MDT technologies GmbH SCN-KP360K3.03 SCN-KP360K3.03 Combi-Presence Detector 360° with room climate sensors

SCN-KP360K3.03 Combi-Presence Detector 360° with room climate sensors SCN-KP360K3.03

MDT technologies GmbH · Order number SCN-KP360K3.03 · Controller › Air quality/CO2 sensor

Combi-Presence Detector 360° 3S with room climate sensors

Download .knxprod Combi-Presence Detector 1.0 · 397 KB

Product

ManufacturerMDT technologies GmbH
Product nameSCN-KP360K3.03 Combi-Presence Detector 360° with room climate sensors
Order numberSCN-KP360K3.03
HardwareKombi-Präsenzmelder
MediumTwisted Pair
Bus current (mA)10
Rail mountedNo
RegistrationRegistered · 2024-06-05
Languagesde-DE, en-US, es-ES, fr-FR
Catalog entryM-0083_H-327-1_HP-0078-10-C9D1_CI-SCN.2DKP360K3.2E03-1
FingerprintC9D1
SHA-2560d45a92c52a9fe8d434c620e4baeced59ac3a0d86a5ea4b5a5588b68b4ec34bc
First seen2026-11-25
Markets69 markets

Application program: Combi-Presence Detector 1.0

Application number$0078
Version1.0
Mask versionMV-07B0 (System B)
KNX Data SecureNo
Minimum ETS version5.0
Parameters1222
Group objects372
Group objects (372)
NoNameFunctionSizeDPTFlags
1CO2 measurementSend measured value2 Bytes9.8 parts/million (ppm)CRT
2CO2 measurementExternal sensor input2 Bytes9.8 parts/million (ppm)CWTU
3CO2 measurementMaximum value exceeded1 Bit1.5 alarmCRT
4CO2 measurementMinimum value fallen below1 Bit1.5 alarmCRT
5CO2 measurementError external sensor1 Bit1.5 alarmCRT
8VOC measurementSend measured value2 Bytes9.8 parts/million (ppm)CRT
8VOC measurementSend measured value1 Byte5.1 percentage (0..100%)CRT
9VOC measurementExternal sensor input2 Bytes9.8 parts/million (ppm)CWTU
9VOC measurementExternal sensor input2 BytesCWTU
9VOC measurementExternal sensor input1 Byte5.1 percentage (0..100%)CWTU
10VOC measurementMaximum value exceeded1 Bit1.5 alarmCRT
11VOC measurementMinimum value fallen below1 Bit1.5 alarmCRT
12VOC measurementError external sensor1 Bit1.5 alarmCRT
15Temperature measurementSend measured value2 Bytes9.1 temperature (°C)CRT
16Temperature measurementExternal sensor input2 Bytes9.1 temperature (°C)CWTU
17Temperature measurementMaximum value exceeded1 Bit1.5 alarmCRT
18Temperature measurementMinimum value fallen below1 Bit1.5 alarmCRT
19Temperature measurementError external sensor1 Bit1.5 alarmCRT
22Relative humidity measurementSend measured value2 Bytes9.7 humidity (%)CRT
23Relative humidity measurementExternal sensor input2 Bytes9.7 humidity (%)CWTU
24Relative humidity measurementMaximum value exceeded1 Bit1.5 alarmCRT
25Relative humidity measurementMinimum value fallen below1 Bit1.5 alarmCRT
26Relative humidity measurementError external sensor1 Bit1.5 alarmCRT
29Air quality traffic lightOutput level 11 Bit1.1 switchCRT
30Air quality traffic lightOutput level 21 Bit1.1 switchCRT
31Air quality traffic lightOutput level 31 Bit1.1 switchCRT
32Air quality traffic lightOutput level 31 Bit1.1 switchCRT
32Air quality traffic lightOutput level 41 Bit1.1 switchCRT
33Air quality traffic lightOutput RGB3 Bytes232.600 RGB value 3x(0..255)CRT
33Air quality traffic lightOutput HSV3 Bytes232.600 RGB value 3x(0..255)CRT
34Air quality traffic lightOutput Scene1 Byte17.1 scene numberCRT
37Air quality controllerPreset setpoint2 Bytes9.8 parts/million (ppm)CW
38Air quality controllerActual setpoint2 Bytes9.8 parts/million (ppm)CRT
38Air quality controllerActual setpoint2 BytesCRT
39Air quality controllerCO2 Input 12 Bytes9.8 parts/million (ppm)CW
39Air quality controllerVOC Input 12 Bytes9.8 parts/million (ppm)CW
39Air quality controllerVOC (IAQ Index) Input 12 BytesCW
40Air quality controllerCO2 Input 22 Bytes9.8 parts/million (ppm)CW
40Air quality controllerVOC Input 22 Bytes9.8 parts/million (ppm)CW
40Air quality controllerVOC (IAQ Index) Input 22 BytesCW
41Air quality controllerCO2 Input 32 Bytes9.8 parts/million (ppm)CW
41Air quality controllerVOC Input 32 Bytes9.8 parts/million (ppm)CW
41Air quality controllerVOC (IAQ Index) Input 32 BytesCW
42Air quality controllerCO2 Input 42 Bytes9.8 parts/million (ppm)CW
42Air quality controllerVOC Input 42 Bytes9.8 parts/million (ppm)CW
42Air quality controllerVOC (IAQ Index) Input 42 BytesCW
43Air quality controllerCO2 Input 52 Bytes9.8 parts/million (ppm)CW
43Air quality controllerVOC Input 52 Bytes9.8 parts/million (ppm)CW
43Air quality controllerVOC (IAQ Index) Input 52 BytesCW
44Air quality controllerCO2 Input 62 Bytes9.8 parts/million (ppm)CW
44Air quality controllerVOC Input 62 Bytes9.8 parts/million (ppm)CW
44Air quality controllerVOC (IAQ Index) Input 62 BytesCW
44Air quality controllerHumidity Input 12 Bytes9.7 humidity (%)CW
45Air quality controllerCO2 Input 72 Bytes9.8 parts/million (ppm)CW
45Air quality controllerVOC Input 72 Bytes9.8 parts/million (ppm)CW
45Air quality controllerVOC (IAQ Index) Input 72 BytesCW
45Air quality controllerHumidity Input 22 Bytes9.7 humidity (%)CW
46Air quality controllerCO2 Input 82 Bytes9.8 parts/million (ppm)CW
46Air quality controllerVOC Input 82 Bytes9.8 parts/million (ppm)CW
46Air quality controllerVOC (IAQ Index) Input 82 BytesCW
46Air quality controllerHumidity Input 32 Bytes9.7 humidity (%)CW
47Air quality controllerCO2 Input 92 Bytes9.8 parts/million (ppm)CW
47Air quality controllerVOC Input 92 Bytes9.8 parts/million (ppm)CW
47Air quality controllerVOC (IAQ Index) Input 92 BytesCW
47Air quality controllerHumidity Input 42 Bytes9.7 humidity (%)CW
48Air quality controllerCO2 Input 102 Bytes9.8 parts/million (ppm)CW
48Air quality controllerVOC Input 102 Bytes9.8 parts/million (ppm)CW
48Air quality controllerVOC (IAQ Index) Input 102 BytesCW
