SCN-KP360K3.03 Combi-Presence Detector 360° with room climate sensors SCN-KP360K3.03
MDT technologies GmbH · Order number SCN-KP360K3.03 · Controller › Air quality/CO2 sensor
Combi-Presence Detector 360° 3S with room climate sensors
Download .knxprod Combi-Presence Detector 1.0 · 397 KB
Product
| Manufacturer | MDT technologies GmbH |
|---|---|
| Product name | SCN-KP360K3.03 Combi-Presence Detector 360° with room climate sensors |
| Order number | SCN-KP360K3.03 |
| Hardware | Kombi-Präsenzmelder |
| Medium | Twisted Pair |
| Bus current (mA) | 10 |
| Rail mounted | No |
| Registration | Registered · 2024-06-05 |
| Languages | de-DE, en-US, es-ES, fr-FR |
| Catalog entry | M-0083_H-327-1_HP-0078-10-C9D1_CI-SCN.2DKP360K3.2E03-1 |
| Fingerprint | C9D1 |
| SHA-256 | 0d45a92c52a9fe8d434c620e4baeced59ac3a0d86a5ea4b5a5588b68b4ec34bc |
| First seen | 2026-11-25 |
| Markets | 69 markets |
Application program: Combi-Presence Detector 1.0
| Application number | $0078 |
|---|---|
| Version | 1.0 |
| Mask version | MV-07B0 (System B) |
| KNX Data Secure | No |
| Minimum ETS version | 5.0 |
| Parameters | 1222 |
| Group objects | 372 |
Group objects (372)
| No | Name | Function | Size | DPT | Flags |
|---|---|---|---|---|---|
| 1 | CO2 measurement | Send measured value | 2 Bytes | 9.8 parts/million (ppm) | CRT |
| 2 | CO2 measurement | External sensor input | 2 Bytes | 9.8 parts/million (ppm) | CWTU |
| 3 | CO2 measurement | Maximum value exceeded | 1 Bit | 1.5 alarm | CRT |
| 4 | CO2 measurement | Minimum value fallen below | 1 Bit | 1.5 alarm | CRT |
| 5 | CO2 measurement | Error external sensor | 1 Bit | 1.5 alarm | CRT |
| 8 | VOC measurement | Send measured value | 2 Bytes | 9.8 parts/million (ppm) | CRT |
| 8 | VOC measurement | Send measured value | 1 Byte | 5.1 percentage (0..100%) | CRT |
| 9 | VOC measurement | External sensor input | 2 Bytes | 9.8 parts/million (ppm) | CWTU |
| 9 | VOC measurement | External sensor input | 2 Bytes | CWTU | |
| 9 | VOC measurement | External sensor input | 1 Byte | 5.1 percentage (0..100%) | CWTU |
| 10 | VOC measurement | Maximum value exceeded | 1 Bit | 1.5 alarm | CRT |
| 11 | VOC measurement | Minimum value fallen below | 1 Bit | 1.5 alarm | CRT |
| 12 | VOC measurement | Error external sensor | 1 Bit | 1.5 alarm | CRT |
| 15 | Temperature measurement | Send measured value | 2 Bytes | 9.1 temperature (°C) | CRT |
| 16 | Temperature measurement | External sensor input | 2 Bytes | 9.1 temperature (°C) | CWTU |
| 17 | Temperature measurement | Maximum value exceeded | 1 Bit | 1.5 alarm | CRT |
| 18 | Temperature measurement | Minimum value fallen below | 1 Bit | 1.5 alarm | CRT |
| 19 | Temperature measurement | Error external sensor | 1 Bit | 1.5 alarm | CRT |
| 22 | Relative humidity measurement | Send measured value | 2 Bytes | 9.7 humidity (%) | CRT |
| 23 | Relative humidity measurement | External sensor input | 2 Bytes | 9.7 humidity (%) | CWTU |
| 24 | Relative humidity measurement | Maximum value exceeded | 1 Bit | 1.5 alarm | CRT |
| 25 | Relative humidity measurement | Minimum value fallen below | 1 Bit | 1.5 alarm | CRT |
| 26 | Relative humidity measurement | Error external sensor | 1 Bit | 1.5 alarm | CRT |
| 29 | Air quality traffic light | Output level 1 | 1 Bit | 1.1 switch | CRT |
| 30 | Air quality traffic light | Output level 2 | 1 Bit | 1.1 switch | CRT |
| 31 | Air quality traffic light | Output level 3 | 1 Bit | 1.1 switch | CRT |
| 32 | Air quality traffic light | Output level 3 | 1 Bit | 1.1 switch | CRT |
| 32 | Air quality traffic light | Output level 4 | 1 Bit | 1.1 switch | CRT |
| 33 | Air quality traffic light | Output RGB | 3 Bytes | 232.600 RGB value 3x(0..255) | CRT |
| 33 | Air quality traffic light | Output HSV | 3 Bytes | 232.600 RGB value 3x(0..255) | CRT |
| 34 | Air quality traffic light | Output Scene | 1 Byte | 17.1 scene number | CRT |
| 37 | Air quality controller | Preset setpoint | 2 Bytes | 9.8 parts/million (ppm) | CW |
| 38 | Air quality controller | Actual setpoint | 2 Bytes | 9.8 parts/million (ppm) | CRT |
| 38 | Air quality controller | Actual setpoint | 2 Bytes | CRT | |
| 39 | Air quality controller | CO2 Input 1 | 2 Bytes | 9.8 parts/million (ppm) | CW |
| 39 | Air quality controller | VOC Input 1 | 2 Bytes | 9.8 parts/million (ppm) | CW |
| 39 | Air quality controller | VOC (IAQ Index) Input 1 | 2 Bytes | CW | |
| 40 | Air quality controller | CO2 Input 2 | 2 Bytes | 9.8 parts/million (ppm) | CW |
| 40 | Air quality controller | VOC Input 2 | 2 Bytes | 9.8 parts/million (ppm) | CW |
| 40 | Air quality controller | VOC (IAQ Index) Input 2 | 2 Bytes | CW | |
| 41 | Air quality controller | CO2 Input 3 | 2 Bytes | 9.8 parts/million (ppm) | CW |
| 41 | Air quality controller | VOC Input 3 | 2 Bytes | 9.8 parts/million (ppm) | CW |
| 41 | Air quality controller | VOC (IAQ Index) Input 3 | 2 Bytes | CW | |
| 42 | Air quality controller | CO2 Input 4 | 2 Bytes | 9.8 parts/million (ppm) | CW |
| 42 | Air quality controller | VOC Input 4 | 2 Bytes | 9.8 parts/million (ppm) | CW |
| 42 | Air quality controller | VOC (IAQ Index) Input 4 | 2 Bytes | CW | |
| 43 | Air quality controller | CO2 Input 5 | 2 Bytes | 9.8 parts/million (ppm) | CW |
| 43 | Air quality controller | VOC Input 5 | 2 Bytes | 9.8 parts/million (ppm) | CW |
| 43 | Air quality controller | VOC (IAQ Index) Input 5 | 2 Bytes | CW | |
| 44 | Air quality controller | CO2 Input 6 | 2 Bytes | 9.8 parts/million (ppm) | CW |
| 44 | Air quality controller | VOC Input 6 | 2 Bytes | 9.8 parts/million (ppm) | CW |
| 44 | Air quality controller | VOC (IAQ Index) Input 6 | 2 Bytes | CW | |
| 44 | Air quality controller | Humidity Input 1 | 2 Bytes | 9.7 humidity (%) | CW |
| 45 | Air quality controller | CO2 Input 7 | 2 Bytes | 9.8 parts/million (ppm) | CW |
| 45 | Air quality controller | VOC Input 7 | 2 Bytes | 9.8 parts/million (ppm) | CW |
| 45 | Air quality controller | VOC (IAQ Index) Input 7 | 2 Bytes | CW | |
| 45 | Air quality controller | Humidity Input 2 | 2 Bytes | 9.7 humidity (%) | CW |
| 46 | Air quality controller | CO2 Input 8 | 2 Bytes | 9.8 parts/million (ppm) | CW |
| 46 | Air quality controller | VOC Input 8 | 2 Bytes | 9.8 parts/million (ppm) | CW |
| 46 | Air quality controller | VOC (IAQ Index) Input 8 | 2 Bytes | CW | |
| 46 | Air quality controller | Humidity Input 3 | 2 Bytes | 9.7 humidity (%) | CW |
| 47 | Air quality controller | CO2 Input 9 | 2 Bytes | 9.8 parts/million (ppm) | CW |
| 47 | Air quality controller | VOC Input 9 | 2 Bytes | 9.8 parts/million (ppm) | CW |
| 47 | Air quality controller | VOC (IAQ Index) Input 9 | 2 Bytes | CW | |
| 47 | Air quality controller | Humidity Input 4 | 2 Bytes | 9.7 humidity (%) | CW |
| 48 | Air quality controller | CO2 Input 10 | 2 Bytes | 9.8 parts/million (ppm) | CW |
| 48 | Air quality controller | VOC Input 10 | 2 Bytes | 9.8 parts/million (ppm) | CW |
| 48 | Air quality controller | VOC (IAQ Index) Input 10 | 2 Bytes | CW | |
| 48 | Air quality controller | Humidity Input 5 | 2 Bytes | 9.7 humidity (%) | CW |
| 51 | Air quality controller | Lock controller | 1 Bit | 1.3 enable | CW |
| 52 | Air quality controller | Output control value | 1 Byte | 5.1 percentage (0..100%) | CRT |
