KNX Database

Analog I/O 2fold, flush mounted AIO-0210V.01

MDT technologies GmbH · Order number AIO-0210V.01 · Actuators › Analog Actuators

Analog Input/Output 2fold, 0-10V / 0-20mA

Download .knxprod Analog I/O 2-fold, flush mounted 1.2 · 150 KB

Product

ManufacturerMDT technologies GmbH
Product nameAnalog I/O 2fold, flush mounted
Order numberAIO-0210V.01
Product textAIO-0210V.01 Analog I/O 2fold, flush mounted
HardwareAnalogaktor 2fach, UP
MediumTwisted Pair
Bus current (mA)12
Rail mountedNo
RegistrationCertified · 2016-10-21
Languagesde-DE, en-US, es-ES, fr-FR
Catalog entryM-0083_H-90-1_HP-005A-12-36CF_CI-AIO.2D0210V.2E01-1
Fingerprint36CF
SHA-2563846ad79012693852721af405b4edf9d19b0af3a93d8530116438310507c6be7
First seen2026-11-25
Markets69 markets

Application program: Analog I/O 2-fold, flush mounted 1.2

Application number$005A
Version1.2
Mask versionMV-0705 (7.5)
KNX Data SecureNo
Minimum ETS version4.0
Parameters540
Group objects327
Group objects (327)
NoNameFunctionSizeDPTFlags
0Channel A: InputSend value1 Byte5.1 percentage (0..100%)CRT
0Channel A: InputSend value2 Bytes9.1 temperature (°C)CRT
0Channel A: InputSend value2 Bytes9.20 voltage (mV)CRT
0Channel A: InputSend value2 Bytes9.4 lux (Lux)CRT
0Channel A: InputSend value2 Bytes9.5 speed (m/s)CRT
0Channel A: InputSend value2 Bytes9.6 pressure (Pa)CRT
0Channel A: InputSend value2 Bytes9.7 humidity (%)CRT
0Channel A: InputSend value2 Bytes9.8 parts/million (ppm)CRT
0Channel A: InputSend value2 Bytes9.25 volume flow (l/h)CRT
0Channel A: InputSend value2 Bytes9.26 rain amount (l/m²)CRT
0Channel A: InputSend value2 Bytes9.21 current (mA)CRT
1Channel A: InputWire break alarm1 Bit1.5 alarmCRT
2Dummy1 Bit
3Channel A: Input Step switchStep 11 Bit1.1 switchCRT
4Channel A: Input Step switchStep 21 Bit1.1 switchCRT
5Channel A: Input Step switchStep 31 Bit1.1 switchCRT
6Channel A: Input Step switchStep 41 Bit1.1 switchCRT
7Channel A: InputMinimum value1 Byte5.1 percentage (0..100%)CRT
7Channel A: InputMinimum value2 Bytes9.20 voltage (mV)CRT
7Channel A: InputMinimum value2 Bytes9.1 temperature (°C)CRT
7Channel A: InputMinimum value2 Bytes9.4 lux (Lux)CRT
7Channel A: InputMinimum value2 Bytes9.5 speed (m/s)CRT
7Channel A: InputMinimum value2 Bytes9.6 pressure (Pa)CRT
7Channel A: InputMinimum value2 Bytes9.7 humidity (%)CRT
7Channel A: InputMinimum value2 Bytes9.8 parts/million (ppm)CRT
7Channel A: InputMinimum value2 Bytes9.25 volume flow (l/h)CRT
7Channel A: InputMinimum value2 Bytes9.26 rain amount (l/m²)CRT
7Channel A: InputMinimum value2 Bytes9.21 current (mA)CRT
8Channel A: InputMaximum value1 Byte5.1 percentage (0..100%)CRT
8Channel A: InputMaximum value2 Bytes9.20 voltage (mV)CRT
8Channel A: InputMaximum value2 Bytes9.1 temperature (°C)CRT
8Channel A: InputMaximum value2 Bytes9.4 lux (Lux)CRT
8Channel A: InputMaximum value2 Bytes9.5 speed (m/s)CRT
8Channel A: InputMaximum value2 Bytes9.6 pressure (Pa)CRT
8Channel A: InputMaximum value2 Bytes9.7 humidity (%)CRT
8Channel A: InputMaximum value2 Bytes9.8 parts/million (ppm)CRT
8Channel A: InputMaximum value2 Bytes9.25 volume flow (l/h)CRT
8Channel A: InputMaximum value2 Bytes9.26 rain amount (l/m²)CRT
8Channel A: InputMaximum value2 Bytes9.21 current (mA)CRT
9Channel A: InputReset min/max value1 Bit1.1 switchCW
10Channel A: InputThreshold 1 exceedance and lower deviation1 Bit1.1 switchCRT
10Channel A: InputThreshold 1 exceedance and lower deviation1 Byte5.1 percentage (0..100%)CRT
10Channel A: InputThreshold 1 exceedance and lower deviation1 Byte17.1 scene numberCRT
11Channel A: InputChange threshold 11 Byte5.1 percentage (0..100%)CW
11Channel A: InputChange threshold 12 Bytes9.20 voltage (mV)CW
11Channel A: InputChange threshold 12 Bytes9.1 temperature (°C)CW
11Channel A: InputChange threshold 12 Bytes9.4 lux (Lux)CW
11Channel A: InputChange threshold 12 Bytes9.5 speed (m/s)CW
11Channel A: InputChange threshold 12 Bytes9.6 pressure (Pa)CW
11Channel A: InputChange threshold 12 Bytes9.7 humidity (%)CW
11Channel A: InputChange threshold 12 Bytes9.8 parts/million (ppm)CW
11Channel A: InputChange threshold 12 Bytes9.25 volume flow (l/h)CW
11Channel A: InputChange threshold 12 Bytes9.26 rain amount (l/m²)CW
