SCN-MGSUP.01 Air quality/CO2 sensor SCN-MGSUP.01
MDT technologies GmbH · Order number SCN-MGSUP.01 · Temperature Controller › Air quality/CO2 sensor
Air quality/CO2 control
Download .knxprod Temperature controller and air quality controller 1.0 · 101 KB
Product
| Manufacturer | MDT technologies GmbH |
|---|---|
| Product name | SCN-MGSUP.01 Air quality/CO2 sensor |
| Order number | SCN-MGSUP.01 |
| Hardware | Mischgassensor/CO2 |
| Medium | Twisted Pair |
| Bus current (mA) | 10 |
| Rail mounted | No |
| Registration | Certified · 2014-04-24 |
| Languages | de-DE, en-US |
| Catalog entry | M-0083_H-71-1_HP-0046-10-0126_CI-SCN.2DMGSUP.2E01-1 |
| Fingerprint | 0126 |
| SHA-256 | c125feb2ed66f9040979c20546394cce60d4d202de5fa3d3d455a18147352c31 |
| First seen | 2026-11-25 |
| Markets | 69 markets |
Application program: Temperature controller and air quality controller 1.0
| Application number | $0046 |
|---|---|
| Version | 1.0 |
| Mask version | MV-0701 (7.1) |
| KNX Data Secure | No |
| Minimum ETS version | 3.0d |
| Parameters | 166 |
| Group objects | 70 |
Group objects (70)
| No | Name | Function | Size | DPT | Flags |
|---|---|---|---|---|---|
| 0 | Temperature controller | Actual temperature value | 2 Bytes | 9.1 temperature (°C) | CRT |
| 1 | Temperature controller | Exceeded max. value | 1 Bit | CRT | |
| 2 | Temperature controller | Undershot min. value | 1 Bit | CRT | |
| 3 | Temperature controller | Send frost alarm | 1 Bit | CRT | |
| 4 | Temperature controller | Send heat alarm | 1 Bit | CRT | |
| 5 | Temperature controller | External sensor | 2 Bytes | 9.1 temperature (°C) | CW |
| 6 | Temperature controller | Specify setpoint comfort | 2 Bytes | 9.1 temperature (°C) | CRWT |
| 7 | Temperature controller | Manual set point value offset | 2 Bytes | 9.2 temperature difference (K) | CW |
| 8 | Temperature controller | Control value heating | 1 Byte | 5.1 percentage (0..100%) | CRT |
| 8 | Temperature controller | Control value heating | 1 Bit | CRT | |
| 8 | Control value heating/cooling | Send control value | 1 Byte | 5.1 percentage (0..100%) | CRT |
| 8 | Control value heating/cooling | Send control value | 1 Bit | CRT | |
| 9 | Temperature controller | Control value add. heating | 1 Bit | CRT | |
| 10 | Temperature controller | Request 0=Cooling 1=Heating | 1 Bit | CRT | |
| 10 | Temperature controller | Control value cooling | 1 Byte | 5.1 percentage (0..100%) | CRT |
| 10 | Temperature controller | Control value cooling | 1 Bit | CRT | |
| 11 | Temperature controller | Mode comfort | 1 Bit | 1.1 switch | CW |
| 12 | Temperature controller | Mode night | 1 Bit | 1.1 switch | CW |
| 13 | Temperature controller | Mode frost/heat protection | 1 Bit | 1.1 switch | CW |
| 14 | Temperature controller | Heating disable object | 1 Bit | 1.3 enable | CW |
| 15 | Temperature controller | Cooling disable object | 1 Bit | 1.3 enable | CW |
| 16 | Temperature controller | Heating request | 1 Bit | 1.1 switch | CRT |
| 17 | Temperature controller | Cooling request | 1 Bit | 1.1 switch | CRT |
| 18 | Temperature controller | Switch Heating=1 / Cooling=0 | 1 Bit | CW | |
| 19 | Temperature controller | Guiding value | 2 Bytes | 9.1 temperature (°C) | CW |
| 20 | Temperature controller | Max memory value | 2 Bytes | 9.1 temperature (°C) | CRT |
| 21 | Temperature controller | Min memory value | 2 Bytes | 9.1 temperature (°C) | CRT |
| 22 | Temperature controller | Min/Max Werte Reset | 1 Bit | 1.3 enable | CW |
| 23 | Temperature controller | Reset setpoints | 1 Bit | 1.3 enable | CW |
| 24 | Temperature controller | DPT_HVAC Status | 1 Byte | CRT | |
| 25 | Temperature controller | Error external sensor | 1 Bit | CRT | |
| 26 | Temperature controller | Actual setpoint | 2 Bytes | 9.1 temperature (°C) | CRT |
| 27 | Temperature controller | RHCC Status | 2 Bytes | CRT | |
| 28 | Temperature controller | mode selection | 1 Byte | CW | |
| 28 | Temperature controller | mode selection | 1 Byte | CRWT | |
