gas meter GZC FacilityWeb GZC-FW
Lingg & Janke · Order number GZC-FW · counters / meters › gas meters
Download .knxprod gas meter GZC-FW F003-14 1.4 · 75 KB
Product
| Manufacturer | Lingg & Janke |
|---|---|
| Product name | gas meter GZC FacilityWeb |
| Order number | GZC-FW |
| Hardware | GZC-FW |
| Medium | Twisted Pair |
| Bus current (mA) | 6 |
| Rail mounted | No |
| Registration | Registered · 2017-06-08 |
| Languages | en-US, de-DE |
| Catalog entry | M-00E1_H-15003-1_HP-F003-14-46AF_CI-GZC.2DFW-1 |
| Fingerprint | 46AF |
| SHA-256 | fae9cacb0343e382f45de97b4b44b659e2bd333ae03e811f96b49a81e0b86d2c |
| First seen | 2026-11-25 |
| Markets | 69 markets |
Application program: gas meter GZC-FW F003-14 1.4
| Application number | $F003 |
|---|---|
| Version | 1.4 |
| Mask version | MV-0021 (2.1) |
| KNX Data Secure | No |
| Parameters | 150 |
| Group objects | 23 |
Group objects (23)
| No | Name | Function | Size | DPT | Flags |
|---|---|---|---|---|---|
| 0 | output 4byte EIS11 | serial number | 4 Bytes | DPT.12 | CT |
| 1 | output 4byte EIS11 | meter number | 4 Bytes | DPT.12 | CT |
| 2 | output 1bit EIS1 | status | 1 Bit | 1.1 switch | CT |
| 3 | input 1bit EIS1 | read meters | 1 Bit | 1.17 trigger | CWU |
| 4 | output 4byte EIS11 | meter reading (m3) | 4 Bytes | DPT.12 | CT |
| 5 | output 4byte EIS11 | meter reading (l) | 4 Bytes | DPT.12 | CT |
| 6 | output 4byte EIS11 | 15min. diff. (l) | 4 Bytes | DPT.13 | CT |
| 7 | output 4byte EIS11 | 60min. diff. (l) | 4 Bytes | DPT.13 | CT |
| 8 | output 4byte EIS11 | rel. counter (m3) | 4 Bytes | DPT.12 | CT |
| 9 | input 1bit EIS1 | reset rel. counter | 1 Bit | 1.17 trigger | CWU |
| 10 | output 4byte EIS11 | rel. reverse counter (m3) | 4 Bytes | DPT.12 | CT |
| 11 | input 4byte EIS11 | set rel. reverse counter | 4 Bytes | DPT.12 | CWU |
| 12 | output 1bit EIS1 | rel. reverse counter is zero | 1 Bit | 1.1 switch | CT |
| 13 | output 4byte EIS11 | due day meter reading (m3) | 4 Bytes | DPT.12 | CT |
| 14 | output 3byte EIS4 | due day date | 3 Bytes | 11.1 date | CT |
| 15 | input 3byte EIS4 | set due day date | 3 Bytes | 11.1 date | CWU |
| 82 | output 4byte EIS9 | flow (m3/h) | 4 Bytes | DPT.14 | CT |
| 83 | output 1bit EIS1 | upper switch point flow | 1 Bit | 1.1 switch | CT |
| 84 | output 1bit EIS1 | lower switch point flow | 1 Bit | 1.1 switch | CT |
| 85 | output 4byte EIS11 | flow (0.0001 m3/h) | 4 Bytes | 13.2 flow rate (m³/h) | CT |
| 91 | output 4byte EIS9 | battery voltage (V) | 4 Bytes | 14.27 electric potential (V) | CT |
| 92 | output 1bit EIS1 | upper switch point battery | 1 Bit | 1.1 switch | CT |
| 93 | output 1bit EIS1 | lower switch point battery | 1 Bit | 1.1 switch | CT |
Parameters (31)
| Parameter | Type | Default |
|---|---|---|
| type of meter | list | Type 1 meter |
| show meter reading | list | yes |
| send meter reading | list | cyclic |
| cycle time in s (5..65535) | unsignedInt 5…65535 | 300 |
| show meter reading (high resolution) | list | no |
| send meter reading (high resolution) | list | cyclic |
| show meter status | list | no |
| show serial number | list | no |
| send meter status and serial number cyclically | list | no |
| show 15 min. and 60 min. meter differences | list | no |
| show relative forward meter | list | no |
| show relative reverse meter | list | no |
| send relative meters | list | cyclic |
| show due date value and date | list | no |
| send due date value and date cyclically | list | yes |
| set due date - day | list | 01 |
| set due date - month | list | 01 |
| show flow | list | no |
| send flow cyclically | list | yes |
| show flow as integer (resolution 0.0001 m3/h) | list | no |
| flow limit monitoring | list | no |
| action at upper limit | list | do nothing |
| upper limit in l/h (1/1000 m3/h) (1..6000) | unsignedInt 1…6000 | 1100 |
| action at lower limit | list | do nothing |
| lower limit in l/h (1/1000 m3/h) (1..6000) | unsignedInt 1…6000 | 900 |
| show battery voltage | list | no |
| send battery voltage cyclically | list | yes |
| battery limit monitoring | list | no |
| upper limit in mV (1..5000) | unsignedInt 1…5000 | 4000 |
| lower limit in mV (1..5000) | unsignedInt 1…5000 | 3000 |
| meter value refresh time in s (5..900) | unsignedInt 5…900 | 5 |
Version history
| Application | App no | Fingerprint | First seen | Size | File |
|---|---|---|---|---|---|
| gas meter GZC-FW F003-14 1.4 latest | $F003 | 46AF | 2026-11-25 | 75 KB | Download |
About this file
This is the official ETS product database for the Lingg & Janke gas meter GZC FacilityWeb (GZC-FW), published by the manufacturer in the KNX online catalog. To use it, open ETS, go to Catalogs → Import and choose the downloaded .knxprod file. The device then appears in your catalog and can be added to a project. Older versions are kept so existing projects can be matched to the application program they were commissioned with.
More from Lingg & Janke
- electricity meter EZD FacilityWeb 22 EZD-FW-22
- L&J secure electricity meter EZD 30 EZD-SEC
- L&J secure gas meter GZC 30 GZC-SEC
- water meter KWZC FacilityWeb KWZC-FW
- L&J secure water meter KWZC 30 KWZC-SEC
- heat meter WMZC FacilityWeb WMZC-FW
- L&J secure heat meter WMZC 30 WMZC-SEC
- AH3F16H-SEC switching actuator 3fold 79236-SEC
- AH5F16H-SEC switching actuator 5fold 79237-SEC
- AH9F16H-SEC switching actuator 9fold 79238-SEC
- COMIP-REG-1-SEC secure IP interface 87342-SEC
- TA4F55-BUDGET-SEC push button 4fold 87840-SEC