48Air quality controllerHumidity Input 52 Bytes9.7 humidity (%)CW
51Air quality controllerLock controller1 Bit1.3 enableCW
52Air quality controllerOutput control value1 Byte5.1 percentage (0..100%)CRT
53Air quality controllerOutput level 11 Bit1.1 switchCRT
53Air quality controllerOutput Bit 01 Bit1.2 booleanCRT
54Air quality controllerOutput level 21 Bit1.1 switchCRT
54Air quality controllerOutput Bit 11 Bit1.2 booleanCRT
55Air quality controllerOutput level 31 Bit1.1 switchCRT
55Air quality controllerOutput Bit 21 Bit1.2 booleanCRT
56Air quality controllerOutput level 41 Bit1.1 switchCRT
57Air quality controllerOverride level1 Byte5.5 ratio (0..255)CW
57Air quality controllerOverride control value1 Byte5.1 percentage (0..100%)CW
60Logic - Comparator 1Input 11 Byte5.1 percentage (0..100%)CW
60Logic - Comparator 1Input 11 Byte5.5 ratio (0..255)CW
60Logic - Comparator 1Input 12 BytesCW
60Logic - Comparator 1Input 12 Bytes9.1 temperature (°C)CW
60Logic - Comparator 1Input 12 Bytes9.4 lux (Lux)CW
60Logic - Comparator 1Input 12 Bytes9.7 humidity (%)CW
60Logic - Comparator 1Input 12 Bytes9.8 parts/million (ppm)CW
61Logic - Comparator 1Input 21 Byte5.1 percentage (0..100%)CW
61Logic - Comparator 1Input 21 Byte5.5 ratio (0..255)CW
61Logic - Comparator 1Input 22 BytesCW
61Logic - Comparator 1Input 22 Bytes9.1 temperature (°C)CW
61Logic - Comparator 1Input 22 Bytes9.4 lux (Lux)CW
61Logic - Comparator 1Input 22 Bytes9.7 humidity (%)CW
61Logic - Comparator 1Input 22 Bytes9.8 parts/million (ppm)CW
62Logic - Comparator 1Input 31 Byte5.1 percentage (0..100%)CW
62Logic - Comparator 1Input 31 Byte5.5 ratio (0..255)CW
62Logic - Comparator 1Input 32 BytesCW
62Logic - Comparator 1Input 32 Bytes9.1 temperature (°C)CW
62Logic - Comparator 1Input 32 Bytes9.4 lux (Lux)CW
62Logic - Comparator 1Input 32 Bytes9.7 humidity (%)CW
62Logic - Comparator 1Input 32 Bytes9.8 parts/million (ppm)CW
63Logic - Comparator 1Input 41 Byte5.1 percentage (0..100%)CW
63Logic - Comparator 1Input 41 Byte5.5 ratio (0..255)CW
63Logic - Comparator 1Input 42 BytesCW
63Logic - Comparator 1Input 42 Bytes9.1 temperature (°C)CW
63Logic - Comparator 1Input 42 Bytes9.4 lux (Lux)CW
63Logic - Comparator 1Input 42 Bytes9.7 humidity (%)CW
63Logic - Comparator 1Input 42 Bytes9.8 parts/million (ppm)CW
64Logic - Comparator 1Input 51 Byte5.1 percentage (0..100%)CW
64Logic - Comparator 1Input 51 Byte5.5 ratio (0..255)CW
64Logic - Comparator 1Input 52 BytesCW
64Logic - Comparator 1Input 52 Bytes9.1 temperature (°C)CW
64Logic - Comparator 1Input 52 Bytes9.4 lux (Lux)CW
64Logic - Comparator 1Input 52 Bytes9.7 humidity (%)CW
64Logic - Comparator 1Input 52 Bytes9.8 parts/million (ppm)CW
65Logic - Comparator 1Output1 Byte5.1 percentage (0..100%)CRT
65Logic - Comparator 1Output1 Byte5.5 ratio (0..255)CRT
65Logic - Comparator 1Output2 BytesCRT
65Logic - Comparator 1Output2 Bytes9.1 temperature (°C)CRT
65Logic - Comparator 1Output2 Bytes9.4 lux (Lux)CRT
65Logic - Comparator 1Output2 Bytes9.7 humidity (%)CRT
65Logic - Comparator 1Output2 Bytes9.8 parts/million (ppm)CRT
66Logic - Comparator 1Lock1 Bit1.3 enableCW
66Logic - Comparator 1Lock1 Bit1.1 switchCW
67Logic - Comparator 1Info - Emergency operation1 Bit1.11 stateCRT
69Logic - Comparator 2Input 11 Byte5.1 percentage (0..100%)CW
69Logic - Comparator 2Input 11 Byte5.5 ratio (0..255)CW
69Logic - Comparator 2Input 12 BytesCW
69Logic - Comparator 2Input 12 Bytes9.1 temperature (°C)CW
69Logic - Comparator 2Input 12 Bytes9.4 lux (Lux)CW
69Logic - Comparator 2Input 12 Bytes9.7 humidity (%)CW
69Logic - Comparator 2Input 12 Bytes9.8 parts/million (ppm)CW
70Logic - Comparator 2Input 21 Byte5.1 percentage (0..100%)CW
70Logic - Comparator 2Input 21 Byte5.5 ratio (0..255)CW
70Logic - Comparator 2Input 22 BytesCW
70Logic - Comparator 2Input 22 Bytes9.1 temperature (°C)CW
70Logic - Comparator 2Input 22 Bytes9.4 lux (Lux)CW
70Logic - Comparator 2Input 22 Bytes9.7 humidity (%)CW
70Logic - Comparator 2Input 22 Bytes9.8 parts/million (ppm)CW
71Logic - Comparator 2Input 31 Byte5.1 percentage (0..100%)CW
71Logic - Comparator 2Input 31 Byte5.5 ratio (0..255)CW
71Logic - Comparator 2Input 32 BytesCW
71Logic - Comparator 2Input 32 Bytes9.1 temperature (°C)CW
71Logic - Comparator 2Input 32 Bytes9.4 lux (Lux)CW
71Logic - Comparator 2Input 32 Bytes9.7 humidity (%)CW
71Logic - Comparator 2Input 32 Bytes9.8 parts/million (ppm)CW
72Logic - Comparator 2Input 41 Byte5.1 percentage (0..100%)CW
72Logic - Comparator 2Input 41 Byte5.5 ratio (0..255)CW
72Logic - Comparator 2Input 42 BytesCW
72Logic - Comparator 2Input 42 Bytes9.1 temperature (°C)CW
72Logic - Comparator 2Input 42 Bytes9.4 lux (Lux)CW
72Logic - Comparator 2Input 42 Bytes9.7 humidity (%)CW
72Logic - Comparator 2Input 42 Bytes9.8 parts/million (ppm)CW
73Logic - Comparator 2Input 51 Byte5.1 percentage (0..100%)CW
73Logic - Comparator 2Input 51 Byte5.5 ratio (0..255)CW
73Logic - Comparator 2Input 52 BytesCW
73Logic - Comparator 2Input 52 Bytes9.1 temperature (°C)CW
73Logic - Comparator 2Input 52 Bytes9.4 lux (Lux)CW
73Logic - Comparator 2Input 52 Bytes9.7 humidity (%)CW
73Logic - Comparator 2Input 52 Bytes9.8 parts/million (ppm)CW
74Logic - Comparator 2Output1 Byte5.1 percentage (0..100%)CRT
74Logic - Comparator 2Output1 Byte5.5 ratio (0..255)CRT
74Logic - Comparator 2Output2 BytesCRT
74Logic - Comparator 2Output2 Bytes9.1 temperature (°C)CRT
74Logic - Comparator 2Output2 Bytes9.4 lux (Lux)CRT
74Logic - Comparator 2Output2 Bytes9.7 humidity (%)CRT
74Logic - Comparator 2Output2 Bytes9.8 parts/million (ppm)CRT
75Logic - Comparator 2Lock1 Bit1.3 enableCW
