KNX Gateway for Panasonic Etherea air conditioning units, flush mounted SCN-ACG0PAN.01
MDT technologies GmbH · Order number SCN-ACG0PAN.01 · System Devices › KNX Gateways
Download .knxprod KNX Gateway for Panasonic Etherea air conditioning units, flush mounted 1.5 · 196 KB
Product
| Manufacturer | MDT technologies GmbH |
|---|---|
| Product name | KNX Gateway for Panasonic Etherea air conditioning units, flush mounted |
| Order number | SCN-ACG0PAN.01 |
| Hardware | PA AC Interface |
| Medium | Twisted Pair |
| Bus current (mA) | 6 |
| Rail mounted | No |
| Registration | Certified · 2026-06-22 |
| Languages | de-DE, en-US, es-ES |
| Catalog entry | M-0083_H-INT03-1-O0077_HP-0483-15-A264-O0077_CI-SCN.2DACG0PAN.2E01-1 |
| Fingerprint | A264 |
| SHA-256 | 792a3a5d92b273aa081f2fc186699715f13edd0ef9d9819ae1172ee19c7de552 |
| First seen | 2026-11-25 |
| Markets | 69 markets |
Application program: KNX Gateway for Panasonic Etherea air conditioning units, flush mounted 1.5
| Application number | $0483 |
|---|---|
| Version | 1.5 |
| Mask version | MV-0025 (2.5) |
| KNX Data Secure | No |
| Minimum ETS version | 5.0 |
| Parameters | 320 |
| Group objects | 177 |
Group objects (177)
| No | Name | Function | Size | DPT | Flags |
|---|---|---|---|---|---|
| 0 | ON/OFF | 1 = ON, 0 = OFF | 1 Bit | 1.1 switch | CWT |
| 1 | Mode: Powerful | 1 = Set Powerful Mode | 1 Bit | 1.2 boolean | CWT |
| 2 | Mode: Quiet | 1 = Set Quiet Mode | 1 Bit | 1.2 boolean | CWT |
| 3 | HVAC Mode | 0 = Auto, 1 = Heat, 3 = Cool, 9 = Fan, 14 = Dry | 1 Byte | CWT | |
| 4 | Mode: Cool/Heat | 0 = Cool, 1 = Heat | 1 Bit | CWT | |
| 5 | Mode: Cool & On | 0 % = Off; 0.1 % - 100 % = On + Cool | 1 Byte | 5.1 percentage (0..100%) | CWT |
| 6 | Mode: Heat & On | 0 % = Off; 0.1 % - 100 % = On + Heat | 1 Byte | 5.1 percentage (0..100%) | CWT |
| 7 | Mode: Auto | 1 = Set AUTO Mode | 1 Bit | 1.2 boolean | CWT |
| 8 | Mode: Heat | 1 = Set HEAT Mode | 1 Bit | 1.2 boolean | CWT |
| 9 | Mode: Cool | 1 = Set COOL Mode | 1 Bit | 1.2 boolean | CWT |
| 10 | Mode: Fan | 1 = Set FAN Mode | 1 Bit | 1.2 boolean | CWT |
| 11 | Mode: Dry | 1 = Set DRY Mode | 1 Bit | 1.2 boolean | CWT |
| 12 | Mode [+/-] | 0 = Decrease, 1 = Increase | 1 Bit | CW | |
| 12 | Mode [+/-] | 0 = Up, 1 = Down | 1 Bit | 1.8 up/down | CW |
| 13 | Fan Speed / 5 Speeds | Thresholds: 30 %, 50 %, 70 %, 90 % | 1 Byte | 5.1 percentage (0..100%) | CWT |
| 13 | Fan Speed / 5 Speeds | Speed values: 1, 2, 3, 4, 5 | 1 Byte | 5.10 counter pulses (0..255) | CWT |
| 14 | Fan Speed Man/Auto | 0 = Manual; 1 = Auto | 1 Bit | 1.2 boolean | CWT |
| 15 | Fan Speed 1 | 1 = Set Fan Speed 1 | 1 Bit | 1.2 boolean | CWT |
| 16 | Fan Speed 2 | 1 = Set Fan Speed 2 | 1 Bit | 1.2 boolean | CWT |
| 17 | Fan Speed 3 | 1 = Set Fan Speed 3 | 1 Bit | 1.2 boolean | CWT |
| 18 | Fan Speed 4 | 1 = Set Fan Speed 4 | 1 Bit | 1.2 boolean | CWT |
| 19 | Fan Speed 5 | 1 = Set Fan Speed 5 | 1 Bit | 1.2 boolean | CWT |
| 20 | Fan Speed [+/-] | 0 = Decrease, 1 = Increase | 1 Bit | CW | |
| 20 | Fan Speed [+/-] | 0 = Up, 1 = Down | 1 Bit | 1.8 up/down | CW |
| 21 | Vanes U-D / 5 Positions | Thresholds: 30 %, 50 %, 70 %, 90 % | 1 Byte | 5.1 percentage (0..100%) | CWT |
| 21 | Vanes U-D / 5 Positions | Position values: 1, 2, 3, 4, 5 | 1 Byte | 5.10 counter pulses (0..255) | CWT |
| 22 | Vanes U-D Man/Auto | 0 = Manual; 1 = Auto | 1 Bit | 1.2 boolean | CWT |
| 23 | Vanes U-D Position 1 | 1 = Set Position 1 | 1 Bit | 1.2 boolean | CWT |
| 24 | Vanes U-D Position 2 | 1 = Set Position 2 | 1 Bit | 1.2 boolean | CWT |
| 25 | Vanes U-D Position 3 | 1 = Set Position 3 | 1 Bit | 1.2 boolean | CWT |
