| 0 | ON/OFF | 1 = ON, 0 = OFF | 1 Bit | 1.1 switch | CWT |
| 1 | HVAC Mode | 0 = Auto, 1 = Heat, 3 = Cool, 9 = Fan, 14 = Dry | 1 Byte | 20.105 HVAC control mode | CWT |
| 2 | Mode: Cool/Heat | 0 = Cool, 1 = Heat | 1 Bit | 1.100 cooling/heating | CWT |
| 3 | Mode: Auto | 1 = Set AUTO Mode | 1 Bit | 1.2 boolean | CWT |
| 4 | Mode: Heat | 1 = Set HEAT Mode | 1 Bit | 1.2 boolean | CWT |
| 5 | Mode: Cool | 1 = Set COOL Mode | 1 Bit | 1.2 boolean | CWT |
| 6 | Mode: Fan | 1 = Set FAN Mode | 1 Bit | 1.2 boolean | CWT |
| 7 | Mode: Dry | 1 = Set DRY Mode | 1 Bit | 1.2 boolean | CWT |
| 8 | Mode [+/-] | 0 = Decrease, 1 = Increase | 1 Bit | 1.7 step | CW |
| 8 | Mode [+/-] | 0 = Up, 1 = Down | 1 Bit | 1.8 up/down | CW |
| 9 | Fan Speed / 3 Speeds | Speed values: 1, 2, 3 | 1 Byte | 5.10 counter pulses (0..255) | CWT |
| 9 | Fan Speed / 2 Speeds | Speed values: 1, 2 | 1 Byte | 5.10 counter pulses (0..255) | CWT |
| 9 | Fan Speed / 4 Speeds | Speed values: 1, 2, 3, 4 | 1 Byte | 5.10 counter pulses (0..255) | CWT |
| 10 | Fan Speed / 3 Speeds | Thresholds: 50 %, 83 % | 1 Byte | 5.1 percentage (0..100%) | CWT |
| 10 | Fan Speed / 4 Speeds | Thresholds: 38 %, 63 %, 88 % | 1 Byte | 5.1 percentage (0..100%) | CWT |
| 10 | Fan Speed / 2 Speeds | Threshold: 75 % | 1 Byte | 5.1 percentage (0..100%) | CWT |
| 11 | Fan Speed Man/Auto | 0 = Manual; 1 = Auto | 1 Bit | 1.2 boolean | CWT |
| 12 | Fan Speed 1 | 1 = Set Fan Speed 1 | 1 Bit | 1.2 boolean | CWT |
| 13 | Fan Speed 2 | 1 = Set Fan Speed 2 | 1 Bit | 1.2 boolean | CWT |
| 14 | Fan Speed 3 | 1 = Set Fan Speed 3 | 1 Bit | 1.2 boolean | CWT |
| 15 | Fan Speed 4 | 1 = Set Fan Speed 4 | 1 Bit | 1.2 boolean | CWT |
| 16 | Fan Speed [+/-] | 0 = Decrease, 1 = Increase | 1 Bit | 1.7 step | CW |
| 16 | Fan Speed [+/-] | 0 = Up, 1 = Down | 1 Bit | 1.8 up/down | CW |
| 17 | Vanes U-D / 5 Positions | Position values: 1, 2, 3, 4, 5 | 1 Byte | 5.10 counter pulses (0..255) | CWT |
| 17 | Vanes Up-Down / 4 Positions | Position values: 1, 2, 3, 4 | 1 Byte | 5.10 counter pulses (0..255) | CWT |
| 18 | Vanes U-D / 5 Positions | Thresholds: 30 %, 50 %, 70 %, 90 % | 1 Byte | 5.1 percentage (0..100%) | CWT |
| 18 | Vanes Up-Down / 4 Positions | Thresholds: 38 %, 63 %, 88 % | 1 Byte | 5.1 percentage (0..100%) | CWT |
| 19 | Vanes U-D Man/Auto | 0 = Manual; 1 = Auto | 1 Bit | 1.2 boolean | CWT |
| 20 | Vanes U-D Position 1 | 1 = Set Position 1 | 1 Bit | 1.2 boolean | CWT |
| 21 | Vanes U-D Position 2 | 1 = Set Position 2 | 1 Bit | 1.2 boolean | CWT |
| 22 | Vanes U-D Position 3 | 1 = Set Position 3 | 1 Bit | 1.2 boolean | CWT |
| 23 | Vanes U-D Position 4 | 1 = Set Position 4 | 1 Bit | 1.2 boolean | CWT |
| 24 | Vanes U-D Position 5 | 1 = Set Position 5 | 1 Bit | 1.2 boolean | CWT |
| 25 | Vanes U-D Swing | 0 = Off, 1 = Swing | 1 Bit | 1.2 boolean | CWT |
| 26 | Vanes U-D [+/-] | 0 = Up, 1 = Down | 1 Bit | 1.8 up/down | CWT |
