KNX Database
MDT technologies GmbH SCN-ACG0DAI.01 KNX Gateway for Daikin residential air conditioning units, flush mounted

KNX Gateway for Daikin residential air conditioning units, flush mounted SCN-ACG0DAI.01

MDT technologies GmbH · Order number SCN-ACG0DAI.01 · System Devices › KNX Gateways

Download .knxprod KNX Gateway for Daikin residential air conditioning units, flush mounted 0.4 · 130 KB

Product

ManufacturerMDT technologies GmbH
Product nameKNX Gateway for Daikin residential air conditioning units, flush mounted
Order numberSCN-ACG0DAI.01
HardwareDK AC Interface
MediumTwisted Pair
Bus current (mA)6
Rail mountedNo
RegistrationCertified · 2026-06-17
Languagesde-DE, en-US, es-ES
Catalog entryM-0083_H-INT01-1-O0077_HP-0481-04-D684-O0077_CI-SCN.2DACG0DAI.2E01-0
FingerprintD684
SHA-2569c501cc7034b21762992378d9dade89cf04d403be7899deb1f0965a7f4289e93
First seen2026-11-25
Markets69 markets

Application program: KNX Gateway for Daikin residential air conditioning units, flush mounted 0.4

Application number$0481
Version0.4
Mask versionMV-0025 (2.5)
KNX Data SecureNo
Parameters55
Group objects50
Group objects (50)
NoNameFunctionSizeDPTFlags
0ON / OFF1 = ON, 0 = OFF1 Bit1.1 switchCRWT
1Mode0 = Auto, 1 = Heat, 2 = Dry, 3 = Fan, 4 = Cool1 ByteCRT
2HVAC Mode0 = Auto, 1 = Heat, 3 = Cool, 9 = Fan, 14 = Dry1 ByteCRT
3Mode: Cool/Heat0 = Cool, 1 = Heat1 BitDPT.1CRWT
4Mode: TextMaximum: 14 characters14 Bytes16.1 Character String (ISO 8859-1)CRT
5Mode: Auto1 = Mode Auto Active1 Bit1.2 booleanCRWT
6Mode: Heat1 = Mode Heat Active1 Bit1.2 booleanCRWT
7Mode: Dry1 = Mode Dry Active1 Bit1.2 booleanCRWT
8Mode: Cool1 = Mode Cool Active1 Bit1.2 booleanCRWT
9Mode: Fan1 = Mode Fan Active1 Bit1.2 booleanCRWT
10Setpoint TemperatureºC2 Bytes9.1 temperature (°C)CRWT
11Setpoint Temperature [+/-]0 = Up, 1 = Down1 Bit1.8 up/downCW
11Setpoint Temperature [+/-]0 = Decrease, 1 = Increase1 BitDPT.1CW
12Virtual Setpoint TemperatureºC2 Bytes9.1 temperature (°C)CWTU
13Virtual Ambient TemperatureºC2 Bytes9.1 temperature (°C)CWTU
14Fan0 = Auto, 1 = Low, 2 = M1, 3 = M2, 4 = M3, 5 = High1 ByteCRT
15Fan: TextMaximum: 14 characters14 Bytes16.1 Character String (ISO 8859-1)CRT
16Fan Speed [+/-]0 = Up, 1 = Down1 Bit1.8 up/downCW
16Fan Speed [+/-]0 = Decrease, 1 = Increase1 BitDPT.1CW
17Fan: Auto1 = Fan Speed Auto1 Bit1.2 booleanCRWT
18Fan: Low1 = Fan Speed Low1 Bit1.2 booleanCRWT
19Fan: Mid11 = Fan Speed Mid 11 Bit1.2 booleanCRWT
20Fan: Mid21 = Fan Speed Mid 21 Bit1.2 booleanCRWT
21Fan: Mid31 = Fan Speed Mid 31 Bit1.2 booleanCRWT
22Fan: High1 = Fan Speed High1 Bit1.2 booleanCRWT
23Swing0 = Off, 1 = Vert, 2 = Hori, 3 = Both1 ByteCRT
24Swing: TextMaximum: 14 characters14 Bytes16.1 Character String (ISO 8859-1)CRT
25Swing: Vertical1 = Swing Vertical1 Bit1.1 switchCRWT
26Swing: Horizontal1 = Swing Horizontal1 Bit1.1 switchCRWT
27Error1 = Error in AC Unit1 BitDPT.1CRT
28Error CodeAC Unit Error Code2 BytesCRT
29Window1 = Closed, 0 = Open1 Bit1.9 open/closeCWTU
30Device Enable1 = Enabled, 0 = Disabled1 Bit1.3 enableCRWT
31Remote Control Enable1 = Enabled, 0 = Disabled1 Bit1.3 enableCRWT
32Time CounterHours2 Bytes7.1 pulsesCRWT
