| 0 | A/C Unit - ON/OFF Status | 0=Off; 1=On | 1 Bit | 1.1 switch | CRT |
| 1 | A/C Unit - Setpoint Status | Setpoint Temperature sent | 2 Bytes | 9.1 temperature (°C) | CRT |
| 2 | A/C Unit - Fan Status | 0%Au;1-33%Mi;34-66%Me;>67%Max | 1 Byte | 5.1 percentage (0..100%) | CRT |
| 3 | Zone 1 - ON/OFF | 0=Off; 1=On | 1 Bit | 1.1 switch | CWTU |
| 4 | Zone 2 - ON/OFF | 0=Off; 1=On | 1 Bit | 1.1 switch | CWTU |
| 5 | Zone 3 - ON/OFF | 0=Off; 1=On | 1 Bit | 1.1 switch | CWTU |
| 6 | Zone 4 - ON/OFF | 0=Off; 1=On | 1 Bit | 1.1 switch | CWTU |
| 7 | Zone 5 - ON/OFF | 0=Off; 1=On | 1 Bit | 1.1 switch | CWTU |
| 8 | Zone 6 - ON/OFF | 0=Off; 1=On | 1 Bit | 1.1 switch | CWTU |
| 9 | Zone 7 - ON/OFF | 0=Off; 1=On | 1 Bit | 1.1 switch | CWTU |
| 10 | Zone 8 - ON/OFF | 0=Off; 1=On | 1 Bit | 1.1 switch | CWTU |
| 11 | Zone 1 - ON/OFF Status | 0=Off; 1=On | 1 Bit | 1.1 switch | CRT |
| 12 | Zone 2 - ON/OFF Status | 0=Off; 1=On | 1 Bit | 1.1 switch | CRT |
| 13 | Zone 3 - ON/OFF Status | 0=Off; 1=On | 1 Bit | 1.1 switch | CRT |
| 14 | Zone 4 - ON/OFF Status | 0=Off; 1=On | 1 Bit | 1.1 switch | CRT |
| 15 | Zone 5 - ON/OFF Status | 0=Off; 1=On | 1 Bit | 1.1 switch | CRT |
| 16 | Zone 6 - ON/OFF Status | 0=Off; 1=On | 1 Bit | 1.1 switch | CRT |
| 17 | Zone 7 - ON/OFF Status | 0=Off; 1=On | 1 Bit | 1.1 switch | CRT |
| 18 | Zone 8 - ON/OFF Status | 0=Off; 1=On | 1 Bit | 1.1 switch | CRT |
| 19 | Zone 1 - Setpoint | Setpoint Temperature | 2 Bytes | 9.1 temperature (°C) | CWTU |
| 20 | Zone 2 - Setpoint | Setpoint Temperature | 2 Bytes | 9.1 temperature (°C) | CWTU |
| 21 | Zone 3 - Setpoint | Setpoint Temperature | 2 Bytes | 9.1 temperature (°C) | CWTU |
| 22 | Zone 4 - Setpoint | Setpoint Temperature | 2 Bytes | 9.1 temperature (°C) | CWTU |
| 23 | Zone 5 - Setpoint | Setpoint Temperature | 2 Bytes | 9.1 temperature (°C) | CWTU |
| 24 | Zone 6 - Setpoint | Setpoint Temperature | 2 Bytes | 9.1 temperature (°C) | CWTU |
| 25 | Zone 7 - Setpoint | Setpoint Temperature | 2 Bytes | 9.1 temperature (°C) | CWTU |
| 26 | Zone 8 - Setpoint | Setpoint Temperature | 2 Bytes | 9.1 temperature (°C) | CWTU |
| 27 | Zone 1 - Setpoint Status | Setpoint Temperature | 2 Bytes | 9.1 temperature (°C) | CRT |
| 28 | Zone 2 - Setpoint Status | Setpoint Temperature | 2 Bytes | 9.1 temperature (°C) | CRT |
| 29 | Zone 3 - Setpoint Status | Setpoint Temperature | 2 Bytes | 9.1 temperature (°C) | CRT |
| 30 | Zone 4 - Setpoint Status | Setpoint Temperature | 2 Bytes | 9.1 temperature (°C) | CRT |
| 31 | Zone 5 - Setpoint Status | Setpoint Temperature | 2 Bytes | 9.1 temperature (°C) | CRT |
| 32 | Zone 6 - Setpoint Status | Setpoint Temperature | 2 Bytes | 9.1 temperature (°C) | CRT |
| 33 | Zone 7 - Setpoint Status | Setpoint Temperature | 2 Bytes | 9.1 temperature (°C) | CRT |
| 34 | Zone 8 - Setpoint Status | Setpoint Temperature | 2 Bytes | 9.1 temperature (°C) | CRT |
| 35 | Zone 1 - Grille Control | 0=Close; 1=Open | 1 Bit | 1.1 switch | CRT |
| 36 | Zone 2 - Grille Control | 0=Close; 1=Open | 1 Bit | 1.1 switch | CRT |
| 37 | Zone 3 - Grille Control | 0=Close; 1=Open | 1 Bit | 1.1 switch | CRT |
| 38 | Zone 4 - Grille Control | 0=Close; 1=Open | 1 Bit | 1.1 switch | CRT |
| 39 | Zone 5 - Grille Control | 0=Close; 1=Open | 1 Bit | 1.1 switch | CRT |
| 40 | Zone 6 - Grille Control | 0=Close; 1=Open | 1 Bit | 1.1 switch | CRT |