| 26 | Vanes U-D Position 4 | 1 = Set Position 4 | 1 Bit | 1.2 boolean | CWT |
| 27 | Vanes U-D Position 5 | 1 = Set Position 5 | 1 Bit | 1.2 boolean | CWT |
| 28 | Vanes U-D [+/-] | 0 = Up, 1 = Down | 1 Bit | 1.8 up/down | CW |
| 28 | Vanes U-D [+/-] | 0 = Decrease, 1 = Increase | 1 Bit | CW | |
| 29 | Vanes L-R / 5 Positions | Thresholds: 30 %, 50 %, 70 %, 90 % | 1 Byte | 5.1 percentage (0..100%) | CWT |
| 29 | Vanes L-R / 5 Positions | Position values: 1, 2, 3, 4, 5 | 1 Byte | 5.10 counter pulses (0..255) | CWT |
| 30 | Vanes L-R Man/Auto | 0 = Manual; 1 = Auto | 1 Bit | 1.2 boolean | CWT |
| 31 | Vanes L-R Position 1 | 1 = Set Position 1 | 1 Bit | 1.2 boolean | CWT |
| 32 | Vanes L-R Position 2 | 1 = Set Position 2 | 1 Bit | 1.2 boolean | CWT |
| 33 | Vanes L-R Position 3 | 1 = Set Position 3 | 1 Bit | 1.2 boolean | CWT |
| 34 | Vanes L-R Position 4 | 1 = Set Position 4 | 1 Bit | 1.2 boolean | CWT |
| 35 | Vanes L-R Position 5 | 1 = Set Position 5 | 1 Bit | 1.2 boolean | CWT |
| 36 | Vanes L-R [+/-] | 0 = Decrease, 1 = Increase | 1 Bit | CW | |
| 36 | Vanes L-R [+/-] | 0 = Up, 1 = Down | 1 Bit | 1.8 up/down | CW |
| 37 | Setpoint Temperature | ºC | 2 Bytes | 9.1 temperature (°C) | CWT |
| 38 | Setpoint Temperature [+/-] | 0 = Decrease, 1 = Increase | 1 Bit | CW | |
| 38 | Setpoint Temperature [+/-] | 0 = Up, 1 = Down | 1 Bit | 1.8 up/down | CW |
| 39 | Ambient Temperature | ºC | 2 Bytes | 9.1 temperature (°C) | CWT |
| 40 | Today | Today's date | 3 Bytes | 11.1 date | CWT |
| 41 | Reset Energy Counter | 1 = Reset counter | 1 Bit | CWT | |
| 42 | Switch Off Timeout | 0 = Stop, 1 = Start | 1 Bit | 1.10 start/stop | CWT |
| 42 | Window Contact Status | 0 = Open, 1 = Closed | 1 Bit | 1.9 open/close | CWT |
| 43 | Occupancy | 0 = Not Occupied, 1 = Occupied | 1 Bit | CWT | |
| 44 | Sleep Timeout | 0 = Stop, 1 = Start | 1 Bit | 1.10 start/stop | CWT |
| 45 | Lock Remote Control | 0 = Unlock, 1 = Lock | 1 Bit | 1.2 boolean | CWT |
| 46 | Lock Control Objects | 0 = Unlock, 1 = Lock | 1 Bit | 1.2 boolean | CWT |
| 47 | Power Mode | 0 = Stop, 1 = Start | 1 Bit | 1.10 start/stop | CWT |
| 48 | Eco Mode | 0 = Stop, 1 = Start | 1 Bit | 1.10 start/stop | CWT |
| 49 | Additional Heating | 0 = Stop, 1 = Start | 1 Bit | 1.10 start/stop | CWT |
| 50 | Additional Cooling | 0 = Stop, 1 = Start | 1 Bit | 1.10 start/stop | CWT |
| 51 | Execute Scene | 0...4 = Execute Scene 1-5 | 1 Byte | CWT | |
| 51 | Save/Execute Scene | 0...4 = Execute Scene 1-5, 128...132 = Save Scene 1-5 | 1 Byte | CWT | |
| 52 | Save Scene 1 | 1 = Save Scene | 1 Bit | 1.2 boolean | CW |
| 53 | Save Scene 2 | 1 = Save Scene | 1 Bit | 1.2 boolean | CW |
| 54 | Save Scene 3 | 1 = Save Scene | 1 Bit | 1.2 boolean | CW |
| 55 | Save Scene 4 | 1 = Save Scene | 1 Bit | 1.2 boolean | CW |
| 56 | Save Scene 5 | 1 = Save Scene | 1 Bit | 1.2 boolean | CW |
| 57 | Execute Scene 1 | 1 = Execute Scene | 1 Bit | 1.2 boolean | CWT |
| 58 | Execute Scene 2 | 1 = Execute Scene | 1 Bit | 1.2 boolean | CWT |
| 59 | Execute Scene 3 | 1 = Execute Scene | 1 Bit | 1.2 boolean | CWT |
| 60 | Execute Scene 4 | 1 = Execute Scene | 1 Bit | 1.2 boolean | CWT |
| 61 | Execute Scene 5 | 1 = Execute Scene | 1 Bit | 1.2 boolean | CWT |
| 62 | Input 1 - Lock object | 0 = Disable, 1 = Enable | 1 Bit | 1.3 enable | CWT |
| 62 | Input 1 - Lock object | 0 = False, 1 = True | 1 Bit | 1.2 boolean | CWT |
| 63 | Input 2 - Lock object | 0 = False, 1 = True | 1 Bit | 1.2 boolean | CWT |
| 63 | Input 2 - Lock object | 0 = Disable, 1 = Enable | 1 Bit | 1.3 enable | CWT |
| 64 | Input 3 - Lock object | 0 = False, 1 = True | 1 Bit | 1.2 boolean | CWT |
| 64 | Input 3 - Lock object | 0 = Disable, 1 = Enable | 1 Bit | 1.3 enable | CWT |
