IRSC Plus ZN1CL-IRSC
Zennio · Order number ZN1CL-IRSC · Infrared › IR Decoder
Air-Conditioning System Controller through IR Commands
Download .knxprod IRSC Plus 6.13 6.13 · 164 KB
Product
| Manufacturer | Zennio |
|---|---|
| Product name | IRSC Plus |
| Order number | ZN1CL-IRSC |
| Product text | IRSC |
| Hardware | IRSC (Air Conditioning Controller) |
| Medium | Twisted Pair |
| Bus current (mA) | 10 |
| Rail mounted | No |
| Registration | Certified · 2017-11-21 |
| Languages | en-US, es-ES, de-DE, fr-FR, nl-NL, it-IT, ru-RU, sv-SE, pt-PT |
| Catalog entry | M-0071_H-ZN1111-4_HP-1130-6D-1CED_CI-ZN1CL.2DIRSC-1 |
| Fingerprint | 1CED |
| SHA-256 | c09d8e08a8abd5c55a8d296c72ee08f5073ccdbdbc14fac749829524c654030b |
| First seen | 2026-11-25 |
| Markets | 59 markets |
Application program: IRSC Plus 6.13 6.13
| Application number | $1130 |
|---|---|
| Version | 6.13 |
| Mask version | MV-0701 (7.1) |
| KNX Data Secure | No |
| Minimum ETS version | 5.0 |
| Parameters | 90 |
| Group objects | 29 |
Group objects (29)
| No | Name | Function | Size | DPT | Flags |
|---|---|---|---|---|---|
| 0 | ON/OFF | Turn ON/OFF the split | 1 Bit | 1.1 switch | CWU |
| 1 | ON/OFF (status) | Split state (ON/OFF) | 1 Bit | 1.1 switch | CRT |
| 2 | Temperature | Value sent to the split | 2 Bytes | 9.1 temperature (°C) | CRWTU |
| 3 | Fan [1byte] | 0%Au;1-33%Mi;34-66%Mid;>67%Max | 1 Byte | 5.1 percentage (0..100%) | CWTU |
| 4 | Fan [1bit] | 0=Lower, 1=Higher | 1 Bit | 1.7 step | CW |
| 5 | Fan (status) | Actual Fan Level | 1 Byte | 5.1 percentage (0..100%) | CRT |
| 6 | Swing | 1=Swing, 0=Stop/Step | 1 Bit | 1.1 switch | CWTU |
| 7 | Swing (status) | Swing state: 0=Stopped,1=Swing | 1 Bit | 1.1 switch | CRT |
| 8 | Heat Mode | 1=Set mode, 0=Nothing | 1 Bit | 1.16 acknowledge | CWTU |
| 9 | Heat Mode (status) | 1=Heat mode is Set, 0=Not Set | 1 Bit | 1.1 switch | CRT |
| 10 | Cool Mode | 1=Set mode, 0=Nothing | 1 Bit | 1.16 acknowledge | CWTU |
| 11 | Cool Mode (status) | 1=Cool mode is Set, 0=Not Set | 1 Bit | 1.1 switch | CRT |
| 12 | Dry Mode | 1=Set mode, 0=Nothing | 1 Bit | 1.16 acknowledge | CWTU |
| 13 | Dry Mode (status) | 1=Dry mode is Set, 0=Not Set | 1 Bit | 1.1 switch | CRT |
| 14 | Fan Mode | 1=Set mode, 0=Nothing | 1 Bit | 1.16 acknowledge | CWTU |
| 15 | Fan Mode (status) | 1=Fan mode is Set, 0=Not Set | 1 Bit | 1.1 switch | CRT |
| 16 | Auto Mode | 1=Set mode, 0=Nothing | 1 Bit | 1.16 acknowledge | CWTU |
| 17 | Auto Mode (status) | 1=Auto mode is Set, 0=Not Set | 1 Bit | 1.1 switch | CRT |
| 18 | Modes [1byte] | 0=Aut;1=Ht;3=Cool;9=Fan;14=Dry | 1 Byte | 20.105 HVAC control mode | CWTU |
| 19 | Modes [1byte] (status) | Actual Mode:0=Auto,1=Heat,etc. | 1 Byte | 20.105 HVAC control mode | CRT |
| 20 | Scenes [1byte] | 0-63(Run(1-64));128-191(Learn) | 1 Byte | 18.1 scene control | CWU |
| 21 | Disable Device | 0=Normal Running, 1=Disabled | 1 Bit | 1.3 enable | CRWU |
| 22 | Fixed Auto-OFF [1bit] | 1=Sw.OFF after "param. value" | 1 Bit | 1.10 start/stop | CRWU |
| 23 | Fixed Auto-ON [1bit] | 1=Sw. ON after "param. value" | 1 Bit | 1.10 start/stop | CRWU |
| 24 | Presence Detection | 0=Empty Room, 1=Presence | 1 Bit | 1.10 start/stop | CWU |
| 25 | Window Sensor | 1=Window Open, 0=Closed | 1 Bit | 1.19 window/door | CWU |
| 26 | Simplified Mode | 0=Heat, 1=Cool | 1 Bit | 1.100 cooling/heating | CWU |
| 26 | Simplified Mode | 0=Cool, 1=Heat | 1 Bit | 1.100 cooling/heating | CWU |
