Room Temperature Controller 1-fold UP SCN-RT1UP.01

MDT technologies GmbH · Order number SCN-RT1UP.01 · Temperature Controller › Room Temperature Controller

Room Temperature Controller flush mounted

Download .knxprod Room temperature controller 1.4 · 100 KB

Product

ManufacturerMDT technologies GmbH
Product nameRoom Temperature Controller 1-fold UP
Order numberSCN-RT1UP.01
Product textRoom temperature controller 1-fold UP
HardwareRaumtemperaturregler UP
MediumTwisted Pair
Bus current (mA)10
Rail mountedNo
RegistrationCertified
Languagesde-DE, en-US, es-ES, fr-FR
Catalog entryM-0083_H-65-1_HP-0041-14-2975_CI-SCN.2DRT1UP.2E01-1
Fingerprint2975
SHA-256692d9b80da1fe16c1b0df918052d11ca9a83214a7dc2eb392b136750f4d34728
First seen2026-11-25
Markets69 markets

Application program: Room temperature controller 1.4

Application number$0041
Version1.4
Mask versionMV-0701 (7.1)
KNX Data SecureNo
Minimum ETS version4.0
Parameters122
Group objects47
Group objects (47)
NoNameFunctionSizeDPTFlags
0Currentl temperature valueTransmit temperature value2 Bytes9.1 temperature (°C)CRT
1Higher message valueSend message1 BitCRT
2Below message value Send message1 BitCRT
3Frost alarmSend alarm1 BitCRT
4Heat alarmSend alarm1 BitCRT
5External sensorRead external sensor2 Bytes9.1 temperature (°C)CW
6Setpoint comfortSet setpoint2 Bytes9.1 temperature (°C)CRWT
7Manual set point value offsetReduction / increase2 Bytes9.2 temperature difference (K)CW
7Manual set point value offsetReduction / increase2 Bytes9.2 temperature difference (K)CWT
8Control value heatingSend control value1 Byte5.1 percentage (0..100%)CRT
8Control value heatingSend control value1 BitCRT
8Control value heating/coolingSend control value1 Byte5.1 percentage (0..100%)CRT
8Control value heating/coolingSend control value1 BitCRT
9Control value additional heating Send control value1 BitCRT
10Status Cooling / Heating0=Cooling 1=Heating1 BitCRT
10Control value coolingSend control value1 Byte5.1 percentage (0..100%)CRT
10Control value coolingSend control value1 BitCRT
11Mode comfortSwitch mode1 Bit1.1 switchCW
12Mode nightSwitch mode1 Bit1.1 switchCW
13Mode frost/heat protectionSwitch mode1 Bit1.1 switchCW
13Mode frost protectionSwitch mode1 Bit1.1 switchCW
13Mode heat protectionSwitch mode1 Bit1.1 switchCW
14Heating disable objectDisable heating1 Bit1.3 enableCW
15Cooling disable objectDisable cooling1 Bit1.3 enableCW
16Object 161 Bit
17Heating requestSend request1 Bit1.1 switchCRT
18Cooling requestSend request1 Bit1.1 switchCRT
19Heating/cooling switchover0=Cooling 1=Heating1 BitCWT
20Guiding valueSetpoint adjustment2 Bytes9.1 temperature (°C)CW
21Max memory valueRead memory2 Bytes9.1 temperature (°C)CRT
22Min memory valueRead memory2 Bytes9.1 temperature (°C)CRT
23Min/max memory resetReset memory1 Bit1.3 enableCW
24Reset setpoint valueParameter read in1 Bit1.3 enableCW
25DPT_HVAC StatusSend controller status1 ByteCRT
26Object 261 Byte
27LCD backlightBacklight on1 Bit1.1 switchCW
28Error external sensorError message1 BitCRT
29Current setpointSend setpoint2 Bytes9.1 temperature (°C)CRT
30RHCC Status Send controller status2 BytesCRT
31mode selectionselect mode1 ByteCW
31mode selectionselect mode1 ByteCRWT
32Manual set point value offsetIncrease / Reduction (1=+/0=-)1 BitCW
33Flow temperatureRead external sensor2 Bytes9.1 temperature (°C)CW
34Object 341 Byte
35Object 351 Byte
36Object 361 Byte
37Object 371 Byte
Parameters (65)
ParameterTypeDefault
Startup delaytimelist0 s
Select hardwarelistSCN-RT1xP.xx without manual control
Send actual value after change oflistDisable
Send actual temperature cyclicallylistDisable
Send min/max valuelistDisable
Internal sensor correction value (value * 0.1K)signedInt -50…500
Internal/external sensorlist100 % intern
AlarmlistInactive
Frostalarm if value <list7 °C
Heatalarm if value >list35 °C
MessageslistInactive
Message if value >list26 °C
Message if value <list13 °C
Controller typelistHeating
PrioritylistFrost(Heat protection)/Comfort/Night/Standby
Basic comfort setpoint (°C)list21,0 °C
Standby reduction (K)list3,0 K
Night reduction (K)list2,0 K
Setpoint frost protection (°C)list7 °C
Max setpoint offsetlist3,0 K
Setpoint value offset via 2Byte objectlistInactive
Send status of setpoint offsetlistInactive
Advanced function can be apply only for hardware starting from version R3.5text<- TIP
Setpoint value offset via 1Bit objectlistInactive
Advanced function can be apply only for hardware starting from version R3.2text<- TIP
Step rangelist0,5 K
Max setpoint offset vaild forlistComfort
Reset setpoint offset after change of modelistNo
Send setpoint changelistNo
Flow temperaturelistInactive
Advanced function can be apply only for hardware starting from version R3.6text<- TIP
Flow temperature limitlist10 °C
Operating mode after resetlistComfort with parameterized set point
Send status on object 31 "Mode selection"listNo
Heating disable objectlistInactive
Heating request object enabledlistNo
GuidinglistInactive
Guiding value minimum (°C)signedInt -100…10028
Guiding value maximum (°C)signedInt -100…10038
Setpoint variation at maximum guiding value (°C)signedInt -100…10010
Standby increase (K)list3,0 K
Night increase (K)list2,0 K
Setpoint heat protection (°C)list35 °C
Cooling disable objectlistInactive
Cooling request object enabledlistNo
Dead zone between heating and cooling (K)list2,0 K
SetpointlistPI control continuous
Direction of controllerlistnormal
Max value of control valuelist100%
Heating systemlistAdjustment via control parameter
Heating systemlistUnderfloor heating (4K / 150min)
Proportional range (K)list4 K
Reset time (min)list120 min
Send control value cycliclistDisable
PWM cycletime (min)list10 min
Hysteresis (K)list2,0 K
Use additional levellistNo
Setpointlist2-step control (switching)
Distance (K)list2,0 K
Cooling systemlistAdjustment via control parameter
Cooling systemlistCooling ceiling (4K / 150min)
Reset time (min)list60 min
Systemlist2 Pipe system
Heating/cooling switch overlistautomatically
Send control value for heating and cooling cycliclistDisable

Version history

ApplicationApp noFingerprintFirst seenSizeFile
Room temperature controller 1.4 latest$004129752026-11-25100 KBDownload

About this file

This is the official ETS product database for the MDT technologies GmbH Room Temperature Controller 1-fold UP (SCN-RT1UP.01), published by the manufacturer in the KNX online catalog. To use it, open ETS, go to Catalogs → Import and choose the downloaded .knxprod file. The device then appears in your catalog and can be added to a project. Older versions are kept so existing projects can be matched to the application program they were commissioned with.