11Channel A: InputChange threshold 12 Bytes9.21 current (mA)CW
12Channel A: InputThreshold 2 exceedance and lower deviation1 Bit1.1 switchCRT
12Channel A: InputThreshold 2 exceedance and lower deviation1 Byte5.1 percentage (0..100%)CRT
12Channel A: InputThreshold 2 exceedance and lower deviation1 Byte17.1 scene numberCRT
13Dummy4 Bytes
14Channel A: InputChange threshold 21 Byte5.1 percentage (0..100%)CW
14Channel A: InputChange threshold 22 Bytes9.20 voltage (mV)CW
14Channel A: InputChange threshold 22 Bytes9.1 temperature (°C)CW
14Channel A: InputChange threshold 22 Bytes9.4 lux (Lux)CW
14Channel A: InputChange threshold 22 Bytes9.5 speed (m/s)CW
14Channel A: InputChange threshold 22 Bytes9.6 pressure (Pa)CW
14Channel A: InputChange threshold 22 Bytes9.7 humidity (%)CW
14Channel A: InputChange threshold 22 Bytes9.8 parts/million (ppm)CW
14Channel A: InputChange threshold 22 Bytes9.25 volume flow (l/h)CW
14Channel A: InputChange threshold 22 Bytes9.26 rain amount (l/m²)CW
14Channel A: InputChange threshold 22 Bytes9.21 current (mA)CW
15Dummy4 Bytes
16Dummy4 Bytes
17Channel A: OutputDefault current set value1 Byte5.1 percentage (0..100%)CW
17Channel A: OutputDefault current set value2 Bytes9.20 voltage (mV)CW
17Channel A: OutputDefault current set value2 Bytes9.1 temperature (°C)CW
17Channel A: OutputDefault current set value2 Bytes9.4 lux (Lux)CW
17Channel A: OutputDefault current set value2 Bytes9.5 speed (m/s)CW
17Channel A: OutputDefault current set value2 Bytes9.6 pressure (Pa)CW
17Channel A: OutputDefault current set value2 Bytes9.7 humidity (%)CW
17Channel A: OutputDefault current set value2 Bytes9.25 volume flow (l/h)CW
17Channel A: OutputDefault current set value2 Bytes9.8 parts/million (ppm)CW
17Channel A: OutputDefault current set value2 Bytes9.26 rain amount (l/m²)CW
18Channel A: OutputStep 11 Bit1.1 switchCW
18Channel A: OutputBinary coded: Bit 01 Bit1.1 switchCW
19Channel A: OutputStep 21 Bit1.1 switchCW
19Channel A: OutputBinary coded: Bit 11 Bit1.1 switchCW
20Channel A: OutputStep 31 Bit1.1 switchCW
20Channel A: OutputBinary coded: Bit 21 Bit1.1 switchCW
21Channel A: OutputStep 41 Bit1.1 switchCW
22Channel A: OutputStep 51 Bit1.1 switchCW
23Channel A: OutputStep 61 Bit1.1 switchCW
24Channel A: OutputStep 71 Bit1.1 switchCW
25Channel A: OutputStep 81 Bit1.1 switchCW
26Channel A: OutputSwitch Heating/Cooling1 Bit1.1 switchCWU
27Channel A: OutputStatus current value2 Bytes9.20 voltage (mV)CRT
27Channel A: OutputStatus current value1 Byte5.1 percentage (0..100%)CRT
28Channel A: OutputLock object 11 Bit1.3 enableCW
29Channel A: OutputLock object 21 Bit1.3 enableCW
30Channel A: OutputSend status of emergency mode1 Bit1.1 switchCRT
31Channel A: OutputEnable Emergency mode1 Bit1.1 switchCW
32Dummy4 Bytes
33Dummy4 Bytes
34Dummy4 Bytes
35Channel B: InputSend value1 Byte5.1 percentage (0..100%)CRT
35Channel B: InputSend value2 Bytes9.1 temperature (°C)CRT
35Channel B: InputSend value2 Bytes9.20 voltage (mV)CRT
35Channel B: InputSend value2 Bytes9.4 lux (Lux)CRT
35Channel B: InputSend value2 Bytes9.5 speed (m/s)CRT
35Channel B: InputSend value2 Bytes9.6 pressure (Pa)CRT
35Channel B: InputSend value2 Bytes9.7 humidity (%)CRT
35Channel B: InputSend value2 Bytes9.8 parts/million (ppm)CRT
35Channel B: InputSend value2 Bytes9.25 volume flow (l/h)CRT
35Channel B: InputSend value2 Bytes9.26 rain amount (l/m²)CRT
35Channel B: InputSend value2 Bytes9.21 current (mA)CRT
36Channel B: InputWire break alarm1 Bit1.5 alarmCRT
37Dummy1 Bit
38Channel B: Input Step switchStep 11 Bit1.1 switchCRT
39Channel B: Input Step switchStep 21 Bit1.1 switchCRT
40Channel B: Input Step switchStep 31 Bit1.1 switchCRT
41Channel B: Input Step switchStep 41 Bit1.1 switchCRT
42Channel B: InputMinimum value1 Byte5.1 percentage (0..100%)CRT
42Channel B: InputMinimum value2 Bytes9.20 voltage (mV)CRT
42Channel B: InputMinimum value2 Bytes9.1 temperature (°C)CRT
42Channel B: InputMinimum value2 Bytes9.4 lux (Lux)CRT
42Channel B: InputMinimum value2 Bytes9.5 speed (m/s)CRT
42Channel B: InputMinimum value2 Bytes9.6 pressure (Pa)CRT
42Channel B: InputMinimum value2 Bytes9.7 humidity (%)CRT
