| 0 | | | 2 Bytes | | |
| 1 | Channel 1 | Higher message value | 1 Bit | | CRT |
| 2 | Channel 1 | Below message value | 1 Bit | | CRT |
| 3 | Channel 1 | Frost alarm | 1 Bit | | CRT |
| 4 | Channel 1 | Heat alarm | 1 Bit | | CRT |
| 5 | Channel 1 | External sensor | 2 Bytes | 9.1 temperature (°C) | CW |
| 6 | Channel 1 | Setpoint comfort | 2 Bytes | 9.1 temperature (°C) | CRWT |
| 7 | Channel 1 | Set point value offset | 2 Bytes | 9.2 temperature difference (K) | CW |
| 7 | Channel 1 | Set point value offset | 2 Bytes | 9.2 temperature difference (K) | CWT |
| 8 | Channel 1 | Control value heating | 1 Byte | 5.1 percentage (0..100%) | CRT |
| 8 | Channel 1 | Control value heating | 1 Bit | | CRT |
| 8 | Channel 1 | Control value heating/cooling | 1 Byte | 5.1 percentage (0..100%) | CRT |
| 8 | Channel 1 | Control value heating/cooling | 1 Bit | | CRT |
| 9 | Channel 1 | Control value cooling | 1 Byte | 5.1 percentage (0..100%) | CRT |
| 9 | Channel 1 | Control value cooling | 1 Bit | | CRT |
| 9 | Channel 1 | Status: 0=Cool 1=Heat | 1 Bit | | CRT |
| 10 | Channel 1 | Mode comfort | 1 Bit | 1.1 switch | CW |
| 11 | Channel 1 | Mode night | 1 Bit | 1.1 switch | CW |
| 12 | Channel 1 | Mode frost protection | 1 Bit | 1.1 switch | CW |
| 12 | Channel 1 | Mode heat protection | 1 Bit | 1.1 switch | CW |
| 12 | Channel 1 | Mode frost/heat protection | 1 Bit | 1.1 switch | CW |
| 13 | Channel 1 | Heating disable object | 1 Bit | 1.3 enable | CW |
| 14 | Channel 1 | Cooling disable object | 1 Bit | 1.3 enable | CW |
| 15 | Channel 1 | Heating request | 1 Bit | 1.1 switch | CRT |
| 16 | Channel 1 | Cooling request | 1 Bit | 1.1 switch | CRT |
| 17 | Channel 1 | Heating/cooling switchover | 1 Bit | | CWT |
| 18 | Channel 1 | Max memory value | 2 Bytes | 9.1 temperature (°C) | CRT |
| 19 | Channel 1 | Min memory value | 2 Bytes | 9.1 temperature (°C) | CRT |
| 20 | Channel 1 | Min/max memory reset | 1 Bit | 1.3 enable | CW |
| 21 | Channel 1 | Reset setpoint value | 1 Bit | 1.3 enable | CW |
| 22 | Channel 1 | DPT_HVAC Status | 1 Byte | | CRT |
| 23 | Channel 1 | Error external sensor | 1 Bit | | CRT |
| 24 | Channel 1 | Actual setpoint | 2 Bytes | 9.1 temperature (°C) | CRT |
| 25 | Channel 1 | DPT_RHCC Status | 2 Bytes | | CRT |
| 26 | Channel 1 | Mode selection | 1 Byte | | CW |
| 26 | Channel 1 | Mode selection | 1 Byte | | CRWT |
| 27 | Channel 1 | Set point offset (1=+/0=-) | 1 Bit | | CW |
| 28 | Channel 1 | Flow temperature | 2 Bytes | 9.1 temperature (°C) | CW |
| 29 | | | 1 Byte | | |
| 30 | | | 1 Bit | | C |
| 31 | | | 1 Byte | | |
| 32 | | | 1 Byte | | |
| 33 | | | 2 Bytes | | |
| 34 | Channel 2 | Higher message value | 1 Bit | | CRT |
| 35 | Channel 2 | Below message value | 1 Bit | | CRT |
| 36 | Channel 2 | Frost alarm | 1 Bit | | CRT |
| 37 | Channel 2 | Heat alarm | 1 Bit | | CRT |
| 38 | Channel 2 | External sensor | 2 Bytes | 9.1 temperature (°C) | CW |
| 39 | Channel 2 | Setpoint comfort | 2 Bytes | 9.1 temperature (°C) | CRWT |
| 40 | Channel 2 | Set point value offset | 2 Bytes | 9.2 temperature difference (K) | CW |
| 40 | Channel 2 | Set point value offset | 2 Bytes | 9.2 temperature difference (K) | CWT |