| 65 | Input 4 - Lock object | 0 = False, 1 = True | 1 Bit | 1.2 boolean | CWT |
| 65 | Input 4 - Lock object | 0 = Disable, 1 = Enable | 1 Bit | 1.3 enable | CWT |
| 66 | ON/OFF | Status: 1 = ON, 0 = OFF | 1 Bit | 1.1 switch | CRT |
| 67 | Mode: Powerful | Status: 1 = Powerful is active | 1 Bit | 1.2 boolean | CRT |
| 68 | Mode: Quiet | Status: 1 = Quiet is active | 1 Bit | 1.2 boolean | CRT |
| 69 | HVAC Mode | Status: 0 = Auto, 1 = Heat, 3 = Cool, 9 = Fan, 14 = Dry | 1 Byte | CRT | |
| 70 | Mode: Cool/Heat | Status: 0 = Cool, 1 = Heat | 1 Bit | CRT | |
| 71 | Mode: Auto | Status: 1 = AUTO is active | 1 Bit | 1.2 boolean | CRT |
| 72 | Mode: Heat | Status: 1 = HEAT is active | 1 Bit | 1.2 boolean | CRT |
| 73 | Mode: Cool | Status: 1 = COOL is active | 1 Bit | 1.2 boolean | CRT |
| 74 | Mode: Fan | Status: 1 = FAN is active | 1 Bit | 1.2 boolean | CRT |
| 75 | Mode: Dry | Status: 1 = DRY is active | 1 Bit | 1.2 boolean | CRT |
| 76 | Mode: Text | Status: Maximum 14 characters | 14 Bytes | 16.1 Character String (ISO 8859-1) | CRT |
| 77 | Fan Speed / 5 Speeds | Status: 20 %, 40 %, 60 %, 80 %, 100 % | 1 Byte | 5.1 percentage (0..100%) | CRT |
| 77 | Fan Speed / 5 Speeds | Status: Speed values 1, 2, 3, 4, 5 | 1 Byte | 5.10 counter pulses (0..255) | CRT |
| 78 | Fan Speed Man/Auto | Status: 0 = Manual; 1 = Auto | 1 Bit | 1.2 boolean | CRT |
| 79 | Fan Speed 1 | Status: 1 = Fan in Speed 1 | 1 Bit | 1.2 boolean | CRT |
| 80 | Fan Speed 2 | Status: 1 = Fan in Speed 2 | 1 Bit | 1.2 boolean | CRT |
| 81 | Fan Speed 3 | Status: 1 = Fan in Speed 3 | 1 Bit | 1.2 boolean | CRT |
| 82 | Fan Speed 4 | Status: 1 = Fan in Speed 4 | 1 Bit | 1.2 boolean | CRT |
| 83 | Fan Speed 5 | Status: 1 = Fan in Speed 5 | 1 Bit | 1.2 boolean | CRT |
| 84 | Fan Speed: Text | Status: Maximum 14 characters | 14 Bytes | 16.1 Character String (ISO 8859-1) | CRT |
| 85 | Vanes U-D / 5 Positions | Status: 20 %, 40 %, 60 %, 80 %, 100 % | 1 Byte | 5.1 percentage (0..100%) | CRT |
| 85 | Vanes U-D / 5 Positions | Status: Position values 1, 2, 3, 4, 5 | 1 Byte | 5.10 counter pulses (0..255) | CRT |
| 86 | Vanes U-D Man/Auto | Status: 0 = Manual; 1 = Auto | 1 Bit | 1.2 boolean | CRT |
| 87 | Vanes U-D Position 1 | Status: 1 = Vanes in Position 1 | 1 Bit | 1.2 boolean | CRT |
| 88 | Vanes U-D Position 2 | Status: 1 = Vanes in Position 2 | 1 Bit | 1.2 boolean | CRT |
| 89 | Vanes U-D Position 3 | Status: 1 = Vanes in Position 3 | 1 Bit | 1.2 boolean | CRT |
| 90 | Vanes U-D Position 4 | Status: 1 = Vanes in Position 4 | 1 Bit | 1.2 boolean | CRT |
| 91 | Vanes U-D Position 5 | Status: 1 = Vanes in Position 5 | 1 Bit | 1.2 boolean | CRT |
| 92 | Vanes U-D Text | Status: Maximum 14 characters | 14 Bytes | 16.1 Character String (ISO 8859-1) | CRT |
| 93 | Vanes L-R / 5 Positions | Status: 20 %, 40 %, 60 %, 80 %, 100 % | 1 Byte | 5.1 percentage (0..100%) | CRT |
| 93 | Vanes L-R / 5 Positions | Status: Position values 1, 2, 3, 4, 5 | 1 Byte | 5.10 counter pulses (0..255) | CRT |
| 94 | Vanes L-R Man/Auto | Status: 0 = Manual; 1 = Auto | 1 Bit | 1.2 boolean | CRT |
| 95 | Vanes L-R Position 1 | Status: 1 = Vanes in Position 1 | 1 Bit | 1.2 boolean | CRT |
| 96 | Vanes L-R Position 2 | Status: 1 = Vanes in Position 2 | 1 Bit | 1.2 boolean | CRT |
| 97 | Vanes L-R Position 3 | Status: 1 = Vanes in Position 3 | 1 Bit | 1.2 boolean | CRT |
| 98 | Vanes L-R Position 4 | Status: 1 = Vanes in Position 4 | 1 Bit | 1.2 boolean | CRT |
| 99 | Vanes L-R Position 5 | Status: 1 = Vanes in Position 5 | 1 Bit | 1.2 boolean | CRT |
| 100 | Vanes L-R Text | Status: Maximum 14 characters | 14 Bytes | 16.1 Character String (ISO 8859-1) | CRT |