75Logic - Comparator 2Lock1 Bit1.1 switchCW
76Logic - Comparator 2Info - Emergency operation1 Bit1.11 stateCRT
78Temperature controllerPreset setpoint2 Bytes9.1 temperature (°C)CW
79Temperature controllerPreset Comfort setpoint2 Bytes9.1 temperature (°C)CW
79Temperature controllerCombined object: Preset setpoint 8 Bytes275.100 Temperature setpoint setting for 4 HVAC ModesCW
79Temperature controllerPreset (Basic) Comfort setpoint2 Bytes9.1 temperature (°C)CW
79Temperature controller(Basic) Comfort setpoint2 Bytes9.1 temperature (°C)CW
79Temperature controllerCombined object (Heating): Preset setpoint8 Bytes275.100 Temperature setpoint setting for 4 HVAC ModesCW
80Temperature controllerPreset Standby setpoint2 Bytes9.1 temperature (°C)CW
81Temperature controllerPreset Night setpoint2 Bytes9.1 temperature (°C)CW
82Temperature controllerPreset Frost protection setpoint2 Bytes9.1 temperature (°C)CW
82Temperature controllerPreset Heat protection setpoint2 Bytes9.1 temperature (°C)CW
83Temperature controllerCombined object (Cooling): Preset setpoint8 Bytes275.100 Temperature setpoint setting for 4 HVAC ModesCW
84Temperature controllerSend current setpoint2 Bytes9.1 temperature (°C)CRT
85Temperature controllerManual setpoint shift (2 Byte)2 Bytes9.2 temperature difference (K)CW
86Temperature controllerManual setpoint shift (1=+ / 0=-)1 Bit1.7 stepCW
86Temperature controllerManual setpoint shift (1 Byte)1 Byte6.10 counter pulses (-128..127)CW
87Temperature controllerSend status setpoint shift2 Bytes9.2 temperature difference (K)CRT
88Temperature controllerControl value Heating: Send control value1 Byte5.1 percentage (0..100%)CRT
88Temperature controllerControl value Heating: Send control value1 Bit1.1 switchCRT
88Temperature controllerControl value Heating/Cooling: Send control value1 Bit1.1 switchCRT
89Temperature controllerControl value Cooling: Send control value1 Byte5.1 percentage (0..100%)CRT
89Temperature controllerControl value Cooling: Send control value1 Bit1.1 switchCRT
90Temperature controllerControl value Heating: Send status1 Byte5.1 percentage (0..100%)CRT
90Temperature controllerControl value Heating/Cooling: Send status1 Byte5.1 percentage (0..100%)CRT
91Temperature controllerControl value Cooling: Send status1 Byte5.1 percentage (0..100%)CRT
92Temperature controllerAdditional level: Send control value Heating1 Bit1.1 switchCT
93Temperature controllerMode selection1 Byte20.102 HVAC modeCW
94Temperature controllerComfort operating mode: Comfort extension1 Bit1.10 start/stopCW
95Temperature controllerComfort mode1 Bit1.1 switchCW
96Temperature controllerNight mode1 Bit1.1 switchCW
97Temperature controllerFrost protection mode1 Bit1.1 switchCW
97Temperature controllerHeat protection mode1 Bit1.1 switchCW
97Temperature controllerFrost/Heat protection mode1 Bit1.1 switchCW
98Temperature controllerDPT_HVAC Status: Send controller status1 ByteCRT
98Temperature controllerDPT_HVAC Mode: Send controller status1 Byte20.102 HVAC modeCRT
99Temperature controllerDPT_HVAC Status: Send controller status1 ByteCRT
99Temperature controllerDPT_HVAC Mode: Send controller status1 Byte20.102 HVAC modeCRT
99Temperature controllerRHCC Status: Send controller status2 Bytes22.101 RHCC statusCRT
99Temperature controllerDPT_RTC combined status: Send controller status2 Bytes22.103 combined status RTCCRT
99Temperature controllerDPT_RTSM combined status: Send controller status1 Byte21.107 combined status RTSMCRT
100Temperature controllerSend Frost alarm1 Bit1.5 alarmCRT
101Temperature controllerSend Heat alarm1 Bit1.5 alarmCRT
102Temperature controllerReceive flow temperature Heating2 Bytes9.1 temperature (°C)CWT
103Temperature controllerReceive surface temperature Cooling2 Bytes9.1 temperature (°C)CWT
103Temperature controllerReceive dew point alarm1 Bit1.5 alarmCWT
104Temperature controllerDiagnosis status14 Bytes16.1 Character String (ISO 8859-1)CRT
105Temperature controllerWindow contact: 0 = closed / 1 = open1 Bit1.19 window/doorCWTU
105Temperature controllerWindow contact: 1=closed / 0=open1 Bit1.1 switchCWTU
106Temperature controllerLock object Heating: Lock control value1 Bit1.3 enableCRWTU
107Temperature controllerLock object Cooling: Lock control value1 Bit1.3 enableCRWTU
110Temperature controllerSwitchover: 1=Heating 0=Cooling1 Bit1.100 cooling/heatingCW
111Temperature controllerStatus: 1=Heating 0=Cooling1 Bit1.100 cooling/heatingCRT
112Temperature controllerSend Heating request1 Bit1.1 switchCRT
113Temperature controllerSend Cooling request1 Bit1.1 switchCRT
114Outdoor temperatureReceive measured value/reference value2 Bytes9.1 temperature (°C)CW
117Light channel 1 - Output 1Switch1 Bit1.1 switchCRT
117Light channel 1 - Output 1 (Day)Switch1 Bit1.1 switchCRT
117Light channel 1 - Output 1Dimming absolute1 Byte5.1 percentage (0..100%)CRT
117Light channel 1 - Output 1Scene1 Byte17.1 scene numberCRT
118Light channel 1 - Output (Night)Switch1 Bit1.1 switchCRT
119Light channel 1 - Output 2 (additional)Switch1 Bit1.1 switchCRT
120Light channel 1 - InputExternal button short1 Bit1.1 switchCW
121Light channel 1 - InputExternal button long1 Bit1.1 switchCW
122Light channel 1 - InputExternal motion (Slave)1 Bit1.1 switchCW
123Light channel 1 - InputStatus of actuator channel1 Bit1.1 switchCW
124Light channel 1 - InputLock motion detection1 Bit1.3 enableCW
125Light channel 1 - InputForced guidance2 Bit2.1 switch controlCW
125Light channel 1 - Inputlock object1 Bit1.3 enableCW
126Light channel 1 - InputLock object ON1 Bit1.3 enableCW
127Light channel 1 - StatusAutomatic mode1 Bit1.11 stateCRT
