |||
| 51 | Dummy | 1 Bit | |||
| 52 | Dummy | 1 Bit | |||
| 53 | Temperature | Send measured value | 2 Bytes | 9.1 temperature (°C) | CRT |
| 54 | Temperature | External sensor | 2 Bytes | 9.1 temperature (°C) | CWTU |
| 55 | Temperature | Max. value exceeded | 1 Bit | 1.5 alarm | CRT |
| 56 | Temperature | Min. value fallen below | 1 Bit | 1.5 alarm | CRT |
| 57 | Temperature | Read out maximum temperature value | 2 Bytes | 9.1 temperature (°C) | CRT |
| 58 | Temperature | Read out minimum temperature value | 2 Bytes | 9.1 temperature (°C) | CRT |
| 59 | Temperature | Reset memory min/max value | 1 Bit | 1.3 enable | CW |
| 60 | Temperature | Error external sensor | 1 Bit | 1.5 alarm | CRT |
| 61 | Relative air humidity | Send measured value | 2 Bytes | 9.7 humidity (%) | CRT |
| 62 | Relative air humidity | External humidity sensor | 2 Bytes | 9.7 humidity (%) | CWTU |
| 63 | Relative air humidity | Max. value exceeded | 1 Bit | 1.5 alarm | CRT |
| 64 | Relative air humidity | Min. value fallen below | 1 Bit | 1.5 alarm | CRT |
| 65 | Relative air humidity | Read out maximum relative humidity | 2 Bytes | 9.7 humidity (%) | CRT |
| 66 | Relative air humidity | Read out minimum relative humidity | 2 Bytes | 9.7 humidity (%) | CRT |
| 67 | Relative air humidity | Reset memory min/max value | 1 Bit | 1.3 enable | CW |
| 68 | Relative air humidity | Error external sensor | 1 Bit | 1.5 alarm | CRT |
| 69 | Absolute air humidity | Send measured value | 2 Bytes | 9.29 absolute humidity (g/m³) | CRT |
| 70 | Dew point temperature | Send measured value | 2 Bytes | 9.1 temperature (°C) | CRT |
| 71 | Dew point temperature | Comparison value | 2 Bytes | 9.1 temperature (°C) | CW |
| 72 | Dew point temperature | Send alarm | 1 Bit | 1.5 alarm | CRT |
| 73 | Comfort | Send status | 1 Bit | 1.11 state | CRT |
| 74 | Buttons 3/4: {{0}} | Switch On/Off | 1 Bit | 1.1 switch | CT |
| 74 | Buttons 3/4: {{0}} | Dimming On/Off | 1 Bit | 1.1 switch | CT |
| 74 | Buttons 3/4: {{0}} | Blinds Up/Down | 1 Bit | 1.8 up/down | CT |
| 74 | Button 3: {{0}} | Switch | 1 Bit | 1.1 switch | CT |
| 74 | Button 3: {{0}} | Toggle | 1 Bit | 1.1 switch | CT |
| 74 | Button 3: {{0}} | Send value | 1 Byte | 5.5 ratio (0..255) | CT |
| 74 | Button 3: {{0}} | Send percent value | 1 Byte | 5.1 percentage (0..100%) | CT |
| 74 | Button 3: {{0}} | Send scene | 1 Byte | 17.1 scene number | CT |
| 74 | Button 3 short: {{0}} | Switch | 1 Bit | 1.1 switch | CT |
| 74 | Button 3 short: {{0}} | Send value | 1 Byte | 5.5 ratio (0..255) | CT |
| 74 | Button 3 short: {{0}} | Send percent value | 1 Byte | 5.1 percentage (0..100%) | CT |
| 74 | Button 3 short: {{0}} | Send scene | 1 Byte | 17.1 scene number | CT |
| 74 | Button 3: {{0}} | Dimming On/Off | 1 Bit | 1.1 switch | CT |
| 74 | Button 3: {{0}} | Blinds Up/Down | 1 Bit | 1.8 up/down | CT |
| 74 | Button 3: {{0}} | Send status | 1 Bit | 1.11 state | CT |
| 74 | Button 3 short: {{0}} | Toggle | 1 Bit | 1.1 switch | CT |
| 75 | Buttons 3/4: {{0}} | Dimming relative | 4 Bit | 3.7 dimming control | CT |
| 75 | Buttons 3/4: {{0}} | Slat adjustment / Stop | 1 Bit | 1.7 step | CT |
| 75 | Button 3: {{0}} | Status for toggle | 1 Bit | 1.1 switch | CWTU |
| 75 | Button 3: {{0}} | Dimming relative | 4 Bit | 3.7 dimming control | CT |
| 75 | Button 3: {{0}} | Slat adjustment / Stop | 1 Bit | 1.7 step | CT |
| 75 | Button 3 short: {{0}} | Status for toggle | 1 Bit | 1.1 switch | CWTU |
| 75 | Button 3 short: {{0}} | Status for display | 1 Bit | 1.1 switch | CWTU |
| 75 | Button 3 short: {{0}} | Status for display | 1 Byte | 5.5 ratio (0..255) | CWTU |
| 75 | Button 3 short: {{0}} | Status for display | 1 Byte | 5.1 percentage (0..100%) | CWTU |
| 76 | Button 3 long: {{0}} | Switch | 1 Bit | 1.1 switch | CT |
| 76 | Button 3 long: {{0}} | Send value | 1 Byte | 5.5 ratio (0..255) | CT |
| 76 | Button 3 long: {{0}} | Send percent value | 1 Byte | 5.1 percentage (0..100%) | CT |
| 76 | Button 3 long: {{0}} | Send scene | 1 Byte | 17.1 scene number | CT |
| 76 | Button 3: {{0}} | Status for toggle | 1 Bit | 1.1 switch | CWTU |
| 76 | Button 3: {{0}} | Status for change of direction | 1 Bit | 1.8 up/down | CWTU |