33Humidifying: Mode0 = Off, 1 = Low, 2 = Stan, 3 = High, 4 = Cont1 ByteCRT
34Humidifying: TextMaximum: 14 characters14 Bytes16.1 Character String (ISO 8859-1)CRWT
35Humidifying: Off1 = Humidifying Off1 Bit1.2 booleanCRWT
36Humidifying: Low1 = Humidifying Low1 Bit1.2 booleanCRWT
37Humidifying: Standard1 = Humidifying Standard1 Bit1.2 booleanCRWT
38Humidifying: High1 = Humidifying High1 Bit1.2 booleanCRWT
39Humidifying: Continuous1 = Humidifying Continuous1 Bit1.2 booleanCRWT
40Save/Execute Scene0 = Scene 1, 1 = Scene 21 ByteCW
41Current Scene0 = Scene 1, 1 = Scene 21 ByteCRT
42Save Scene 11 = Save Scene 11 Bit1.2 booleanCW
43Save Scene 21 = Save Scene 21 Bit1.2 booleanCW
44Execute Scene 11 = Execute Scene 11 Bit1.2 booleanCW
45Execute Scene 21 = Execute Scene 21 Bit1.2 booleanCW
46Auto Heat1 = Auto Heat Active1 Bit1.2 booleanCRT
47Auto Cool1 = Auto Cool Active1 Bit1.2 booleanCRT
Parameters (46)
ParameterTypeDefault
AC unit typelistCONVENTIONAL
FeaturestextTwo Swing Modes; No Humidifier
FeaturestextTwo Swing Modes; With Humidifier
FeaturestextNo Swing; No Humidifier
Window minutesunsignedInt 0…300
Send object values to KNX bus on startuplistYes
When window closes go to last statelistNo
Virtual temperature controllistNo
Dual Setpoint TemperaturelistNo
Temperature UnitslistCelsius
Mode [1byte] object typelistDPT_20.105_HVAC_Mode
Show "Mode: Cool/Heat" object (1 Bit)listNo
Show Device ObjectslistNo
Show Mode BitslistNo
Show Fan BitslistNo
Show Swing BitslistNo
Show Humidifying ObjectslistNo
Show Humidifying BitslistNo
Show Scene ObjectslistNo
Show Scene BitslistNo
Show Auto DetailslistNo
Enable Mode/Fan/Swing/Humi TextslistNo
Show Fan Speed [+/-] objectlistNo
Fan Speed [+/-] object typelistDPT_1.007_Step (0=Dec/1=Inc)
Show Setpoint Temperature [+/-] objectlistNo
Setpoint Temperature [+/-] object typelistDPT_1.007_Step (0=Dec/1=Inc)
Mode Auto TexttextAuto
Mode Heat TexttextHeat
Mode Dry TexttextDry
Mode Fan TexttextFan
Mode Cool TexttextCool
Fan Auto texttextAuto
Fan Low texttextLow
Fan Middle-1 texttextMiddle-1
Fan Middle-2 texttextMiddle-2
Fan Middle-3 texttextMiddle-3
Fan High texttextHigh
Swing Off TexttextOff
Swing Vertical TexttextVertical
Swing Horizontal TexttextHorizontal
Swing Both TexttextBoth
Humidifying Off TexttextOff
Humidifying Low TexttextLow
Humidifying Standard TexttextStandard
Humidifying High TexttextHigh
Humidifying Continuous TexttextContinuous

Version history

ApplicationApp noFingerprintFirst seenSizeFile
KNX Gateway for Daikin residential air conditioning units, flush mounted 0.4 latest$0481D6842026-11-25130 KBDownload

About this file

This is the official ETS product database for the MDT technologies GmbH KNX Gateway for Daikin residential air conditioning units, flush mounted (SCN-ACG0DAI.01), published by the manufacturer in the KNX online catalog. To use it, open ETS, go to Catalogs → Import and choose the downloaded .knxprod file. The device then appears in your catalog and can be added to a project. Older versions are kept so existing projects can be matched to the application program they were commissioned with.

More from MDT technologies GmbH