| 101 | AC Setpoint Temperature | Status (ºC) | 2 Bytes | 9.1 temperature (°C) | CRT |
| 102 | AC Return Temperature | Status (ºC) | 2 Bytes | 9.1 temperature (°C) | CRT |
| 103 | Outdoor Temperature | Status (ºC) | 2 Bytes | 9.1 temperature (°C) | CRT |
| 104 | Error/Alarm | Status: 0 = No alarm, 1 = Alarm | 1 Bit | CRT | |
| 105 | Error Code | Status: 0 = No error / Any other see manual | 2 Bytes | CRT | |
| 106 | Error Text Code | Status: 3 char PA Error; Empty - None | 14 Bytes | 16.1 Character String (ISO 8859-1) | CRT |
| 107 | Power Consumption | Status (W) | 4 Bytes | 14.56 power (W) | CRT |
| 108 | Today Energy | Status (Wh) | 4 Bytes | CRT | |
| 109 | Yesterday Energy | Status (Wh) | 4 Bytes | CRT | |
| 110 | Total Energy | Status (Wh) | 4 Bytes | CRT | |
| 111 | Today | Status: Today's date | 3 Bytes | 11.1 date | CRT |
| 112 | Lock Remote Control | Status: 0 = Unlocked, 1 = Locked | 1 Bit | 1.2 boolean | CRT |
| 113 | Lock Control Objects | Status: 0 = Unlocked, 1 = Locked | 1 Bit | 1.2 boolean | CRT |
| 114 | Power Mode | Status: 0 = OFF, 1 = ON | 1 Bit | 1.1 switch | CRT |
| 115 | Eco Mode | Status: 0 = OFF, 1 = ON | 1 Bit | 1.1 switch | CRT |
| 116 | Additional Heating | Status: 0 = OFF, 1 = ON | 1 Bit | 1.1 switch | CRT |
| 117 | Additional Cooling | Status: 0 = OFF, 1 = ON | 1 Bit | 1.1 switch | CRT |
| 118 | Operating Hours Counter | Status: Number of operating hours | 2 Bytes | 7.1 pulses | CRT |
| 119 | Current Scene | Status: 0...4 = Scene X+1, 63 = No Scene | 1 Byte | CRT | |
| 120 | Input 1 - Switch | Status: 0 = OFF, 1 = ON | 1 Bit | 1.1 switch | CRT |
| 120 | Input 1 - Dimming | Status: 0 = OFF, 1 = ON | 1 Bit | 1.1 switch | CRT |
| 120 | Input 1 - Shutter/Blinds | Status: 0 = Step Up; 1 = Step Down | 1 Bit | CRT | |
| 121 | Input 1 - Dimming | Status: Dimming step | 4 Bit | 3.7 dimming control | CRT |
| 121 | Input 1 - Shutter/Blinds | Status: 0 = Move Up; 1 = Move Down | 1 Bit | 1.8 up/down | CRT |
| 121 | Input 1 - Value | Status: 4 Byte unsigned value | 4 Bytes | 12.1 counter pulses (unsigned) | CRT |
| 121 | Input 1 - Value | Status: 1 Byte unsigned value | 1 Byte | 5.10 counter pulses (0..255) | CRT |
| 121 | Input 1 - Value | Status: 2 Byte signed value | 2 Bytes | 8.1 pulses difference | CRT |
| 121 | Input 1 - Value | Status: Temperature (ºC) | 2 Bytes | 9.1 temperature (°C) | CRT |
| 121 | Input 1 - Value | Status: 2 Byte unsigned value | 2 Bytes | 7.1 pulses | CRT |
| 122 | Input 2 - Switch | Status: 0 = OFF, 1 = ON | 1 Bit | 1.1 switch | CRT |
| 122 | Input 2 - Dimming | Status: 0 = OFF, 1 = ON | 1 Bit | 1.1 switch | CRT |
| 122 | Input 2 - Shutter/Blinds | Status: 0 = Step Up; 1 = Step Down | 1 Bit | CRT | |
| 123 | Input 2 - Dimming | Status: Dimming step | 4 Bit | 3.7 dimming control | CRT |
| 123 | Input 2 - Value | Status: 2 Byte unsigned value | 2 Bytes | 7.1 pulses | CRT |
| 123 | Input 2 - Value | Status: 1 Byte unsigned value | 1 Byte | 5.10 counter pulses (0..255) | CRT |
| 123 | Input 2 - Shutter/Blinds | Status: 0 = Move Up; 1 = Move Down | 1 Bit | 1.8 up/down | CRT |
| 123 | Input 2 - Value | Status: 4 Byte unsigned value | 4 Bytes | 12.1 counter pulses (unsigned) | CRT |
| 123 | Input 2 - Value | Status: Temperature (ºC) | 2 Bytes | 9.1 temperature (°C) | CRT |
| 123 | Input 2 - Value | Status: 2 Byte signed value | 2 Bytes | 8.1 pulses difference | CRT |
| 124 | Input 3 - Switch | Status: 0 = OFF, 1 = ON | 1 Bit | 1.1 switch | CRT |
| 124 | Input 3 - Dimming | Status: 0 = OFF, 1 = ON | 1 Bit | 1.1 switch | CRT |
| 124 | Input 3 - Shutter/Blinds | Status: 0 = Step Up; 1 = Step Down | 1 Bit | CRT | |