| 76 | Button 3 long: {{0}} | Toggle | 1 Bit | 1.1 switch | CT |
| 77 | Button 3 long: {{0}} | Status for toggle | 1 Bit | 1.11 state | CWTU |
| 77 | Buttons 3/4: {{0}} | Status for display | 1 Bit | 1.11 state | CWTU |
| 77 | Button 3: {{0}} | Status for display | 1 Bit | 1.11 state | CWTU |
| 77 | Button 3: {{0}} | Status for display | 1 Byte | 5.1 percentage (0..100%) | CWTU |
| 77 | Buttons 3/4: {{0}} | Status for display | 1 Byte | 5.1 percentage (0..100%) | CWTU |
| 77 | Button 3: {{0}} | Status for display | 1 Byte | 5.5 ratio (0..255) | CWTU |
| 78 | Buttons 3/4: {{0}} | Lock object | 1 Bit | 1.3 enable | CW |
| 78 | Button 3: Mode selection | Lock object | 1 Bit | 1.3 enable | CW |
| 78 | Button 3: Ventilation control | Lock object | 1 Bit | 1.3 enable | CW |
| 78 | Button 3: Control value = 0% | Lock object | 1 Bit | 1.3 enable | CW |
| 78 | Button 3: Heating/Cooling | Lock object | 1 Bit | 1.3 enable | CW |
| 78 | Button 3: {{0}} | Lock object | 1 Bit | 1.3 enable | CW |
| 79 | Button 4: {{0}} | Switch | 1 Bit | 1.1 switch | CT |
| 79 | Button 4: {{0}} | Toggle | 1 Bit | 1.1 switch | CT |
| 79 | Button 4: {{0}} | Send value | 1 Byte | 5.5 ratio (0..255) | CT |
| 79 | Button 4: {{0}} | Send percent value | 1 Byte | 5.1 percentage (0..100%) | CT |
| 79 | Button 4: {{0}} | Send scene | 1 Byte | 17.1 scene number | CT |
| 79 | Button 4 short: {{0}} | Switch | 1 Bit | 1.1 switch | CT |
| 79 | Button 4 short: {{0}} | Send value | 1 Byte | 5.5 ratio (0..255) | CT |
| 79 | Button 4 short: {{0}} | Send percent value | 1 Byte | 5.1 percentage (0..100%) | CT |
| 79 | Button 4 short: {{0}} | Send scene | 1 Byte | 17.1 scene number | CT |
| 79 | Button 4: {{0}} | Dimming On/Off | 1 Bit | 1.1 switch | CT |
| 79 | Button 4: {{0}} | Blinds Up/Down | 1 Bit | 1.8 up/down | CT |
| 79 | Button 4: {{0}} | Send status | 1 Bit | 1.11 state | CT |
| 79 | Button 4 short: {{0}} | Toggle | 1 Bit | 1.1 switch | CT |
| 80 | Button 4: {{0}} | Status for toggle | 1 Bit | 1.1 switch | CWTU |
| 80 | Button 4: {{0}} | Dimming relative | 4 Bit | 3.7 dimming control | CT |
| 80 | Button 4: {{0}} | Slat adjustment / Stop | 1 Bit | 1.7 step | CT |
| 80 | Button 4 short: {{0}} | Status for toggle | 1 Bit | 1.1 switch | CWTU |
| 80 | Button 4: {{0}} | Status for display | 1 Bit | 1.1 switch | CWTU |
| 80 | Button 4: {{0}} | Status for display | 1 Byte | 5.5 ratio (0..255) | CWTU |
| 80 | Button 4: {{0}} | Status for display | 1 Byte | 5.1 percentage (0..100%) | CWTU |
| 81 | Button 4 long: {{0}} | Switch | 1 Bit | 1.1 switch | CT |
| 81 | Button 4 long: {{0}} | Send value | 1 Byte | 5.5 ratio (0..255) | CT |
| 81 | Button 4 long: {{0}} | Send percent value | 1 Byte | 5.1 percentage (0..100%) | CT |
| 81 | Button 4 long: {{0}} | Send scene | 1 Byte | 17.1 scene number | CT |
| 81 | Button 4: {{0}} | Status for toggle | 1 Bit | 1.1 switch | CWTU |
| 81 | Button 4: {{0}} | Status for change of direction | 1 Bit | 1.8 up/down | CWTU |
| 81 | Button 4 long: {{0}} | Toggle | 1 Bit | 1.1 switch | CT |
| 82 | Button 4 long: {{0}} | Status for toggle | 1 Bit | 1.11 state | CWTU |
| 82 | Button 4: {{0}} | Status for display | 1 Bit | 1.11 state | CWTU |
| 82 | Button 4: {{0}} | Status for display | 1 Byte | 5.1 percentage (0..100%) | CWTU |
| 82 | Button 4: {{0}} | Status for display | 1 Byte | 5.5 ratio (0..255) | CWTU |
| 83 | Button 4: Mode selection | Lock object | 1 Bit | 1.3 enable | CW |
| 83 | Button 4: Ventilation control | Lock object | 1 Bit | 1.3 enable | CW |
| 83 | Button 4: Control value = 0% | Lock object | 1 Bit | 1.3 enable | CW |
| 83 | Button 4: Heating/Cooling | Lock object | 1 Bit | 1.3 enable | CW |
| 83 | Button 4: {{0}} | Lock object | 1 Bit | 1.3 enable | CW |
| 84 | Inputs 1/2: {{0}} | Switch On/Off | 1 Bit | 1.1 switch | CRT |
| 84 | Inputs 1/2: {{0}} | Dimming On/Off | 1 Bit | 1.1 switch | CRT |
| 84 | Inputs 1/2: {{0}} | Blinds Up/Down | 1 Bit | 1.8 up/down | CRT |
| 84 | Input 1: {{0}} | Switch | 1 Bit | 1.1 switch | CRT |
| 84 | Input 1: {{0}} | Toggle | 1 Bit | 1.1 switch | CRT |
| 84 | Input 1: {{0}} | Send value | 1 Byte | 5.5 ratio (0..255) | CRT |