42Channel B: InputMinimum value2 Bytes9.8 parts/million (ppm)CRT
42Channel B: InputMinimum value2 Bytes9.25 volume flow (l/h)CRT
42Channel B: InputMinimum value2 Bytes9.26 rain amount (l/m²)CRT
42Channel B: InputMinimum value2 Bytes9.21 current (mA)CRT
43Channel B: InputMaximum value1 Byte5.1 percentage (0..100%)CRT
43Channel B: InputMaximum value2 Bytes9.20 voltage (mV)CRT
43Channel B: InputMaximum value2 Bytes9.1 temperature (°C)CRT
43Channel B: InputMaximum value2 Bytes9.4 lux (Lux)CRT
43Channel B: InputMaximum value2 Bytes9.5 speed (m/s)CRT
43Channel B: InputMaximum value2 Bytes9.6 pressure (Pa)CRT
43Channel B: InputMaximum value2 Bytes9.7 humidity (%)CRT
43Channel B: InputMaximum value2 Bytes9.8 parts/million (ppm)CRT
43Channel B: InputMaximum value2 Bytes9.25 volume flow (l/h)CRT
43Channel B: InputMaximum value2 Bytes9.26 rain amount (l/m²)CRT
43Channel B: InputMaximum value2 Bytes9.21 current (mA)CRT
44Channel B: InputReset min/max value1 Bit1.1 switchCW
45Channel B: InputThreshold 1 exceedance and lower deviation1 Bit1.1 switchCRT
45Channel B: InputThreshold 1 exceedance and lower deviation1 Byte5.1 percentage (0..100%)CRT
45Channel B: InputThreshold 1 exceedance and lower deviation1 Byte17.1 scene numberCRT
46Channel B: InputChange threshold 11 Byte5.1 percentage (0..100%)CW
46Channel B: InputChange threshold 12 Bytes9.20 voltage (mV)CW
46Channel B: InputChange threshold 12 Bytes9.1 temperature (°C)CW
46Channel B: InputChange threshold 12 Bytes9.4 lux (Lux)CW
46Channel B: InputChange threshold 12 Bytes9.5 speed (m/s)CW
46Channel B: InputChange threshold 12 Bytes9.6 pressure (Pa)CW
46Channel B: InputChange threshold 12 Bytes9.7 humidity (%)CW
46Channel B: InputChange threshold 12 Bytes9.8 parts/million (ppm)CW
46Channel B: InputChange threshold 12 Bytes9.25 volume flow (l/h)CW
46Channel B: InputChange threshold 12 Bytes9.26 rain amount (l/m²)CW
46Channel B: InputChange threshold 12 Bytes9.21 current (mA)CW
47Channel B: InputThreshold 2 exceedance and lower deviation1 Bit1.1 switchCRT
47Channel B: InputThreshold 2 exceedance and lower deviation1 Byte5.1 percentage (0..100%)CRT
47Channel B: InputThreshold 2 exceedance and lower deviation1 Byte17.1 scene numberCRT
48Dummy4 Bytes
49Channel B: InputChange threshold 21 Byte5.1 percentage (0..100%)CW
49Channel B: InputChange threshold 22 Bytes9.20 voltage (mV)CW
49Channel B: InputChange threshold 22 Bytes9.1 temperature (°C)CW
49Channel B: InputChange threshold 22 Bytes9.4 lux (Lux)CW
49Channel B: InputChange threshold 22 Bytes9.5 speed (m/s)CW
49Channel B: InputChange threshold 22 Bytes9.6 pressure (Pa)CW
49Channel B: InputChange threshold 22 Bytes9.7 humidity (%)CW
49Channel B: InputChange threshold 22 Bytes9.8 parts/million (ppm)CW
49Channel B: InputChange threshold 22 Bytes9.25 volume flow (l/h)CW
49Channel B: InputChange threshold 22 Bytes9.26 rain amount (l/m²)CW
49Channel B: InputChange threshold 22 Bytes9.21 current (mA)CW
50Dummy4 Bytes
51Dummy4 Bytes
52Channel B: OutputDefault current set value1 Byte5.1 percentage (0..100%)CW
52Channel B: OutputDefault current set value2 Bytes9.20 voltage (mV)CW
52Channel B: OutputDefault current set value2 Bytes9.1 temperature (°C)CW
52Channel B: OutputDefault current set value2 Bytes9.4 lux (Lux)CW
52Channel B: OutputDefault current set value2 Bytes9.5 speed (m/s)CW
52Channel B: OutputDefault current set value2 Bytes9.6 pressure (Pa)CW
52Channel B: OutputDefault current set value2 Bytes9.7 humidity (%)CW
52Channel B: OutputDefault current set value2 Bytes9.25 volume flow (l/h)CW
52Channel B: OutputDefault current set value2 Bytes9.8 parts/million (ppm)CW
52Channel B: OutputDefault current set value2 Bytes9.26 rain amount (l/m²)CW
53Channel B: OutputStep 11 Bit1.1 switchCW
53Channel B: OutputBinary coded: Bit 01 Bit1.1 switchCW
54Channel B: OutputStep 21 Bit1.1 switchCW
54Channel B: OutputBinary coded: Bit 11 Bit1.1 switchCW
55Channel B: OutputStep 31 Bit1.1 switchCW
55Channel B: OutputBinary coded: Bit 21 Bit1.1 switchCW
56Channel B: OutputStep 41 Bit1.1 switchCW
57Channel B: OutputStep 51 Bit1.1 switchCW
58Channel B: OutputStep 61 Bit1.1 switchCW
59Channel B: OutputStep 71 Bit1.1 switchCW
