L&J secure water meter KWZC 30 KWZC-SEC
Lingg & Janke · Order number KWZC-SEC · counters / meters › L&J secure water meters
Download .knxprod SEC water meter KWZC F002-30 3.0 · 118 KB
Product
| Manufacturer | Lingg & Janke |
|---|---|
| Product name | L&J secure water meter KWZC 30 |
| Order number | KWZC-SEC |
| Product text | L&J secure water meter KWZC |
| Hardware | KWZC-SEC |
| Medium | Twisted Pair |
| Bus current (mA) | 10 |
| Rail mounted | No |
| Registration | Registered · 2021-06-30 |
| Languages | en-US, de-DE |
| Catalog entry | M-00E1_H-15002.2D10-1_HP-F002-30-04C3_CI-KWZC.2DSEC-1 |
| Fingerprint | 04C3 |
| SHA-256 | ab129802f4b04fe4ef4251e091ccfa412e8123ce35ee9e6eaf646b8e04d7cfff |
| First seen | 2026-11-25 |
| Markets | 69 markets |
Application program: SEC water meter KWZC F002-30 3.0
| Application number | $F002 |
|---|---|
| Version | 3.0 |
| Mask version | MV-0021 (2.1) |
| KNX Data Secure | Yes |
| Minimum ETS version | 5.0 |
| Parameters | 141 |
| Group objects | 19 |
Group objects (19)
| No | Name | Function | Size | DPT | Flags |
|---|---|---|---|---|---|
| 0 | output 4byte EIS11 | serial number | 4 Bytes | DPT.12 | CT |
| 1 | output 4byte EIS11 | meter number | 4 Bytes | DPT.12 | CT |
| 2 | output 1bit EIS1 | status | 1 Bit | 1.11 state | CT |
| 3 | input 1bit EIS1 | read meters | 1 Bit | 1.17 trigger | CWU |
| 4 | output 4byte EIS11 | meter reading (m3) | 4 Bytes | 12.1201 volume (m³) | CT |
| 5 | output 4byte EIS11 | meter reading (l) | 4 Bytes | 12.1200 volume liquid (l) | CT |
| 6 | output 4byte EIS11 | 15min. diff. (l) | 4 Bytes | 13.1200 delta volume liquid (l) | CT |
| 7 | output 4byte EIS11 | 60min. diff. (l) | 4 Bytes | 13.1200 delta volume liquid (l) | CT |
| 8 | output 4byte EIS11 | rel. counter (m3) | 4 Bytes | 12.1201 volume (m³) | CT |
| 9 | input 1bit EIS1 | reset rel. counter | 1 Bit | 1.15 reset | CWU |
| 10 | output 4byte EIS11 | rel. reverse counter (m3) | 4 Bytes | 12.1201 volume (m³) | CT |
| 11 | input 4byte EIS11 | set rel. reverse counter | 4 Bytes | 12.1201 volume (m³) | CWU |
| 12 | output 1bit EIS1 | rel. reverse counter is zero | 1 Bit | 1.2 boolean | CT |
| 16 | output 4byte EIS11 | volume forward (m3) | 4 Bytes | 12.1201 volume (m³) | CT |
| 18 | output 4byte EIS11 | volume reverse (m3) | 4 Bytes | 12.1201 volume (m³) | CT |
| 82 | output 4byte EIS9 | flow (m3/h) | 4 Bytes | 14.1200 volume flux for meters (m³/h) | CT |
| 83 | output 1bit EIS1 | upper switch point flow | 1 Bit | 1.1 switch | CT |
| 84 | output 1bit EIS1 | lower switch point flow | 1 Bit | 1.1 switch | CT |
| 85 | output 4byte EIS11 | flow (0.0001 m3/h) | 4 Bytes | 13.2 flow rate (m³/h) | CT |
Parameters (22)
| Parameter | Type | Default |
|---|---|---|
| type of meter | list | Type 1 meter |
| show meter readings | list | yes |
| send meter readings | list | cyclic |
| cycle time in s (5..65535) | unsignedInt 5…65535 | 300 |
| show meter reading (high resolution) | list | no |
| send meter reading (high resolution) | list | cyclic |
| show meter status | list | no |
| show serial number | list | no |
| send meter status and serial number cyclically | list | no |
| show 15 min. and 60 min. meter differences | list | no |
| show relative forward meter | list | no |
| show relative reverse meter | list | no |
| send relative meters | list | cyclic |
| show flow | list | no |
| send flow cyclically | list | yes |
| show flow as integer (resolution 0.0001 m3/h) | list | no |
| flow limit monitoring | list | no |
| action at upper limit | list | do nothing |
| upper limit in l/h (1/1000 m3/h) (1..65000) | unsignedInt 1…65000 | 1100 |
| action at lower limit | list | do nothing |
| lower limit in l/h (1/1000 m3/h) (1..65000) | unsignedInt 1…65000 | 900 |
| meter value refresh time in s (5..900) | unsignedInt 5…900 | 5 |
Version history
| Application | App no | Fingerprint | First seen | Size | File |
|---|---|---|---|---|---|
| SEC water meter KWZC F002-30 3.0 latest | $F002 | 04C3 | 2026-11-25 | 118 KB | Download |
About this file
This is the official ETS product database for the Lingg & Janke L&J secure water meter KWZC 30 (KWZC-SEC), published by the manufacturer in the KNX online catalog. To use it, open ETS, go to Catalogs → Import and choose the downloaded .knxprod file. The device then appears in your catalog and can be added to a project. Older versions are kept so existing projects can be matched to the application program they were commissioned with.
More from Lingg & Janke
- electricity meter EZD FacilityWeb 22 EZD-FW-22
- L&J secure electricity meter EZD 30 EZD-SEC
- gas meter GZC FacilityWeb GZC-FW
- L&J secure gas meter GZC 30 GZC-SEC
- water meter KWZC FacilityWeb KWZC-FW
- heat meter WMZC FacilityWeb WMZC-FW
- L&J secure heat meter WMZC 30 WMZC-SEC
- AH3F16H-SEC switching actuator 3fold 79236-SEC
- AH5F16H-SEC switching actuator 5fold 79237-SEC
- AH9F16H-SEC switching actuator 9fold 79238-SEC
- COMIP-REG-1-SEC secure IP interface 87342-SEC