| 84 | Input 1: {{0}} | Send percent value | 1 Byte | 5.1 percentage (0..100%) | CRT |
| 84 | Input 1: {{0}} | Send scene | 1 Byte | 17.1 scene number | CRT |
| 84 | Input 1 short: {{0}} | Switch | 1 Bit | 1.1 switch | CRT |
| 84 | Input 1 short: {{0}} | Send value | 1 Byte | 5.5 ratio (0..255) | CRT |
| 84 | Input 1 short: {{0}} | Send percent value | 1 Byte | 5.1 percentage (0..100%) | CRT |
| 84 | Input 1 short: {{0}} | Send scene | 1 Byte | 17.1 scene number | CRT |
| 84 | Input 1: {{0}} | Dimming On/Off | 1 Bit | 1.1 switch | CRT |
| 84 | Input 1: {{0}} | Blinds Up/Down | 1 Bit | 1.8 up/down | CRT |
| 84 | Input 1: {{0}} | Send status | 1 Bit | 1.11 state | CRT |
| 84 | Input 1 short: {{0}} | Toggle | 1 Bit | 1.1 switch | CRT |
| 85 | Inputs 1/2: {{0}} | Dimming relative | 4 Bit | 3.7 dimming control | CRT |
| 85 | Inputs 1/2: {{0}} | Slat adjustment / Stop | 1 Bit | 1.7 step | CRT |
| 85 | Input 1: {{0}} | Status for toggle | 1 Bit | 1.1 switch | CWTU |
| 85 | Input 1 short: {{0}} | Status for toggle | 1 Bit | 1.1 switch | CWTU |
| 85 | Input 1: {{0}} | Dimming relative | 4 Bit | 3.7 dimming control | CRT |
| 85 | Input 1: {{0}} | Slat adjustment / Stop | 1 Bit | 1.7 step | CRT |
| 86 | Input 1 long: {{0}} | Switch | 1 Bit | 1.1 switch | CRT |
| 86 | Input 1 long: {{0}} | Send value | 1 Byte | 5.5 ratio (0..255) | CRT |
| 86 | Input 1 long: {{0}} | Send percent value | 1 Byte | 5.1 percentage (0..100%) | CRT |
| 86 | Input 1 long: {{0}} | Send scene | 1 Byte | 17.1 scene number | CRT |
| 86 | Input 1: {{0}} | Status for toggle | 1 Bit | 1.1 switch | CWTU |
| 86 | Input 1: {{0}} | Status for change of direction | 1 Bit | 1.8 up/down | CWTU |
| 86 | Input 1 long: {{0}} | Toggle | 1 Bit | 1.1 switch | CRT |
| 87 | Input 1 long: {{0}} | Status for toggle | 1 Bit | 1.11 state | CWTU |
| 88 | Inputs 1/2: {{0}} | Lock object | 1 Bit | 1.3 enable | CW |
| 88 | Input 1 | Lock object | 1 Bit | 1.3 enable | CW |
| 89 | Input 2: {{0}} | Switch | 1 Bit | 1.1 switch | CRT |
| 89 | Input 2: {{0}} | Toggle | 1 Bit | 1.1 switch | CRT |
| 89 | Input 2: {{0}} | Send value | 1 Byte | 5.5 ratio (0..255) | CRT |
| 89 | Input 2: {{0}} | Send percent value | 1 Byte | 5.1 percentage (0..100%) | CRT |
| 89 | Input 2: {{0}} | Send scene | 1 Byte | 17.1 scene number | CRT |
| 89 | Input 2 short: {{0}} | Switch | 1 Bit | 1.1 switch | CRT |
| 89 | Input 2 short: {{0}} | Send value | 1 Byte | 5.5 ratio (0..255) | CRT |
| 89 | Input 2 short: {{0}} | Send percent value | 1 Byte | 5.1 percentage (0..100%) | CRT |
| 89 | Input 2 short: {{0}} | Send scene | 1 Byte | 17.1 scene number | CRT |
| 89 | Input 2: {{0}} | Dimming On/Off | 1 Bit | 1.1 switch | CRT |
| 89 | Input 2: {{0}} | Blinds Up/Down | 1 Bit | 1.8 up/down | CRT |
| 89 | Input 2: {{0}} | Send status | 1 Bit | 1.11 state | CRT |
| 89 | Input 2 short: {{0}} | Toggle | 1 Bit | 1.1 switch | CRT |
| 90 | Input 2: {{0}} | Status for toggle | 1 Bit | 1.1 switch | CWTU |
| 90 | Input 2 short: {{0}} | Status for toggle | 1 Bit | 1.1 switch | CWTU |
| 90 | Input 2: {{0}} | Dimming relative | 4 Bit | 3.7 dimming control | CRT |
| 90 | Input 2: {{0}} | Slat adjustment / Stop | 1 Bit | 1.7 step | CRT |
| 91 | Input 2 long: {{0}} | Switch | 1 Bit | 1.1 switch | CRT |
| 91 | Input 2 long: {{0}} | Send value | 1 Byte | 5.5 ratio (0..255) | CRT |
| 91 | Input 2 long: {{0}} | Send percent value | 1 Byte | 5.1 percentage (0..100%) | CRT |
| 91 | Input 2 long: {{0}} | Send scene | 1 Byte | 17.1 scene number | CRT |
| 91 | Input 2: {{0}} | Status for toggle | 1 Bit | 1.1 switch | CWTU |
| 91 | Input 2: {{0}} | Status for change of direction | 1 Bit | 1.8 up/down | CWTU |
| 91 | Input 2 long: {{0}} | Toggle | 1 Bit | 1.1 switch | CRT |
| 92 | Input 2 long: {{0}} | Status for toggle | 1 Bit | 1.11 state | CWTU |
| 93 | Input 2: {{0}} | Lock object | 1 Bit | 1.3 enable | CW |
| 94 | Inputs 3/4: {{0}} | Switch On/Off | 1 Bit | 1.1 switch | CRT |
| 94 | Inputs 3/4: {{0}} | Dimming On/Off | 1 Bit | 1.1 switch | CRT |
| 94 | Inputs 3/4: {{0}} | Blinds Up/Down | 1 Bit | 1.8 up/down | CRT |
| 94 | Input 3: {{0}} | Switch | 1 Bit | 1.1 switch | CRT |