| 53 | Air quality controller | Output level 1 | 1 Bit | 1.1 switch | CRT |
| 53 | Air quality controller | Output Bit 0 | 1 Bit | 1.2 boolean | CRT |
| 54 | Air quality controller | Output level 2 | 1 Bit | 1.1 switch | CRT |
| 54 | Air quality controller | Output Bit 1 | 1 Bit | 1.2 boolean | CRT |
| 55 | Air quality controller | Output level 3 | 1 Bit | 1.1 switch | CRT |
| 55 | Air quality controller | Output Bit 2 | 1 Bit | 1.2 boolean | CRT |
| 56 | Air quality controller | Output level 4 | 1 Bit | 1.1 switch | CRT |
| 57 | Air quality controller | Override level | 1 Byte | 5.5 ratio (0..255) | CW |
| 57 | Air quality controller | Override control value | 1 Byte | 5.1 percentage (0..100%) | CW |
| 60 | Logic - Comparator 1 | Input 1 | 1 Byte | 5.1 percentage (0..100%) | CW |
| 60 | Logic - Comparator 1 | Input 1 | 1 Byte | 5.5 ratio (0..255) | CW |
| 60 | Logic - Comparator 1 | Input 1 | 2 Bytes | CW | |
| 60 | Logic - Comparator 1 | Input 1 | 2 Bytes | 9.1 temperature (°C) | CW |
| 60 | Logic - Comparator 1 | Input 1 | 2 Bytes | 9.4 lux (Lux) | CW |
| 60 | Logic - Comparator 1 | Input 1 | 2 Bytes | 9.7 humidity (%) | CW |
| 60 | Logic - Comparator 1 | Input 1 | 2 Bytes | 9.8 parts/million (ppm) | CW |
| 61 | Logic - Comparator 1 | Input 2 | 1 Byte | 5.1 percentage (0..100%) | CW |
| 61 | Logic - Comparator 1 | Input 2 | 1 Byte | 5.5 ratio (0..255) | CW |
| 61 | Logic - Comparator 1 | Input 2 | 2 Bytes | CW | |
| 61 | Logic - Comparator 1 | Input 2 | 2 Bytes | 9.1 temperature (°C) | CW |
| 61 | Logic - Comparator 1 | Input 2 | 2 Bytes | 9.4 lux (Lux) | CW |
| 61 | Logic - Comparator 1 | Input 2 | 2 Bytes | 9.7 humidity (%) | CW |
| 61 | Logic - Comparator 1 | Input 2 | 2 Bytes | 9.8 parts/million (ppm) | CW |
| 62 | Logic - Comparator 1 | Input 3 | 1 Byte | 5.1 percentage (0..100%) | CW |
| 62 | Logic - Comparator 1 | Input 3 | 1 Byte | 5.5 ratio (0..255) | CW |
| 62 | Logic - Comparator 1 | Input 3 | 2 Bytes | CW | |
| 62 | Logic - Comparator 1 | Input 3 | 2 Bytes | 9.1 temperature (°C) | CW |
| 62 | Logic - Comparator 1 | Input 3 | 2 Bytes | 9.4 lux (Lux) | CW |
| 62 | Logic - Comparator 1 | Input 3 | 2 Bytes | 9.7 humidity (%) | CW |
| 62 | Logic - Comparator 1 | Input 3 | 2 Bytes | 9.8 parts/million (ppm) | CW |
| 63 | Logic - Comparator 1 | Input 4 | 1 Byte | 5.1 percentage (0..100%) | CW |
| 63 | Logic - Comparator 1 | Input 4 | 1 Byte | 5.5 ratio (0..255) | CW |
| 63 | Logic - Comparator 1 | Input 4 | 2 Bytes | CW | |
| 63 | Logic - Comparator 1 | Input 4 | 2 Bytes | 9.1 temperature (°C) | CW |
| 63 | Logic - Comparator 1 | Input 4 | 2 Bytes | 9.4 lux (Lux) | CW |
| 63 | Logic - Comparator 1 | Input 4 | 2 Bytes | 9.7 humidity (%) | CW |
| 63 | Logic - Comparator 1 | Input 4 | 2 Bytes | 9.8 parts/million (ppm) | CW |
| 64 | Logic - Comparator 1 | Input 5 | 1 Byte | 5.1 percentage (0..100%) | CW |
| 64 | Logic - Comparator 1 | Input 5 | 1 Byte | 5.5 ratio (0..255) | CW |
| 64 | Logic - Comparator 1 | Input 5 | 2 Bytes | CW | |
| 64 | Logic - Comparator 1 | Input 5 | 2 Bytes | 9.1 temperature (°C) | CW |
| 64 | Logic - Comparator 1 | Input 5 | 2 Bytes | 9.4 lux (Lux) | CW |
| 64 | Logic - Comparator 1 | Input 5 | 2 Bytes | 9.7 humidity (%) | CW |
| 64 | Logic - Comparator 1 | Input 5 | 2 Bytes | 9.8 parts/million (ppm) | CW |
| 65 | Logic - Comparator 1 | Output | 1 Byte | 5.1 percentage (0..100%) | CRT |
| 65 | Logic - Comparator 1 | Output | 1 Byte | 5.5 ratio (0..255) | CRT |
| 65 | Logic - Comparator 1 | Output | 2 Bytes | CRT | |
| 65 | Logic - Comparator 1 | Output | 2 Bytes | 9.1 temperature (°C) | CRT |
| 65 | Logic - Comparator 1 | Output | 2 Bytes | 9.4 lux (Lux) | CRT |
| 65 | Logic - Comparator 1 | Output | 2 Bytes | 9.7 humidity (%) | CRT |
| 65 | Logic - Comparator 1 | Output | 2 Bytes | 9.8 parts/million (ppm) | CRT |
| 66 | Logic - Comparator 1 | Lock | 1 Bit | 1.3 enable | CW |
| 66 | Logic - Comparator 1 | Lock | 1 Bit | 1.1 switch | CW |
| 67 | Logic - Comparator 1 | Info - Emergency operation | 1 Bit | 1.11 state | CRT |
| 69 | Logic - Comparator 2 | Input 1 | 1 Byte | 5.1 percentage (0..100%) | CW |
| 69 | Logic - Comparator 2 | Input 1 | 1 Byte | 5.5 ratio (0..255) | CW |
| 69 | Logic - Comparator 2 | Input 1 | 2 Bytes | CW | |
| 69 | Logic - Comparator 2 | Input 1 | 2 Bytes | 9.1 temperature (°C) | CW |
| 69 | Logic - Comparator 2 | Input 1 | 2 Bytes | 9.4 lux (Lux) | CW |
| 69 | Logic - Comparator 2 | Input 1 | 2 Bytes | 9.7 humidity (%) | CW |
| 69 | Logic - Comparator 2 | Input 1 | 2 Bytes | 9.8 parts/million (ppm) | CW |
| 70 | Logic - Comparator 2 | Input 2 | 1 Byte | 5.1 percentage (0..100%) | CW |
| 70 | Logic - Comparator 2 | Input 2 | 1 Byte | 5.5 ratio (0..255) | CW |
| 70 | Logic - Comparator 2 | Input 2 | 2 Bytes | CW | |
| 70 | Logic - Comparator 2 | Input 2 | 2 Bytes | 9.1 temperature (°C) | CW |
| 70 | Logic - Comparator 2 | Input 2 | 2 Bytes | 9.4 lux (Lux) | CW |
| 70 | Logic - Comparator 2 | Input 2 | 2 Bytes | 9.7 humidity (%) | CW |
| 70 | Logic - Comparator 2 | Input 2 | 2 Bytes | 9.8 parts/million (ppm) | CW |
| 71 | Logic - Comparator 2 | Input 3 | 1 Byte | 5.1 percentage (0..100%) | CW |
| 71 | Logic - Comparator 2 | Input 3 | 1 Byte | 5.5 ratio (0..255) | CW |
| 71 | Logic - Comparator 2 | Input 3 | 2 Bytes | CW | |
| 71 | Logic - Comparator 2 | Input 3 | 2 Bytes | 9.1 temperature (°C) | CW |
| 71 | Logic - Comparator 2 | Input 3 | 2 Bytes | 9.4 lux (Lux) | CW |
| 71 | Logic - Comparator 2 | Input 3 | 2 Bytes | 9.7 humidity (%) | CW |
| 71 | Logic - Comparator 2 | Input 3 | 2 Bytes | 9.8 parts/million (ppm) | CW |
| 72 | Logic - Comparator 2 | Input 4 | 1 Byte | 5.1 percentage (0..100%) | CW |
| 72 | Logic - Comparator 2 | Input 4 | 1 Byte | 5.5 ratio (0..255) | CW |
| 72 | Logic - Comparator 2 | Input 4 | 2 Bytes | CW | |
| 72 | Logic - Comparator 2 | Input 4 | 2 Bytes | 9.1 temperature (°C) | CW |
| 72 | Logic - Comparator 2 | Input 4 | 2 Bytes | 9.4 lux (Lux) | CW |
| 72 | Logic - Comparator 2 | Input 4 | 2 Bytes | 9.7 humidity (%) | CW |
| 72 | Logic - Comparator 2 | Input 4 | 2 Bytes | 9.8 parts/million (ppm) | CW |
| 73 | Logic - Comparator 2 | Input 5 | 1 Byte | 5.1 percentage (0..100%) | CW |
| 73 | Logic - Comparator 2 | Input 5 | 1 Byte | 5.5 ratio (0..255) | CW |
| 73 | Logic - Comparator 2 | Input 5 | 2 Bytes | CW | |
| 73 | Logic - Comparator 2 | Input 5 | 2 Bytes | 9.1 temperature (°C) | CW |
| 73 | Logic - Comparator 2 | Input 5 | 2 Bytes | 9.4 lux (Lux) | CW |
| 73 | Logic - Comparator 2 | Input 5 | 2 Bytes | 9.7 humidity (%) | CW |
| 73 | Logic - Comparator 2 | Input 5 | 2 Bytes | 9.8 parts/million (ppm) | CW |
| 74 | Logic - Comparator 2 | Output | 1 Byte | 5.1 percentage (0..100%) | CRT |
| 74 | Logic - Comparator 2 | Output | 1 Byte | 5.5 ratio (0..255) | CRT |
| 74 | Logic - Comparator 2 | Output | 2 Bytes | CRT | |
| 74 | Logic - Comparator 2 | Output | 2 Bytes | 9.1 temperature (°C) | CRT |
| 74 | Logic - Comparator 2 | Output | 2 Bytes | 9.4 lux (Lux) | CRT |
| 74 | Logic - Comparator 2 | Output | 2 Bytes | 9.7 humidity (%) | CRT |
| 74 | Logic - Comparator 2 | Output | 2 Bytes | 9.8 parts/million (ppm) | CRT |
| 75 | Logic - Comparator 2 | Lock | 1 Bit | 1.3 enable | CW |