| 125 | Input 3 - Dimming | Status: Dimming step | 4 Bit | 3.7 dimming control | CRT |
| 125 | Input 3 - Value | Status: 4 Byte unsigned value | 4 Bytes | 12.1 counter pulses (unsigned) | CRT |
| 125 | Input 3 - Value | Status: Temperature (ºC) | 2 Bytes | 9.1 temperature (°C) | CRT |
| 125 | Input 3 - Value | Status: 2 Byte signed value | 2 Bytes | 8.1 pulses difference | CRT |
| 125 | Input 3 - Value | Status: 2 Byte unsigned value | 2 Bytes | 7.1 pulses | CRT |
| 125 | Input 3 - Value | Status: 1 Byte unsigned value | 1 Byte | 5.10 counter pulses (0..255) | CRT |
| 125 | Input 3 - Shutter/Blinds | Status: 0 = Move Up; 1 = Move Down | 1 Bit | 1.8 up/down | CRT |
| 126 | Input 4 - Switch | Status: 0 = OFF, 1 = ON | 1 Bit | 1.1 switch | CRT |
| 126 | Input 4 - Dimming | Status: 0 = OFF, 1 = ON | 1 Bit | 1.1 switch | CRT |
| 126 | Input 4 - Shutter/Blinds | Status: 0 = Step Up; 1 = Step Down | 1 Bit | CRT | |
| 127 | Input 4 - Dimming | Status: Dimming step | 4 Bit | 3.7 dimming control | CRT |
| 127 | Input 4 - Value | Status: 4 Byte unsigned value | 4 Bytes | 12.1 counter pulses (unsigned) | CRT |
| 127 | Input 4 - Value | Status: Temperature (ºC) | 2 Bytes | 9.1 temperature (°C) | CRT |
| 127 | Input 4 - Value | Status: 2 Byte signed value | 2 Bytes | 8.1 pulses difference | CRT |
| 127 | Input 4 - Value | Status: 2 Byte unsigned value | 2 Bytes | 7.1 pulses | CRT |
| 127 | Input 4 - Value | Status: 1 Byte unsigned value | 1 Byte | 5.10 counter pulses (0..255) | CRT |
| 127 | Input 4 - Shutter/Blinds | Status: 0 = Move Up; 1 = Move Down | 1 Bit | 1.8 up/down | CRT |
Parameters (190)
| Parameter | Type | Default |
|---|---|---|
| Download latest database entry for this product and its User Manual from: | text | http://www.intesis.com |
| Send READs for Control objects on bus recovery (T & U flags must be active) | list | No |
| > Delay before sending READs (sec) | unsignedInt 0…30 | 10 |
| Scene to load on bus recovery / startup (needs to define values for that scene) | list | (none) |
| Enable object "Error Code" | list | No |
| Disallow control from remote controller | list | No |
| > Enable "Lock Remote Control" objects | list | No |
| Enable function "Lock Control Objects" | list | No |
| Enable function "Operating Hours Counter" | list | No |
| When mode is AUTO, Status objects report actual operating status (HEAT/COOL/..) | list | No |
| Enable "Mode Cool/Heat" objects (for Control and Status) | list | No |
| Enable PID-Compat. Scaling Mode Objects | list | No |
| Enable use of +/- object for Mode | list | No |
| > Datapoint type | list | 0 = Decrease, 1 = Increase [DPT_1.007] |
| Enable use of bit-type Mode objects (for Control) | list | No |
| Enable use of bit-type Mode objects (for Status) | list | No |
| Enable use of Text object for Mode | list | No |
| ASCII strings shown in status object "Mode: Text" | text | << 14-byte string values >> |
| > String when mode is AUTO | text | AUTO |
| > String when mode is HEAT | text | HEAT |
| > String when mode is COOL | text | COOL |
| > String when mode is FAN | text | FAN |
| > String when mode is DRY | text | DRY |
| Enable use of "Powerful" mode (AC feature) | list | No |
| Enable use of "Quiet" mode (AC feature) | list | No |
| Enable use of Power mode | list | No |
| > Action time for this mode (minutes) | unsignedInt 1…180 | 30 |
| > Setpoint delta increase (HEAT) or decrease (COOL) | list | 2.0 ºC |
| > Fan Speed | list | SPEED 5 |
| Enable use of Economy mode | list | No |
| > Setpoint delta decrease (HEAT) or increase (COOL) | list | 2.0 ºC |
| > Fan Speed | list | SPEED 1 |
| Enable use of Sleep function | list | No |