| 41 | Channel 2 | Control value heating | 1 Byte | 5.1 percentage (0..100%) | CRT |
| 41 | Channel 2 | Control value heating | 1 Bit | | CRT |
| 41 | Channel 2 | Control value heating/cooling | 1 Byte | 5.1 percentage (0..100%) | CRT |
| 41 | Channel 2 | Control value heating/cooling | 1 Bit | | CRT |
| 42 | Channel 2 | Control value cooling | 1 Byte | 5.1 percentage (0..100%) | CRT |
| 42 | Channel 2 | Control value cooling | 1 Bit | | CRT |
| 42 | Channel 2 | Status: 0=Cool 1=Heat | 1 Bit | | CRT |
| 43 | Channel 2 | Mode comfort | 1 Bit | 1.1 switch | CW |
| 44 | Channel 2 | Mode night | 1 Bit | 1.1 switch | CW |
| 45 | Channel 2 | Mode frost protection | 1 Bit | 1.1 switch | CW |
| 45 | Channel 2 | Mode heat protection | 1 Bit | 1.1 switch | CW |
| 45 | Channel 2 | Mode frost/heat protection | 1 Bit | 1.1 switch | CW |
| 46 | Channel 2 | Heating disable object | 1 Bit | 1.3 enable | CW |
| 47 | Channel 2 | Cooling disable object | 1 Bit | 1.3 enable | CW |
| 48 | Channel 2 | Heating request | 1 Bit | 1.1 switch | CRT |
| 49 | Channel 2 | Cooling request | 1 Bit | 1.1 switch | CRT |
| 50 | Channel 2 | Heating/cooling switchover | 1 Bit | | CWT |
| 51 | Channel 2 | Max memory value | 2 Bytes | 9.1 temperature (°C) | CRT |
| 52 | Channel 2 | Min memory value | 2 Bytes | 9.1 temperature (°C) | CRT |
| 53 | Channel 2 | Min/max memory reset | 1 Bit | 1.3 enable | CW |
| 54 | Channel 2 | Reset setpoint value | 1 Bit | 1.3 enable | CW |
| 55 | Channel 2 | DPT_HVAC Status | 1 Byte | | CRT |
| 56 | Channel 2 | Error external sensor | 1 Bit | | CRT |
| 57 | Channel 2 | Actual setpoint | 2 Bytes | 9.1 temperature (°C) | CRT |
| 58 | Channel 2 | DPT_RHCC Status | 2 Bytes | | CRT |
| 59 | Channel 2 | Mode selection | 1 Byte | | CW |
| 59 | Channel 2 | Mode selection | 1 Byte | | CRWT |
| 60 | Channel 2 | Set point offset (1=+/0=-) | 1 Bit | | CW |
| 61 | Channel 2 | Flow temperature | 2 Bytes | 9.1 temperature (°C) | CW |
| 62 | | | 1 Byte | | |
| 63 | | | 1 Byte | | |
| 64 | | | 1 Byte | | |
| 65 | | | 1 Byte | | |
| 66 | | | 1 Byte | | |
| 67 | Channel 3 | Higher message value | 1 Bit | | CRT |
| 68 | Channel 3 | Below message value | 1 Bit | | CRT |
| 69 | Channel 3 | Frost alarm | 1 Bit | | CRT |
| 70 | Channel 3 | Heat alarm | 1 Bit | | CRT |
| 71 | Channel 3 | External sensor | 2 Bytes | 9.1 temperature (°C) | CW |
| 72 | Channel 3 | Setpoint comfort | 2 Bytes | 9.1 temperature (°C) | CRWT |
| 73 | Channel 3 | Set point value offset | 2 Bytes | 9.2 temperature difference (K) | CW |
| 73 | Channel 3 | Set point value offset | 2 Bytes | 9.2 temperature difference (K) | CWT |
| 74 | Channel 3 | Control value heating | 1 Byte | 5.1 percentage (0..100%) | CRT |
| 74 | Channel 3 | Control value heating | 1 Bit | | CRT |
| 74 | Channel 3 | Control value heating/cooling | 1 Byte | 5.1 percentage (0..100%) | CRT |
| 74 | Channel 3 | Control value heating/cooling | 1 Bit | | CRT |
| 75 | Channel 3 | Control value cooling | 1 Byte | 5.1 percentage (0..100%) | CRT |
| 75 | Channel 3 | Control value cooling | 1 Bit | | CRT |
| 75 | Channel 3 | Status: 0=Cool 1=Heat | 1 Bit | | CRT |
| 76 | Channel 3 | Mode comfort | 1 Bit | 1.1 switch | CW |