| 75 | Logic - Comparator 2 | Lock | 1 Bit | 1.1 switch | CW |
| 76 | Logic - Comparator 2 | Info - Emergency operation | 1 Bit | 1.11 state | CRT |
| 78 | Temperature controller | Preset setpoint | 2 Bytes | 9.1 temperature (°C) | CW |
| 79 | Temperature controller | Preset Comfort setpoint | 2 Bytes | 9.1 temperature (°C) | CW |
| 79 | Temperature controller | Combined object: Preset setpoint | 8 Bytes | 275.100 Temperature setpoint setting for 4 HVAC Modes | CW |
| 79 | Temperature controller | Preset (Basic) Comfort setpoint | 2 Bytes | 9.1 temperature (°C) | CW |
| 79 | Temperature controller | (Basic) Comfort setpoint | 2 Bytes | 9.1 temperature (°C) | CW |
| 79 | Temperature controller | Combined object (Heating): Preset setpoint | 8 Bytes | 275.100 Temperature setpoint setting for 4 HVAC Modes | CW |
| 80 | Temperature controller | Preset Standby setpoint | 2 Bytes | 9.1 temperature (°C) | CW |
| 81 | Temperature controller | Preset Night setpoint | 2 Bytes | 9.1 temperature (°C) | CW |
| 82 | Temperature controller | Preset Frost protection setpoint | 2 Bytes | 9.1 temperature (°C) | CW |
| 82 | Temperature controller | Preset Heat protection setpoint | 2 Bytes | 9.1 temperature (°C) | CW |
| 83 | Temperature controller | Combined object (Cooling): Preset setpoint | 8 Bytes | 275.100 Temperature setpoint setting for 4 HVAC Modes | CW |
| 84 | Temperature controller | Send current setpoint | 2 Bytes | 9.1 temperature (°C) | CRT |
| 85 | Temperature controller | Manual setpoint shift (2 Byte) | 2 Bytes | 9.2 temperature difference (K) | CW |
| 86 | Temperature controller | Manual setpoint shift (1=+ / 0=-) | 1 Bit | 1.7 step | CW |
| 86 | Temperature controller | Manual setpoint shift (1 Byte) | 1 Byte | 6.10 counter pulses (-128..127) | CW |
| 87 | Temperature controller | Send status setpoint shift | 2 Bytes | 9.2 temperature difference (K) | CRT |
| 88 | Temperature controller | Control value Heating: Send control value | 1 Byte | 5.1 percentage (0..100%) | CRT |
| 88 | Temperature controller | Control value Heating: Send control value | 1 Bit | 1.1 switch | CRT |
| 88 | Temperature controller | Control value Heating/Cooling: Send control value | 1 Bit | 1.1 switch | CRT |
| 89 | Temperature controller | Control value Cooling: Send control value | 1 Byte | 5.1 percentage (0..100%) | CRT |
| 89 | Temperature controller | Control value Cooling: Send control value | 1 Bit | 1.1 switch | CRT |
| 90 | Temperature controller | Control value Heating: Send status | 1 Byte | 5.1 percentage (0..100%) | CRT |
| 90 | Temperature controller | Control value Heating/Cooling: Send status | 1 Byte | 5.1 percentage (0..100%) | CRT |
| 91 | Temperature controller | Control value Cooling: Send status | 1 Byte | 5.1 percentage (0..100%) | CRT |
| 92 | Temperature controller | Additional level: Send control value Heating | 1 Bit | 1.1 switch | CT |
| 93 | Temperature controller | Mode selection | 1 Byte | 20.102 HVAC mode | CW |
| 94 | Temperature controller | Comfort operating mode: Comfort extension | 1 Bit | 1.10 start/stop | CW |
| 95 | Temperature controller | Comfort mode | 1 Bit | 1.1 switch | CW |
| 96 | Temperature controller | Night mode | 1 Bit | 1.1 switch | CW |
| 97 | Temperature controller | Frost protection mode | 1 Bit | 1.1 switch | CW |
| 97 | Temperature controller | Heat protection mode | 1 Bit | 1.1 switch | CW |
| 97 | Temperature controller | Frost/Heat protection mode | 1 Bit | 1.1 switch | CW |
| 98 | Temperature controller | DPT_HVAC Status: Send controller status | 1 Byte | CRT | |
| 98 | Temperature controller | DPT_HVAC Mode: Send controller status | 1 Byte | 20.102 HVAC mode | CRT |
| 99 | Temperature controller | DPT_HVAC Status: Send controller status | 1 Byte | CRT | |
| 99 | Temperature controller | DPT_HVAC Mode: Send controller status | 1 Byte | 20.102 HVAC mode | CRT |
| 99 | Temperature controller | RHCC Status: Send controller status | 2 Bytes | 22.101 RHCC status | CRT |
| 99 | Temperature controller | DPT_RTC combined status: Send controller status | 2 Bytes | 22.103 combined status RTC | CRT |
| 99 | Temperature controller | DPT_RTSM combined status: Send controller status | 1 Byte | 21.107 combined status RTSM | CRT |
| 100 | Temperature controller | Send Frost alarm | 1 Bit | 1.5 alarm | CRT |
| 101 | Temperature controller | Send Heat alarm | 1 Bit | 1.5 alarm | CRT |
| 102 | Temperature controller | Receive flow temperature Heating | 2 Bytes | 9.1 temperature (°C) | CWT |
| 103 | Temperature controller | Receive surface temperature Cooling | 2 Bytes | 9.1 temperature (°C) | CWT |
| 103 | Temperature controller | Receive dew point alarm | 1 Bit | 1.5 alarm | CWT |
| 104 | Temperature controller | Diagnosis status | 14 Bytes | 16.1 Character String (ISO 8859-1) | CRT |
| 105 | Temperature controller | Window contact: 0 = closed / 1 = open | 1 Bit | 1.19 window/door | CWTU |
| 105 | Temperature controller | Window contact: 1=closed / 0=open | 1 Bit | 1.1 switch | CWTU |
| 106 | Temperature controller | Lock object Heating: Lock control value | 1 Bit | 1.3 enable | CRWTU |
| 107 | Temperature controller | Lock object Cooling: Lock control value | 1 Bit | 1.3 enable | CRWTU |
| 110 | Temperature controller | Switchover: 1=Heating 0=Cooling | 1 Bit | 1.100 cooling/heating | CW |
| 111 | Temperature controller | Status: 1=Heating 0=Cooling | 1 Bit | 1.100 cooling/heating | CRT |
| 112 | Temperature controller | Send Heating request | 1 Bit | 1.1 switch | CRT |
| 113 | Temperature controller | Send Cooling request | 1 Bit | 1.1 switch | CRT |
| 114 | Outdoor temperature | Receive measured value/reference value | 2 Bytes | 9.1 temperature (°C) | CW |
| 117 | Light channel 1 - Output 1 | Switch | 1 Bit | 1.1 switch | CRT |
| 117 | Light channel 1 - Output 1 (Day) | Switch | 1 Bit | 1.1 switch | CRT |
| 117 | Light channel 1 - Output 1 | Dimming absolute | 1 Byte | 5.1 percentage (0..100%) | CRT |
| 117 | Light channel 1 - Output 1 | Scene | 1 Byte | 17.1 scene number | CRT |
| 118 | Light channel 1 - Output (Night) | Switch | 1 Bit | 1.1 switch | CRT |
| 119 | Light channel 1 - Output 2 (additional) | Switch | 1 Bit | 1.1 switch | CRT |
| 120 | Light channel 1 - Input | External button short | 1 Bit | 1.1 switch | CW |
| 121 | Light channel 1 - Input | External button long | 1 Bit | 1.1 switch | CW |
| 122 | Light channel 1 - Input | External motion (Slave) | 1 Bit | 1.1 switch | CW |
| 123 | Light channel 1 - Input | Status of actuator channel | 1 Bit | 1.1 switch | CW |
| 124 | Light channel 1 - Input | Lock motion detection | 1 Bit | 1.3 enable | CW |
| 125 | Light channel 1 - Input | Forced guidance | 2 Bit | 2.1 switch control | CW |
| 125 | Light channel 1 - Input | lock object | 1 Bit | 1.3 enable | CW |
| 126 | Light channel 1 - Input | Lock object ON | 1 Bit | 1.3 enable | CW |
| 127 | Light channel 1 - Status | Automatic mode | 1 Bit | 1.11 state | CRT |
| 127 | Light channel 1 - Status | Lock/Manual mode | 1 Bit | 1.11 state | CRT |
| 128 | Light channel 1 - Input | Switch dark | 1 Bit | 1.1 switch | CW |
| 129 | Light channel 1 - Input | Teach-in dimming value for ON | 1 Byte | 5.1 percentage (0..100%) | CWTU |