127Light channel 1 - StatusLock/Manual mode1 Bit1.11 stateCRT
128Light channel 1 - InputSwitch dark1 Bit1.1 switchCW
129Light channel 1 - InputTeach-in dimming value for ON1 Byte5.1 percentage (0..100%)CWTU
130Light channel 1 - InputFollow-up time 10 - 65000s2 Bytes7.5 time (s)CWTU
132Light channel 2 - Output 1Switch1 Bit1.1 switchCRT
132Light channel 2 - Output 1 (Day)Switch1 Bit1.1 switchCRT
132Light channel 2 - Output 1Dimming absolute1 Byte5.1 percentage (0..100%)CRT
132Light channel 2 - Output 1Scene1 Byte17.1 scene numberCRT
133Light channel 2 - Output (Night)Switch1 Bit1.1 switchCRT
134Light channel 2 - Output 2 (additional)Switch1 Bit1.1 switchCRT
135Light channel 2 - InputExternal button short1 Bit1.1 switchCW
136Light channel 2 - InputExternal button long1 Bit1.1 switchCW
137Light channel 2 - InputExternal motion (Slave)1 Bit1.1 switchCW
138Light channel 2 - InputStatus of actuator channel1 Bit1.1 switchCW
139Light channel 2 - InputLock motion detection1 Bit1.3 enableCW
140Light channel 2 - InputForced guidance2 Bit2.1 switch controlCW
140Light channel 2 - Inputlock object1 Bit1.3 enableCW
141Light channel 2 - InputLock object ON1 Bit1.3 enableCW
142Light channel 2 - StatusAutomatic mode1 Bit1.11 stateCRT
142Light channel 2 - StatusLock/Manual mode1 Bit1.11 stateCRT
143Light channel 2 - InputSwitch dark1 Bit1.1 switchCW
144Light channel 2 - InputTeach-in dimming value for ON1 Byte5.1 percentage (0..100%)CWTU
145Light channel 2 - InputFollow-up time 10 - 65000s2 Bytes7.5 time (s)CWTU
147Light channel 3 - Output 1Switch1 Bit1.1 switchCRT
147Light channel 3 - Output 1 (Day)Switch1 Bit1.1 switchCRT
147Light channel 3 - Output 1Dimming absolute1 Byte5.1 percentage (0..100%)CRT
147Light channel 3 - Output 1Scene1 Byte17.1 scene numberCRT
148Light channel 3 - Output (Night)Switch1 Bit1.1 switchCRT
149Light channel 3 - Output 2 (additional)Switch1 Bit1.1 switchCRT
150Light channel 3 - InputExternal button short1 Bit1.1 switchCW
151Light channel 3 - InputExternal button long1 Bit1.1 switchCW
152Light channel 3 - InputExternal motion (Slave)1 Bit1.1 switchCW
153Light channel 3 - InputStatus of actuator channel1 Bit1.1 switchCW
154Light channel 3 - InputLock motion detection1 Bit1.3 enableCW
155Light channel 3 - InputForced guidance2 Bit2.1 switch controlCW
155Light channel 3 - Inputlock object1 Bit1.3 enableCW
156Light channel 3 - InputLock object ON1 Bit1.3 enableCW
157Light channel 3 - StatusAutomatic mode1 Bit1.11 stateCRT
157Light channel 3 - StatusLock/Manual mode1 Bit1.11 stateCRT
158Light channel 3 - InputSwitch dark1 Bit1.1 switchCW
159Light channel 3 - InputTeach-in dimming value for ON1 Byte5.1 percentage (0..100%)CWTU
160Light channel 3 - InputFollow-up time 10 - 65000s2 Bytes7.5 time (s)CWTU
177HVAC - OutputSwitch1 Bit1.1 switchCRT
177HVAC - OutputDimming absolute1 Byte5.1 percentage (0..100%)CRT
177HVAC - OutputScene1 Byte17.1 scene numberCRT
180HVAC - InputExternal button short1 Bit1.1 switchCW
181HVAC - InputExternal button long1 Bit1.1 switchCW
182HVAC - InputExternal motion1 Bit1.1 switchCW
183HVAC - InputStatus of actuator channel1 Bit1.1 switchCW
184HVAC - InputLock motion detection1 Bit1.3 enableCW
185HVAC - InputForced guidance2 Bit2.1 switch controlCW
185HVAC - Inputlock object1 Bit1.3 enableCW
186HVAC - InputLock object ON1 Bit1.3 enableCW
187HVAC - StatusAutomatic mode1 Bit1.11 stateCRT
187HVAC - StatusLock/Manual mode1 Bit1.11 stateCRT
188HVAC - InputSwitch dark1 Bit1.1 switchCW
189HVAC - InputTeach-in dimming value for ON1 Byte5.1 percentage (0..100%)CWTU
190HVAC - InputFollow-up time 10 - 65000s2 Bytes7.5 time (s)CWTU
192Alarm - OutputSwitch1 Bit1.1 switchCRT
192Alarm - Output (Day)Switch1 Bit1.1 switchCRT
193Alarm - Output (Night)Switch1 Bit1.1 switchCRT
200Alarm - InputLock1 Bit1.3 enableCW
200Alarm - InputRelease1 Bit1.3 enableCW
207LED greenSwitch1 Bit1.1 switchCW
207LED greenFlashing1 Bit1.1 switchCW
208LED redFlashing1 Bit1.1 switchCW
209LED whiteSwitch1 Bit1.1 switchCW
209LED whiteValue1 Byte5.1 percentage (0..100%)CW
210RGB traffic lightInput level 11 Bit1.1 switchCW
210RGB traffic lightInput1 Byte5.5 ratio (0..255)CW
210RGB traffic lightInput3 Bytes232.600 RGB value 3x(0..255)CW
210RGB traffic lightInput3 BytesCW
211RGB traffic lightInput level 21 Bit1.1 switchCW
212RGB traffic lightInput level 31 Bit1.1 switchCW
213RGB traffic lightInput level 41 Bit1.1 switchCW
214RGB traffic lightBrightness (1 = bright / 0 = dark)1 Bit1.6 binary valueCW
215PIR ScenesInput1 Byte17.1 scene numberCW
216BrightnessThreshold switch1 Bit1.1 switchCRT
217BrightnessMeasured value2 Bytes9.4 lux (Lux)CRT
218BrightnessSet switch-on threshold for light channels2 Bytes9.4 lux (Lux)CW
219Input Teach-inStart calibration1 Bit1.10 start/stopCW
220Input Teach-inStatus absolute dimming value1 Byte5.1 percentage (0..100%)CW
226Logic 1 {{0}}Input C1 Bit1.2 booleanCWTU
227Logic 1 {{0}}Input D1 Bit1.2 booleanCWTU
228Logic 1 {{0}}Input E1 Bit1.2 booleanCWTU
229Logic 1 {{0}}Input F1 Bit1.2 booleanCWTU
230Logic 1 {{0}}Output 11 Bit1.2 booleanCRT
230Logic 1 {{0}}Output 11 Byte17.1 scene numberCRT
230Logic 1 {{0}}Output 11 Byte5.5 ratio (0..255)CRT
230Logic 1 {{0}}Output 11 Byte5.1 percentage (0..100%)CRT
230Logic 1 {{0}}Output 12 Bit2.1 switch controlCRT
231Logic 2 {{0}}Input C1 Bit1.2 booleanCWTU
232Logic 2 {{0}}Input D1 Bit1.2 booleanCWTU
233Logic 2 {{0}}Input E1 Bit1.2 booleanCWTU
234Logic 2 {{0}}Input F1 Bit1.2 booleanCWTU
235Logic 2 {{0}}Output 21 Bit1.2 booleanCRT
235Logic 2 {{0}}Output 21 Byte17.1 scene numberCRT
235Logic 2 {{0}}Output 21 Byte5.5 ratio (0..255)CRT
235Logic 2 {{0}}Output 21 Byte5.1 percentage (0..100%)CRT