| 77 | Channel 3 | Mode night | 1 Bit | 1.1 switch | CW |
| 78 | Channel 3 | Mode frost protection | 1 Bit | 1.1 switch | CW |
| 78 | Channel 3 | Mode heat protection | 1 Bit | 1.1 switch | CW |
| 78 | Channel 3 | Mode frost/heat protection | 1 Bit | 1.1 switch | CW |
| 79 | Channel 3 | Heating disable object | 1 Bit | 1.3 enable | CW |
| 80 | Channel 3 | Cooling disable object | 1 Bit | 1.3 enable | CW |
| 81 | Channel 3 | Heating request | 1 Bit | 1.1 switch | CRT |
| 82 | Channel 3 | Cooling request | 1 Bit | 1.1 switch | CRT |
| 83 | Channel 3 | Heating/cooling switchover | 1 Bit | | CWT |
| 84 | Channel 3 | Max memory value | 2 Bytes | 9.1 temperature (°C) | CRT |
| 85 | Channel 3 | Min memory value | 2 Bytes | 9.1 temperature (°C) | CRT |
| 86 | Channel 3 | Min/max memory reset | 1 Bit | 1.3 enable | CW |
| 87 | Channel 3 | Reset setpoint value | 1 Bit | 1.3 enable | CW |
| 88 | Channel 3 | DPT_HVAC Status | 1 Byte | | CRT |
| 89 | Channel 3 | Error external sensor | 1 Bit | | CRT |
| 90 | Channel 3 | Actual setpoint | 2 Bytes | 9.1 temperature (°C) | CRT |
| 91 | Channel 3 | DPT_RHCC Status | 2 Bytes | | CRT |
| 92 | Channel 3 | Mode selection | 1 Byte | | CW |
| 92 | Channel 3 | Mode selection | 1 Byte | | CRWT |
| 93 | Channel 3 | Set point offset (1=+/0=-) | 1 Bit | | CW |
| 94 | Channel 3 | Flow temperature | 2 Bytes | 9.1 temperature (°C) | CW |
| 95 | | | 1 Byte | | |
| 96 | | | 1 Byte | | |
| 97 | | | 1 Byte | | |
| 98 | | | 1 Byte | | |
| 99 | | | 2 Bytes | | |
| 100 | Channel 4 | Higher message value | 1 Bit | | CRT |
| 101 | Channel 4 | Below message value | 1 Bit | | CRT |
| 102 | Channel 4 | Frost alarm | 1 Bit | | CRT |
| 103 | Channel 4 | Heat alarm | 1 Bit | | CRT |
| 104 | Channel 4 | External sensor | 2 Bytes | 9.1 temperature (°C) | CW |
| 105 | Channel 4 | Setpoint comfort | 2 Bytes | 9.1 temperature (°C) | CRWT |
| 106 | Channel 4 | Set point value offset | 2 Bytes | 9.2 temperature difference (K) | CW |
| 106 | Channel 4 | Set point value offset | 2 Bytes | 9.2 temperature difference (K) | CWT |
| 107 | Channel 4 | Control value heating | 1 Byte | 5.1 percentage (0..100%) | CRT |
| 107 | Channel 4 | Control value heating | 1 Bit | | CRT |
| 107 | Channel 4 | Control value heating/cooling | 1 Byte | 5.1 percentage (0..100%) | CRT |
| 107 | Channel 4 | Control value heating/cooling | 1 Bit | | CRT |
| 108 | Channel 4 | Control value cooling | 1 Byte | 5.1 percentage (0..100%) | CRT |
| 108 | Channel 4 | Control value cooling | 1 Bit | | CRT |
| 108 | Channel 4 | Status: 0=Cool 1=Heat | 1 Bit | | CRT |
| 109 | Channel 4 | Mode comfort | 1 Bit | 1.1 switch | CW |
| 110 | Channel 4 | Mode night | 1 Bit | 1.1 switch | CW |
| 111 | Channel 4 | Mode frost protection | 1 Bit | 1.1 switch | CW |
| 111 | Channel 4 | Mode heat protection | 1 Bit | 1.1 switch | CW |
| 111 | Channel 4 | Mode frost/heat protection | 1 Bit | 1.1 switch | CW |
| 112 | Channel 4 | Heating disable object | 1 Bit | 1.3 enable | CW |
| 113 | Channel 4 | Cooling disable object | 1 Bit | 1.3 enable | CW |
| 114 | Channel 4 | Heating request | 1 Bit | 1.1 switch | CRT |
| 115 | Channel 4 | Cooling request | 1 Bit | 1.1 switch | CRT |
