KNX Database
MDT technologies GmbH SCN-ACG0MIT.01 KNX Gateway for Mitsubishi air conditioning units, flush mounted

KNX Gateway for Mitsubishi air conditioning units, flush mounted SCN-ACG0MIT.01

MDT technologies GmbH · Order number SCN-ACG0MIT.01 · System Devices › KNX Gateways

Download .knxprod KNX Gateway for Mitsubishi air conditioning units, flush mounted 1.0 · 137 KB

Product

ManufacturerMDT technologies GmbH
Product nameKNX Gateway for Mitsubishi air conditioning units, flush mounted
Order numberSCN-ACG0MIT.01
Product textKNX Gateway for Mitsubishi air conditioning units, flush mounted
HardwareME AC Interface
MediumTwisted Pair
Bus current (mA)6
Rail mountedNo
RegistrationCertified · 2026-06-22
Languagesde-DE, en-US, es-ES
Catalog entryM-0083_H-INT02-1-O0077_HP-0482-10-5CB7-O0077_CI-SCN.2DACG0MIT.2E01-2
Fingerprint5CB7
SHA-25695245aaa5438bfd5f8b827273ab181adc71e87be264ca5f9e2a67946c1833c71
First seen2026-11-25
Markets69 markets

Application program: KNX Gateway for Mitsubishi air conditioning units, flush mounted 1.0

