KNX Database

AH5F16H-SEC switching actuator 5fold 79237-SEC

Lingg & Janke · Order number 79237-SEC · binary output › L&J secure series

Download .knxprod SECSL 5x switching, time, scene, announce, inh. 2034-40 4.0 · 149 KB

Product

ManufacturerLingg & Janke
Product nameAH5F16H-SEC switching actuator 5fold
Order number79237-SEC
Product textAH5F16H-SEC switching actuator 5f
HardwareAH5F16H-SEC
MediumTwisted Pair
Bus current (mA)5
Rail mountedYes
Width (mm)160
RegistrationRegistered · 2026-03-05
Languagesen-US, de-DE
Catalog entryM-00E1_H-2034.2D10-1_HP-2034-40-093F_CI-79237.2DSEC-1
Fingerprint093F
SHA-2565c1a584992affa617eb63b3c8813ce275a543b4d97cdb46650db540a326891ab
First seen2026-11-25
Markets69 markets

Application program: SECSL 5x switching, time, scene, announce, inh. 2034-40 4.0

Application number$2034
Version4.0
Mask versionMV-0021 (2.1)
KNX Data SecureYes
Minimum ETS version6.0
Parameters550
Group objects80
Group objects (80)
NoNameFunctionSizeDPTFlags
0input A, CH1 switchingchannel A, CH1 object 11 Bit1.1 switchCW
0input A1, CH1 ORchannel A, CH1 object 11 Bit1.1 switchCW
0input A1, CH1 EXORchannel A, CH1 object 11 Bit1.1 switchCW
0input A1, CH1 ANDchannel A, CH1 object 11 Bit1.1 switchCW
1input A2, CH1 ORchannel A, CH1 object 21 Bit1.1 switchCW
1input A2, CH1 EXORchannel A, CH1 object 21 Bit1.1 switchCW
1input A2, CH1 ANDchannel A, CH1 object 21 Bit1.1 switchCW
2output A, CH1 statuschannel A, CH1 object 31 Bit1.1 switchCT
2output A, CH1 status INVchannel A, CH1 object 31 Bit1.1 switchCT
3input A, CH1 sceneschannel A, CH1 object 41 Byte18.1 scene controlCW
4input A, CH1 announcechannel A, CH1 object 51 Bit1.1 switchCW
5input A, CH1 inhibitchannel A, CH1 object 61 Bit1.3 enableCW
6input A, CH1 reset hour meterchannel A, CH1 object 71 Bit1.15 resetCW
7output A, CH1 hour meter (h)channel A, CH1 object 82 Bytes7.7 time (h)CT
7output A, CH1 hour meter (s)channel A, CH1 object 84 Bytes13.100 time lag (s)CT
8output A, CH1 limit reachedchannel A, CH1 object 91 Bit1.2 booleanCT
9input B1, CH2 ORchannel B, CH2 object 11 Bit1.1 switchCW
9input B1, CH2 EXORchannel B, CH2 object 11 Bit1.1 switchCW
9input B1, CH2 ANDchannel B, CH2 object 11 Bit1.1 switchCW
9input B, CH2 switchingchannel B, CH2 object 11 Bit1.1 switchCW
10input B2, CH2 EXORchannel B, CH2 object 21 Bit1.1 switchCW
10input B2, CH2 ANDchannel B, CH2 object 21 Bit1.1 switchCW
10input B2, CH2 ORchannel B, CH2 object 21 Bit1.1 switchCW
11output B, CH2 statuschannel B, CH2 object 31 Bit1.1 switchCT
11output B, CH2 status INVchannel B, CH2 object 31 Bit1.1 switchCT
12input B, CH2 sceneschannel B, CH2 object 41 Byte18.1 scene controlCW
13input B, CH2 announcechannel B, CH2 object 51 Bit1.1 switchCW
14input B, CH2 inhibitchannel B, CH2 object 61 Bit1.3 enableCW
15input B, CH2 reset hour meterchannel B, CH2 object 71 Bit1.15 resetCW
16output B, CH2 hour meter (h)channel B, CH2 object 82 Bytes7.7 time (h)CT
16output B, CH2 hour meter (s)channel B, CH2 object 84 Bytes13.100 time lag (s)CT
17output B, CH2 limit reachedchannel B, CH2 object 91 Bit1.2 booleanCT
18input C1, CH3 ORchannel C, CH3 object 11 Bit1.1 switchCW
18input C1, CH3 EXORchannel C, CH3 object 11 Bit1.1 switchCW
18input C1, CH3 ANDchannel C, CH3 object 11 Bit1.1 switchCW
18input C, CH3 switchingchannel C, CH3 object 11 Bit1.1 switchCW
19input C2, CH3 ANDchannel C, CH3 object 21 Bit1.1 switchCW
19input C2, CH3 ORchannel C, CH3 object 21 Bit1.1 switchCW
19input C2, CH3 EXORchannel C, CH3 object 21 Bit1.1 switchCW
20output C, CH3 statuschannel C, CH3 object 31 Bit1.1 switchCT