| 116 | Channel 4 | Heating/cooling switchover | 1 Bit | | CWT |
| 117 | Channel 4 | Max memory value | 2 Bytes | 9.1 temperature (°C) | CRT |
| 118 | Channel 4 | Min memory value | 2 Bytes | 9.1 temperature (°C) | CRT |
| 119 | Channel 4 | Min/max memory reset | 1 Bit | 1.3 enable | CW |
| 120 | Channel 4 | Reset setpoint value | 1 Bit | 1.3 enable | CW |
| 121 | Channel 4 | DPT_HVAC Status | 1 Byte | | CRT |
| 122 | Channel 4 | Error external sensor | 1 Bit | | CRT |
| 123 | Channel 4 | Actual setpoint | 2 Bytes | 9.1 temperature (°C) | CRT |
| 124 | Channel 4 | DPT_RHCC Status | 2 Bytes | | CRT |
| 125 | Channel 4 | Mode selection | 1 Byte | | CW |
| 125 | Channel 4 | Mode selection | 1 Byte | | CRWT |
| 126 | Channel 4 | Set point offset (1=+/0=-) | 1 Bit | | CW |
| 127 | Channel 4 | Flow temperature | 2 Bytes | 9.1 temperature (°C) | CW |
| 128 | | | 1 Byte | | |
| 129 | | | 1 Byte | | |
| 130 | | | 1 Byte | | |
| 131 | | | 1 Byte | | |
| 132 | | | 2 Bytes | | |
| 133 | Channel 5 | Higher message value | 1 Bit | | CRT |
| 134 | Channel 5 | Below message value | 1 Bit | | CRT |
| 135 | Channel 5 | Frost alarm | 1 Bit | | CRT |
| 136 | Channel 5 | Heat alarm | 1 Bit | | CRT |
| 137 | Channel 5 | External sensor | 2 Bytes | 9.1 temperature (°C) | CW |
| 138 | Channel 5 | Setpoint comfort | 2 Bytes | 9.1 temperature (°C) | CRWT |
| 139 | Channel 5 | Set point value offset | 2 Bytes | 9.2 temperature difference (K) | CW |
| 139 | Channel 5 | Set point value offset | 2 Bytes | 9.2 temperature difference (K) | CWT |
| 140 | Channel 5 | Control value heating | 1 Byte | 5.1 percentage (0..100%) | CRT |
| 140 | Channel 5 | Control value heating | 1 Bit | | CRT |
| 140 | Channel 5 | Control value heating/cooling | 1 Byte | 5.1 percentage (0..100%) | CRT |
| 140 | Channel 5 | Control value heating/cooling | 1 Bit | | CRT |
| 141 | Channel 5 | Control value cooling | 1 Byte | 5.1 percentage (0..100%) | CRT |
| 141 | Channel 5 | Control value cooling | 1 Bit | | CRT |
| 141 | Channel 5 | Status: 0=Cool 1=Heat | 1 Bit | | CRT |
| 142 | Channel 5 | Mode comfort | 1 Bit | 1.1 switch | CW |
| 143 | Channel 5 | Mode night | 1 Bit | 1.1 switch | CW |
| 144 | Channel 5 | Mode frost protection | 1 Bit | 1.1 switch | CW |
| 144 | Channel 5 | Mode heat protection | 1 Bit | 1.1 switch | CW |
| 144 | Channel 5 | Mode frost/heat protection | 1 Bit | 1.1 switch | CW |
| 145 | Channel 5 | Heating disable object | 1 Bit | 1.3 enable | CW |
| 146 | Channel 5 | Cooling disable object | 1 Bit | 1.3 enable | CW |
| 147 | Channel 5 | Heating request | 1 Bit | 1.1 switch | CRT |
| 148 | Channel 5 | Cooling request | 1 Bit | 1.1 switch | CRT |
| 149 | Channel 5 | Heating/cooling switchover | 1 Bit | | CWT |
| 150 | Channel 5 | Max memory value | 2 Bytes | 9.1 temperature (°C) | CRT |
| 151 | Channel 5 | Min memory value | 2 Bytes | 9.1 temperature (°C) | CRT |
| 152 | Channel 5 | Min/max memory reset | 1 Bit | 1.3 enable | CW |
| 153 | Channel 5 | Reset setpoint value | 1 Bit | 1.3 enable | CW |
| 154 | Channel 5 | DPT_HVAC Status | 1 Byte | | CRT |
| 155 | Channel 5 | Error external sensor | 1 Bit | | CRT |
| 156 | Channel 5 | Actual setpoint | 2 Bytes | 9.1 temperature (°C) | CRT |