60Channel B: OutputStep 81 Bit1.1 switchCW
61Channel B: OutputSwitch Heating/Cooling1 Bit1.1 switchCWU
62Channel B: OutputStatus current value2 Bytes9.20 voltage (mV)CRT
62Channel B: OutputStatus current value1 Byte5.1 percentage (0..100%)CRT
63Channel B: OutputLock object 11 Bit1.3 enableCW
64Channel B: OutputLock object 21 Bit1.3 enableCW
65Channel B: OutputSend status of emergency mode1 Bit1.1 switchCRT
66Channel B: OutputEnable Emergency mode1 Bit1.1 switchCW
67Dummy4 Bytes
68Dummy4 Bytes
69Dummy4 Bytes
70Difference measurement 1Input object1 Byte5.1 percentage (0..100%)CW
70Difference measurement 1Input object2 Bytes9.20 voltage (mV)CW
70Difference measurement 1Input object2 Bytes9.1 temperature (°C)CW
70Difference measurement 1Input object2 Bytes9.4 lux (Lux)CW
70Difference measurement 1Input object2 Bytes9.5 speed (m/s)CW
70Difference measurement 1Input object2 Bytes9.6 pressure (Pa)CW
70Difference measurement 1Input object2 Bytes9.7 humidity (%)CW
70Difference measurement 1Input object2 Bytes9.8 parts/million (ppm)CW
70Difference measurement 1Input object2 Bytes9.25 volume flow (l/h)CW
70Difference measurement 1Input object2 Bytes9.26 rain amount (l/m²)CW
70Difference measurement 1Input object2 Bytes9.21 current (mA)CW
71Difference measurement 1Output object1 Byte5.1 percentage (0..100%)CRT
71Difference measurement 1Output object2 Bytes9.20 voltage (mV)CRT
71Difference measurement 1Output object2 Bytes9.1 temperature (°C)CRT
71Difference measurement 1Output object2 Bytes9.4 lux (Lux)CRT
71Difference measurement 1Output object2 Bytes9.5 speed (m/s)CRT
71Difference measurement 1Output object2 Bytes9.6 pressure (Pa)CRT
71Difference measurement 1Output object2 Bytes9.7 humidity (%)CRT
71Difference measurement 1Output object2 Bytes9.8 parts/million (ppm)CRT
71Difference measurement 1Output object2 Bytes9.25 volume flow (l/h)CRT
71Difference measurement 1Output object2 Bytes9.26 rain amount (l/m²)CRT
71Difference measurement 1Output object2 Bytes9.21 current (mA)CRT
71Difference measurement 1Output object1 Bit1.1 switchCRT
71Difference measurement 1Output object1 Byte17.1 scene numberCRT
72Dummy4 BytesCW
73Dummy4 BytesCW
74Dummy4 BytesCW
75Difference measurement 2Input object1 Byte5.1 percentage (0..100%)CW
75Difference measurement 2Input object2 Bytes9.20 voltage (mV)CW
75Difference measurement 2Input object2 Bytes9.1 temperature (°C)CW
75Difference measurement 2Input object2 Bytes9.4 lux (Lux)CW
75Difference measurement 2Input object2 Bytes9.5 speed (m/s)CW
75Difference measurement 2Input object2 Bytes9.6 pressure (Pa)CW
75Difference measurement 2Input object2 Bytes9.7 humidity (%)CW
75Difference measurement 2Input object2 Bytes9.8 parts/million (ppm)CW
75Difference measurement 2Input object2 Bytes9.25 volume flow (l/h)CW
75Difference measurement 2Input object2 Bytes9.26 rain amount (l/m²)CW
75Difference measurement 2Input object2 Bytes9.21 current (mA)CW
76Difference measurement 2Output object1 Byte5.1 percentage (0..100%)CRT
76Difference measurement 2Output object2 Bytes9.20 voltage (mV)CRT
76Difference measurement 2Output object2 Bytes9.1 temperature (°C)CRT
76Difference measurement 2Output object2 Bytes9.4 lux (Lux)CRT
76Difference measurement 2Output object2 Bytes9.5 speed (m/s)CRT
76Difference measurement 2Output object2 Bytes9.6 pressure (Pa)CRT
76Difference measurement 2Output object2 Bytes9.7 humidity (%)CRT
76Difference measurement 2Output object2 Bytes9.8 parts/million (ppm)CRT
76Difference measurement 2Output object2 Bytes9.25 volume flow (l/h)CRT
76Difference measurement 2Output object2 Bytes9.26 rain amount (l/m²)CRT
76Difference measurement 2Output object2 Bytes9.21 current (mA)CRT
76Difference measurement 2Output object1 Bit1.1 switchCRT
76Difference measurement 2Output object1 Byte17.1 scene numberCRT
77Dummy4 BytesCW
78Dummy4 BytesCW
79Dummy4 BytesCW
80Difference measurement 3Input object1 Byte5.1 percentage (0..100%)CW
80Difference measurement 3Input object2 Bytes9.20 voltage (mV)CW
80Difference measurement 3Input object2 Bytes9.1 temperature (°C)CW
80Difference measurement 3Input object2 Bytes9.4 lux (Lux)CW