| 130 | Light channel 1 - Input | Follow-up time 10 - 65000s | 2 Bytes | 7.5 time (s) | CWTU |
| 132 | Light channel 2 - Output 1 | Switch | 1 Bit | 1.1 switch | CRT |
| 132 | Light channel 2 - Output 1 (Day) | Switch | 1 Bit | 1.1 switch | CRT |
| 132 | Light channel 2 - Output 1 | Dimming absolute | 1 Byte | 5.1 percentage (0..100%) | CRT |
| 132 | Light channel 2 - Output 1 | Scene | 1 Byte | 17.1 scene number | CRT |
| 133 | Light channel 2 - Output (Night) | Switch | 1 Bit | 1.1 switch | CRT |
| 134 | Light channel 2 - Output 2 (additional) | Switch | 1 Bit | 1.1 switch | CRT |
| 135 | Light channel 2 - Input | External button short | 1 Bit | 1.1 switch | CW |
| 136 | Light channel 2 - Input | External button long | 1 Bit | 1.1 switch | CW |
| 137 | Light channel 2 - Input | External motion (Slave) | 1 Bit | 1.1 switch | CW |
| 138 | Light channel 2 - Input | Status of actuator channel | 1 Bit | 1.1 switch | CW |
| 139 | Light channel 2 - Input | Lock motion detection | 1 Bit | 1.3 enable | CW |
| 140 | Light channel 2 - Input | Forced guidance | 2 Bit | 2.1 switch control | CW |
| 140 | Light channel 2 - Input | lock object | 1 Bit | 1.3 enable | CW |
| 141 | Light channel 2 - Input | Lock object ON | 1 Bit | 1.3 enable | CW |
| 142 | Light channel 2 - Status | Automatic mode | 1 Bit | 1.11 state | CRT |
| 142 | Light channel 2 - Status | Lock/Manual mode | 1 Bit | 1.11 state | CRT |
| 143 | Light channel 2 - Input | Switch dark | 1 Bit | 1.1 switch | CW |
| 144 | Light channel 2 - Input | Teach-in dimming value for ON | 1 Byte | 5.1 percentage (0..100%) | CWTU |
| 145 | Light channel 2 - Input | Follow-up time 10 - 65000s | 2 Bytes | 7.5 time (s) | CWTU |
| 147 | Light channel 3 - Output 1 | Switch | 1 Bit | 1.1 switch | CRT |
| 147 | Light channel 3 - Output 1 (Day) | Switch | 1 Bit | 1.1 switch | CRT |
| 147 | Light channel 3 - Output 1 | Dimming absolute | 1 Byte | 5.1 percentage (0..100%) | CRT |
| 147 | Light channel 3 - Output 1 | Scene | 1 Byte | 17.1 scene number | CRT |
| 148 | Light channel 3 - Output (Night) | Switch | 1 Bit | 1.1 switch | CRT |
| 149 | Light channel 3 - Output 2 (additional) | Switch | 1 Bit | 1.1 switch | CRT |
| 150 | Light channel 3 - Input | External button short | 1 Bit | 1.1 switch | CW |
| 151 | Light channel 3 - Input | External button long | 1 Bit | 1.1 switch | CW |
| 152 | Light channel 3 - Input | External motion (Slave) | 1 Bit | 1.1 switch | CW |
| 153 | Light channel 3 - Input | Status of actuator channel | 1 Bit | 1.1 switch | CW |
| 154 | Light channel 3 - Input | Lock motion detection | 1 Bit | 1.3 enable | CW |
| 155 | Light channel 3 - Input | Forced guidance | 2 Bit | 2.1 switch control | CW |
| 155 | Light channel 3 - Input | lock object | 1 Bit | 1.3 enable | CW |
| 156 | Light channel 3 - Input | Lock object ON | 1 Bit | 1.3 enable | CW |
| 157 | Light channel 3 - Status | Automatic mode | 1 Bit | 1.11 state | CRT |
| 157 | Light channel 3 - Status | Lock/Manual mode | 1 Bit | 1.11 state | CRT |
| 158 | Light channel 3 - Input | Switch dark | 1 Bit | 1.1 switch | CW |
| 159 | Light channel 3 - Input | Teach-in dimming value for ON | 1 Byte | 5.1 percentage (0..100%) | CWTU |
| 160 | Light channel 3 - Input | Follow-up time 10 - 65000s | 2 Bytes | 7.5 time (s) | CWTU |
| 177 | HVAC - Output | Switch | 1 Bit | 1.1 switch | CRT |
| 177 | HVAC - Output | Dimming absolute | 1 Byte | 5.1 percentage (0..100%) | CRT |
| 177 | HVAC - Output | Scene | 1 Byte | 17.1 scene number | CRT |
| 180 | HVAC - Input | External button short | 1 Bit | 1.1 switch | CW |
| 181 | HVAC - Input | External button long | 1 Bit | 1.1 switch | CW |
| 182 | HVAC - Input | External motion | 1 Bit | 1.1 switch | CW |
| 183 | HVAC - Input | Status of actuator channel | 1 Bit | 1.1 switch | CW |
| 184 | HVAC - Input | Lock motion detection | 1 Bit | 1.3 enable | CW |
| 185 | HVAC - Input | Forced guidance | 2 Bit | 2.1 switch control | CW |
| 185 | HVAC - Input | lock object | 1 Bit | 1.3 enable | CW |
| 186 | HVAC - Input | Lock object ON | 1 Bit | 1.3 enable | CW |
| 187 | HVAC - Status | Automatic mode | 1 Bit | 1.11 state | CRT |
| 187 | HVAC - Status | Lock/Manual mode | 1 Bit | 1.11 state | CRT |
| 188 | HVAC - Input | Switch dark | 1 Bit | 1.1 switch | CW |
| 189 | HVAC - Input | Teach-in dimming value for ON | 1 Byte | 5.1 percentage (0..100%) | CWTU |
| 190 | HVAC - Input | Follow-up time 10 - 65000s | 2 Bytes | 7.5 time (s) | CWTU |
| 192 | Alarm - Output | Switch | 1 Bit | 1.1 switch | CRT |
| 192 | Alarm - Output (Day) | Switch | 1 Bit | 1.1 switch | CRT |
| 193 | Alarm - Output (Night) | Switch | 1 Bit | 1.1 switch | CRT |
| 200 | Alarm - Input | Lock | 1 Bit | 1.3 enable | CW |
| 200 | Alarm - Input | Release | 1 Bit | 1.3 enable | CW |
| 207 | LED green | Switch | 1 Bit | 1.1 switch | CW |
| 207 | LED green | Flashing | 1 Bit | 1.1 switch | CW |
| 208 | LED red | Flashing | 1 Bit | 1.1 switch | CW |
| 209 | LED white | Switch | 1 Bit | 1.1 switch | CW |
| 209 | LED white | Value | 1 Byte | 5.1 percentage (0..100%) | CW |
| 210 | RGB traffic light | Input level 1 | 1 Bit | 1.1 switch | CW |
| 210 | RGB traffic light | Input | 1 Byte | 5.5 ratio (0..255) | CW |
| 210 | RGB traffic light | Input | 3 Bytes | 232.600 RGB value 3x(0..255) | CW |
| 210 | RGB traffic light | Input | 3 Bytes | CW | |
| 211 | RGB traffic light | Input level 2 | 1 Bit | 1.1 switch | CW |
| 212 | RGB traffic light | Input level 3 | 1 Bit | 1.1 switch | CW |
| 213 | RGB traffic light | Input level 4 | 1 Bit | 1.1 switch | CW |
| 214 | RGB traffic light | Brightness (1 = bright / 0 = dark) | 1 Bit | 1.6 binary value | CW |
| 215 | PIR Scenes | Input | 1 Byte | 17.1 scene number | CW |
| 216 | Brightness | Threshold switch | 1 Bit | 1.1 switch | CRT |
| 217 | Brightness | Measured value | 2 Bytes | 9.4 lux (Lux) | CRT |
| 218 | Brightness | Set switch-on threshold for light channels | 2 Bytes | 9.4 lux (Lux) | CW |
| 219 | Input Teach-in | Start calibration | 1 Bit | 1.10 start/stop | CW |
| 220 | Input Teach-in | Status absolute dimming value | 1 Byte | 5.1 percentage (0..100%) | CW |
| 226 | Logic 1 {{0}} | Input C | 1 Bit | 1.2 boolean | CWTU |
| 227 | Logic 1 {{0}} | Input D | 1 Bit | 1.2 boolean | CWTU |
| 228 | Logic 1 {{0}} | Input E | 1 Bit | 1.2 boolean | CWTU |
| 229 | Logic 1 {{0}} | Input F | 1 Bit | 1.2 boolean | CWTU |
| 230 | Logic 1 {{0}} | Output 1 | 1 Bit | 1.2 boolean | CRT |
| 230 | Logic 1 {{0}} | Output 1 | 1 Byte | 17.1 scene number | CRT |
| 230 | Logic 1 {{0}} | Output 1 | 1 Byte | 5.5 ratio (0..255) | CRT |
| 230 | Logic 1 {{0}} | Output 1 | 1 Byte | 5.1 percentage (0..100%) | CRT |
| 230 | Logic 1 {{0}} | Output 1 | 2 Bit | 2.1 switch control | CRT |
| 231 | Logic 2 {{0}} | Input C | 1 Bit | 1.2 boolean | CWTU |
| 232 | Logic 2 {{0}} | Input D | 1 Bit | 1.2 boolean | CWTU |
| 233 | Logic 2 {{0}} | Input E | 1 Bit | 1.2 boolean | CWTU |
| 234 | Logic 2 {{0}} | Input F | 1 Bit | 1.2 boolean | CWTU |
| 235 | Logic 2 {{0}} | Output 2 | 1 Bit | 1.2 boolean | CRT |
| 235 | Logic 2 {{0}} | Output 2 | 1 Byte | 17.1 scene number | CRT |
| 235 | Logic 2 {{0}} | Output 2 | 1 Byte | 5.5 ratio (0..255) | CRT |