| 27 | Disable Temperature Limitation | 0=Disabled, 1=Enabled | 1 Bit | 1.3 enable | CRWU |
Parameters (48)
| Parameter | Type | Default |
|---|---|---|
| Split Model (See Table on Zennio website) | unsignedInt 0…255 | 1 |
| Min. time set between two consecutive IR messages [t=0.1x(sec)] | unsignedInt 10…255 | 20 |
| Simplified Mode (1bit control for Heat and Cool modes) | list | No |
| Temperature Range (*) (only for Heat and Cool modes) | list | No |
| - Cool Mode Min. Temperature | unsignedInt 16…30 | 21 |
| - Heat Mode Max. Temperature | unsignedInt 16…30 | 24 |
| Status shall this function be used? | list | No |
| - ON/OFF | list | No |
| - Mode | list | No |
| - Fan | list | No |
| - Swing | list | No |
| Initial Configuration | list | Default |
| - ON/OFF | list | Last saved status |
| - Temperature | list | Last saved status |
| Initial Temperature [T=x(ºC)] | unsignedInt 16…30 | 20 |
| - Mode | list | Last saved status |
| - Fan | list | Last saved status |
| - Swing | list | Last saved status |
| Send Reset Configuration to the split (when reset occurs) | list | No |
| - ON/OFF (*) | list | Don't send |
| - Temperature | list | Don't send |
| - Mode (*) | list | Don't send |
| - Fan (*) | list | Don't send |
| - Swing (*) | list | Don't send |
| Data Update DELAY [x 1sec] | unsignedInt 0…255 | 0 |
| Scenes (Will scenes be used?) | list | No |
| Scene 1 | list | No |
| - Scene Number | unsignedInt 1…64 | 1 |
| - ON/OFF | list | No Change |
| - Temperature | list | No Change |
| - Mode | list | No Change |
| - Fan | list | No Change |
| - Swing | list | Stop |
| Scene 2 | list | No |
| - Swing | list | No Change |
| Scene 3 | list | No |
| Scene 4 | list | No |
| - Swing | list | Swing |
| - Automatic OFF | list | Disabled |
| - Automatic OFF value | unsignedInt 0…255 | 30 |
| - Automatic OFF time units | list | Minutes |
| - Automatic ON | list | Disabled |
| - Automatic ON value | unsignedInt 0…255 | 30 |
| - Automatic ON time units | list | Minutes |
| Window Sensor | list | Disabled |
| Waiting period [seconds] to turn the split OFF after the window is open | unsignedInt 0…255 | 20 |
| Presence Detector | list | Disabled |
| Waiting period [minutes] to turn the split OFF since the room gets empty | unsignedInt 0…255 | 15 |
Version history
| Application | App no | Fingerprint | First seen | Size | File |
|---|---|---|---|---|---|
| IRSC Plus 8.3 8.3 latest | $1130 | E27A | 2026-11-25 | 115 KB | Download |
| IRSC Plus 6.13 6.13 | $1130 | 1CED | 2026-11-25 | 164 KB | Download |
| IRSC Zone 1.9 1.9 | $1140 | 2E7C | 2026-11-25 | 103 KB | Download |
| IRSC Open 1.2 1.2 | $2311 | E95D | 2026-11-25 | 108 KB | Download |
About this file
This is the official ETS product database for the Zennio IRSC Plus (ZN1CL-IRSC), published by the manufacturer in the KNX online catalog. To use it, open ETS, go to Catalogs → Import and choose the downloaded .knxprod file. The device then appears in your catalog and can be added to a project. Older versions are kept so existing projects can be matched to the application program they were commissioned with.
More from Zennio
- HeatingBOX 24V 4X ZCL-4HT24
- HeatingBOX 24V 8X ZCL-8HT24
- KLIC-FJ ZCL-FJ
- KLIC-LG1 ZCL-LG1
- KLIC-TS ZCL-TS
- ZoningBOX 4 ZCL-ZB4
- ZoningBOX 6 ZCL-ZB6
- HeatingBOX 230V 2X v2 ZCL2H230V2
- HeatingBOX 230V 4X v2 ZCL4H230V2
- HeatingBOX 230V 6X v2 ZCL6H230V2
- HeatingBOX 230V 8X v2 ZCL8H230V2
- KLIC-DA v2 ZCLDAV2