80Difference measurement 3Input object2 Bytes9.5 speed (m/s)CW
80Difference measurement 3Input object2 Bytes9.6 pressure (Pa)CW
80Difference measurement 3Input object2 Bytes9.7 humidity (%)CW
80Difference measurement 3Input object2 Bytes9.8 parts/million (ppm)CW
80Difference measurement 3Input object2 Bytes9.25 volume flow (l/h)CW
80Difference measurement 3Input object2 Bytes9.26 rain amount (l/m²)CW
80Difference measurement 3Input object2 Bytes9.21 current (mA)CW
81Difference measurement 3Output object1 Byte5.1 percentage (0..100%)CRT
81Difference measurement 3Output object2 Bytes9.20 voltage (mV)CRT
81Difference measurement 3Output object2 Bytes9.1 temperature (°C)CRT
81Difference measurement 3Output object2 Bytes9.4 lux (Lux)CRT
81Difference measurement 3Output object2 Bytes9.5 speed (m/s)CRT
81Difference measurement 3Output object2 Bytes9.6 pressure (Pa)CRT
81Difference measurement 3Output object2 Bytes9.7 humidity (%)CRT
81Difference measurement 3Output object2 Bytes9.8 parts/million (ppm)CRT
81Difference measurement 3Output object2 Bytes9.25 volume flow (l/h)CRT
81Difference measurement 3Output object2 Bytes9.26 rain amount (l/m²)CRT
81Difference measurement 3Output object2 Bytes9.21 current (mA)CRT
81Difference measurement 3Output object1 Bit1.1 switchCRT
81Difference measurement 3Output object1 Byte17.1 scene numberCRT
82Dummy4 BytesCW
83Dummy4 BytesCW
84Dummy4 BytesCW
85Difference measurement 4Input object1 Byte5.1 percentage (0..100%)CW
85Difference measurement 4Input object2 Bytes9.20 voltage (mV)CW
85Difference measurement 4Input object2 Bytes9.1 temperature (°C)CW
85Difference measurement 4Input object2 Bytes9.4 lux (Lux)CW
85Difference measurement 4Input object2 Bytes9.5 speed (m/s)CW
85Difference measurement 4Input object2 Bytes9.6 pressure (Pa)CW
85Difference measurement 4Input object2 Bytes9.7 humidity (%)CW
85Difference measurement 4Input object2 Bytes9.8 parts/million (ppm)CW
85Difference measurement 4Input object2 Bytes9.25 volume flow (l/h)CW
85Difference measurement 4Input object2 Bytes9.26 rain amount (l/m²)CW
85Difference measurement 4Input object2 Bytes9.21 current (mA)CW
86Difference measurement 4Output object1 Byte5.1 percentage (0..100%)CRT
86Difference measurement 4Output object2 Bytes9.20 voltage (mV)CRT
86Difference measurement 4Output object2 Bytes9.1 temperature (°C)CRT
86Difference measurement 4Output object2 Bytes9.4 lux (Lux)CRT
86Difference measurement 4Output object2 Bytes9.5 speed (m/s)CRT
86Difference measurement 4Output object2 Bytes9.6 pressure (Pa)CRT
86Difference measurement 4Output object2 Bytes9.7 humidity (%)CRT
86Difference measurement 4Output object2 Bytes9.8 parts/million (ppm)CRT
86Difference measurement 4Output object2 Bytes9.25 volume flow (l/h)CRT
86Difference measurement 4Output object2 Bytes9.26 rain amount (l/m²)CRT
86Difference measurement 4Output object2 Bytes9.21 current (mA)CRT
86Difference measurement 4Output object1 Bit1.1 switchCRT
86Difference measurement 4Output object1 Byte17.1 scene numberCRT
87Dummy4 BytesCW
88Dummy4 BytesCW
89Dummy4 BytesCW
90Operation modeSend status1 Bit1.11 stateCRT
91Day/NightSwitching1 Bit1.2 booleanCWU
91Day/NightSwitching1 Bit1.2 booleanCRWTU
92Overload/Short circuitSend alarm1 Bit1.5 alarmCT
93Dummy4 Bytes
94Dummy4 Bytes
95Dummy4 Bytes
96Dummy4 Bytes
97Dummy4 Bytes
98Dummy4 Bytes
99Dummy4 Bytes
100Dummy4 Bytes
101Dummy4 Bytes
102Dummy4 Bytes
103Dummy4 Bytes
Parameters (247)
ParameterTypeDefault
Startup delaytimeunsignedInt 0…1205
NumberOfChannelsunsignedInt 0…2554
Cyclic "Operation mode"listnot use
Day/Night objectlistuse, no request
Polarity of object Day/NightlistDay = 0 / Night = 1
Overload / Short circuat detectionlistnot active
Channel Alistnot active
Channel Blistnot active
Differenzmessung 1listactive
Setting sensor typelist0 - 10V Sensor
Wire break detectionlistnot active
Object type for measurement outputlistDPT 9.020 Voltage (mV)
Object type for measurement outputlistDPT 9.021 Current (mA)
Scaling of output for voltage value = 0V (-60…250°C)signedInt -60…2500
Scaling of output for voltage value = 0V (0…100000 Lux)unsignedInt 0…1000000
Scaling of output for voltage value = 0V (0…360 m/s)unsignedInt 0…3600