| 26 | Vanes U-D [+/-] | 0 = Decrease, 1 = Increase | 1 Bit | 1.7 step | CWT |
| 27 | Setpoint Temperature | ºC | 2 Bytes | 9.1 temperature (°C) | CWT |
| 28 | Setpoint Temperature [+/-] | 0 = Decrease, 1 = Increase | 1 Bit | 1.7 step | CW |
| 28 | Setpoint Temperature [+/-] | 0 = Up, 1 = Down | 1 Bit | 1.8 up/down | CW |
| 29 | Ambient Temperature | ºC | 2 Bytes | 9.1 temperature (°C) | CWT |
| 30 | Operating Hours Counter (h) | Number of operating hours | 2 Bytes | 7.7 time (h) | CWT |
| 31 | Operating Hours Counter (sec) | Number of operating seconds | 4 Bytes | 13.100 time lag (s) | CWT |
| 32 | Window Contact Status | 0 = Open, 1 = Closed | 1 Bit | 1.9 open/close | CWT |
| 33 | Lock Remote Control | 0 = Unlock, 1 = Lock | 1 Bit | 1.2 boolean | CWT |
| 34 | Lock Control Objects | 0 = Unlock, 1 = Lock | 1 Bit | 1.2 boolean | CWT |
| 35 | Save/Execute Scene | 0...4 = Execute Scene 1-5, 128...132 = Save Scene 1-5 | 1 Byte | 18.1 scene control | CWT |
| 36 | Save Scene 1 | 1 = Save Scene | 1 Bit | 1.2 boolean | CW |
| 37 | Save Scene 2 | 1 = Save Scene | 1 Bit | 1.2 boolean | CW |
| 38 | Save Scene 3 | 1 = Save Scene | 1 Bit | 1.2 boolean | CW |
| 39 | Save Scene 4 | 1 = Save Scene | 1 Bit | 1.2 boolean | CW |
| 40 | Save Scene 5 | 1 = Save Scene | 1 Bit | 1.2 boolean | CW |
| 41 | Execute Scene 1 | 1 = Execute Scene | 1 Bit | 1.2 boolean | CWT |
| 42 | Execute Scene 2 | 1 = Execute Scene | 1 Bit | 1.2 boolean | CWT |
| 43 | Execute Scene 3 | 1 = Execute Scene | 1 Bit | 1.2 boolean | CWT |
| 44 | Execute Scene 4 | 1 = Execute Scene | 1 Bit | 1.2 boolean | CWT |
| 45 | Execute Scene 5 | 1 = Execute Scene | 1 Bit | 1.2 boolean | CWT |
| 46 | ON/OFF | Status: 0 = OFF, 1 = ON | 1 Bit | 1.1 switch | CRT |
| 47 | HVAC Mode | Status: 0 = Auto, 1 = Heat, 3 = Cool, 9 = Fan, 14 = Dry | 1 Byte | 20.105 HVAC control mode | CRT |
| 48 | Mode: Cool/Heat | Status: 0 = Cool, 1 = Heat | 1 Bit | 1.100 cooling/heating | CRT |
| 49 | Mode: Auto | Status: 1 = AUTO is active | 1 Bit | 1.2 boolean | CRT |
| 50 | Mode: Heat | Status: 1 = HEAT is active | 1 Bit | 1.2 boolean | CRT |
| 51 | Mode: Cool | Status: 1 = COOL is active | 1 Bit | 1.2 boolean | CRT |
| 52 | Mode: Fan | Status: 1 = FAN is active | 1 Bit | 1.2 boolean | CRT |
| 53 | Mode: Dry | Status: 1 = DRY is active | 1 Bit | 1.2 boolean | CRT |
| 54 | Mode: Text | Status: Maximum 14 characters | 14 Bytes | 16.1 Character String (ISO 8859-1) | CRT |
| 55 | Fan Speed / 3 Speeds | Status: Speed values 1, 2, 3 | 1 Byte | 5.10 counter pulses (0..255) | CRT |
| 55 | Fan Speed / 2 Speeds | Status: Speed values 1, 2 | 1 Byte | 5.10 counter pulses (0..255) | CRT |
| 55 | Fan Speed / 4 Speeds | Status: Speed values 1, 2, 3, 4 | 1 Byte | 5.10 counter pulses (0..255) | CRT |
| 56 | Fan Speed / 2 Speeds | Status: 50 %, 100 % | 1 Byte | 5.1 percentage (0..100%) | CRT |
| 56 | Fan Speed / 4 Speeds | Status: 25 %, 50 %, 75 %, 100 % | 1 Byte | 5.1 percentage (0..100%) | CRT |
