KNX Database
Zennio ZN1CL-IRSC IRSC Plus

IRSC Plus ZN1CL-IRSC

Zennio · Order number ZN1CL-IRSC · Infrared › IR Decoder

Air-Conditioning System Controller through IR Commands

Download .knxprod IRSC Plus 8.3 8.3 · 115 KB

Product

ManufacturerZennio
Product nameIRSC Plus
Order numberZN1CL-IRSC
Product textIRSC
HardwareIRSC (Air Conditioning Controller)
MediumTwisted Pair
Bus current (mA)10
Rail mountedNo
RegistrationCertified · 2017-11-21
Languagesen-US, es-ES, fr-FR, de-DE, nl-NL, it-IT, ru-RU, sv-SE, pt-PT, uk-UA
Catalog entryM-0071_H-ZN1111-4_HP-1130-83-E27A_CI-ZN1CL.2DIRSC-1
FingerprintE27A
SHA-256ea881cbd6a5554a5e2f698010500b9a206e440a4f9debc7525264abe1b3d69cc
First seen2026-11-25
Markets59 markets

Application program: IRSC Plus 8.3 8.3

Application number$1130
Version8.3
Mask versionMV-0701 (7.1)
KNX Data SecureNo
Parameters85
Group objects29
Group objects (29)
NoNameFunctionSizeDPTFlags
0ON/OFFTurn ON/OFF the split1 Bit1.1 switchCWU
1ON/OFF (status)Split state (ON/OFF)1 Bit1.1 switchCRT
2TemperatureValue sent to the split2 Bytes9.1 temperature (°C)CRWTU
3Fan [1byte]0%Au;1-33%Mi;34-66%Mid;>67%Max1 Byte5.1 percentage (0..100%)CWTU
4Fan [1bit]0=Lower, 1=Higher1 Bit1.7 stepCW
5Fan (status)Actual Fan Level1 Byte5.1 percentage (0..100%)CRT
6Swing1=Swing, 0=Stop/Step1 Bit1.1 switchCWTU
7Swing (status)Swing state: 0=Stopped,1=Swing1 Bit1.1 switchCRT
8Heat Mode1=Set mode, 0=Nothing1 Bit1.16 acknowledgeCWTU
9Heat Mode (status)1=Heat mode is Set, 0=Not Set1 Bit1.1 switchCRT
10Cool Mode1=Set mode, 0=Nothing1 Bit1.16 acknowledgeCWTU
11Cool Mode (status)1=Cool mode is Set, 0=Not Set1 Bit1.1 switchCRT
12Dry Mode1=Set mode, 0=Nothing1 Bit1.16 acknowledgeCWTU
13Dry Mode (status)1=Dry mode is Set, 0=Not Set1 Bit1.1 switchCRT
14Fan Mode1=Set mode, 0=Nothing1 Bit1.16 acknowledgeCWTU
15Fan Mode (status)1=Fan mode is Set, 0=Not Set1 Bit1.1 switchCRT
16Auto Mode1=Set mode, 0=Nothing1 Bit1.16 acknowledgeCWTU
17Auto Mode (status)1=Auto mode is Set, 0=Not Set1 Bit1.1 switchCRT
18Modes [1byte]0=Aut;1=Ht;3=Cool;9=Fan;14=Dry1 Byte20.105 HVAC control modeCWTU
19Modes [1byte] (status)Actual Mode:0=Auto,1=Heat,etc.1 Byte20.105 HVAC control modeCRT
20Scenes [1byte]0-63(Run(1-64));128-191(Learn)1 Byte18.1 scene controlCWU
21Disable Device0=Normal Running, 1=Disabled1 Bit1.3 enableCRWU
22Fixed Auto-OFF [1bit]1=Sw.OFF after "param. value"1 Bit1.10 start/stopCRWU
23Fixed Auto-ON [1bit]1=Sw. ON after "param. value"1 Bit1.10 start/stopCRWU
24Presence Detection0=Empty Room, 1=Presence1 Bit1.10 start/stopCWU
25Window Sensor1=Window Open, 0=Closed1 Bit1.19 window/doorCWU
26Simplified Mode0=Heat, 1=Cool1 Bit1.100 heating/coolingCWU
26Simplified Mode0=Cool, 1=Heat1 Bit1.100 heating/coolingCWU
27Disable Temperature Limitation0=Disabled, 1=Enabled1 Bit1.3 enableCRWU
Parameters (46)
ParameterTypeDefault
Split Model (See Table on Zennio website)unsignedInt 0…2551
Min. time set between two consecutive IR messages [t=0.1x(sec)]unsignedInt 10…25520
Simplified Mode (1bit control for Heat and Cool modes)listNo
Temperature Range (*) (only for Heat and Cool modes)listNo
- Cool Mode Min. TemperatureunsignedInt 16…3021
- Heat Mode Max. TemperatureunsignedInt 16…3024
Status shall this function be used?listNo
- ON/OFFlistNo
- ModelistNo
- FanlistNo
- SwinglistNo
Initial ConfigurationlistDefault
- ON/OFFlistLast saved status
- TemperaturelistLast saved status
Initial Temperature [T=x(ºC)]unsignedInt 16…3020
- ModelistLast saved status
- FanlistLast saved status
- SwinglistLast saved status
Send Reset Configuration to the split (when reset occurs)listNo
- ON/OFF (*)listDon't send
- TemperaturelistDon't send
- Mode (*)listDon't send
- Fan (*)listDon't send
- Swing (*)listDon't send
Data Update DELAY [x 1sec]unsignedInt 0…2550
Scenes (Will scenes be used?)listNo
Scene 1listNo
- Scene NumberunsignedInt 1…641
- ON/OFFlistNo Change
- TemperaturelistNo Change
- ModelistNo Change
- FanlistNo Change
- SwinglistNo Change
Scene 2listNo
Scene 3listNo
Scene 4listNo
- Automatic OFFlistDisabled
- Automatic OFF valueunsignedInt 0…25530
- Automatic OFF time unitslistMinutes
- Automatic ONlistDisabled
- Automatic ON valueunsignedInt 0…25530
- Automatic ON time unitslistMinutes
Window SensorlistDisabled
Waiting period [seconds] to turn the split OFF after the window is openunsignedInt 0…25520
Presence DetectorlistDisabled
Waiting period [minutes] to turn the split OFF since the room gets emptyunsignedInt 0…25515

Version history

ApplicationApp noFingerprintFirst seenSizeFile
IRSC Plus 8.3 8.3 latest$1130E27A2026-11-25115 KBDownload
IRSC Plus 6.13 6.13$11301CED2026-11-25164 KBDownload
IRSC Zone 1.9 1.9$11402E7C2026-11-25103 KBDownload
IRSC Open 1.2 1.2$2311E95D2026-11-25108 KBDownload

About this file

This is the official ETS product database for the Zennio IRSC Plus (ZN1CL-IRSC), published by the manufacturer in the KNX online catalog. To use it, open ETS, go to Catalogs → Import and choose the downloaded .knxprod file. The device then appears in your catalog and can be added to a project. Older versions are kept so existing projects can be matched to the application program they were commissioned with.

More from Zennio

All Zennio products