| 29 | Temperature controller | Manual set point value offset | 1 Bit | CW | |
| 30 | Dummy | 1 Byte | |||
| 31 | Dummy | 1 Byte | |||
| 32 | Dummy | 1 Byte | |||
| 33 | Dummy | 1 Byte | |||
| 34 | Air quality controller | Transmit temp. value | 2 Bytes | CRT | |
| 35 | Air quality controller | Receive external measure value | 2 Bytes | CW | |
| 36 | Air quality controller | Exceeded max. value | 1 Bit | 1.1 switch | CRT |
| 37 | Air quality controller | Undershot min. value | 1 Bit | 1.1 switch | CRT |
| 38 | Air quality controller | Set setpoint | 2 Bytes | CW | |
| 39 | Air quality controller | Actual setpoint | 2 Bytes | CRT | |
| 40 | Air quality controller | Block controller | 1 Bit | 1.3 enable | CW |
| 41 | Air quality controller | Output Control value | 1 Byte | 5.1 percentage (0..100%) | CRT |
| 42 | Air quality controller | Output Level 1 | 1 Bit | 1.1 switch | CT |
| 42 | Air quality controller | Output level Bit 0 | 1 Bit | 1.2 boolean | CT |
| 43 | Air quality controller | Output Level 2 | 1 Bit | 1.1 switch | CT |
| 43 | Air quality controller | Output level Bit 1 | 1 Bit | 1.2 boolean | CT |
| 44 | Air quality controller | Output Level 3 | 1 Bit | 1.1 switch | CT |
| 44 | Air quality controller | Output level Bit 2 | 1 Bit | 1.2 boolean | CT |
| 45 | Air quality controller | Output Level 4 | 1 Bit | 1.1 switch | CT |
| 46 | Dummy | 1 Bit | |||
| 47 | Dummy | 1 Bit | |||
| 48 | Dummy | 1 Bit | |||
| 49 | Air quality controller | Switching Day/Night | 1 Bit | 1.2 boolean | CW |
| 50 | Air quality controller | Green light | 1 Bit | 1.1 switch | CRT |
| 51 | Air quality controller | Yellow light | 1 Bit | 1.1 switch | CRT |
| 52 | Air quality controller | Orange light | 1 Bit | 1.1 switch | CRT |
| 53 | Air quality controller | Red light | 1 Bit | 1.1 switch | CRT |
| 54 | Air quality controller | Internal sensor fault | 1 Bit | 1.1 switch | CT |
| 55 | Air quality controller | external sensor fault | 1 Bit | 1.1 switch | CT |
| 56 | Dummy | 1 Bit | |||
| 57 | Dummy | 1 Bit | |||
| 58 | Dummy | 1 Bit | |||
| 59 | Dummy | 1 Bit | |||
| 60 | Dummy | 1 Bit |
Parameters (95)
| Parameter | Type | Default |
|---|---|---|
| Startup delaytime | list | 0 s |
| Select hardware | list | SCN-RT1xP.xx without manual control |
| Temperature controller | list | Inactive |
| Send actual value after change of | list | Disable |
| Send actual temperature cyclically | list | Disable |
| Send min/max value | list | Disable |
| Internal sensor correction value (value * 0.1K) | signedInt -50…50 | 0 |
| Internal/external sensor | list | 100 % intern |
| Alarm | list | Inactive |
| Frostalarm if value < | list | 7 °C |
| Heatalarm if value > | list | 35 °C |
| Messages | list | Inactive |
| Message if value > | list | 26 °C |
| Message if value < | list | 13 °C |
| Controller type | list | Controller off |
| Priority | list | Frost(Heat protection)/Comfort/Night/Standby |
| Basic comfort setpoint (°C) | list | 21,0 °C |
| Standby reduction (K) | list | 2,0 K |
| Night reduction (K) | list | 3,0 K |
| Setpoint frost protection (°C) | list | 7 °C |
| Max setpoint offset | list | 3,0 K |
| Set point value offset via | list | 2 Byte Object |
| Diese Einstellung gilt nur für die Hardware ab Version 3.2 | text | <- TIP |
| Step range | list | 0,5 K |
| Max setpoint offset vaild for | list | Comfort |
| Reset setpoint offset after change of mode | list | No |
| Send setpoint change | list | No |
| Operating mode after reset | list | Comfort with parameterized set point |
| Send status with object 28 "mode selection" | list | No |
| Heating disable object | list | Inactive |
| Heating request object enabled | list | No |
| Guiding | list | Inactive |
| Guiding value minimum (°C) | signedInt -100…100 | 28 |
| Guiding value maximum (°C) | signedInt -100…100 | 38 |
| Setpoint variation at maximum guiding value (°C) | signedInt -100…100 | 10 |
| Standby increase (K) | list | 3,0 K |
| Night increase (K) | list | 2,0 K |
| Setpoint heat protection (°C) | list | 35 °C |
| Cooling disable object | list | Inactive |