20output C, CH3 status INVchannel C, CH3 object 31 Bit1.1 switchCT
21input C, CH3 sceneschannel C, CH3 object 41 Byte18.1 scene controlCW
22input C, CH3 announcechannel C, CH3 object 51 Bit1.1 switchCW
23input C, CH3 inhibitchannel C, CH3 object 61 Bit1.3 enableCW
24input C, CH3 reset hour meterchannel C, CH3 object 71 Bit1.15 resetCW
25output C, CH3 hour meter (h)channel C, CH3 object 82 Bytes7.7 time (h)CT
25output C, CH3 hour meter (s)channel C, CH3 object 84 Bytes13.100 time lag (s)CT
26output C, CH3 limit reachedchannel C, CH3 object 91 Bit1.2 booleanCT
27input D1, CH4 ORchannel D, CH4 object 11 Bit1.1 switchCW
27input D1, CH4 EXORchannel D, CH4 object 11 Bit1.1 switchCW
27input D1, CH4 ANDchannel D, CH4 object 11 Bit1.1 switchCW
27input D, CH4 switchingchannel D, CH4 object 11 Bit1.1 switchCW
28input D2, CH4 ANDchannel D, CH4 object 21 Bit1.1 switchCW
28input D2, CH4 ORchannel D, CH4 object 21 Bit1.1 switchCW
28input D2, CH4 EXORchannel D, CH4 object 21 Bit1.1 switchCW
29output D, CH4 statuschannel D, CH4 object 31 Bit1.1 switchCT
29output D, CH4 status INVchannel D, CH4 object 31 Bit1.1 switchCT
30input D, CH4 sceneschannel D, CH4 object 41 Byte18.1 scene controlCW
31input D, CH4 announcechannel D, CH4 object 51 Bit1.1 switchCW
32input D, CH4 inhibitchannel D, CH4 object 61 Bit1.3 enableCW
33input D, CH4 reset hour meterchannel D, CH4 object 71 Bit1.15 resetCW
34output D, CH4 hour meter (h)channel D, CH4 object 82 Bytes7.7 time (h)CT
34output D, CH4 hour meter (s)channel D, CH4 object 84 Bytes13.100 time lag (s)CT
35output D, CH4 limit reachedchannel D, CH4 object 91 Bit1.2 booleanCT
36input E, CH5 switchingchannel E, CH5 object 11 Bit1.1 switchCW
36input E1, CH5 ORchannel E, CH5 object 11 Bit1.1 switchCW
36input E1, CH5 EXORchannel E, CH5 object 11 Bit1.1 switchCW
36input E1, CH5 ANDchannel E, CH5 object 11 Bit1.1 switchCW
37input E2, CH5 EXORchannel E, CH5 object 21 Bit1.1 switchCW
37input E2, CH5 ANDchannel E, CH5 object 21 Bit1.1 switchCW
37input E2, CH5 ORchannel E, CH5 object 21 Bit1.1 switchCW
38output E, CH5 statuschannel E, CH5 object 31 Bit1.1 switchCT
38output E, CH5 status INVchannel E, CH5 object 31 Bit1.1 switchCT
39input E, CH5 sceneschannel E, CH5 object 41 Byte18.1 scene controlCW
40input E, CH5 announcechannel E, CH5 object 51 Bit1.1 switchCW
41input E, CH5 inhibitchannel E, CH5 object 61 Bit1.3 enableCW
42input E, CH5 reset hour meterchannel E, CH5 object 71 Bit1.15 resetCW
43output E, CH5 hour meter (h)channel E, CH5 object 82 Bytes7.7 time (h)CT
43output E, CH5 hour meter (s)channel E, CH5 object 84 Bytes13.100 time lag (s)CT
44output E, CH5 limit reachedchannel E, CH5 object 91 Bit1.2 booleanCT
Parameters (121)
ParameterTypeDefault
channel A, CH1text
output A, CH1 usagelistenabled
at buspower recovery set switching object tolistdo not initialize
relay contact islistNO (norm. open)
at buspower failure contact islistno change
timing functionslistno
logic combinationlistno
statuslistno
sceneslistno
announce functionlistno
inhibit functionlistno
hour meterlistno
channel A, CH1 timing functionstext
switch on delaylistno
delay time (1..255 sec)unsignedInt 1…2555
switch off delaylistno
staircase function / blinkinglistno
on time (1..255 sec)unsignedInt 1…2553
off time (1..255 sec)unsignedInt 1…2553
staircase on time (1..64800 sec)unsignedInt 1…64800180
retrigger staircase time (only, if on/off delay disabled)listyes
staircase prewarninglistno
prewarning off time (1..30 *100 ms)unsignedInt 1…305
prewarning on time (1..255 sec)unsignedInt 1…2553
number of prewarnings (1..7)unsignedInt 1…73