| > AC switch-off timeout (minutes) | unsignedInt 0…180 | 60 |
| Enable use of Additional Heating mode | list | No |
| > Fan Speed | list | AUTO |
| Enable use of Additional Cooling mode | list | No |
| Enable "Fan Speed Man/Auto" objects (for Control and Status) | list | No |
| Available fanspeeds in Indoor Unit (see docum. for your indoor unit) | unsignedInt 2…7 | 5 |
| Datapoint type | list | Scaling [DPT_5.001] |
| Enable use of +/- object for Fan Speed | list | No |
| > Does +/- sequence include Fan Speed AUTO? | list | No |
| > Roll-over Speed at upper/lower limit (when controlling with +/- object) | list | Yes |
| Enable use of bit-type Fan Speed objects (for Control) | list | No |
| Enable use of bit-type Fan Speed objects (for Status) | list | No |
| Enable use of Text object for Fan Speed | list | No |
| ASCII strings shown in status object "Fan Speed: Text" | text | << 14-byte string values >> |
| > String when Fan Speed is AUTO | text | AUTO |
| > String when Fan Speed is 1 | text | SPEED 1 |
| > String when Fan Speed is 2 | text | SPEED 2 |
| > String when Fan Speed is 3 | text | SPEED 3 |
| > String when Fan Speed is 4 | text | SPEED 4 |
| > String when Fan Speed is 5 | text | SPEED 5 |
| Indoor unit has Up-Down Vanes (see documentation of indoor unit) | list | Yes |
| Enable "Vanes U-D Man/Auto" objects (for Control and Status) | list | No |
| Enable use of +/- object for Vanes U-D | list | No |
| > Does +/- sequence include Vanes Up-Down AUTO? | list | No |
| > Roll-over Vanes at upper/lower limit (when controlling with +/- object) | list | Yes |
| Enable use of bit-type Vanes U-D objects (for Control) | list | No |
| Enable use of bit-type Vanes U-D objects (for Status) | list | No |
| Enable use of Text object for Vanes U-D | list | No |
| ASCII strings shown in status object "Vanes U-D: Text" | text | << 14-byte string values >> |
| > String when Vanes U-D in AUTO | text | U-D AUTO |
| > String when Vanes U-D in POS 1 | text | U-D POS 1 |
| > String when Vanes U-D in POS 2 | text | U-D POS 2 |
| > String when Vanes U-D in POS 3 | text | U-D POS 3 |
| > String when Vanes U-D in POS 4 | text | U-D POS 4 |
| > String when Vanes U-D in POS 5 | text | U-D POS 5 |
| Indoor unit has Left-Right Vanes (see documentation of indoor unit) | list | Yes |
| Enable "Vanes L-R Man/Auto" objects (for Control and Status) | list | No |
| Enable use of +/- object for Vanes L-R | list | No |
| > Does +/- sequence include Vanes Left-Right AUTO? | list | No |
| Enable use of bit-type Vanes L-R objects (for Control) | list | No |
| Enable use of bit-type Vanes L-R objects (for Status) | list | No |
| Enable use of Text object for Vanes L-R | list | No |
| ASCII strings shown in status object "Vanes L-R: Text" | text | << 14-byte string values >> |
| > String when Vanes L-R in AUTO | text | L-R AUTO |
| > String when Vanes L-R in POS 1 | text | L-R POS 1 |
| > String when Vanes L-R in POS 2 | text | L-R POS 2 |
| > String when Vanes L-R in POS 3 | text | L-R POS 3 |
| > String when Vanes L-R in POS 4 | text | L-R POS 4 |
| > String when Vanes L-R in POS 5 | text | L-R POS 5 |
| Cyclic sending of "AC Setpoint Temperature" (in seconds; 0 = not active) | unsignedInt 0…255 | 0 |
| Enable use of +/- object for Setpoint Temperature | list | No |
| > [+/-] step size | list | 1.0 ºC |
| Enable limits for object "Setpoint Temperature" | list | No |
| > Lower limit | list | 16.0 ºC |
| > Upper limit | list | 30.0 ºC |
| Ambient temperature reference is provided from KNX (see User Guide if enabled) | list | No |
| Enable use of scenes | list | No |
| Scenes can be saved from KNX bus | list | No |