| Cooling request object enabled | list | No |
| Dead zone between heating and cooling (K) | list | 2,0 K |
| Setpoint | list | PI control continuous |
| Direction of controller | list | normal |
| Max value of control value | list | 100% |
| Heating system | list | Adjustment via control parameter |
| Heating system | list | Underfloor heating (4 K / 150 min) |
| Proportional range (K) | list | 4 K |
| Reset time (min) | list | 120 min |
| Send control value cyclic | list | Disable |
| PWM cycletime (min) | list | 10 min |
| Hysteresis (K) | list | 2,0 K |
| Use additional level | list | No |
| Setpoint | list | 2-step control (switching) |
| Distance (K) | list | 2,0 K |
| Cooling system | list | Adjustment via control parameter |
| Cooling system | list | Cooling ceiling (4 K / 150 min.) |
| Reset time (min) | list | 60 min |
| System | list | 2 Pipe system |
| Heating/cooling switch over | list | automatically |
| Send setpoint for heating and cooling cyclic | list | Disable |
| Activate air quality controller as | list | Inactive |
| Message if CO2-Value < | list | 700 ppm |
| Message if CO2-Value > | list | 1500 ppm |
| Day/Night switching | list | Value 0 = Day / Value 1 = Night |
| Minimum level at day | list | Level 1 |
| Maximum level at day | list | Level 4 |
| Minimum level at night | list | Level 1 |
| Maximum level at night | list | Level 2 |
| Air threshold 1 | list | 600 ppm |
| Air threshold 2 | list | 800 ppm |
| Air threshold 3 | list | 1000 ppm |
| Air threshold 4 | list | 1200 ppm |
| Hysteresis | list | 10% |
| Send output cyclic | list | Disable |
| Behavior by blocking | list | not used |
| Level by blocking | list | Level 1 |
| Level for initrun and emergency mode | list | Level 1 |
| Byte Objekt | list | Level controller |
| Light function | list | Inactive |
| Threshold Light level 1 (below = green, above = yellow) | list | 700 ppm |
| Threshold Light level 2 (below = yellow, above = orange) | list | 1200 ppm |
| Threshold Light level 3 (below = orange, above = red) | list | 2000 ppm |
| Set point applies | list | for day |
| Set point at day | list | 600 ppm |
| Minimum value at day | list | 10% |
| Maximum value at day | list | 100% |
| Set point at night | list | 700 ppm |
| Minimum value at night | list | 10% |
| Maximum value at night | list | 30% |
| Proportional value | list | 1000 |
| Reset time | list | 15 min |
| Value by blocking | list | 0% |
| Value for initrun and emergency mode | list | 20% |
| Output value at day | list | 0% |
| Output value at night | list | 0% |
Version history
| Application | App no | Fingerprint | First seen | Size | File |
|---|---|---|---|---|---|
| Temperature controller and air quality controller 1.0 latest | $0046 | 0126 | 2026-11-25 | 101 KB | Download |
About this file
This is the official ETS product database for the MDT technologies GmbH SCN-MGSUP.01 Air quality/CO2 sensor (SCN-MGSUP.01), published by the manufacturer in the KNX online catalog. To use it, open ETS, go to Catalogs → Import and choose the downloaded .knxprod file. The device then appears in your catalog and can be added to a project. Older versions are kept so existing projects can be matched to the application program they were commissioned with.
More from MDT technologies GmbH
- SCN-LSD01.01 Brightness Sensor/Controller SCN-LSD01.01
- Glass Room temperature controller SCN-RT1Gx.01
- Room Temperature Controller 1-fold UP SCN-RT1UP.01
- Room Temp. Contr. 1-fold with adjustment knob UP SCN-RT1UPE.01
- Temperature controller / sensor 2-fold UP SCN-RT2UP.01
- Temperature controller / sensor 4-fold UP SCN-RT4UP.01
- Controller / Sensor 6-fold AP SCN-RT6AP.01
- Temperature Controller 6-fold, 2SU MDRC SCN-RT6REG.01
- SCN-RT8REG.02 Temperature Controller 8-fold MDRC SCN-RT8REG.02
- SCN-RTN55S.01 Room Temperature Extension Unit Smart 55 SCN-RTN55S.01
- SCN-RTN60S.01 Room Temperature Extension Unit Smart 60 CH SCN-RTN60S.01
- SCN-RTN63S.01 Room Temperature Extension Unit Smart 63 SCN-RTN63S.01