| 94 | Input 3: {{0}} | Toggle | 1 Bit | 1.1 switch | CRT |
| 94 | Input 3: {{0}} | Send value | 1 Byte | 5.5 ratio (0..255) | CRT |
| 94 | Input 3: {{0}} | Send percent value | 1 Byte | 5.1 percentage (0..100%) | CRT |
| 94 | Input 3: {{0}} | Send scene | 1 Byte | 17.1 scene number | CRT |
| 94 | Input 3 short: {{0}} | Switch | 1 Bit | 1.1 switch | CRT |
| 94 | Input 3 short: {{0}} | Send value | 1 Byte | 5.5 ratio (0..255) | CRT |
| 94 | Input 3 short: {{0}} | Send percent value | 1 Byte | 5.1 percentage (0..100%) | CRT |
| 94 | Input 3 short: {{0}} | Send scene | 1 Byte | 17.1 scene number | CRT |
| 94 | Input 3: {{0}} | Dimming On/Off | 1 Bit | 1.1 switch | CRT |
| 94 | Input 3: {{0}} | Blinds Up/Down | 1 Bit | 1.8 up/down | CRT |
| 94 | Input 3: {{0}} | Send status | 1 Bit | 1.11 state | CRT |
| 94 | Input 3 short: {{0}} | Toggle | 1 Bit | 1.1 switch | CRT |
| 95 | Inputs 3/4: {{0}} | Dimming relative | 4 Bit | 3.7 dimming control | CRT |
| 95 | Inputs 3/4: {{0}} | Slat adjustment / Stop | 1 Bit | 1.7 step | CRT |
| 95 | Input 3: {{0}} | Status for toggle | 1 Bit | 1.1 switch | CWTU |
| 95 | Input 3 short: {{0}} | Status for toggle | 1 Bit | 1.1 switch | CWTU |
| 95 | Input 3: {{0}} | Dimming relative | 4 Bit | 3.7 dimming control | CRT |
| 95 | Input 3: {{0}} | Slat adjustment / Stop | 1 Bit | 1.7 step | CRT |
| 96 | Input 3 long: {{0}} | Switch | 1 Bit | 1.1 switch | CRT |
| 96 | Input 3 long: {{0}} | Send value | 1 Byte | 5.5 ratio (0..255) | CRT |
| 96 | Input 3 long: {{0}} | Send percent value | 1 Byte | 5.1 percentage (0..100%) | CRT |
| 96 | Input 3 long: {{0}} | Send scene | 1 Byte | 17.1 scene number | CRT |
| 96 | Input 3: {{0}} | Status for toggle | 1 Bit | 1.1 switch | CWTU |
| 96 | Input 3: {{0}} | Status for change of direction | 1 Bit | 1.8 up/down | CWTU |
| 96 | Input 3 long: {{0}} | Toggle | 1 Bit | 1.1 switch | CRT |
| 97 | Input 3 long: {{0}} | Status for toggle | 1 Bit | 1.11 state | CWTU |
| 98 | Inputs 3/4: {{0}} | Lock object | 1 Bit | 1.3 enable | CW |
| 98 | Input 3 | Lock object | 1 Bit | 1.3 enable | CW |
| 99 | Input 4: {{0}} | Switch | 1 Bit | 1.1 switch | CRT |
| 99 | Input 4: {{0}} | Toggle | 1 Bit | 1.1 switch | CRT |
| 99 | Input 4: {{0}} | Send value | 1 Byte | 5.5 ratio (0..255) | CRT |
| 99 | Input 4: {{0}} | Send percent value | 1 Byte | 5.1 percentage (0..100%) | CRT |
| 99 | Input 4: {{0}} | Send scene | 1 Byte | 17.1 scene number | CRT |
| 99 | Input 4 short: {{0}} | Switch | 1 Bit | 1.1 switch | CRT |
| 99 | Input 4 short: {{0}} | Send value | 1 Byte | 5.5 ratio (0..255) | CRT |
| 99 | Input 4 short: {{0}} | Send percent value | 1 Byte | 5.1 percentage (0..100%) | CRT |
| 99 | Input 4 short: {{0}} | Send scene | 1 Byte | 17.1 scene number | CRT |
| 99 | Input 4: {{0}} | Dimming On/Off | 1 Bit | 1.1 switch | CRT |
| 99 | Input 4: {{0}} | Blinds Up/Down | 1 Bit | 1.8 up/down | CRT |
| 99 | Input 4: {{0}} | Send status | 1 Bit | 1.11 state | CRT |
| 99 | Input 4 short: {{0}} | Toggle | 1 Bit | 1.1 switch | CRT |
| 100 | Input 4: {{0}} | Status for toggle | 1 Bit | 1.1 switch | CWTU |
| 100 | Input 4 short: {{0}} | Status for toggle | 1 Bit | 1.1 switch | CWTU |
| 100 | Input 4: {{0}} | Dimming relative | 4 Bit | 3.7 dimming control | CRT |
| 100 | Input 4: {{0}} | Slat adjustment / Stop | 1 Bit | 1.7 step | CRT |
| 101 | Input 4 long: {{0}} | Switch | 1 Bit | 1.1 switch | CRT |
| 101 | Input 4 long: {{0}} | Send value | 1 Byte | 5.5 ratio (0..255) | CRT |
| 101 | Input 4 long: {{0}} | Send percent value | 1 Byte | 5.1 percentage (0..100%) | CRT |
| 101 | Input 4 long: {{0}} | Send scene | 1 Byte | 17.1 scene number | CRT |
| 101 | Input 4: {{0}} | Status for toggle | 1 Bit | 1.1 switch | CWTU |
| 101 | Input 4: {{0}} | Status for change of direction | 1 Bit | 1.8 up/down | CWTU |
| 101 | Input 4 long: {{0}} | Toggle | 1 Bit | 1.1 switch | CRT |
| 102 | Input 4 long: {{0}} | Status for toggle | 1 Bit | 1.11 state | CWTU |
| 103 | Input 4: {{0}} | Lock object | 1 Bit | 1.3 enable | CW |
| 104 | Buttons 1/2: Setpoint shift | Lock object | 1 Bit | 1.3 enable | CW |
| 105 | Operating | Output | 1 Bit | 1.11 state | CRT |