235Logic 2 {{0}}Output 22 Bit2.1 switch controlCRT
236Logic 3 {{0}}Input C1 Bit1.2 booleanCWTU
237Logic 3 {{0}}Input D1 Bit1.2 booleanCWTU
238Logic 3 {{0}}Input E1 Bit1.2 booleanCWTU
239Logic 3 {{0}}Input F1 Bit1.2 booleanCWTU
240Logic 3 {{0}}Output 31 Bit1.2 booleanCRT
240Logic 3 {{0}}Output 31 Byte17.1 scene numberCRT
240Logic 3 {{0}}Output 31 Byte5.5 ratio (0..255)CRT
240Logic 3 {{0}}Output 31 Byte5.1 percentage (0..100%)CRT
240Logic 3 {{0}}Output 32 Bit2.1 switch controlCRT
241Logic 4 {{0}}Input C1 Bit1.2 booleanCWTU
242Logic 4 {{0}}Input D1 Bit1.2 booleanCWTU
243Logic 4 {{0}}Input E1 Bit1.2 booleanCWTU
244Logic 4 {{0}}Input F1 Bit1.2 booleanCWTU
245Logic 4 {{0}}Output 41 Bit1.2 booleanCRT
245Logic 4 {{0}}Output 41 Byte17.1 scene numberCRT
245Logic 4 {{0}}Output 41 Byte5.5 ratio (0..255)CRT
245Logic 4 {{0}}Output 41 Byte5.1 percentage (0..100%)CRT
245Logic 4 {{0}}Output 42 Bit2.1 switch controlCRT
246Constant lightSwitch1 Bit1.1 switchCW
247Constant lightDimming relative4 Bit3.7 dimming controlCW
248Constant lightDimming absolute1 Byte5.1 percentage (0..100%)CW
250Constant lightLock1 Bit1.3 enableCW
251Constant lightScenes1 Byte17.1 scene numberCW
251Constant lightScene control1 Byte18.1 scene controlCW
252Constant lightDimming absolute - middle1 Byte5.1 percentage (0..100%)CRT
253Constant lightDimming absolute - wall1 Byte5.1 percentage (0..100%)CRT
254Constant lightDimming absolute - window1 Byte5.1 percentage (0..100%)CRT
255Constant lightStatus1 Bit1.11 stateCRT
256In operationOutput1 Bit1.11 stateCRT
257Day/Night - Presence detectorDay = 1 / Night = 01 Bit1.24 day/nightCWTU
257Day/Night - Presence detectorNight = 1 / Day = 01 Bit1.1 switchCWTU
258Day/Night - Air quality controllerDay = 1 / Night = 01 Bit1.24 day/nightCWTU
258Day/Night - Air quality controllerNight = 1 / Day = 01 Bit1.1 switchCWTU
Parameters (526)
ParameterTypeDefault
Startup timeunsignedInt 2…2402
Send "In operation" cyclicallylistnot active
Day/Night switchoverlistactive
Value for Day/NightlistDay = 1 / Night = 0
Day/Night object after bus power returnlistrequest
Language diagnosis textlistGerman
Toggle Day/Nightlistat next presence
Trigger sensitivitylist6
Trigger sensitivity "Day"list6
Trigger sensitivity "Night"list3 (low)
Presence sensitivitylist8 (high)
Reduce sensitivity for sensorslistnot active
Trigger sensitivitylist2
Trigger sensitivity "Day"list2
Trigger sensitivity "Night"list1 (very low)
Switch-on thresholdunsignedInt 5…1000400
Switch-on threshold "Day"unsignedInt 5…1000400
Switch-on threshold "Night"unsignedInt 5…1000400
Switch-off on exceedancelistnot active
Switches OFF on exceedance ofunsignedInt 75…1000800
Fallback of forced guidance/locklistnot active
Follow-up time for forced guidance/locklist3 min
Follow-up time for forced guidance/lock "Day"list3 min
Follow-up time for forced guidance/lock "Night"list3 min
Fallback time for forced guidance/locklist3 min
Fallback time for forced guidance/lock "Day"list3 min
Fallback time for forced guidance/lock "Night"list3 min
Fallback: External button long (Manual => Auto)listafter presence and follow-up time
Manual mode follow-up time for ONlist3 min
Manual mode, follow-up time at OFFlist3 min
Manual mode, follow-up time at ON "Day"list3 min
Manual mode, follow-up time at OFF "Day"list3 min
Manual mode, follow-up time at ON "Night"list3 min
Manual mode, follow-up time at OFF "Night"list3 min
Fallback time "manual mode" for ONlist3 min
Fallback time "manual mode" for OFFlist3 min
Fallback time "manual mode" for ON "Day"list3 min
Fallback time "manual mode" for OFF "Day"list3 min
Fallback time "manual mode" for ON "Night"list3 min
Fallback time "manual mode" for OFF "Night"list3 min
CO2 measurementlistactive
VOC measurementlistactive
Temperature measurementlistactive
Relative humidity measurementlistactive
Send measured value on changelistnot active
Send measured value on change offloat 10…50020
Send measured value cyclicallylistnot active
Messageslistnot active
Upper message valuefloat 400…20001500
Lower message valuefloat 400…2000500
Calibration value for internal sensorfloat -500…5000
Sensor internal/externallist100 % internal
Measured value output inlistppm
IAQ Index descriptionpicture
Send measured value on change ofunsignedInt 1…505
Upper message valuefloat 100…50002000
Lower message valuefloat 100…50001000
Upper message valueunsignedInt 0…500200
Lower message valueunsignedInt 0…50050
Send measured value on change offloat 0.1…20.1
Upper message valuefloat 20…4528
Lower message valuefloat 3…3018
Calibration value for internal sensorfloat -10…100
Send measured value on change offloat 1…101
Upper message valuefloat 25…10070
Lower message valuefloat 0…7530
Calibration value for internal sensorfloat -20…200
Send measured value on change oflist5 %
Upper message valuelist50 %
Lower message valuelist10 %
Air quality traffic lightlistnot active
Activate aslistStep output
Sensor for Air quality traffic lightlistCO2
Hysteresis inlistpercent
Hysteresislist5 %
HysteresisunsignedInt 10…500100
HysteresisunsignedInt 0…505
Traffic light withlist3 levels
Scene number for level 1list1
Scene number for level 2list2
Scene number for level 3list4
Scene number for level 3list3
Scene number for level 4list4
Colour value for level 1color#00FF00
Colour value for level 2color#FFFF00
Colour value for level 3color#FF0000
Colour value for level 3color#FF8000
Colour value for level 4color#FF0000
Threshold value 1 (level 1 -> level 2)unsignedInt 0…2000800
Threshold value 2 (level 2 -> level 3)unsignedInt 0…20001200