Scaling of output for voltage value = 0V (0…670000 Pa)unsignedInt 0…6700000
Scaling of output for voltage value = 0V (0…100%)unsignedInt 0…1000
Scaling of output for voltage value = 0V (0…5000 ppm)unsignedInt 0…50000
Scaling of output for voltage value = 0V (0…5000 l/h)unsignedInt 0…50000
Scaling of output for voltage value = 0V (0…200 l/m²)unsignedInt 0…2000
Scaling of output for voltage value = 10V (0…100 %)unsignedInt 0…1000
Scaling of output for voltage value = 10V (-60…250 °C)signedInt -60…2500
Scaling of output for voltage value = 10V (0…100000 Lux)unsignedInt 0…1000000
Scaling of output for voltage value = 10V (0…360 m/s)unsignedInt 0…3600
Scaling of output for voltage value = 10V (0…670000 Pa)unsignedInt 0…6700000
Scaling of output for voltage value = 10V (0…5000 ppm)unsignedInt 0…50000
Scaling of output for voltage value = 10V (0…5000 l/h)unsignedInt 0…50000
Scaling of output for voltage value = 10V (0…200 l/m²)unsignedInt 0…2000
Scaling the output for voltage value = 2V (-60…250 °C)signedInt -60…2500
Scaling the output for voltage value = 2V (0…100000 Lux)unsignedInt 0…1000000
Scaling the output for voltage value = 2V (0…360 m/s)unsignedInt 0…3600
Scaling the output for voltage value = 2V (0…670000 Pa)unsignedInt 0…6700000
Scaling the output for voltage value = 2V (0…100 %)unsignedInt 0…1000
Scaling the output for voltage value = 2V (0…5000 ppm)unsignedInt 0…50000
Scaling the output for voltage value = 2V (0…5000 l/h)unsignedInt 0…50000
Scaling the output for voltage value = 2V (0…200 l/m²)unsignedInt 0…2000
Scaling the output for current value = 0mA (-60…250 °C)signedInt -60…2500
Scaling the output for current value = 20mA (-60…250 °C)signedInt -60…2500
Scaling the output for current value = 0mA (0…100000 Lux)unsignedInt 0…1000000
Scaling the output for current value = 20mA (0…100000 Lux)unsignedInt 0…1000000
Scaling the output for current value = 0mA (0…360 m/s)unsignedInt 0…3600
Scaling the output for current value = 20mA (0…360 m/s)unsignedInt 0…3600
Scaling the output for current value = 0mA (0…670000 Pa)unsignedInt 0…6700000
Scaling the output for current value = 20mA (0…670000 Pa)unsignedInt 0…6700000
Scaling the output for current value = 0mA (0…100 %)unsignedInt 0…1000
Scaling the output for current value = 20mA (0…100 %)unsignedInt 0…1000
Scaling the output for current value = 0mA (0…5000 ppm)unsignedInt 0…50000
Scaling the output for current value = 20mA (0…5000 ppm)unsignedInt 0…50000
Scaling the output for current value = 0mA (0…5000 l/h)unsignedInt 0…50000
Scaling the output for current value = 20mA (0…5000 l/h)unsignedInt 0…50000
Scaling the output for current value = 0mA (0…200 l/m²)unsignedInt 0…2000
Scaling the output for current value = 20mA (0…200 l/m²)unsignedInt 0…2000
Scaling the output for current value = 4mA (-60…250 °C)signedInt -60…2500
Scaling the output for current value = 4mA (0…100000 Lux)unsignedInt 0…1000000
Scaling the output for current value = 4mA (0…360 m/s)unsignedInt 0…3600
Scaling the output for current value = 4mA (0…670000 Pa)unsignedInt 0…6700000
Scaling the output for current value = 4mA (0…100 %)unsignedInt 0…1000
Scaling the output for current value = 4mA (0…5000 ppm)unsignedInt 0…50000
Scaling the output for current value = 4mA (0…5000 l/h)unsignedInt 0…50000
Scaling the output for current value = 4mA (0…200 l/m²)unsignedInt 0…2000
Status outputlistonly request
Send value at changelist1%
Send value cyclic with interval oflist1 min
Step regulatorlistnot active
HysteresisunsignedInt 0…502
Min/max valueslistnot active
Threshold switchlistnot active
Threshold switch is changeable over Buslistnot active
Output object threshold 1listBit
Value for lower deviationunsignedInt 0…1000
Value for lower deviationlistBit 0
Szene number at lower deviationlist1
Value for exceedanceunsignedInt 0…100100
Value for exceedancelistBit 1
Scene number at exceedancelist2
ThresholdsignedInt -60…25040
ThresholdunsignedInt 0…1000000
ThresholdunsignedInt 0…3600
ThresholdunsignedInt 0…6700000
ThresholdunsignedInt 0…1000
ThresholdunsignedInt 0…50000
ThresholdunsignedInt 0…2000
Hysteresis for switch-off thresholdunsignedInt 0…500
Output object threshold 2listBit