| 106 | Day / Night | Day = 1 / Night = 0 | 1 Bit | 1.24 day/night | CWTU |
| 106 | Day / Night | Night = 1 / Day = 0 | 1 Bit | 1.24 day/night | CWTU |
| 107 | Presence | Input | 1 Bit | 1.1 switch | CWTU |
| 108 | Button operation | Output | 1 Bit | 1.11 state | CRT |
| 109 | Display | Brightness | 1 Byte | 5.1 percentage (0..100%) | CW |
| 109 | Display | Brightness | 2 Bytes | 9.4 lux (Lux) | CW |
| 110 | Time | Receive current value | 3 Bytes | 10.1 time of day | CWTU |
| 111 | Date | Receive current value | 3 Bytes | 11.1 date | CWTU |
| 112 | Time / Date | Receive current value | 8 Bytes | 19.1 date time | CWTU |
| 113 | Dummy | 1 Bit | |||
| 114 | Dummy | 1 Bit | |||
| 115 | Dummy | 1 Bit | |||
| 116 | Dummy | 1 Bit | |||
| 117 | Dummy | 1 Bit | |||
| 118 | Dummy | 1 Bit | |||
| 119 | Dummy | 1 Bit | |||
| 120 | Dummy | 1 Bit | |||
| 121 | Dummy | 1 Bit |
Parameters (294)
| Parameter | Type | Default |
|---|---|---|
| Send "Operation" cyclically | list | not active |
| Startup time | unsignedInt 2…240 | 2 |
| Reaction time on keypress | list | fast |
| Time for long keypress | list | 0,4 s |
| Menu language | list | German |
| Value for Day/Night | list | Day = 1 / Night = 0 |
| Object Day/Night | list | request |
| Status for toggle | list | request |
| Objects Time/Date | list | request |
| Background color | list | Day = white; Night = black |
| Behavior on object "Presence" | list | display is switched on and off |
| Brightness at Day | list | 100% |
| Brightness at Night | list | 10% |
| User-defined colors | list | not active |
| Red part | list | 0% |
| Green part | list | 0% |
| Blue part | list | 0% |
| Expiry time | unsignedInt 5…240 | 20 |
| Change time of display | unsignedInt 1…60 | 5 |
| Temperature setpoint display | list | top row |
| Status value 1 (left) | list | actual temperature |
| Status value 2 (right) | list | air humidity |
| Send measured value on change of | float 0.1…2 | 0.1 |
| Send measured value on change | list | not active |
| Send measured value cyclically | list | 5 min |
| Sensor internal/external | list | 100 % internal |
| Min/Max values | list | not active |
| Calibration value for internal sensor | float -5…5 | 0 |
| Messages | list | not active |
| Upper message value | float 20…45 | 28 |
| Lower message value | float 3…30 | 18 |
| Send measured value on change of | float 1…10 | 1 |
| Calibration value for internal sensor | float -20…20 | 0 |
| Upper message value | float 25…100 | 70 |
| Lower message value | float 0…75 | 30 |
| Dew point temperature | list | not active |
| Object Comfort | list | not active |
| min. temperature | unsignedInt 10…45 | 18 |
| max. temperature | unsignedInt 10…45 | 26 |
| min. relative air humidity | unsignedInt 0…100 | 30 |
| max. relative air humidity | unsignedInt 0…100 | 70 |
| Labeling | text | |
| Colour of symbol for Comfort | list | foreground color |
| Symbols for setpoint temperature | list | HVAC-Mode |
| Signalize control value | list | not active |
| Symbol for Eco/Night mode | list | Eco symbol |
| Colour of symbol for Standby | list | foreground color |
| Colour of symbol for Eco/Night | list | foreground color |
| Colour of symbol for Frost/Heat protection | list | foreground color |
| Colour of symbol for set value = 0% (Heating) | list | foreground color |
| Colour of symbol for set value > 0% (Heating) | list | foreground color |
| Colour of symbol for set value = 0% (Cooling) | list | foreground color |
| Colour of symbol for set value > 0% (Cooling) | list | foreground color |
| Colour of symbol for Heating | list | foreground color |
| Colour of symbol for Cooling | list | foreground color |
| Controller type | list | Heating |
| Priority | list | Frost(Heat) protection/Comfort/Night/Standby |
| Standby reduction | list | 2,0 K |
| Night reduction | list | 3,0 K |
| Step width | list | 0,5 K |
| Setpoint shift applies to | list | Comfort |
| Delete setpoint shift after change of operating mode | list | not active |
| Send setpoint changes | list | active |
| Flow temperature | list | not active |
| Limit flow temperature to | unsignedInt 10…60 | 40 |
| Operating mode after reset | list | Comfort with configured setpoint |