Threshold value 1 (level 1 -> level 2)unsignedInt 0…500100
Threshold value 2 (level 2 -> level 3)unsignedInt 0…500250
Threshold value 3 (level 3 -> level 4)unsignedInt 0…20001700
Threshold value 3 (level 3 -> level 4)unsignedInt 0…500400
Sending condition of outputlistnot active
Send cyclically every…list60 min
Air quality controllistnot active
Activate aslistStep controller Bit coded
Controller: Actual valuelistCO2
Number of external room sensorslistnot active
Air quality control with humidity increase by…listnot active
Threshold for exceeding the air humiditylist75 %
Follow-up time after falling belowunsignedInt 1…6030
Minimum levellistLevel 0
Maximum levellistLevel 4
Minimum level for "Day"listLevel 0
Maximum level for "Day"listLevel 4
Minimum level for "Night"listLevel 0
Maximum level for "Night"listLevel 2
Threshold level 1unsignedInt 400…2000600
Threshold level 2unsignedInt 400…2000800
Threshold level 3unsignedInt 400…20001000
Threshold level 4unsignedInt 400…20001200
Hysteresislist10 %
HysteresisunsignedInt 10…50050
Threshold level 1unsignedInt 50…50080
Threshold level 2unsignedInt 50…500160
Threshold level 3unsignedInt 50…500240
Threshold level 4unsignedInt 50…500320
Hysteresis inlistIAQ
Behaviour on locklistnot active
Level at locklistLevel 1
Control value (level 1)list25 %
Control value (level 2)list50 %
Control value (level 3)list75 %
Control value (level 4)list100 %
Control value for "Day" (level 1)list25 %
Control value for "Day" (level 2)list50 %
Control value for "Day" (level 3)list75 %
Control value for "Day" (level 4)list100 %
Control value for "Night" (level 1)list10 %
Control value for "Night" (level 2)list30 %
Control value for "Night" (level 3)list50 %
Control value for "Night" (level 4)list70 %
Value at locklist0 %
SetpointunsignedInt 400…2000600
SetpointunsignedInt 0…50080
Minimum control valuelist0 %
Maximum control valuelist100 %
Setpoint validlistfor "Day" ("Night" not active)
Reset the value set via object "Preset setpoint" to parameter setting at the next Day/Night switchoverlistactive
Setpoint for "Day"unsignedInt 400…2000600
Setpoint for "Day"unsignedInt 0…50080
Minimum control value for "Day"list0 %
Maximum control value for "Day"list100 %
Setpoint for "Night"unsignedInt 400…2000700
Setpoint for "Night"unsignedInt 0…500100
Minimum control value for "Night"list0 %
Maximum control value for "Night"list30 %
Proportional valueunsignedInt 100…20001000
Proportional valueunsignedInt 10…250100
Reset timelist15 min
Send setpoint/output cyclicallylistnot active
Operating modelistnot active
PrioritylistFrost(Heat protection)/Comfort/Night/Standby
Setpoints for Standby/Nightlistdepending on setpoint Comfort (Basic)
Setpoint Comfort (Basic)float 7…3521
Setpoint Standbyfloat 7…3519
Setpoint Nightfloat 7…3518
Standby reductionlist2,0 K
Night reductionlist3,0 K
Setpoint Frost protectionfloat 3…127
Separate objects for setpoints Comfort/Standby/Night/Frost protectionlistnot active
Maximum setpoint shiftfloat 0…103
Setpoint shift via 1Bit/1Byte objectlist1 Bit
Step widthlist0,5 K
Status setpoint shiftlistnot active
Setpoint shift applies tolistComfort
Action if shift during Night/Standbylistno action
Delete setpoint shift after change of operating modelistnot active
Delete setpoint shift after new absolute setpointlistactive
Reset setpoints to the parameter setting after change of operating modelistactive
Reset basic setpoint to configured value after change of operation modelistactive
Delete setpoint shift after new basic setpointlistactive
Send setpoint changeslistactive
Send current setpoint cyclicallylistnot active
Comfort extention with timelistnot active
Comfort extention timelistnot active
Operating mode after resetlistComfort with configured setpoint
Operating mode after reprogramminglistComfort
HVAC status objectlistHVAC Mode (DPT 20.102)
Additional HVAC Status objectlistnot active
Send HVAC Status object cyclicallylistnot active
Lock object: Control value Heatinglistnot active
Object for Heating requestlistnot active
Flow temperaturelistnot active
Limit flow temperature tounsignedInt 10…6040
Setpoint Comfort (Basic)float 7…3523
Setpoint Standbyfloat 7…3524
Setpoint Nightfloat 7…3525
Standby increaselist2,0 K
Night increaselist3,0 K
Setpoint Heat protectionfloat 24…4035
Separate objects for setpoints Comfort/Standby/Night/Heat protectionlistnot active
Lock object: Control value Coolinglistnot active
Object for Cooling requestlistnot active
Reference control via outdoor temperaturelistnot active
Reference variable minimumunsignedInt 10…6028
Reference variable maximumunsignedInt 10…6038
Setpoint change at maximum reference variablefloat 1…1010
Offset to dew point temperaturelist0 K
(Basic) Comfort setpointfloat 7…3521
Switchover Heating/Coolinglistautomatically
Dead zone between Heating and Coolinglist2,0 K
Dead zone between Heating and Coolinglist0 K
Separate objects for setpoints Comfort/Standby/Night/Frost-/Heat protectionlistnot active
Operating mode after reprogramminglistComfort (Cooling)
Alarmslistnot active
Frost alarm if value lessunsignedInt 3…107
Heat alarm if value greaterunsignedInt 25…4035
Window contactlistnot active
State of windowlist0=closed / 1=open (standard DPT)
Delay timeunsignedInt 0…2405
Action when opening the windowlistforce Frost/Heat protection
Action when closing the windowlistHVAC Modus before locking
Release timelist12 h
Control valuelistPI control continuous
Direction of controllerlistnormal
Maximum value of control valuelist100%
Heating systemlistUnderfloor Heating (4K / 150min)
Proportional rangelist4 K
Reset timelist150 min
PWM cyclelist10 min
