KNX Database

L&J secure heat meter WMZC 30 WMZC-SEC

Lingg & Janke · Order number WMZC-SEC · counters / meters › L&J secure heat meters

Download .knxprod SEC heat meter WMZC F006-30 3.0 · 132 KB

Product

ManufacturerLingg & Janke
Product nameL&J secure heat meter WMZC 30
Order numberWMZC-SEC
Product textL&J secure heat meter WMZC
HardwareWMZC-SEC
MediumTwisted Pair
Bus current (mA)10
Rail mountedNo
RegistrationRegistered · 2021-06-30
Languagesen-US, de-DE
Catalog entryM-00E1_H-15006.2D10-1_HP-F006-30-B097_CI-WMZC.2DSEC-1
FingerprintB097
SHA-256407efb80a0585c64a7cb9ab912f7543335edc33bec41c9cac6a6afd43ca64be8
First seen2026-11-25
Markets69 markets

Application program: SEC heat meter WMZC F006-30 3.0

Application number$F006
Version3.0
Mask versionMV-0021 (2.1)
KNX Data SecureYes
Minimum ETS version5.0
Parameters362
Group objects35
Group objects (35)
NoNameFunctionSizeDPTFlags
0output 4byte EIS11serial number4 BytesDPT.12CT
1output 4byte EIS11meter number4 BytesDPT.12CT
2output 1bit EIS1status1 Bit1.11 stateCT
3input 1bit EIS1read meters1 Bit1.17 triggerCWU
4output 4byte EIS11meter reading (MWh)4 Bytes13.16 active energy (MWh)CT
4output 4byte EIS11meter reading thermal e. (MWh)4 Bytes13.16 active energy (MWh)CT
5output 4byte EIS11meter reading (kWh)4 Bytes13.13 active energy (kWh)CT
5output 4byte EIS11meter reading thermal e. (kWh)4 Bytes13.13 active energy (kWh)CT
6output 4byte EIS1115min. diff. (kWh)4 Bytes13.13 active energy (kWh)CT
7output 4byte EIS1160min. diff. (kWh)4 Bytes13.13 active energy (kWh)CT
8output 4byte EIS11rel. counter (MWh)4 Bytes13.16 active energy (MWh)CT
9input 1bit EIS1reset rel. counter1 Bit1.15 resetCWU
10output 4byte EIS11rel. reverse counter (MWh)4 Bytes13.16 active energy (MWh)CT
11input 4byte EIS11set rel. reverse counter4 Bytes13.16 active energy (MWh)CWU
12output 1bit EIS1rel. reverse counter is zero1 Bit1.2 booleanCT
16output 4byte EIS11volume (m3)4 Bytes12.1201 volume (m³)CT
17output 4byte EIS11volume (l)4 Bytes12.1200 volume liquid (l)CT
18output 4byte EIS11meter reading cooling e. (MWh)4 Bytes13.16 active energy (MWh)CT
19output 4byte EIS11meter reading cooling e. (kWh)4 Bytes13.13 active energy (kWh)CT
61output 4byte EIS9power (W)4 Bytes14.56 power (W)CT
62output 1bit EIS1upper switch point power1 Bit1.1 switchCT
63output 1bit EIS1lower switch point power1 Bit1.1 switchCT
82output 4byte EIS9flow (m3/h)4 Bytes14.1200 volume flux for meters (m³/h)CT
83output 1bit EIS1upper switch point flow1 Bit1.1 switchCT
84output 1bit EIS1lower switch point flow1 Bit1.1 switchCT
85output 4byte EIS11flow (0.0001 m3/h)4 Bytes13.2 flow rate (m³/h)CT
91output 4byte EIS9temperature forward flow (°C)2 Bytes9.1 temperature (°C)CT
92output 1bit EIS1upper switch point temp. forw.1 Bit1.1 switchCT
93output 1bit EIS1lower switch point temp. forw.1 Bit1.1 switchCT
94output 4byte EIS9temperature return flow (°C)2 Bytes9.1 temperature (°C)CT
95output 1bit EIS1upper switch point temp. ret.1 Bit1.1 switchCT
96output 1bit EIS1lower switch point temp. ret.1 Bit1.1 switchCT
97output 4byte EIS9temperature difference (K)2 Bytes9.2 temperature difference (K)CT
98output 1bit EIS1upper switch point temp. diff.1 Bit1.1 switchCT
99output 1bit EIS1lower switch point temp. diff.1 Bit1.1 switchCT
Parameters (36)
ParameterTypeDefault
type of meterlistType 1 meter
show meter readingslistyes
send meter readingslistcyclic
cycle time in s (5..65535)unsignedInt 5…65535300
show meter readings (high resolution)listno
send meter readings (high resolution)listcyclic
show meter statuslistno
show serial numberlistno
send meter status and serial number cyclicallylistno
show 15 min. and 60 min. meter differenceslistno
show relative forward meterlistno
show relative reverse meterlistno
send relative meterslistcyclic
show powerlistno
send power cyclicallylistyes
power limit monitoringlistno
action at upper limitlistdo nothing
upper limit in W (1..65000)unsignedInt 1…650001100
action at lower limitlistdo nothing
lower limit in W (1..65000)unsignedInt 1…65000900
show flowlistno
send flow cyclicallylistyes
show flow as integer (resolution 0.0001 m3/h)listno
flow limit monitoringlistno
upper limit in l/h (1/1000 m3/h) (1..65000)unsignedInt 1…650001100
lower limit in l/h (1/1000 m3/h) (1..65000)unsignedInt 1…65000900
show temperaturelistno
send temperature cyclicallylistyes
temperature forward limit monitoringlistno
temperature return limit monitoringlistno
temperature difference limit monitoringlistno
upper limit in °C (1..100)unsignedInt 1…10080
lower limit in °C (1..100)unsignedInt 1…10060
upper limit in K (1..100)unsignedInt 1…10020
lower limit in K (1..100)unsignedInt 1…1005
meter value refresh time in s (5..900)unsignedInt 5…9005

Version history

ApplicationApp noFingerprintFirst seenSizeFile
SEC heat meter WMZC F006-30 3.0 latest$F006B0972026-11-25132 KBDownload

About this file

This is the official ETS product database for the Lingg & Janke L&J secure heat meter WMZC 30 (WMZC-SEC), published by the manufacturer in the KNX online catalog. To use it, open ETS, go to Catalogs → Import and choose the downloaded .knxprod file. The device then appears in your catalog and can be added to a project. Older versions are kept so existing projects can be matched to the application program they were commissioned with.