| Lock object for control value Heating | list | not active |
| Object for Heating request | list | not active |
| Lock object for control value Cooling | list | not active |
| Object for Cooling request | list | not active |
| Operating mode | list | PI control continuous |
| Direction of controller | list | normal |
| Maximum value of control value | list | 100% |
| Heating system | list | Underfloor Heating (4K / 150min) |
| Proportional range | list | 4 K |
| Reset time | list | 150 min |
| Send control value cyclically | list | 5 min |
| PWM cycle | list | 10 min |
| Switching hysteresis | list | 2,0 K |
| Cooling system | list | Cooling ceiling (4K / 150min) |
| System | list | 2 pipe / 1 circuit (Heating or Cooling) |
| Toggle Heating/Cooling | list | automatically |
| Ventilation control | list | not active |
| Send outputs cyclically every | list | not active |
| Pause between individual levels [x100ms] | unsignedInt 0…255 | 0 |
| Type of thresholds | list | control value |
| Total number of steps | list | 4 |
| Minimum level for Day | list | Level 0 |
| Maximum level for Day | list | Level 2 |
| Minimum level for Night | list | Level 0 |
| Maximum level for Night | list | Level 2 |
| Threshold level 1 | list | 10% |
| Threshold level 2 | list | 30% |
| Maximum level for Day | list | Level 3 |
| Maximum level for Night | list | Level 3 |
| Threshold level 3 | list | 50% |
| Maximum level for Day | list | Level 4 |
| Maximum level for Night | list | Level 4 |
| Threshold level 4 | list | 70% |
| Hysteresis | list | 5% |
| Behavior at lock | list | not active |
| Behavior when unlocking | list | not active |
| Level when unlocking | list | Level 0 |
| Level at lock | list | Level 0 |
| Threshold level 1 | list | 2,0 K |
| Threshold level 2 | list | 4,0 K |
| Threshold level 3 | list | 6,0 K |
| Threshold level 4 | list | 8,0 K |
| Hysteresis | list | 0,5 K |
| Behavior at init | list | Automatic mode |
| Sticking protection (Trigger highest level after 24 hours at level 0) | list | not active |
| Priority | list | not active |
| Switch priority with | list | Level 0 |
| Output value for stage 1 at day | list | 10% |
| Output value for stage 1 at night | list | 10% |
| Output value for stage 2 at day | list | 30% |
| Output value for stage 2 at night | list | 30% |
| Output value for stage 3 at day | list | 50% |
| Output value for stage 3 at night | list | 50% |
| Output value for stage 4 at day | list | 70% |
| Output value for stage 4 at night | list | 70% |
| Function buttons 1/2 (top left/right) | list | temperature shift |
| Step width of setpoint shift | float 0.1…1 | 0.5 |
| Lower limit | float -10…10 | -3 |
| Upper limit | float -10…10 | 3 |
| Repeated sending with pressed button | list | 1 s |
| Repetition time | list | 1 s |
| Function button 3 (bottom left) | list | mode selection (internal connection) |
| Mode selection | list | Comfort / Standby / Night /Frost (Heat) protection |
| 1Byte value [0…255] | unsignedInt 0…255 | 0 |
| No switchover when other operating mode | unsignedInt 0…1 | 0 |
| Display | list | symbol by status |
| Text | text | |
| Text for "Comfort" | text | |
| Text for "Standby" | text | |
| Colour of symbol for Comfort mode | list | foreground color |
| Colour of symbol for Standby mode | list | sun orange |
| Colour of symbol for Eco mode | list | sun orange |
| Colour of symbol for Frost/Heating protection mode | list | sun orange |
| Colour of symbol "Off" | list | foreground color |
| Symbol "Off" | list | |
| Colour of symbol "On" | list | sun orange |
| Symbol "On" | list | |
| Colour of symbol | list | foreground color |
| Symbol | list | |
| Function button 4 (bottom right) | list | Heating/Cooling (internal connection) |
| Setpoints for Standby/Night | list | depending on setpoint comfort (basic) |
| Setpoint Comfort (Basic) | float 7…35 | 21 |
| Setpoint Comfort (Basic) | float 7…35 | 23 |
| Setpoint Standby | float 7…35 | 19 |
| Setpoint Night | float 7…35 | 18 |
| Setpoint Frost protection | float 3…12 | 7 |
| Setpoint shift over 1Bit/1Byte object | list | 1Bit |
| Status setpoint shift | list | not active |