Switching hysteresislist2,0 K
Send control value cyclicallylist5 min
Additional levellistnot active
Direction of action with rising temperaturelistnormal
Control valuelist2-step control (switching)
Distancelist2,0 K
Operating modelistPI control continuous
Cooling systemlistCooling ceiling (4K / 150min)
Systemlist2 pipe / 1 circuit (Heating or Cooling)
Light channel 1listactive
Light channel 2listnot active
Light channel 3listnot active
LED whitelistnot active
Brightness at "Night"list10 %
Light channels influence the brightness measurementlistyes (several lights in the room)
Send brightness on change oflist10 %
Correction valuelist0 %
Room reflection factorlist0,4 medium
Threshold switchlistnot active
Threshold switch switches atunsignedInt 5…1000300
Hysteresis of threshold switchunsignedInt 5…20030
Object value when exceededlistON
Object value at "Day" and exceedancelistON
Object value at "Night" and exceedancelistON
Object value when falling belowlistOFF
SendlistON and OFF
Send at "Day"listON and OFF
Send at "Night"listON and OFF
Brightness value for teach-inunsignedInt 200…1000450
Teach-in value when loading applicationlistuse default value
Active sensorslist123
Sensitivitylistbasic setting (General setting)
Trigger sensitivitylist3 (low)
Trigger sensitivity "Day"list3 (low)
Brightnesslistbasic setting or object "Switch dark" is active
Channel operating modelistfully automatic
Motion filter in standbylistnot active, no filtering
Reduction of follow-up timelistnot active
Maximum duration for short time presencelist20 s
Follow-up time for short time presencelist30 s
Follow-up timelist3 min
Follow-up time "Day"list3 min
Follow-up time "Night"list30 s
Forced guidance or lock objectlistforced guidance object (2 Bit)
Action on lockinglistlock motion (lock current state)
Fallback of forced guidance/lock (General setting)listactive
Object type for output - LightlistSwitch
Output objects for Day/Nightlistone common object
Dimming value for ONlist100 %
Dimming value for OFFlist0 %
Dimming value at "Day" for ONlist100 %
Dimming value at "Day" for OFFlist0 %
Dimming value at "Night" for ONlist30 %
Dimming value at "Night" for OFFlist0 %
Orientation light for leavinglistswitch-off immediately
Switch-off delaylist30 s
Switch-off dimming valuelist30 %
Switch-off delay for "Day"list30 s
Switch-off dimming value for "Day"list30 %
Switch-off delay for "Night"list30 s
Switch-off dimming value for "Night"list20 %
Scene number for ONlist1
Scene number for OFFlist2
Scene number at "Day" for ONlist1
Scene number at "Day" for OFFlist2
Scene number at "Night" for ONlist3
Scene number at "Night" for OFFlist4
Output object 1 sendslistON and OFF
Output object 1 sends ON cyclicallylistnot active
Output object 1 sendslistdimming value for ON and OFF
Output object 1 sends value for ON cyclicallylistnot active
Output object 1 sendslistscene number for ON and OFF
Output object 1 sends scene for ON cyclicallylistnot active
Output 2 (Additional switch object)listnot active
External button short reacts tolistON and OFF
Idle time after external button short is OFFunsignedInt 1…305
External button long reacts tolistON and OFF
Idle time after switch offunsignedInt 0…601
If Night light is activelistswitch to Day light
If output "Day" is already ONlistswitch to manual mode
If output is already ONlistswitch to manual mode
Status informationlistnot active
HVAC Channellistnot active
Number of monitoring time slotslist3
Length of monitoring time slotunsignedInt 0…3000030
Object type for output - HVAClistSwitch
Object value for ONlistvalue 1
Object value for OFFlistvalue 0
Object value at "Day" for ONlistvalue 1
Object value at "Day" for OFFlistvalue 0
Object value at "Night" for ONlistvalue 1
Object value at "Night" for OFFlistvalue 0
Output object 1 sends cyclicallylistnot active
Output object 1 sends value cyclicallylistnot active
Output object 1 sends scene cyclicallylistnot active
Alarm/Message channellistnot active
Trigger sensitivity "Night"list2
Presence sensitivitylist6
Interference / motion filterlistnot active, no filtering
Length of monitoring time slotlist2 s
Number of monitoring time slotlist3
Lock or release objectlistlock object
Fallback of forced guidance/lock (General setting)listnot active
Output object sends atlistON and OFF
Output object sends cycliclistnot active
Scene A numberlistnot active
Scene A Light channel 1listnot active
Scene A Light channel 2listnot active
Scene A Light channel 3listnot active
Scene B numberlistnot active
Scene B Light channel 1listnot active
Scene B Light channel 2listnot active
Scene B Light channel 3listnot active
Scene C numberlistnot active
Scene C Light channel 1listnot active
Scene C Light channel 2listnot active
Scene C Light channel 3listnot active
Scene D numberlistnot active
Scene D Light channel 1listnot active
Scene D Light channel 2listnot active
Scene D Light channel 3listnot active
Scene E numberlistnot active
Scene E Light channel 1listnot active
Scene E Light channel 2listnot active
Scene E Light channel 3listnot active
Scene F numberlistnot active
Scene F Light channel 1listnot active
Scene F Light channel 2listnot active
Scene F Light channel 3listnot active
Scene G numberlistnot active
Scene G Light channel 1listnot active
Scene G Light channel 2listnot active
Scene G Light channel 3listnot active
Scene H numberlistnot active
Scene H Light channel 1listnot active
Scene H Light channel 2listnot active
Scene H Light channel 3listnot active
Constant light controllistnot active
Control sunlightlistlittle
Selection of lighting groupslist1 lighting group