| 157 | Channel 5 | DPT_RHCC Status | 2 Bytes | | CRT |
| 158 | Channel 5 | Mode selection | 1 Byte | | CW |
| 158 | Channel 5 | Mode selection | 1 Byte | | CRWT |
| 159 | Channel 5 | Set point offset (1=+/0=-) | 1 Bit | | CW |
| 160 | Channel 5 | Flow temperature | 2 Bytes | 9.1 temperature (°C) | CW |
| 161 | | | 1 Byte | | |
| 162 | | | 1 Byte | | |
| 163 | | | 1 Byte | | |
| 164 | | | 1 Byte | | |
| 165 | | | 2 Bytes | | |
| 166 | Channel 6 | Higher message value | 1 Bit | | CRT |
| 167 | Channel 6 | Below message value | 1 Bit | | CRT |
| 168 | Channel 6 | Frost alarm | 1 Bit | | CRT |
| 169 | Channel 6 | Heat alarm | 1 Bit | | CRT |
| 170 | Channel 6 | External sensor | 2 Bytes | 9.1 temperature (°C) | CW |
| 171 | Channel 6 | Setpoint comfort | 2 Bytes | 9.1 temperature (°C) | CRWT |
| 172 | Channel 6 | Set point value offset | 2 Bytes | 9.2 temperature difference (K) | CWT |
| 172 | Channel 6 | Set point value offset | 2 Bytes | 9.2 temperature difference (K) | CW |
| 173 | Channel 6 | Control value heating | 1 Byte | 5.1 percentage (0..100%) | CRT |
| 173 | Channel 6 | Control value heating | 1 Bit | | CRT |
| 173 | Channel 6 | Control value heating/cooling | 1 Byte | 5.1 percentage (0..100%) | CRT |
| 173 | Channel 6 | Control value heating/cooling | 1 Bit | | CRT |
| 174 | Channel 6 | Control value cooling | 1 Byte | 5.1 percentage (0..100%) | CRT |
| 174 | Channel 6 | Control value cooling | 1 Bit | | CRT |
| 174 | Channel 6 | Status: 0=Cool 1=Heat | 1 Bit | | CRT |
| 175 | Channel 6 | Mode comfort | 1 Bit | 1.1 switch | CW |
| 176 | Channel 6 | Mode night | 1 Bit | 1.1 switch | CW |
| 177 | Channel 6 | Mode frost protection | 1 Bit | 1.1 switch | CW |
| 177 | Channel 6 | Mode heat protection | 1 Bit | 1.1 switch | CW |
| 177 | Channel 6 | Mode frost/heat protection | 1 Bit | 1.1 switch | CW |
| 178 | Channel 6 | Heating disable object | 1 Bit | 1.3 enable | CW |
| 179 | Channel 6 | Cooling disable object | 1 Bit | 1.3 enable | CW |
| 180 | Channel 6 | Heating request | 1 Bit | 1.1 switch | CRT |
| 181 | Channel 6 | Cooling request | 1 Bit | 1.1 switch | CRT |
| 182 | Channel 6 | Heating/cooling switchover | 1 Bit | | CWT |
| 183 | Channel 6 | Max memory value | 2 Bytes | 9.1 temperature (°C) | CRT |
| 184 | Channel 6 | Min memory value | 2 Bytes | 9.1 temperature (°C) | CRT |
| 185 | Channel 6 | Min/max memory reset | 1 Bit | 1.3 enable | CW |
| 186 | Channel 6 | Reset setpoint value | 1 Bit | 1.3 enable | CW |
| 187 | Channel 6 | DPT_HVAC Status | 1 Byte | | CRT |
| 188 | Channel 6 | Error external sensor | 1 Bit | | CRT |
| 189 | Channel 6 | Actual setpoint | 2 Bytes | 9.1 temperature (°C) | CRT |
| 190 | Channel 6 | DPT_RHCC Status | 2 Bytes | | CRT |
| 191 | Channel 6 | Mode selection | 1 Byte | | CW |
| 191 | Channel 6 | Mode selection | 1 Byte | | CRWT |
| 192 | Channel 6 | Set point offset (1=+/0=-) | 1 Bit | | CW |
| 193 | Channel 6 | Flow temperature | 2 Bytes | 9.1 temperature (°C) | CW |
| 194 | | | 1 Byte | | |
| 195 | | | 1 Byte | | |
| 196 | | | 1 Byte | | |
| 197 | | | 1 Byte | | |
| 198 | | | 1 Bit | | |
| 199 | | | 1 Bit | | |
| 200 | | | 1 Bit | | |
| 201 | | | 1 Bit | | |
| 202 | | | 1 Bit | | |