| 235 | Logic 2 {{0}} | Output 2 | 1 Byte | 5.1 percentage (0..100%) | CRT |
| 235 | Logic 2 {{0}} | Output 2 | 2 Bit | 2.1 switch control | CRT |
| 236 | Logic 3 {{0}} | Input C | 1 Bit | 1.2 boolean | CWTU |
| 237 | Logic 3 {{0}} | Input D | 1 Bit | 1.2 boolean | CWTU |
| 238 | Logic 3 {{0}} | Input E | 1 Bit | 1.2 boolean | CWTU |
| 239 | Logic 3 {{0}} | Input F | 1 Bit | 1.2 boolean | CWTU |
| 240 | Logic 3 {{0}} | Output 3 | 1 Bit | 1.2 boolean | CRT |
| 240 | Logic 3 {{0}} | Output 3 | 1 Byte | 17.1 scene number | CRT |
| 240 | Logic 3 {{0}} | Output 3 | 1 Byte | 5.5 ratio (0..255) | CRT |
| 240 | Logic 3 {{0}} | Output 3 | 1 Byte | 5.1 percentage (0..100%) | CRT |
| 240 | Logic 3 {{0}} | Output 3 | 2 Bit | 2.1 switch control | CRT |
| 241 | Logic 4 {{0}} | Input C | 1 Bit | 1.2 boolean | CWTU |
| 242 | Logic 4 {{0}} | Input D | 1 Bit | 1.2 boolean | CWTU |
| 243 | Logic 4 {{0}} | Input E | 1 Bit | 1.2 boolean | CWTU |
| 244 | Logic 4 {{0}} | Input F | 1 Bit | 1.2 boolean | CWTU |
| 245 | Logic 4 {{0}} | Output 4 | 1 Bit | 1.2 boolean | CRT |
| 245 | Logic 4 {{0}} | Output 4 | 1 Byte | 17.1 scene number | CRT |
| 245 | Logic 4 {{0}} | Output 4 | 1 Byte | 5.5 ratio (0..255) | CRT |
| 245 | Logic 4 {{0}} | Output 4 | 1 Byte | 5.1 percentage (0..100%) | CRT |
| 245 | Logic 4 {{0}} | Output 4 | 2 Bit | 2.1 switch control | CRT |
| 246 | Constant light | Switch | 1 Bit | 1.1 switch | CW |
| 247 | Constant light | Dimming relative | 4 Bit | 3.7 dimming control | CW |
| 248 | Constant light | Dimming absolute | 1 Byte | 5.1 percentage (0..100%) | CW |
| 250 | Constant light | Lock | 1 Bit | 1.3 enable | CW |
| 251 | Constant light | Scenes | 1 Byte | 17.1 scene number | CW |
| 251 | Constant light | Scene control | 1 Byte | 18.1 scene control | CW |
| 252 | Constant light | Dimming absolute - middle | 1 Byte | 5.1 percentage (0..100%) | CRT |
| 253 | Constant light | Dimming absolute - wall | 1 Byte | 5.1 percentage (0..100%) | CRT |
| 254 | Constant light | Dimming absolute - window | 1 Byte | 5.1 percentage (0..100%) | CRT |
| 255 | Constant light | Status | 1 Bit | 1.11 state | CRT |
| 256 | In operation | Output | 1 Bit | 1.11 state | CRT |
| 257 | Day/Night - Presence detector | Day = 1 / Night = 0 | 1 Bit | 1.24 day/night | CWTU |
| 257 | Day/Night - Presence detector | Night = 1 / Day = 0 | 1 Bit | 1.1 switch | CWTU |
| 258 | Day/Night - Air quality controller | Day = 1 / Night = 0 | 1 Bit | 1.24 day/night | CWTU |
| 258 | Day/Night - Air quality controller | Night = 1 / Day = 0 | 1 Bit | 1.1 switch | CWTU |
Parameters (526)
| Parameter | Type | Default |
|---|---|---|
| Startup time | unsignedInt 2…240 | 2 |
| Send "In operation" cyclically | list | not active |
| Day/Night switchover | list | active |
| Value for Day/Night | list | Day = 1 / Night = 0 |
| Day/Night object after bus power return | list | request |
| Language diagnosis text | list | German |
| Toggle Day/Night | list | at next presence |
| Trigger sensitivity | list | 6 |
| Trigger sensitivity "Day" | list | 6 |
| Trigger sensitivity "Night" | list | 3 (low) |
| Presence sensitivity | list | 8 (high) |
| Reduce sensitivity for sensors | list | not active |
| Trigger sensitivity | list | 2 |
| Trigger sensitivity "Day" | list | 2 |
| Trigger sensitivity "Night" | list | 1 (very low) |
| Switch-on threshold | unsignedInt 5…1000 | 400 |
| Switch-on threshold "Day" | unsignedInt 5…1000 | 400 |
| Switch-on threshold "Night" | unsignedInt 5…1000 | 400 |
| Switch-off on exceedance | list | not active |
| Switches OFF on exceedance of | unsignedInt 75…1000 | 800 |
| Fallback of forced guidance/lock | list | not active |
| Follow-up time for forced guidance/lock | list | 3 min |
| Follow-up time for forced guidance/lock "Day" | list | 3 min |
| Follow-up time for forced guidance/lock "Night" | list | 3 min |
| Fallback time for forced guidance/lock | list | 3 min |
| Fallback time for forced guidance/lock "Day" | list | 3 min |
| Fallback time for forced guidance/lock "Night" | list | 3 min |
| Fallback: External button long (Manual => Auto) | list | after presence and follow-up time |
| Manual mode follow-up time for ON | list | 3 min |
| Manual mode, follow-up time at OFF | list | 3 min |
| Manual mode, follow-up time at ON "Day" | list | 3 min |
| Manual mode, follow-up time at OFF "Day" | list | 3 min |
| Manual mode, follow-up time at ON "Night" | list | 3 min |
| Manual mode, follow-up time at OFF "Night" | list | 3 min |
| Fallback time "manual mode" for ON | list | 3 min |
| Fallback time "manual mode" for OFF | list | 3 min |
| Fallback time "manual mode" for ON "Day" | list | 3 min |
| Fallback time "manual mode" for OFF "Day" | list | 3 min |
| Fallback time "manual mode" for ON "Night" | list | 3 min |
| Fallback time "manual mode" for OFF "Night" | list | 3 min |
| CO2 measurement | list | active |
| VOC measurement | list | active |
| Temperature measurement | list | active |
| Relative humidity measurement | list | active |
| Send measured value on change | list | not active |
| Send measured value on change of | float 10…500 | 20 |
| Send measured value cyclically | list | not active |
| Messages | list | not active |
| Upper message value | float 400…2000 | 1500 |
| Lower message value | float 400…2000 | 500 |
| Calibration value for internal sensor | float -500…500 | 0 |
| Sensor internal/external | list | 100 % internal |
| Measured value output in | list | ppm |
| IAQ Index description | picture | |
| Send measured value on change of | unsignedInt 1…50 | 5 |
| Upper message value | float 100…5000 | 2000 |
| Lower message value | float 100…5000 | 1000 |
| Upper message value | unsignedInt 0…500 | 200 |
| Lower message value | unsignedInt 0…500 | 50 |
| Send measured value on change of | float 0.1…2 | 0.1 |
| Upper message value | float 20…45 | 28 |
| Lower message value | float 3…30 | 18 |
| Calibration value for internal sensor | float -10…10 | 0 |
| Send measured value on change of | float 1…10 | 1 |
| Upper message value | float 25…100 | 70 |
| Lower message value | float 0…75 | 30 |
| Calibration value for internal sensor | float -20…20 | 0 |
| Send measured value on change of | list | 5 % |
| Upper message value | list | 50 % |
| Lower message value | list | 10 % |
| Air quality traffic light | list | not active |
| Activate as | list | Step output |
| Sensor for Air quality traffic light | list | CO2 |
| Hysteresis in | list | percent |
| Hysteresis | list | 5 % |
| Hysteresis | unsignedInt 10…500 | 100 |
| Hysteresis | unsignedInt 0…50 | 5 |
| Traffic light with | list | 3 levels |
| Scene number for level 1 | list | 1 |
| Scene number for level 2 | list | 2 |
| Scene number for level 3 | list | 4 |
| Scene number for level 3 | list | 3 |
| Scene number for level 4 | list | 4 |
| Colour value for level 1 | color | #00FF00 |
| Colour value for level 2 | color | #FFFF00 |
| Colour value for level 3 | color | #FF0000 |
| Colour value for level 3 | color | #FF8000 |
| Colour value for level 4 | color | #FF0000 |
| Threshold value 1 (level 1 -> level 2) | unsignedInt 0…2000 | 800 |
| Threshold value 2 (level 2 -> level 3) | unsignedInt 0…2000 | 1200 |
| Threshold value 1 (level 1 -> level 2) | unsignedInt 0…500 | 100 |
