KNX Database

heat meter WMZC FacilityWeb WMZC-FW

Lingg & Janke · Order number WMZC-FW · counters / meters › heat meters

Download .knxprod heat meter WMZC-FW F006-22 2.2 · 90 KB

Product

ManufacturerLingg & Janke
Product nameheat meter WMZC FacilityWeb
Order numberWMZC-FW
HardwareWMZC-FW
MediumTwisted Pair
Bus current (mA)6
Rail mountedNo
RegistrationRegistered · 2017-05-31
Languagesen-US, de-DE
Catalog entryM-00E1_H-15006-1_HP-F006-22-6BA4_CI-WMZC.2DFW-1
Fingerprint6BA4
SHA-25658f5c37a0a5f6605c4cfaaaef7b2f3d43d37330c30135529ddd8bb6e46a6c498
First seen2026-11-25
Markets69 markets

Application program: heat meter WMZC-FW F006-22 2.2

Application number$F006
Version2.2
Mask versionMV-0021 (2.1)
KNX Data SecureNo
Parameters394
Group objects38
Group objects (38)
NoNameFunctionSizeDPTFlags
0output 4byte EIS11serial number4 BytesDPT.12CT
1output 4byte EIS11meter number4 BytesDPT.12CT
2output 1bit EIS1status1 Bit1.1 switchCT
3input 1bit EIS1read meters1 Bit1.17 triggerCWU
4output 4byte EIS11meter reading (MWh)4 BytesDPT.13CT
4output 4byte EIS11meter reading thermal e. (MWh)4 BytesDPT.13CT
5output 4byte EIS11meter reading (kWh)4 Bytes13.13 active energy (kWh)CT
5output 4byte EIS11meter reading thermal e. (kWh)4 Bytes13.13 active energy (kWh)CT
6output 4byte EIS1115min. diff. (kWh)4 Bytes13.13 active energy (kWh)CT
7output 4byte EIS1160min. diff. (kWh)4 Bytes13.13 active energy (kWh)CT
8output 4byte EIS11rel. counter (MWh)4 BytesDPT.13CT
9input 1bit EIS1reset rel. counter1 Bit1.17 triggerCWU
10output 4byte EIS11rel. reverse counter (MWh)4 BytesDPT.13CT
11input 4byte EIS11set rel. reverse counter4 BytesDPT.13CWU
12output 1bit EIS1rel. reverse counter is zero1 Bit1.1 switchCT
13output 4byte EIS11due day meter reading (MWh)4 BytesDPT.13CT
14output 3byte EIS4due day date3 Bytes11.1 dateCT
15input 3byte EIS4set due day date3 Bytes11.1 dateCWU
16output 4byte EIS11volume (m3)4 BytesDPT.12CT
17output 4byte EIS11volume (l)4 BytesDPT.12CT
18output 4byte EIS11meter reading cooling e. (MWh)4 BytesDPT.13CT
19output 4byte EIS11meter reading cooling e. (kWh)4 Bytes13.13 active energy (kWh)CT
61output 4byte EIS9power (W)4 Bytes14.56 power (W)CT
62output 1bit EIS1upper switch point power1 Bit1.1 switchCT
63output 1bit EIS1lower switch point power1 Bit1.1 switchCT
82output 4byte EIS9flow (m3/h)4 BytesDPT.14CT
83output 1bit EIS1upper switch point flow1 Bit1.1 switchCT
84output 1bit EIS1lower switch point flow1 Bit1.1 switchCT
85output 4byte EIS11flow (0.0001 m3/h)4 Bytes13.2 flow rate (m³/h)CT
91output 4byte EIS9temperature forward flow (°C)2 Bytes9.1 temperature (°C)CT
92output 1bit EIS1upper switch point temp. forw.1 Bit1.1 switchCT
93output 1bit EIS1lower switch point temp. forw.1 Bit1.1 switchCT
94output 4byte EIS9temperature return flow (°C)2 Bytes9.1 temperature (°C)CT
95output 1bit EIS1upper switch point temp. ret.1 Bit1.1 switchCT
96output 1bit EIS1lower switch point temp. ret.1 Bit1.1 switchCT
97output 4byte EIS9temperature difference (K)2 Bytes9.2 temperature difference (K)CT
98output 1bit EIS1upper switch point temp. diff.1 Bit1.1 switchCT
99output 1bit EIS1lower switch point temp. diff.1 Bit1.1 switchCT
Parameters (43)
ParameterTypeDefault
type of meterlistType 1 meter
show meter readingslistyes
send meter readingslistcyclic
cycle time in s (5..65535)unsignedInt 5…65535300
show meter readings (high resolution)listno
send meter readings (high resolution)listcyclic
show meter statuslistno
show serial numberlistno
send meter status and serial number cyclicallylistno
show 15 min. and 60 min. meter differenceslistno
show relative forward meterlistno
show relative reverse meterlistno
send relative meterslistcyclic
show due date value and datelistno
send due date value and date cyclicallylistyes
set due date - daylist01
set due date - monthlist01
show powerlistno
send power cyclicallylistyes
power limit monitoringlistno
action at upper limitlistdo nothing
upper limit in W (1..65000)unsignedInt 1…650001100
action at lower limitlistdo nothing
lower limit in W (1..65000)unsignedInt 1…65000900
show flowlistno
send flow cyclicallylistyes
show flow as integer (resolution 0.0001 m3/h)listno
flow limit monitoringlistno
upper limit in l/h (1/1000 m3/h) (1..65000)unsignedInt 1…650001100
lower limit in l/h (1/1000 m3/h) (1..65000)unsignedInt 1…65000900
show temperaturelistno
send temperature cyclicallylistyes
temperature forward limit monitoringlistno
temperature return limit monitoringlistno
temperature difference limit monitoringlistno
upper limit in °C (1..100)unsignedInt 1…10080
lower limit in °C (1..100)unsignedInt 1…10060
upper limit in K (1..100)unsignedInt 1…10020
lower limit in K (1..100)unsignedInt 1…1005
meter value refresh time in s (5..900)unsignedInt 5…9005
recording in 1st columnlistmeter reading
recording in 1st columnlistmeter reading thermal energy
recording in 2nd columnlistvolume

Version history

ApplicationApp noFingerprintFirst seenSizeFile
heat meter WMZC-FW F006-22 2.2 latest$F0066BA42026-11-2590 KBDownload

About this file

This is the official ETS product database for the Lingg & Janke heat meter WMZC FacilityWeb (WMZC-FW), published by the manufacturer in the KNX online catalog. To use it, open ETS, go to Catalogs → Import and choose the downloaded .knxprod file. The device then appears in your catalog and can be added to a project. Older versions are kept so existing projects can be matched to the application program they were commissioned with.

More from Lingg & Janke

All Lingg & Janke products