ThresholdsignedInt -60…25020
Dummy_objectslistnot active
Set value default setting overlist1Byte continuous (0-100%)
Day/Night objectlistnot active
Minimum value dayunsignedInt 0…1000
Maximum value dayunsignedInt 0…100100
Maximum value nightunsignedInt 0…100100
Minimum value nightunsignedInt 0…1000
Maximum valueunsignedInt 0…100100
Minimum valueunsignedInt 0…1000
Switch-off point (Output = 0V)float 0…100000
End stop (Output = 10V)float 0…1000010000
Datapoint settinglistDPT 9.020 Voltage (mV)
Number of stepslist2
Modelist1Bit Inputs
Voltage value step 1 at dayunsignedInt 0…1000
Voltage value step 2 at dayunsignedInt 0…10020
Voltage value step 3 at dayunsignedInt 0…10030
Voltage value step 4 at dayunsignedInt 0…10040
Voltage value step 5 at dayunsignedInt 0…10050
Voltage value step 6 at dayunsignedInt 0…10060
Voltage value step 7 at dayunsignedInt 0…10070
Voltage value step 8 at dayunsignedInt 0…10080
Voltage value step 8 at nightunsignedInt 0…100100
Voltage value step 7 at nightunsignedInt 0…10095
Voltage value step 6 at nightunsignedInt 0…10085
Voltage value step 5 at nightunsignedInt 0…10070
Voltage value step 4 at nightunsignedInt 0…10055
Voltage value step 3 at nightunsignedInt 0…10040
Voltage value step 2 at nightunsignedInt 0…10025
Voltage value step 1 at nightunsignedInt 0…10010
Voltage value step 1unsignedInt 0…1000
Voltage value step 2unsignedInt 0…10020
Voltage value step 3unsignedInt 0…10030
Voltage value step 4unsignedInt 0…10040
Voltage value step 5unsignedInt 0…10050
Voltage value step 6unsignedInt 0…10060
Voltage value step 7unsignedInt 0…10070
Voltage value step 8unsignedInt 0…10080
Switching threshold step 1 <-> step 2unsignedInt 0…10010
Switching threshold step 2 <-> step 3unsignedInt 0…10020
Switching threshold step 3 <-> step 4unsignedInt 0…10030
Switching threshold step 4 <-> step 5unsignedInt 0…10045
Switching threshold step 5 <-> step 6unsignedInt 0…10060
Switching threshold step 6 <-> step 7unsignedInt 0…10070
Switching threshold step 7 <-> step 8unsignedInt 0…10080
HysteresisunsignedInt 0…500
Switching threshold step 1 <-> step 2float -671088.64…670760.960
Switching threshold step 2 <-> step 3float -671088.64…670760.960
Switching threshold step 3 <-> step 4float -671088.64…670760.960
Switching threshold step 4 <-> step 5float -671088.64…670760.960
Switching threshold step 5 <-> step 6float -671088.64…670760.960
Switching threshold step 6 <-> step 7float -671088.64…670760.960
Switching threshold step 7 <-> step 8float -671088.64…670760.960
Send value cyclic eachlist1 min
Datapoint for status objectlistDPT 9.020 Voltage (mV)
Time to achieve target value scaled to a throughput of 0-10V (0s = directly)unsignedInt 0…1200
Lock function 1 (higher priority)listnot active
Action at activationlistswitch output to voltage value 0-10V
Voltage valueunsignedInt 0…10050
Actio at deactivationlistmemory function
Voltage valueunsignedInt 0…100100
Lock function 2listnot active
Emergency modelistnot use
Activation of emergency mode at daylist30 min
Action at activation of emergency mode at daylistswitch output to voltage value 0-10V
Action at activation of emergency mode at nightlistswitch output to voltage value 0-10V
Action at activation of emergency modelistswitch output to voltage value 0-10V
Behavior after bus power returnlistno changes (Memory function)
Voltage valueunsignedInt 0…1000
Difference measurement 1listnot active
Type of calculationlistarithmetic
Measurement input 1listChannel A
Measurement input 2listexternal object
Reference valueunsignedInt 0…1000
Reference valueunsignedInt 0…100000
Threshold for switching to step 1unsignedInt 0…10020
Threshold for switching to step 2unsignedInt 0…10040
Threshold for switching to step 3unsignedInt 0…10060
Threshold for switching to step 4unsignedInt 0…10080
Threshold for switching to step 1unsignedInt 20…10020
Threshold for switching to step 2unsignedInt 20…10040
Threshold for switching to step 3unsignedInt 20…10060
Threshold for switching to step 4unsignedInt 20…10080
Threshold for switching to step 1unsignedInt 0…20040
Threshold for switching to step 2unsignedInt 0…20080
Threshold for switching to step 3unsignedInt 0…200120