| Enable use of bit objects for scene execution | list | No |
| > Enable use of bit objects for saving scenes (from bus) | list | No |
| Scene 1 preset | list | No |
| > Scene 1 / Value for ON/OFF | list | (unchanged) |
| > Scene 1 / Value for Mode | list | (unchanged) |
| > Scene 1 / Value for Fan Speed | list | (unchanged) |
| > Scene 1 / Value for Vanes U-D (if available) | list | (unchanged) |
| > Scene 1 / Value for Vanes L-R (if available) | list | (unchanged) |
| > Scene 1 / Value for Setpoint Temp | list | (unchanged) |
| > Scene 1 / Value for Remote Lock | list | (unchanged) |
| Scene 2 preset | list | No |
| > Scene 2 / Value for ON/OFF | list | (unchanged) |
| > Scene 2 / Value for Mode | list | (unchanged) |
| > Scene 2 / Value for Fan Speed | list | (unchanged) |
| > Scene 2 / Value for Vanes U-D (if available) | list | (unchanged) |
| > Scene 2 / Value for Vanes L-R (if available) | list | (unchanged) |
| > Scene 2 / Value for Setpoint Temp | list | (unchanged) |
| > Scene 2 / Value for Remote Lock | list | (unchanged) |
| Scene 3 preset | list | No |
| > Scene 3 / Value for ON/OFF | list | (unchanged) |
| > Scene 3 / Value for Mode | list | (unchanged) |
| > Scene 3 / Value for Fan Speed | list | (unchanged) |
| > Scene 3 / Value for Vanes U-D (if available) | list | (unchanged) |
| > Scene 3 / Value for Vanes L-R (if available) | list | (unchanged) |
| > Scene 3 / Value for Setpoint Temp | list | (unchanged) |
| > Scene 3 / Value for Remote Lock | list | (unchanged) |
| Scene 4 preset | list | No |
| > Scene 4 / Value for ON/OFF | list | (unchanged) |
| > Scene 4 / Value for Mode | list | (unchanged) |
| > Scene 4 / Value for Fan Speed | list | (unchanged) |
| > Scene 4 / Value for Vanes U-D (if available) | list | (unchanged) |
| > Scene 4 / Value for Vanes L-R (if available) | list | (unchanged) |
| > Scene 4 / Value for Setpoint Temp | list | (unchanged) |
| > Scene 4 / Value for Remote Lock | list | (unchanged) |
| Scene 5 preset | list | No |
| > Scene 5 / Value for ON/OFF | list | (unchanged) |
| > Scene 5 / Value for Mode | list | (unchanged) |
| > Scene 5 / Value for Fan Speed | list | (unchanged) |
| > Scene 5 / Value for Vanes U-D (if available) | list | (unchanged) |
| > Scene 5 / Value for Vanes L-R (if available) | list | (unchanged) |
| > Scene 5 / Value for Setpoint Temp | list | (unchanged) |
| > Scene 5 / Value for Remote Lock | list | (unchanged) |
| Enable use of Open Window / Switch off timeout function | list | No |
| > AC switch-off timeout (minutes) | unsignedInt 0…30 | 10 |
| > Datapoint type | list | 0 = Stop / 1 = Start Timeout [DPT_1.010] |
| > Reload last On/Off value once window is closed | list | No |
| Enable use of Occupancy function | list | No |
| > Timeout to apply action (minutes) | unsignedInt 0…180 | 20 |
| > Action after timeout elapsed | list | Switch-Off AC |
| > Setpoint delta decrease (HEAT) or increase (COOL) | list | 2.0 ºC |
| > Enable secondary timeout | list | No |
| > Timeout to apply action (min) | unsignedInt 1…180 | 20 |
| > Setpoint delta decrease (HEAT) or increase (COOL) | list | 2.0 ºC |
| Enable object "Error Text Code" (3 ASCII-char Error Code) | list | Yes |
| Indoor unit has HEAT mode (see documentation of indoor unit) | list | Yes |
| > Disallow On/Off operation while window is open | list | No |
| > Disallow On/Off operation while timeout is elapsed | list | No |
| > Reload last On/Off value once timeout is stopped | list | No |
| > Disallow On/Off operation while not occupied | list | No |
| > Reload last On/Off value when occupied | list | No |
| > Debounce time | list | 50 ms |