Application number$0482
Version1.0
Mask versionMV-0025 (2.5)
KNX Data SecureNo
Minimum ETS version5.0
Parameters78
Group objects101
Group objects (101)
NoNameFunctionSizeDPTFlags
0ON/OFF1 = ON, 0 = OFF1 Bit1.1 switchCWT
1HVAC Mode0 = Auto, 1 = Heat, 3 = Cool, 9 = Fan, 14 = Dry1 Byte20.105 HVAC control modeCWT
2Mode: Cool/Heat0 = Cool, 1 = Heat1 Bit1.100 cooling/heatingCWT
3Mode: Auto1 = Set AUTO Mode1 Bit1.2 booleanCWT
4Mode: Heat1 = Set HEAT Mode1 Bit1.2 booleanCWT
5Mode: Cool1 = Set COOL Mode1 Bit1.2 booleanCWT
6Mode: Fan1 = Set FAN Mode1 Bit1.2 booleanCWT
7Mode: Dry1 = Set DRY Mode1 Bit1.2 booleanCWT
8Mode [+/-]0 = Decrease, 1 = Increase1 Bit1.7 stepCW
8Mode [+/-]0 = Up, 1 = Down1 Bit1.8 up/downCW
9Fan Speed / 3 SpeedsSpeed values: 1, 2, 31 Byte5.10 counter pulses (0..255)CWT
9Fan Speed / 2 SpeedsSpeed values: 1, 21 Byte5.10 counter pulses (0..255)CWT
9Fan Speed / 4 SpeedsSpeed values: 1, 2, 3, 41 Byte5.10 counter pulses (0..255)CWT
10Fan Speed / 3 SpeedsThresholds: 50 %, 83 %1 Byte5.1 percentage (0..100%)CWT
10Fan Speed / 4 SpeedsThresholds: 38 %, 63 %, 88 %1 Byte5.1 percentage (0..100%)CWT
10Fan Speed / 2 SpeedsThreshold: 75 %1 Byte5.1 percentage (0..100%)CWT
11Fan Speed Man/Auto0 = Manual; 1 = Auto1 Bit1.2 booleanCWT
12Fan Speed 11 = Set Fan Speed 11 Bit1.2 booleanCWT
13Fan Speed 21 = Set Fan Speed 21 Bit1.2 booleanCWT
14Fan Speed 31 = Set Fan Speed 31 Bit1.2 booleanCWT
15Fan Speed 41 = Set Fan Speed 41 Bit1.2 booleanCWT
16Fan Speed [+/-]0 = Decrease, 1 = Increase1 Bit1.7 stepCW
16Fan Speed [+/-]0 = Up, 1 = Down1 Bit1.8 up/downCW
17Vanes U-D / 5 PositionsPosition values: 1, 2, 3, 4, 51 Byte5.10 counter pulses (0..255)CWT
17Vanes Up-Down / 4 PositionsPosition values: 1, 2, 3, 41 Byte5.10 counter pulses (0..255)CWT
18Vanes U-D / 5 PositionsThresholds: 30 %, 50 %, 70 %, 90 %1 Byte5.1 percentage (0..100%)CWT
18Vanes Up-Down / 4 PositionsThresholds: 38 %, 63 %, 88 %1 Byte5.1 percentage (0..100%)CWT
19Vanes U-D Man/Auto0 = Manual; 1 = Auto1 Bit1.2 booleanCWT
20Vanes U-D Position 11 = Set Position 11 Bit1.2 booleanCWT
21Vanes U-D Position 21 = Set Position 21 Bit1.2 booleanCWT
22Vanes U-D Position 31 = Set Position 31 Bit1.2 booleanCWT
23Vanes U-D Position 41 = Set Position 41 Bit1.2 booleanCWT
24Vanes U-D Position 51 = Set Position 51 Bit1.2 booleanCWT
25Vanes U-D Swing0 = Off, 1 = Swing1 Bit1.2 booleanCWT
26Vanes U-D [+/-]0 = Up, 1 = Down1 Bit1.8 up/downCWT
26Vanes U-D [+/-]0 = Decrease, 1 = Increase1 Bit1.7 stepCWT
27Setpoint TemperatureºC2 Bytes9.1 temperature (°C)CWT
28Setpoint Temperature [+/-]0 = Decrease, 1 = Increase1 Bit1.7 stepCW
28Setpoint Temperature [+/-]0 = Up, 1 = Down1 Bit1.8 up/downCW
29Ambient TemperatureºC2 Bytes9.1 temperature (°C)CWT
30Operating Hours Counter (h)Number of operating hours2 Bytes7.7 time (h)CWT
31Operating Hours Counter (sec)Number of operating seconds4 Bytes13.100 time lag (s)CWT
32Window Contact Status0 = Open, 1 = Closed1 Bit1.9 open/closeCWT
33Lock Remote Control0 = Unlock, 1 = Lock1 Bit1.2 booleanCWT
34Lock Control Objects0 = Unlock, 1 = Lock1 Bit1.2 booleanCWT
35Save/Execute Scene0...4 = Execute Scene 1-5, 128...132 = Save Scene 1-51 Byte18.1 scene controlCWT
36Save Scene 11 = Save Scene1 Bit1.2 booleanCW
37Save Scene 21 = Save Scene1 Bit1.2 booleanCW
38Save Scene 31 = Save Scene1 Bit1.2 booleanCW
39Save Scene 41 = Save Scene1 Bit1.2 booleanCW
40Save Scene 51 = Save Scene1 Bit1.2 booleanCW
41Execute Scene 11 = Execute Scene1 Bit1.2 booleanCWT
42Execute Scene 21 = Execute Scene1 Bit1.2 booleanCWT
43Execute Scene 31 = Execute Scene1 Bit1.2 booleanCWT
44Execute Scene 41 = Execute Scene1 Bit1.2 booleanCWT
45Execute Scene 51 = Execute Scene1 Bit1.2 booleanCWT
46ON/OFFStatus: 0 = OFF, 1 = ON1 Bit1.1 switchCRT