| 56 | Fan Speed / 3 Speeds | Status: 33 %, 67 %, 100 % | 1 Byte | 5.1 percentage (0..100%) | CRT |
| 57 | Fan Speed Man/Auto | Status: 0 = Manual, 1 = Auto | 1 Bit | 1.2 boolean | CRT |
| 58 | Fan Speed 1 | Status: 1 = Fan in Speed 1 | 1 Bit | 1.2 boolean | CRT |
| 59 | Fan Speed 2 | Status: 1 = Fan in Speed 2 | 1 Bit | 1.2 boolean | CRT |
| 60 | Fan Speed 3 | Status: 1 = Fan in Speed 3 | 1 Bit | 1.2 boolean | CRT |
| 61 | Fan Speed 4 | Status: 1 = Fan in Speed 4 | 1 Bit | 1.2 boolean | CRT |
| 62 | Fan Speed: Text | Status: Maximum 14 characters | 14 Bytes | 16.1 Character String (ISO 8859-1) | CRT |
| 63 | Vanes U-D / 5 Positions | Status: Position values 1, 2, 3, 4, 5 | 1 Byte | 5.10 counter pulses (0..255) | CRT |
| 63 | Vanes Up-Down / 4 Positions | Status: Position values 1, 2, 3, 4 | 1 Byte | 5.10 counter pulses (0..255) | CRT |
| 64 | Vanes U-D / 5 Positions | Status: 20 %, 40 %, 60 %, 80 %, 100 % | 1 Byte | 5.1 percentage (0..100%) | CRT |
| 64 | Vanes Up-Down / 4 Positions | Status: 25 %, 50 %, 75 %, 100 % | 1 Byte | 5.1 percentage (0..100%) | CRT |
| 65 | Vanes U-D Man/Auto | Status: 0 = Manual, 1 = Auto | 1 Bit | 1.2 boolean | CRT |
| 66 | Vanes U-D Position 1 | Status: 1 = Vanes in Position 1 | 1 Bit | 1.2 boolean | CRT |
| 67 | Vanes U-D Position 2 | Status: 1 = Vanes in Position 2 | 1 Bit | 1.2 boolean | CRT |
| 68 | Vanes U-D Position 3 | Status: 1 = Vanes in Position 3 | 1 Bit | 1.2 boolean | CRT |
| 69 | Vanes U-D Position 4 | Status: 1 = Vanes in Position 4 | 1 Bit | 1.2 boolean | CRT |
| 70 | Vanes U-D Position 5 | Status: 1 = Vanes in Position 5 | 1 Bit | 1.2 boolean | CRT |
| 71 | Vanes U-D Swing | Status: 0 = Off, 1 = Swing | 1 Bit | 1.2 boolean | CRT |
| 72 | Vanes U-D: Text | Status: Maximum 14 characters | 14 Bytes | 16.1 Character String (ISO 8859-1) | CRT |
| 73 | AC Setpoint Temperature | Status (ºC) | 2 Bytes | 9.1 temperature (°C) | CRT |
| 74 | AC Return Temperature | Status (ºC) | 2 Bytes | 9.1 temperature (°C) | CRT |
| 75 | Error/Alarm | Status: 0 = No alarm, 1 = Alarm | 1 Bit | 1.5 alarm | CRT |
| 76 | Error Code | Status: AC Unit Error Code | 2 Bytes | DPT.8 | CRT |
| 77 | Operating Hours Counter (h) | Status: Number of operating hours | 2 Bytes | 7.7 time (h) | CRT |
| 78 | Operating Hours Counter (sec) | Status: Number of operating seconds | 4 Bytes | 13.100 time lag (s) | CRT |
| 79 | Lock Remote Control | Status: 0 = Unlocked, 1 = Locked | 1 Bit | 1.2 boolean | CRT |
| 80 | Lock Control Objects | Status: 0 = Unlocked, 1 = Locked | 1 Bit | 1.2 boolean | CRT |
| 81 | Current Scene | Status: 0...4 = Scene X+1, 63 = No Scene | 1 Byte | 17.1 scene number | CRT |
| 82 | Legacy_ Mode | 0 = Auto, 1 = Heat, 2 = Dry, 3 = Fan, 4 = Cool | 1 Byte | DPT.5 | CRWT |
| 83 | Legacy_ Fan Speed | 0 = Auto, 1...4 = Speed 1...4 | 1 Byte | DPT.5 | CRWT |
| 84 | Legacy_ Vanes | 0 = Auto, 1...5 = Pos 1...5, 6 = Swing | 1 Byte | DPT.5 | CRWT |