| 41 | Zone 7 - Grille Control | 0=Close; 1=Open | 1 Bit | 1.1 switch | CRT |
| 42 | Zone 8 - Grille Control | 0=Close; 1=Open | 1 Bit | 1.1 switch | CRT |
| 43 | Zone 1 - Grille Status Reception | Link with Grille Status | 1 Bit | 1.1 switch | CWU |
| 44 | Zone 2 - Grille Status Reception | Link with Grille Status | 1 Bit | 1.1 switch | CWU |
| 45 | Zone 3 - Grille Status Reception | Link with Grille Status | 1 Bit | 1.1 switch | CWU |
| 46 | Zone 4 - Grille Status Reception | Link with Grille Status | 1 Bit | 1.1 switch | CWU |
| 47 | Zone 5 - Grille Status Reception | Link with Grille Status | 1 Bit | 1.1 switch | CWU |
| 48 | Zone 6 - Grille Status Reception | Link with Grille Status | 1 Bit | 1.1 switch | CWU |
| 49 | Zone 7 - Grille Status Reception | Link with Grille Status | 1 Bit | 1.1 switch | CWU |
| 50 | Zone 8 - Grille Status Reception | Link with Grille Status | 1 Bit | 1.1 switch | CWU |
| 51 | Zone 1 - Reference Temperature | External Sensor Temperature | 2 Bytes | 9.1 temperature (°C) | CWTU |
| 52 | Zone 2 - Reference Temperature | External Sensor Temperature | 2 Bytes | 9.1 temperature (°C) | CWTU |
| 53 | Zone 3 - Reference Temperature | External Sensor Temperature | 2 Bytes | 9.1 temperature (°C) | CWTU |
| 54 | Zone 4 - Reference Temperature | External Sensor Temperature | 2 Bytes | 9.1 temperature (°C) | CWTU |
| 55 | Zone 5 - Reference Temperature | External Sensor Temperature | 2 Bytes | 9.1 temperature (°C) | CWTU |
| 56 | Zone 6 - Reference Temperature | External Sensor Temperature | 2 Bytes | 9.1 temperature (°C) | CWTU |
| 57 | Zone 7 - Reference Temperature | External Sensor Temperature | 2 Bytes | 9.1 temperature (°C) | CWTU |
| 58 | Zone 8 - Reference Temperature | External Sensor Temperature | 2 Bytes | 9.1 temperature (°C) | CWTU |
| 59 | Additional bypass | 0=Close; 1=Open | 1 Bit | 1.1 switch | CWT |
| 60 | A/C Unit - Modes [1byte] | 0=Aut;1=Ht;3=Cool;9=Fan;14=Dry | 1 Byte | | CWTU |
| 61 | A/C Unit - Modes Status [1byte] | Actual Mode:0=Auto,1=Heat,etc. | 1 Byte | | CRT |
| 62 | A/C Unit - Heat Mode | 1=Set Heat mode; 0=Nothing | 1 Bit | | CWTU |
| 63 | A/C Unit - Heat Mode Status | 1=Heat mode is Set; 0=Not Set | 1 Bit | | CRT |
| 64 | A/C Unit - Cool Mode | 1=Set Cool mode; 0=Nothing | 1 Bit | | CWTU |
| 65 | A/C Unit - Cool Mode Status | 1=Cool mode is Set; 0=Not Set | 1 Bit | | CRT |
| 66 | A/C Unit - Dry Mode | 1=Set Dry mode; 0=Nothing | 1 Bit | | CWTU |
| 67 | A/C Unit - Dry Mode Status | 1=Dry mode is Set; 0=Not Set | 1 Bit | | CRT |
| 68 | A/C Unit - Fan Mode | 1=Set Fan mode; 0=Nothing | 1 Bit | | CWTU |
| 69 | A/C Unit - Fan Mode Status | 1=Fan mode is Set; 0=Not Set | 1 Bit | | CRT |
| 70 | A/C Unit - Auto Mode | 1=Set Auto mode; 0=Nothing | 1 Bit | | CWTU |
| 71 | A/C Unit - Auto Mode Status | 1=Auto mode is Set; 0=Not Set | 1 Bit | | CRT |
| 72 | A/C Unit - Simplified Mode | 0=Cool; 1=Heat | 1 Bit | | CWTU |
| 73 | A/C Unit - Fan [1byte] | 0%Au;1-33%Mi;34-66%Me;>67%Max | 1 Byte | 5.1 percentage (0..100%) | CWTU |
| 74 | A/C Unit - Fan [1bit] | 0=Lower; 1=Higher | 1 Bit | 1.1 switch | CWU |
| 75 | Temperature Restriction | 1=T.Restricted; 0=No restric. | 1 Bit | 1.3 enable | CWTU |
| 76 | External Temperature Returned | External Sensor Temperature | 2 Bytes | 9.1 temperature (°C) | CRWTU |