| > Contact type | list | NO: Normally Open |
| > Lock function | list | No |
| > Function | list | Switch |
| > Sending delay after bus recovery (seconds) | unsignedInt 0…255 | 10 |
| > Send telegram after bus recovery | list | No action |
| Indoor unit has FAN mode (see documentation of indoor unit) | list | Yes |
| > Value on rising edge (contact activated) | list | No action |
| > Value on falling edge (contact deactivated) | list | No action |
| > Send cyclically every (seconds) | unsignedInt 1…65535 | 10 |
| > Cyclical sending | list | Never |
| > Scene when contact is activated (needs to be defined) | list | Scene 1 |
| > Setpoint temperature | list | 20.0 ºC |
| > Setpoint temperature | list | 30.0 ºC |
| Enable use of Input 1 | list | No |
| Enable use of Input 2 | list | No |
| Enable use of Input 3 | list | No |
| Enable use of Input 4 | list | No |
| > Reset Input when enabling | list | No |
| > Mode for short (long) operation | list | Toggle: ON/OFF (increase/decrease) |
| > Increasing step | list | + 25 % |
| > Decreasing step | list | - 25 % |
| > Short/long operation limit (x 100 ms) | unsignedInt 1…255 | 10 |
| > Cycle time to send in long operation (x 100 ms) (0 = not active) | unsignedInt 0…255 | 0 |
| > Operation | list | Toggle (Up/Down) |
| > Method | list | Step-Move-Step |
| > Vanes adjustment time (x 100 ms) | unsignedInt 1…255 | 10 |
| > Datapoint type to be sent | list | DPT 5.010 (1 Byte) |
| > Value on rising edge (when contact activated) | unsignedInt 0…255 | 0 |
| > Value on rising edge (when contact activated) | unsignedInt 0…65535 | 0 |
| > Value on rising edge (when contact activated) | signedInt -32768…32767 | 0 |
| > Value on rising edge (x 0.1 ºC) (when contact activated) | signedInt -2730…3276 | 250 |
| > Value on rising edge (when contact activated) | unsignedInt 0…4294967295 | 0 |
| Enable use of Power Consumption | list | No |
| > Power threshold to update (W) | unsignedInt 0…255 | 50 |
| > Power update timeout (s) | unsignedInt 0…255 | 30 |
| > Energy update timeout (min) | unsignedInt 0…255 | 1 |
| Etherea AC model | list | CS-xyyMKE or CS-xyyNKE |
| Power consumption is not available for current AC model: | text | CS-xyyMKE or CS-xyyNKE |
Version history
| Application | App no | Fingerprint | First seen | Size | File |
|---|---|---|---|---|---|
| KNX Gateway for Panasonic Etherea air conditioning units, flush mounted 1.5 latest | $0483 | A264 | 2026-11-25 | 196 KB | Download |
About this file
This is the official ETS product database for the MDT technologies GmbH KNX Gateway for Panasonic Etherea air conditioning units, flush mounted (SCN-ACG0PAN.01), published by the manufacturer in the KNX online catalog. To use it, open ETS, go to Catalogs → Import and choose the downloaded .knxprod file. The device then appears in your catalog and can be added to a project. Older versions are kept so existing projects can be matched to the application program they were commissioned with.
More from MDT technologies GmbH
- KNX Gateway for Daikin residential air conditioning units, flush mounted SCN-ACG0DAI.01
- KNX Gateway for Mitsubishi air conditioning units, flush mounted SCN-ACG0MIT.01
- KNX Gateway for Daikin commercial air conditioning units, flush mounted SCN-ACG1DAI.01
- DALI Control 64 Gateway SCN-DA641.04
- DALI Control Pro64 Gateway SCN-DA641P.04S
- DALI Control 2x64 Gateway SCN-DA642.04
- Dali Control Broadcast Gateway SCN-DABC4.01
- DaliControl 16 SCN-DALI16.03
- DaliControl 32 SCN-DALI32.03
- DaliControl IP 64 SCN-DALI64.03
- SCN-IP000.02/.03 IP Interface without Secure SCN-IP000.02
- SCN-IP000.03 IP Interface with Secure SCN-IP000.03