channel A, CH1 logic combinationtext
logic combinationlistnone
at buspower recovery set logic object tolist"0"
channel A, CH1 statustext
status is transmittedlistat value change
status send delay time (0..120 *100 ms)unsignedInt 0…1201
channel A, CH1 scenestext
scene 1listno action
scene 2listno action
scene 3listno action
scene 4listno action
scene 5listno action
scene 6listno action
scene 7listno action
scene 8listno action
scene 9listno action
scene 10listno action
scene 11listno action
scene 12listno action
scene 13listno action
scene 14listno action
scene 15listno action
scene 16listno action
scene 17listno action
scene 18listno action
scene 19listno action
scene 20listno action
scene 21listno action
scene 22listno action
scene 23listno action
scene 24listno action
scene 25listno action
scene 26listno action
scene 27listno action
scene 28listno action
scene 29listno action
scene 30listno action
scene 31listno action
scene 32listno action
enable scene savinglistno
channel A, CH1 announce functiontext
announce withlist"1"
at bus voltage recovery set announce object tolist"0"
action when announce startslistno action
on time (1..15 sec)unsignedInt 1…153
off time (1..15 sec)unsignedInt 1…153
action when announce endslistno action
channel A, CH1 inhibit functiontext
inhibit withlist"1"
at bus voltage recovery set inhibit object tolist"0"
action when inhibit startslistno action
action when inhibit endslistno action
channel A, CH1 hour metertext
hour meter values are presented inlistDPT 7.007 hours (16bit unsigned int EIS10)
hour meter reading is transmittedlistcyclically
cycle timelist5 min
hour meter limit monitoringlistno
limit (1..65000 h)unsignedInt 1…655351000
hour meter >= limit -> limit reached object = 1text
channel B, CH2text
output B, CH2 usagelistenabled
channel B, CH2 timing functionstext
channel B, CH2 logic combinationtext
channel B, CH2 statustext
channel B, CH2 scenestext
channel B, CH2 announce functiontext
channel B, CH2 inhibit functiontext
channel B, CH2 hour metertext
channel C, CH3text
output C, CH3 usagelistenabled
channel C, CH3 timing functionstext
channel C, CH3 logic combinationtext
channel C, CH3 statustext
channel C, CH3 scenestext
channel C, CH3 announce functiontext
channel C, CH3 inhibit functiontext
channel C, CH3 hour metertext
channel D, CH4text
output D, CH4 usagelistenabled
channel D, CH4 timing functionstext
channel D, CH4 logic combinationtext
channel D, CH4 statustext
channel D, CH4 scenestext
channel D, CH4 announce functiontext
channel D, CH4 inhibit functiontext
channel D, CH4 hour metertext
channel E, CH5text
output E, CH5 usagelistenabled
channel E, CH5 timing functionstext
channel E, CH5 logic combinationtext
channel E, CH5 statustext
status is transmittedlistdo not transmit
channel E, CH5 scenestext
channel E, CH5 announce functiontext
channel E, CH5 inhibit functiontext
channel E, CH5 hour metertext

Version history

ApplicationApp noFingerprintFirst seenSizeFile
SECSL 5x switching, time, scene, announce, inh. 2034-40 4.0 latest$2034093F2026-11-25149 KBDownload

About this file

This is the official ETS product database for the Lingg & Janke AH5F16H-SEC switching actuator 5fold (79237-SEC), published by the manufacturer in the KNX online catalog. To use it, open ETS, go to Catalogs → Import and choose the downloaded .knxprod file. The device then appears in your catalog and can be added to a project. Older versions are kept so existing projects can be matched to the application program they were commissioned with.

More from Lingg & Janke

All Lingg & Janke products