| Threshold value 2 (level 2 -> level 3) | unsignedInt 0…500 | 250 |
| Threshold value 3 (level 3 -> level 4) | unsignedInt 0…2000 | 1700 |
| Threshold value 3 (level 3 -> level 4) | unsignedInt 0…500 | 400 |
| Sending condition of output | list | not active |
| Send cyclically every… | list | 60 min |
| Air quality control | list | not active |
| Activate as | list | Step controller Bit coded |
| Controller: Actual value | list | CO2 |
| Number of external room sensors | list | not active |
| Air quality control with humidity increase by… | list | not active |
| Threshold for exceeding the air humidity | list | 75 % |
| Follow-up time after falling below | unsignedInt 1…60 | 30 |
| Minimum level | list | Level 0 |
| Maximum level | list | Level 4 |
| Minimum level for "Day" | list | Level 0 |
| Maximum level for "Day" | list | Level 4 |
| Minimum level for "Night" | list | Level 0 |
| Maximum level for "Night" | list | Level 2 |
| Threshold level 1 | unsignedInt 400…2000 | 600 |
| Threshold level 2 | unsignedInt 400…2000 | 800 |
| Threshold level 3 | unsignedInt 400…2000 | 1000 |
| Threshold level 4 | unsignedInt 400…2000 | 1200 |
| Hysteresis | list | 10 % |
| Hysteresis | unsignedInt 10…500 | 50 |
| Threshold level 1 | unsignedInt 50…500 | 80 |
| Threshold level 2 | unsignedInt 50…500 | 160 |
| Threshold level 3 | unsignedInt 50…500 | 240 |
| Threshold level 4 | unsignedInt 50…500 | 320 |
| Hysteresis in | list | IAQ |
| Behaviour on lock | list | not active |
| Level at lock | list | Level 1 |
| Control value (level 1) | list | 25 % |
| Control value (level 2) | list | 50 % |
| Control value (level 3) | list | 75 % |
| Control value (level 4) | list | 100 % |
| Control value for "Day" (level 1) | list | 25 % |
| Control value for "Day" (level 2) | list | 50 % |
| Control value for "Day" (level 3) | list | 75 % |
| Control value for "Day" (level 4) | list | 100 % |
| Control value for "Night" (level 1) | list | 10 % |
| Control value for "Night" (level 2) | list | 30 % |
| Control value for "Night" (level 3) | list | 50 % |
| Control value for "Night" (level 4) | list | 70 % |
| Value at lock | list | 0 % |
| Setpoint | unsignedInt 400…2000 | 600 |
| Setpoint | unsignedInt 0…500 | 80 |
| Minimum control value | list | 0 % |
| Maximum control value | list | 100 % |
| Setpoint valid | list | for "Day" ("Night" not active) |
| Reset the value set via object "Preset setpoint" to parameter setting at the next Day/Night switchover | list | active |
| Setpoint for "Day" | unsignedInt 400…2000 | 600 |
| Setpoint for "Day" | unsignedInt 0…500 | 80 |
| Minimum control value for "Day" | list | 0 % |
| Maximum control value for "Day" | list | 100 % |
| Setpoint for "Night" | unsignedInt 400…2000 | 700 |
| Setpoint for "Night" | unsignedInt 0…500 | 100 |
| Minimum control value for "Night" | list | 0 % |
| Maximum control value for "Night" | list | 30 % |
| Proportional value | unsignedInt 100…2000 | 1000 |
| Proportional value | unsignedInt 10…250 | 100 |
| Reset time | list | 15 min |
| Send setpoint/output cyclically | list | not active |
| Operating mode | list | not active |
| Priority | list | Frost(Heat protection)/Comfort/Night/Standby |
| Setpoints for Standby/Night | list | depending on setpoint Comfort (Basic) |
| Setpoint Comfort (Basic) | float 7…35 | 21 |
| Setpoint Standby | float 7…35 | 19 |
| Setpoint Night | float 7…35 | 18 |
| Standby reduction | list | 2,0 K |
| Night reduction | list | 3,0 K |
| Setpoint Frost protection | float 3…12 | 7 |
| Separate objects for setpoints Comfort/Standby/Night/Frost protection | list | not active |
| Maximum setpoint shift | float 0…10 | 3 |
| Setpoint shift via 1Bit/1Byte object | list | 1 Bit |
| Step width | list | 0,5 K |
| Status setpoint shift | list | not active |
| Setpoint shift applies to | list | Comfort |
| Action if shift during Night/Standby | list | no action |
| Delete setpoint shift after change of operating mode | list | not active |
| Delete setpoint shift after new absolute setpoint | list | active |
| Reset setpoints to the parameter setting after change of operating mode | list | active |
| Reset basic setpoint to configured value after change of operation mode | list | active |
| Delete setpoint shift after new basic setpoint | list | active |
| Send setpoint changes | list | active |
| Send current setpoint cyclically | list | not active |
| Comfort extention with time | list | not active |
| Comfort extention time | list | not active |
| Operating mode after reset | list | Comfort with configured setpoint |
| Operating mode after reprogramming | list | Comfort |
| HVAC status object | list | HVAC Mode (DPT 20.102) |
| Additional HVAC Status object | list | not active |
| Send HVAC Status object cyclically | list | not active |
| Lock object: Control value Heating | list | not active |
| Object for Heating request | list | not active |
| Flow temperature | list | not active |
| Limit flow temperature to | unsignedInt 10…60 | 40 |
| Setpoint Comfort (Basic) | float 7…35 | 23 |
| Setpoint Standby | float 7…35 | 24 |
| Setpoint Night | float 7…35 | 25 |
| Standby increase | list | 2,0 K |
| Night increase | list | 3,0 K |
| Setpoint Heat protection | float 24…40 | 35 |
| Separate objects for setpoints Comfort/Standby/Night/Heat protection | list | not active |
| Lock object: Control value Cooling | list | not active |
| Object for Cooling request | list | not active |
| Reference control via outdoor temperature | list | not active |
| Reference variable minimum | unsignedInt 10…60 | 28 |
| Reference variable maximum | unsignedInt 10…60 | 38 |
| Setpoint change at maximum reference variable | float 1…10 | 10 |
| Offset to dew point temperature | list | 0 K |
| (Basic) Comfort setpoint | float 7…35 | 21 |
| Switchover Heating/Cooling | list | automatically |
| Dead zone between Heating and Cooling | list | 2,0 K |
| Dead zone between Heating and Cooling | list | 0 K |
| Separate objects for setpoints Comfort/Standby/Night/Frost-/Heat protection | list | not active |
| Operating mode after reprogramming | list | Comfort (Cooling) |
| Alarms | list | not active |
| Frost alarm if value less | unsignedInt 3…10 | 7 |
| Heat alarm if value greater | unsignedInt 25…40 | 35 |
| Window contact | list | not active |
| State of window | list | 0=closed / 1=open (standard DPT) |
| Delay time | unsignedInt 0…240 | 5 |
| Action when opening the window | list | force Frost/Heat protection |
| Action when closing the window | list | HVAC Modus before locking |
| Release time | list | 12 h |
| Control value | list | PI control continuous |
| Direction of controller | list | normal |
| Maximum value of control value | list | 100% |
| Heating system | list | Underfloor Heating (4K / 150min) |
| Proportional range | list | 4 K |
| Reset time | list | 150 min |
| PWM cycle | list | 10 min |
| Switching hysteresis | list | 2,0 K |
| Send control value cyclically | list | 5 min |
| Additional level | list | not active |
| Direction of action with rising temperature | list | normal |
| Control value | list | 2-step control (switching) |
| Distance | list | 2,0 K |
| Operating mode | list | PI control continuous |