47HVAC ModeStatus: 0 = Auto, 1 = Heat, 3 = Cool, 9 = Fan, 14 = Dry1 Byte20.105 HVAC control modeCRT
48Mode: Cool/HeatStatus: 0 = Cool, 1 = Heat1 Bit1.100 cooling/heatingCRT
49Mode: AutoStatus: 1 = AUTO is active1 Bit1.2 booleanCRT
50Mode: HeatStatus: 1 = HEAT is active1 Bit1.2 booleanCRT
51Mode: CoolStatus: 1 = COOL is active1 Bit1.2 booleanCRT
52Mode: FanStatus: 1 = FAN is active1 Bit1.2 booleanCRT
53Mode: DryStatus: 1 = DRY is active1 Bit1.2 booleanCRT
54Mode: TextStatus: Maximum 14 characters14 Bytes16.1 Character String (ISO 8859-1)CRT
55Fan Speed / 3 SpeedsStatus: Speed values 1, 2, 31 Byte5.10 counter pulses (0..255)CRT
55Fan Speed / 2 SpeedsStatus: Speed values 1, 21 Byte5.10 counter pulses (0..255)CRT
55Fan Speed / 4 SpeedsStatus: Speed values 1, 2, 3, 41 Byte5.10 counter pulses (0..255)CRT
56Fan Speed / 2 SpeedsStatus: 50 %, 100 %1 Byte5.1 percentage (0..100%)CRT
56Fan Speed / 4 SpeedsStatus: 25 %, 50 %, 75 %, 100 %1 Byte5.1 percentage (0..100%)CRT
56Fan Speed / 3 SpeedsStatus: 33 %, 67 %, 100 %1 Byte5.1 percentage (0..100%)CRT
57Fan Speed Man/AutoStatus: 0 = Manual, 1 = Auto1 Bit1.2 booleanCRT
58Fan Speed 1Status: 1 = Fan in Speed 11 Bit1.2 booleanCRT
59Fan Speed 2Status: 1 = Fan in Speed 21 Bit1.2 booleanCRT
60Fan Speed 3Status: 1 = Fan in Speed 31 Bit1.2 booleanCRT
61Fan Speed 4Status: 1 = Fan in Speed 41 Bit1.2 booleanCRT
62Fan Speed: TextStatus: Maximum 14 characters14 Bytes16.1 Character String (ISO 8859-1)CRT
63Vanes U-D / 5 PositionsStatus: Position values 1, 2, 3, 4, 51 Byte5.10 counter pulses (0..255)CRT
63Vanes Up-Down / 4 PositionsStatus: Position values 1, 2, 3, 41 Byte5.10 counter pulses (0..255)CRT
64Vanes U-D / 5 PositionsStatus: 20 %, 40 %, 60 %, 80 %, 100 %1 Byte5.1 percentage (0..100%)CRT
64Vanes Up-Down / 4 PositionsStatus: 25 %, 50 %, 75 %, 100 %1 Byte5.1 percentage (0..100%)CRT
65Vanes U-D Man/AutoStatus: 0 = Manual, 1 = Auto1 Bit1.2 booleanCRT
66Vanes U-D Position 1Status: 1 = Vanes in Position 11 Bit1.2 booleanCRT
67Vanes U-D Position 2Status: 1 = Vanes in Position 21 Bit1.2 booleanCRT
68Vanes U-D Position 3Status: 1 = Vanes in Position 31 Bit1.2 booleanCRT
69Vanes U-D Position 4Status: 1 = Vanes in Position 41 Bit1.2 booleanCRT
70Vanes U-D Position 5Status: 1 = Vanes in Position 51 Bit1.2 booleanCRT
71Vanes U-D SwingStatus: 0 = Off, 1 = Swing1 Bit1.2 booleanCRT
72Vanes U-D: TextStatus: Maximum 14 characters14 Bytes16.1 Character String (ISO 8859-1)CRT
73AC Setpoint TemperatureStatus (ºC)2 Bytes9.1 temperature (°C)CRT
74AC Return TemperatureStatus (ºC)2 Bytes9.1 temperature (°C)CRT
75Error/AlarmStatus: 0 = No alarm, 1 = Alarm1 Bit1.5 alarmCRT
76Error CodeStatus: AC Unit Error Code2 BytesDPT.8CRT
77Operating Hours Counter (h)Status: Number of operating hours2 Bytes7.7 time (h)CRT
78Operating Hours Counter (sec)Status: Number of operating seconds4 Bytes13.100 time lag (s)CRT
79Lock Remote ControlStatus: 0 = Unlocked, 1 = Locked1 Bit1.2 booleanCRT
80Lock Control ObjectsStatus: 0 = Unlocked, 1 = Locked1 Bit1.2 booleanCRT
81Current SceneStatus: 0...4 = Scene X+1, 63 = No Scene1 Byte17.1 scene numberCRT
82Legacy_ Mode0 = Auto, 1 = Heat, 2 = Dry, 3 = Fan, 4 = Cool1 ByteDPT.5CRWT
83Legacy_ Fan Speed0 = Auto, 1...4 = Speed 1...41 ByteDPT.5CRWT
84Legacy_ Vanes0 = Auto, 1...5 = Pos 1...5, 6 = Swing1 ByteDPT.5CRWT
Parameters (62)
ParameterTypeDefault
Download latest database entry for this product and its User Manual from:texthttp://www.intesisbox.com
Send READs for Control objects on bus recovery (T & U flags must be active)listNo
> Delay before sending READs (sec)unsignedInt 0…3010
Enable "Lock Remote Control" objectslistNo
Enable "Lock Control Objects" objectslistNo