Threshold for switching to step 4unsignedInt 0…200160
Threshold for switching to step 1unsignedInt 40…20040
Threshold for switching to step 2unsignedInt 40…20080
Threshold for switching to step 3unsignedInt 40…200120
Threshold for switching to step 4unsignedInt 40…200160
Reference valuesignedInt -60…2500
Reference valueunsignedInt 0…1000000
Reference valueunsignedInt 0…3600
Reference valueunsignedInt 0…6700000
Reference valueunsignedInt 0…50000
Reference valueunsignedInt 0…2000
Reference valueunsignedInt 2000…100000
Reference valuefloat 0…200
Reference valuefloat 4…204
Send behaviorlistsend at changes and cyclic
Send value with a interval oflist1 min
Arithmetic operationlistInput 1 + Input 2
Send at change oflist2%
Reference operationlistInput 1 = Input 2
Hysteresislist2%
Output objectlistBit
Percent valueunsignedInt 0…100100
Bit valuelistBit 1
Scene numberlist1
Percent valueunsignedInt 0…1000
Bit valuelistBit 0
Scene numberlist2
Send telegram if reference condition is compliedlistyes
Send telegram if reference condition is not compliedlistyes
Operating action of outputlistnormal
Inversion of Heating/CoolinglistHeating = inverse / Cooling = normal
Difference measurement 2listnot active
Switch-off point (Output = 0V)float 0…1000010000
End stop (Output = 10V)unsignedInt 0…100000
Difference measurement 3listnot active
Difference measurement 4listnot active
Send cyclicallistnot active
Mean filteringlistdirect
ThresholdunsignedInt 40…2000
Switch-off point (Output = 0V) (-60…250 °C)float -60…2000
Switch-off point (Output = 0V) (0...100000 Lux)float 0…1000000
Switch-off point (Output = 0V) (0...360 m/s)float 0…3600
Switch-off point (Output = 0V) (0...670000 Pa)float 0…6700000
Switch-off point (Output = 0V) (0...100 %)float 0…1000
Switch-off point (Output = 0V) (0...5000 ppm)float 0…50000
Switch-off point (Output = 0V) (0...5000 l/h)float 0…50000
Switch-off point (Output = 0V) (0...200 l/m²)float 0…2000
End stop (Output = 10V) (-60...250 °C)float -60…200100
End stop (Output = 10V) (0...100000 Lux)float 0…100000100000
End stop (Output = 10V) (0...360 m/s)float 0…360360
End stop (Output = 10V) (0...670000 Pa)float 0…670000670000
End stop (Output = 10V) (0...100 %)float 0…100100
End stop (Output = 10V) (0...5000 ppm)float 0…50005000
End stop (Output = 10V) (0...5000 l/h)float 0…50005000
End stop (Output = 10V) (0...200 l/m²)float 0…200200
Switch-off point (Output = 0V) (-60...250 °C)float -60…200100
Switch-off point (Output = 0V) (0...100000 Lux)float 0…100000100000
Switch-off point (Output = 0V) (0...360 m/s)float 0…360360
Switch-off point (Output = 0V) (0...670000 Pa)float 0…670000670000
Switch-off point (Output = 0V) (0...100 %)float 0…100100
Switch-off point (Output = 0V) (0...5000 ppm)float 0…50005000
Switch-off point (Output = 0V) (0...5000 l/h)float 0…50005000
Switch-off point (Output = 0V) (0...200 l/m²)float 0…200200
End stop (Output = 10V) (-60...250 °C)signedInt -60…2500
End stop (Output = 10V) (0...100000 Lux)unsignedInt 0…1000000
End stop (Output = 10V) (0...360 m/s)unsignedInt 0…3600
End stop (Output = 10V) (0...670000 Pa)unsignedInt 0…6700000
End stop (Output = 10V) (0...100 %)unsignedInt 0…1000
End stop (Output = 10V) (0...5000 ppm)unsignedInt 0…50000
End stop (Output = 10V) (0...5000 l/h)unsignedInt 0…50000
End stop (Output = 10V) (0...200 l/m²)unsignedInt 0…2000
ThresholdunsignedInt 20…1000
ThresholdunsignedInt 20…10020
ThresholdunsignedInt 40…20040
Send threshold cycliclistnot active

Version history

ApplicationApp noFingerprintFirst seenSizeFile
Analog I/O 2-fold, flush mounted 1.2 latest$005A36CF2026-11-25150 KBDownload

About this file

This is the official ETS product database for the MDT technologies GmbH Analog I/O 2fold, flush mounted (AIO-0210V.01), published by the manufacturer in the KNX online catalog. To use it, open ETS, go to Catalogs → Import and choose the downloaded .knxprod file. The device then appears in your catalog and can be added to a project. Older versions are kept so existing projects can be matched to the application program they were commissioned with.

More from MDT technologies GmbH

All MDT technologies GmbH products