| Cooling system | list | Cooling ceiling (4K / 150min) |
| System | list | 2 pipe / 1 circuit (Heating or Cooling) |
| Light channel 1 | list | active |
| Light channel 2 | list | not active |
| Light channel 3 | list | not active |
| LED white | list | not active |
| Brightness at "Night" | list | 10 % |
| Light channels influence the brightness measurement | list | yes (several lights in the room) |
| Send brightness on change of | list | 10 % |
| Correction value | list | 0 % |
| Room reflection factor | list | 0,4 medium |
| Threshold switch | list | not active |
| Threshold switch switches at | unsignedInt 5…1000 | 300 |
| Hysteresis of threshold switch | unsignedInt 5…200 | 30 |
| Object value when exceeded | list | ON |
| Object value at "Day" and exceedance | list | ON |
| Object value at "Night" and exceedance | list | ON |
| Object value when falling below | list | OFF |
| Send | list | ON and OFF |
| Send at "Day" | list | ON and OFF |
| Send at "Night" | list | ON and OFF |
| Brightness value for teach-in | unsignedInt 200…1000 | 450 |
| Teach-in value when loading application | list | use default value |
| Active sensors | list | 123 |
| Sensitivity | list | basic setting (General setting) |
| Trigger sensitivity | list | 3 (low) |
| Trigger sensitivity "Day" | list | 3 (low) |
| Brightness | list | basic setting or object "Switch dark" is active |
| Channel operating mode | list | fully automatic |
| Motion filter in standby | list | not active, no filtering |
| Reduction of follow-up time | list | not active |
| Maximum duration for short time presence | list | 20 s |
| Follow-up time for short time presence | list | 30 s |
| Follow-up time | list | 3 min |
| Follow-up time "Day" | list | 3 min |
| Follow-up time "Night" | list | 30 s |
| Forced guidance or lock object | list | forced guidance object (2 Bit) |
| Action on locking | list | lock motion (lock current state) |
| Fallback of forced guidance/lock (General setting) | list | active |
| Object type for output - Light | list | Switch |
| Output objects for Day/Night | list | one common object |
| Dimming value for ON | list | 100 % |
| Dimming value for OFF | list | 0 % |
| Dimming value at "Day" for ON | list | 100 % |
| Dimming value at "Day" for OFF | list | 0 % |
| Dimming value at "Night" for ON | list | 30 % |
| Dimming value at "Night" for OFF | list | 0 % |
| Orientation light for leaving | list | switch-off immediately |
| Switch-off delay | list | 30 s |
| Switch-off dimming value | list | 30 % |
| Switch-off delay for "Day" | list | 30 s |
| Switch-off dimming value for "Day" | list | 30 % |
| Switch-off delay for "Night" | list | 30 s |
| Switch-off dimming value for "Night" | list | 20 % |
| Scene number for ON | list | 1 |
| Scene number for OFF | list | 2 |
| Scene number at "Day" for ON | list | 1 |
| Scene number at "Day" for OFF | list | 2 |
| Scene number at "Night" for ON | list | 3 |
| Scene number at "Night" for OFF | list | 4 |
| Output object 1 sends | list | ON and OFF |
| Output object 1 sends ON cyclically | list | not active |
| Output object 1 sends | list | dimming value for ON and OFF |
| Output object 1 sends value for ON cyclically | list | not active |
| Output object 1 sends | list | scene number for ON and OFF |
| Output object 1 sends scene for ON cyclically | list | not active |
| Output 2 (Additional switch object) | list | not active |
| External button short reacts to | list | ON and OFF |
| Idle time after external button short is OFF | unsignedInt 1…30 | 5 |
| External button long reacts to | list | ON and OFF |
| Idle time after switch off | unsignedInt 0…60 | 1 |
| If Night light is active | list | switch to Day light |
| If output "Day" is already ON | list | switch to manual mode |
| If output is already ON | list | switch to manual mode |
| Status information | list | not active |
| HVAC Channel | list | not active |
| Number of monitoring time slots | list | 3 |
| Length of monitoring time slot | unsignedInt 0…30000 | 30 |
| Object type for output - HVAC | list | Switch |
| Object value for ON | list | value 1 |
| Object value for OFF | list | value 0 |
| Object value at "Day" for ON | list | value 1 |
| Object value at "Day" for OFF | list | value 0 |
| Object value at "Night" for ON | list | value 1 |
| Object value at "Night" for OFF | list | value 0 |
| Output object 1 sends cyclically | list | not active |
| Output object 1 sends value cyclically | list | not active |
| Output object 1 sends scene cyclically | list | not active |
| Alarm/Message channel | list | not active |
| Trigger sensitivity "Night" | list | 2 |
| Presence sensitivity | list | 6 |
| Interference / motion filter | list | not active, no filtering |
| Length of monitoring time slot | list | 2 s |
| Number of monitoring time slot | list | 3 |
| Lock or release object | list | lock object |
| Fallback of forced guidance/lock (General setting) | list | not active |
| Output object sends at | list | ON and OFF |
| Output object sends cyclic | list | not active |
| Scene A number | list | not active |
| Scene A Light channel 1 | list | not active |
| Scene A Light channel 2 | list | not active |
| Scene A Light channel 3 | list | not active |
| Scene B number | list | not active |
| Scene B Light channel 1 | list | not active |
| Scene B Light channel 2 | list | not active |
| Scene B Light channel 3 | list | not active |
| Scene C number | list | not active |
| Scene C Light channel 1 | list | not active |
| Scene C Light channel 2 | list | not active |
| Scene C Light channel 3 | list | not active |
| Scene D number | list | not active |
| Scene D Light channel 1 | list | not active |
| Scene D Light channel 2 | list | not active |
| Scene D Light channel 3 | list | not active |
| Scene E number | list | not active |
| Scene E Light channel 1 | list | not active |
| Scene E Light channel 2 | list | not active |
| Scene E Light channel 3 | list | not active |
| Scene F number | list | not active |
| Scene F Light channel 1 | list | not active |
| Scene F Light channel 2 | list | not active |
| Scene F Light channel 3 | list | not active |
| Scene G number | list | not active |
| Scene G Light channel 1 | list | not active |
| Scene G Light channel 2 | list | not active |
| Scene G Light channel 3 | list | not active |
| Scene H number | list | not active |
| Scene H Light channel 1 | list | not active |
| Scene H Light channel 2 | list | not active |
| Scene H Light channel 3 | list | not active |
| Constant light control | list | not active |
| Control sunlight | list | little |
| Selection of lighting groups | list | 1 lighting group |
| Influence of proportional zone control - wall | list | medium (x0,7) |
| Influence of proportional zone control - window | list | medium (x1,6) |
| Switch constant light via | list | Presence (Light channel 1) |
| Time from switching on to start of control | list | 5 s |
| Controller switches the light off | list | not active |
| Minimum dimming value at dimming output | list | 0 % |
| Maximum dimming value at dimming output | list | 100 % |
| Switch-on value “Day” | list | calculate switch-on value (via lux value) |