| Action when shift in Night/Standby | list | no action |
| Delete setpoint shift after new absolute setpoint | list | active |
| Delete setpoint shift after new basic setpoint | list | active |
| Reset basic setpoint to configured value after change of operation mode | list | active |
| Reset setpoints to parameterization after operating mode change | list | active |
| Send current setpoint cyclically | list | not active |
| Comfort extention with time | list | not active |
| Comfort extention time | list | not active |
| HVAC Status object | list | HVAC Mode (DPT 20.102) |
| Additional HVAC Status object | list | not active |
| Send HVAC Status object cyclically | list | not active |
| Window contact | list | not active |
| State of window | list | 0=closed / 1=open (standard DPT) |
| Delay time | unsignedInt 0…240 | 5 |
| Action when opening the window | list | force Frost/Heat protection |
| Action when closing the window | list | HVAC Mode before locking |
| Release time | list | 12 h |
| Separate objects for setpoints Comfort/Standby/Night/Frost protection/Heating protection | list | not active |
| Separate objects for setpoints Comfort/Standby/Night/Frost protection | list | not active |
| Maximum setpoint shift | float 0…10 | 3 |
| Setpoint Standby | float 7…35 | 24 |
| Setpoint Night | float 7…35 | 25 |
| Standby increase | list | 2,0 K |
| Night increase | list | 3,0 K |
| Setpoint Heating protection | float 24…40 | 35 |
| Separate objects for setpoints of Comfort/Standby/Night Heating protection | list | not active |
| Reference control via outside temperature | list | not active |
| Reference variable minimum | unsignedInt 10…60 | 28 |
| Reference variable maximum | unsignedInt 10…60 | 38 |
| Setpoint change at maximum reference variable | float 1…10 | 10 |
| Limit temperature of cooling medium over dew point monitoring | list | not active |
| Offset to dew point temperature | list | 0 K |
| Additional level | list | not active |
| Direction of action with rising temperature | list | normal |
| Control value | list | 2-step control (switching) |
| Distance | list | 2,0 K |
| Dead zone between Heating and Cooling | list | 2,0 K |
| Dead zone between Heating and Cooling | list | 0 K |
| Alarms | list | not active |
| Frost alarm if value less | unsignedInt 3…10 | 7 |
| Heat alarm if value greater | unsignedInt 25…40 | 35 |
| Function buttons 3/4 (bottom left/right) | list | not active |
| Object description | text | |
| Basic function | list | switch |
| Button assignment 3/4 | list | OFF / ON |
| Button assignment 3/4 | list | darker / brighter |
| Button assignment 3/4 | list | UP / DOWN |
| Operating function | list | long=move / short=stop/slats open/close |
| Subfunction | list | switch when button is pressed |
| Value for pressed button | list | ON |
| Value | list | 1Byte value |
| Percent value | list | 100% |
| Scene number | list | 1 |
| Value for short button - Object 1 | list | on |
| Send value | list | 1Byte value |
| Percent value | list | 0% |
| Value for long button - Object 2 | list | nothing |
| Value for released button | list | OFF |
| Cyclical sending | list | not active |
| Send cyclically every | unsignedInt 1…3000 | 1 |
| Send status after bus power return | list | active |
| Text for "Off" | text | |
| Text for "On" | text | |
| Text for "Eco/Night" | text | |
| Text for "Frost alarm" | text | |
| Symbol for operation mode Eco/Night | list | Eco symbol |
| Symbol for 0% | list | |
| Colour of symbol for 0% | list | foreground color |
| Symbol for 0% - 90% | list | |
| Colour of symbol for 0% - 90% | list | sun orange |
| Symbol for > 90% | list | |
| Colour of symbol for > 90% | list | sun orange |
| Symbol for 0 | list | |
| Colour of symbol for 0 | list | foreground color |
| Symbol for 1 - 230 | list | |
| Colour of symbol for 1 - 230 | list | sun orange |
| Symbol for >230 | list | |
| Colour of symbol for >230 | list | sun orange |
| Symbol for scenes | list | |
| Colour of symbol for scenes | list | foreground color |
| Lock object | list | not active |
| Function inputs 1/2 | list | not active |