Influence of proportional zone control - walllistmedium (x0,7)
Influence of proportional zone control - windowlistmedium (x1,6)
Switch constant light vialistPresence (Light channel 1)
Time from switching on to start of controllist5 s
Controller switches the light offlistnot active
Minimum dimming value at dimming outputlist0 %
Maximum dimming value at dimming outputlist100 %
Switch-on value “Day”listcalculate switch-on value (via lux value)
Dimming value at switch-on "Day"list80 %
Preset setpoint at "Day"list450 Lux
Constant light control at "Night"listactive
Dimming value at switch-on “Night”list20 %
Switch-on value “Night”listparameter (settable dimming value)
Preset setpoint at "Night"list50 Lux
Brightness value at switch-onlistuse parameter value
CL status sends value 1listwhen control active
Send dimming value cyclicallylistnot active
Send dimming value on change oflist0,5 %
Behaviour of CL on relative dimminglistuse new dimming value
Time for relative dimminglist20 s
Standby/Orientation lightlistnot active
Standby setpointlist50 %
Standby timelist10 s
lock objectlistnot active
Lock object value = 1listON (100%)
Valuelist0 %
Lock object value = 0listrestore previous state
Sceneslistnot active
Behavior at setting of scenelistsets only switch-on value
Scenes learning modelistactive
Scene 1list260 Lux
Scene 2list300 Lux
Scene 3list360 Lux
Scene 4list400 Lux
Scene 5list450 Lux
Scene 6list500 Lux
Scene 7list550 Lux
Scene 8list600 Lux
Dead bandunsignedInt 1…501
Cycle timeunsignedInt 1…32767500
Kp - mulltipliersignedInt -32768…3276720
Kp - dividersignedInt -32768…3276710
Ki - mulltipliersignedInt -32768…327671
Ki - dividersignedInt -32768…327673500
Kd - multipliersignedInt -32768…327670
Kp - mulltipliersignedInt -32768…3276710
Ki - dividersignedInt -32768…327674500
Cycle time [0,1s]unsignedInt 1…32767500
### Kd - multipliersignedInt -32768…327670
### Ki - dividersignedInt -32768…327674500
### Ki - mulltipliersignedInt -32768…327671
### Kp - dividersignedInt -32768…3276710
### Kp - mulltipliersignedInt -32768…3276710
### Ki - dividersignedInt -32768…327673500
### Kp - mulltipliersignedInt -32768…3276720
Logic function 1listnot active
Description of functiontext
Additional texttext
FunctionlistAND
Output objectlistSwitch
Sending conditionliston change of output
Outputlistnormal
Scene number for output value "False"list1
Scene number for output value "True"list1
Datapoint typelist1 Byte DPT 5.005 Decimal (0…255)
Value for output value "False"unsignedInt 0…2550
Value for output value "True"unsignedInt 0…2550
Percent value for output value "False"list0 %
Percent value for output value "True"list0 %
Forced guidance for output value "False"list00 - no priority, Off
Forced guidance for output value "True"list00 - no priority, Off
Internal input Alistnot active
Object numberunsignedInt 0…2550
Internal input Blistnot active
External input Clistnot active
Preset logic input after reset withlistvalue 0
External input Dlistnot active
External input Elistnot active
External input Flistnot active
Logic function 2listnot active
Logic function 3listnot active
Logic function 4listnot active
Request inputs after bus power returnlistnot active
RGB LEDs react tolistinternal air quality traffic light
Control bylistTraffic light level via 1 Bit objects
Brightness of levelslistalways set to "bright"
Level 1listdisplay permanently
State flashing at intervals of ...unsignedInt 10…30030
Number of flashesunsignedInt 1…51
Value - brightcolor#00FF00
Value - darkcolor#007F00
Level 2listdisplay permanently
Value - brightcolor#7F7F00
Value - darkcolor#3F3F00
Value - brightcolor#B14D00
Value - darkcolor#552600
Value - brightcolor#FF0000
Value - darkcolor#7F0000
Level 3listdisplay permanently
Light channel 1unsignedInt 0…11
Light channel 2unsignedInt 0…10
Light channel 3unsignedInt 0…10
RGB valuelistgreen - bright
RGB valuelistgreen - dark
Manual mode ONlistnot active
RGB valuelistblue - bright
RGB valuelistblue - dark
Manual mode OFFlistnot active
RGB valuelistred - bright
RGB valuelistred - dark
Lock/Forced guidance ONlistnot active
Lock/Forced guidance OFFlistnot active
LED brightnesslistalways set to "bright"
Display behaviourlistdisplay permanently
RGB LEDs flashing at intervals of ...unsignedInt 10…30030
Display behaviour LED "bright"listvia fixed values
Display behaviour LED "dark"listvia fixed values
RGB valuecolor#007F00
RGB valuecolor#00FF00
RGB valuecolor#7F7F00
RGB valuecolor#3F3F00
RGB valuecolor#B14D00
RGB valuecolor#552600
RGB valuecolor#FF0000
RGB valuecolor#7F0000
RGB valuecolor#000019
RGB valuecolor#000005
Logic function: Comparator 1listnot active
Datapoint type of the comparisonlist1 Byte DPT 5.001 Percent (0...100%)
Output typelistMinimum value
Input 1listactive
Input 2listactive
Input 3listnot active
Input 4listnot active
Input 5listnot active
Monitoringlistnot active
Send on change oflist1 %

First 500 of 526 parameters shown. Download the .knxprod for the full list.

Version history

ApplicationApp noFingerprintFirst seenSizeFile
Combi-Presence Detector 1.0 latest$0078C9D12026-11-25397 KBDownload

About this file

This is the official ETS product database for the MDT technologies GmbH SCN-KP360K3.03 Combi-Presence Detector 360° with room climate sensors (SCN-KP360K3.03), published by the manufacturer in the KNX online catalog. To use it, open ETS, go to Catalogs → Import and choose the downloaded .knxprod file. The device then appears in your catalog and can be added to a project. Older versions are kept so existing projects can be matched to the application program they were commissioned with.