| Dimming value at switch-on "Day" | list | 80 % |
| Preset setpoint at "Day" | list | 450 Lux |
| Constant light control at "Night" | list | active |
| Dimming value at switch-on “Night” | list | 20 % |
| Switch-on value “Night” | list | parameter (settable dimming value) |
| Preset setpoint at "Night" | list | 50 Lux |
| Brightness value at switch-on | list | use parameter value |
| CL status sends value 1 | list | when control active |
| Send dimming value cyclically | list | not active |
| Send dimming value on change of | list | 0,5 % |
| Behaviour of CL on relative dimming | list | use new dimming value |
| Time for relative dimming | list | 20 s |
| Standby/Orientation light | list | not active |
| Standby setpoint | list | 50 % |
| Standby time | list | 10 s |
| lock object | list | not active |
| Lock object value = 1 | list | ON (100%) |
| Value | list | 0 % |
| Lock object value = 0 | list | restore previous state |
| Scenes | list | not active |
| Behavior at setting of scene | list | sets only switch-on value |
| Scenes learning mode | list | active |
| Scene 1 | list | 260 Lux |
| Scene 2 | list | 300 Lux |
| Scene 3 | list | 360 Lux |
| Scene 4 | list | 400 Lux |
| Scene 5 | list | 450 Lux |
| Scene 6 | list | 500 Lux |
| Scene 7 | list | 550 Lux |
| Scene 8 | list | 600 Lux |
| Dead band | unsignedInt 1…50 | 1 |
| Cycle time | unsignedInt 1…32767 | 500 |
| Kp - mulltiplier | signedInt -32768…32767 | 20 |
| Kp - divider | signedInt -32768…32767 | 10 |
| Ki - mulltiplier | signedInt -32768…32767 | 1 |
| Ki - divider | signedInt -32768…32767 | 3500 |
| Kd - multiplier | signedInt -32768…32767 | 0 |
| Kp - mulltiplier | signedInt -32768…32767 | 10 |
| Ki - divider | signedInt -32768…32767 | 4500 |
| Cycle time [0,1s] | unsignedInt 1…32767 | 500 |
| ### Kd - multiplier | signedInt -32768…32767 | 0 |
| ### Ki - divider | signedInt -32768…32767 | 4500 |
| ### Ki - mulltiplier | signedInt -32768…32767 | 1 |
| ### Kp - divider | signedInt -32768…32767 | 10 |
| ### Kp - mulltiplier | signedInt -32768…32767 | 10 |
| ### Ki - divider | signedInt -32768…32767 | 3500 |
| ### Kp - mulltiplier | signedInt -32768…32767 | 20 |
| Logic function 1 | list | not active |
| Description of function | text | |
| Additional text | text | |
| Function | list | AND |
| Output object | list | Switch |
| Sending condition | list | on change of output |
| Output | list | normal |
| Scene number for output value "False" | list | 1 |
| Scene number for output value "True" | list | 1 |
| Datapoint type | list | 1 Byte DPT 5.005 Decimal (0…255) |
| Value for output value "False" | unsignedInt 0…255 | 0 |
| Value for output value "True" | unsignedInt 0…255 | 0 |
| Percent value for output value "False" | list | 0 % |
| Percent value for output value "True" | list | 0 % |
| Forced guidance for output value "False" | list | 00 - no priority, Off |
| Forced guidance for output value "True" | list | 00 - no priority, Off |
| Internal input A | list | not active |
| Object number | unsignedInt 0…255 | 0 |
| Internal input B | list | not active |
| External input C | list | not active |
| Preset logic input after reset with | list | value 0 |
| External input D | list | not active |
| External input E | list | not active |
| External input F | list | not active |
| Logic function 2 | list | not active |
| Logic function 3 | list | not active |
| Logic function 4 | list | not active |
| Request inputs after bus power return | list | not active |
| RGB LEDs react to | list | internal air quality traffic light |
| Control by | list | Traffic light level via 1 Bit objects |
| Brightness of levels | list | always set to "bright" |
| Level 1 | list | display permanently |
| State flashing at intervals of ... | unsignedInt 10…300 | 30 |
| Number of flashes | unsignedInt 1…5 | 1 |
| Value - bright | color | #00FF00 |
| Value - dark | color | #007F00 |
| Level 2 | list | display permanently |
| Value - bright | color | #7F7F00 |
| Value - dark | color | #3F3F00 |
| Value - bright | color | #B14D00 |
| Value - dark | color | #552600 |
| Value - bright | color | #FF0000 |
| Value - dark | color | #7F0000 |
| Level 3 | list | display permanently |
| Light channel 1 | unsignedInt 0…1 | 1 |
| Light channel 2 | unsignedInt 0…1 | 0 |
| Light channel 3 | unsignedInt 0…1 | 0 |
| RGB value | list | green - bright |
| RGB value | list | green - dark |
| Manual mode ON | list | not active |
| RGB value | list | blue - bright |
| RGB value | list | blue - dark |
| Manual mode OFF | list | not active |
| RGB value | list | red - bright |
| RGB value | list | red - dark |
| Lock/Forced guidance ON | list | not active |
| Lock/Forced guidance OFF | list | not active |
| LED brightness | list | always set to "bright" |
| Display behaviour | list | display permanently |
| RGB LEDs flashing at intervals of ... | unsignedInt 10…300 | 30 |
| Display behaviour LED "bright" | list | via fixed values |
| Display behaviour LED "dark" | list | via fixed values |
| RGB value | color | #007F00 |
| RGB value | color | #00FF00 |
| RGB value | color | #7F7F00 |
| RGB value | color | #3F3F00 |
| RGB value | color | #B14D00 |
| RGB value | color | #552600 |
| RGB value | color | #FF0000 |
| RGB value | color | #7F0000 |
| RGB value | color | #000019 |
| RGB value | color | #000005 |
| Logic function: Comparator 1 | list | not active |
| Datapoint type of the comparison | list | 1 Byte DPT 5.001 Percent (0...100%) |
| Output type | list | Minimum value |
| Input 1 | list | active |
| Input 2 | list | active |
| Input 3 | list | not active |
| Input 4 | list | not active |
| Input 5 | list | not active |
| Monitoring | list | not active |
| Send on change of | list | 1 % |
First 500 of 526 parameters shown. Download the .knxprod for the full list.
Version history
| Application | App no | Fingerprint | First seen | Size | File |
|---|---|---|---|---|---|
| Combi-Presence Detector 1.0 latest | $0078 | C9D1 | 2026-11-25 | 397 KB | Download |
About this file
This is the official ETS product database for the MDT technologies GmbH SCN-KP360K3.03 Combi-Presence Detector 360° with room climate sensors (SCN-KP360K3.03), published by the manufacturer in the KNX online catalog. To use it, open ETS, go to Catalogs → Import and choose the downloaded .knxprod file. The device then appears in your catalog and can be added to a project. Older versions are kept so existing projects can be matched to the application program they were commissioned with.
More from MDT technologies GmbH
- BE-BZS86.01 Central Operation Unit Smart 86 BE-BZS86.01
- BE-GBZx.01 Glass Central Operation Unit Smart BE-GBZx.01
- SCN-CO2M601x.02 CO2 / VOC Combi Sensor 60 CH SCN-CO2M601x.02
- SCN-CO2MGS.02 CO2 / VOC Combi Sensor 55 SCN-CO2MGS.02
- Glass Central Operation Unit with LCD SCN-LCDGx.01
- Analog I/O 2fold, flush mounted AIO-0210V.01
- Analog I/O 4fold, MDRC AIO-0410V.01
- AKD-0103.01 Dimming actuator 1-f, 4TE, 230VAC,600W AKD-0103.01
- AKD-0201.01 Dimming actuator 2-f, 4TE, 230VAC,250W AKD-0201.01
- AKD-0201.02 Dimming Actuator 2-fold AKD-0201.02
- AKD-0203.01 Dimming actuator 2-f, 8TE, 230VAC,600W AKD-0203.01
- AKD-0224V.01 LED Controller 2 channel AKD-0224V.01