| Inputs assignment 1/2 | list | OFF / ON |
| Inputs assignment 1/2 | list | darker / brighter |
| Inputs assignment 1/2 | list | UP / DOWN |
| Value for closed contact | list | ON |
| Value for open contact | list | ON |
| Send cyclically every | unsignedInt 1…3000 | 300 |
| Value for opend contact | list | ON |
| Function inputs 3/4 | list | not active |
| Inputs assignment 3/4 | list | OFF / ON |
| Inputs assignment 3/4 | list | darker / brighter |
| Inputs assignment 3/4 | list | UP / DOWN |
| Control of display brightness over object | list | not active, Day/Night |
| Brightness on start | list | 100% |
| Ambient brightness for 100% | list | 1000 Lux (medium) |
| Minimum brightness Day | list | 100% |
| Minimum brightness Night | list | 10% |
| Switch off display | list | only Night |
| Ambient brightness for switch off | unsignedInt 1…200 | 50 |
| (Basic) Comfort setpoint | float 7…35 | 21 |
| Switch off display after time | list | not active |
| Operating mode after reprogramming | list | Comfort (Cooling) |
| Operating mode after reprogramming | list | Comfort |
| Ambient brightness for restart | unsignedInt 1…200 | 100 |
| Text for Enable / Active | text | |
| Text for Disable / Inactive (0%) | text | |
| Symbol for Enable / Active | list | |
| Colour of symbol for Enable / Active | list | foreground color |
| Symbol for Disable / Inactive (0%) | list | |
| Colour of symbol for Disable / Inactive (0%) | list | sun orange |
| Symbol for level 0 | list | |
| Colour of symbol for level 0 | list | foreground color |
| Symbol for level >0 | list | |
| Colour of symbol for level >0 | list | sun orange |
| Symbol for Automatic | list | |
| Colour of Symbol for Automatic | list | sun orange |
| Symbol for 10% - 90% | list | |
| Colour of symbol for 10% - 90% | list | sun orange |
| Symbol for Cooling | list | |
| Symbol for Heating | list | |
| Colour of symbol for Heating | list | sun orange |
| Release time from manual control to automatic mode | list | not active |
| Control as extension unit | list | not active |
| Enable Automatic | list | not active |
| Button labeling left | list | text entry |
| Button labeling right | list | text entry |
| Use device as | list | Controller |
| Extention unit for | list | Heating |
| Temperature shift | list | 1Bit |
| Switchover considers status object | list | active |
| Lower limit | float 0…45 | 19 |
| Upper limit | float 0…45 | 23 |
| Colour of symbol for Night mode | list | sun orange |
| Send value cyclically | list | not active |
| Dew point alarm | list | not active |
| Alarm when difference smaller or equal | float -10…10 | 2 |
| Signal control value | list | not active |
| Switch off display | list | only Day |
| Label_Auto | text |
Version history
| Application | App no | Fingerprint | First seen | Size | File |
|---|---|---|---|---|---|
| Room temperature controller Smart 55/63 1.4 latest | $005C | B9A9 | 2026-11-25 | 278 KB | Download |
About this file
This is the official ETS product database for the MDT technologies GmbH SCN-RTR60S.01 Room Temperature Controller Smart 60 CH (SCN-RTR60S.01), published by the manufacturer in the KNX online catalog. To use it, open ETS, go to Catalogs → Import and choose the downloaded .knxprod file. The device then appears in your catalog and can be added to a project. Older versions are kept so existing projects can be matched to the application program they were commissioned with.
More from MDT technologies GmbH
- SCN-LSD01.01 Brightness Sensor/Controller SCN-LSD01.01
- SCN-MGSUP.01 Air quality/CO2 sensor SCN-MGSUP.01
- Glass Room temperature controller SCN-RT1Gx.01
- Room Temperature Controller 1-fold UP SCN-RT1UP.01
- Room Temp. Contr. 1-fold with adjustment knob UP SCN-RT1UPE.01
- Temperature controller / sensor 2-fold UP SCN-RT2UP.01
- Temperature controller / sensor 4-fold UP SCN-RT4UP.01
- Controller / Sensor 6-fold AP SCN-RT6AP.01
- Temperature Controller 6-fold, 2SU MDRC SCN-RT6REG.01
- SCN-RT8REG.02 Temperature Controller 8-fold MDRC SCN-RT8REG.02
- SCN-RTN55S.01 Room Temperature Extension Unit Smart 55 SCN-RTN55S.01
- SCN-RTN60S.01 Room Temperature Extension Unit Smart 60 CH SCN-RTN60S.01