Enable function "Operating Hours Counter"listNo
Enable object "Error Code"listNo
Indoor unit has FAN mode (see manual for the Indoor unit)listYes
Enable "Mode: Cool/Heat" objects (for Control and Status)listNo
Enable use of +/- object for ModelistNo
> Datapoint typelist0 = Decrease, 1 = Increase [DPT_1.007]
Enable use of bit-type Mode objects (for Control)listNo
Enable use of bit-type Mode objects (for Status)listNo
Enable use of Text object for ModelistNo
ASCII strings shown via object "Mode: Text"text<< 14-byte string values >>
> String when mode is AUTOtextAUTO
> String when mode is HEATtextHEAT
> String when mode is COOLtextCOOL
> String when mode is FANtextFAN
> String when mode is DRYtextDRY
Enable use of Legacy_ object for ModelistNo
Fan is accessible in Indoor unit (see manual for the Indoor unit)listYes
Available Fan Speeds in Indoor Unit (see manual for the Indoor unit)unsignedInt 2…43
Indoor unit has AUTO fan speed (see manual for the Indoor unit)listNo
Enable use of +/- object for Fan SpeedlistNo
Enable "Fan Speed Man/Auto" objects (for Control and Status)listNo
Enable use of bit-type Fan Speed objects (for Control)listNo
Enable use of bit-type Fan Speed objects (for Status)listNo
Enable use of Text object for Fan SpeedlistNo
ASCII strings shown via object "Fan Speed: Text"text<< 14-byte string values >>
> String when fan speed is AUTOtextAUTO
> String when fan speed is 1textSPEED 1
> String when fan speed is 2textSPEED 2
> String when fan speed is 3textSPEED 3
> String when fan speed is 4textSPEED 4
Enable use of Legacy_ object for Fan SpeedlistNo
Indoor unit has U-D Vanes (see manual for the Indoor unit)listNo
Available positions in Indoor Unit (see manual for the Indoor unit)unsignedInt 4…55
Indoor unit has AUTO Vanes U-D (see manual for the Indoor unit)listNo
Enable "Vanes U-D Swing" objects (for Control and Status)listNo
Enable "Vanes U-D Man/Auto" objects (for Control and Status)listNo
Enable use of +/- object for Vanes U-DlistNo
Enable use of bit-type Vanes U-D objects (for Control)listNo
Enable use of bit-type Vanes U-D objects (for Status)listNo
Enable use of Text object for Vanes U-DlistNo
ASCII strings shown via object "Vanes U-D: Text"text<< 14-byte string values >>
> String when in AUTOtextU-D AUTO
> String when in Position 1textU-D POS 1
> String when in Position 2textU-D POS 2
> String when in Position 3textU-D POS 3
> String when in Position 4textU-D POS 4
> String when in Position 5textU-D POS 5
> String when in SWINGtextU-D SWING
Enable use of Legacy_ object for VaneslistNo
Enable use of +/- object for Setpoint TemperaturelistNo
Ambient temperature reference is provided from KNX (see User Guide if enabled)listNo
Enable use of sceneslistNo
Enable use of bit objects for saving sceneslistNo
Enable use of bit objects for scene executionlistNo
Enable use of Open Window functionlistNo
> AC switch-off timeout (min)unsignedInt 0…3010
> Reload last On/Off value once window is closedlistNo

Version history

ApplicationApp noFingerprintFirst seenSizeFile
KNX Gateway for Mitsubishi air conditioning units, flush mounted 1.0 latest$04825CB72026-11-25137 KBDownload

About this file

This is the official ETS product database for the MDT technologies GmbH KNX Gateway for Mitsubishi air conditioning units, flush mounted (SCN-ACG0MIT.01), published by the manufacturer in the KNX online catalog. To use it, open ETS, go to Catalogs → Import and choose the downloaded .knxprod file. The device then appears in your catalog and can be added to a project. Older versions are kept so existing projects can be matched to the application program they were commissioned with.

More from MDT technologies GmbH

All MDT technologies GmbH products