Valve actuator AP 562/02 5WG1 562-7AB02
Siemens · Order number 5WG1 562-7AB02 · Heating, Air conditioning, Ventilation › Valve actuators
Download .knxprod 12 A1 Valve actuator 510E01 0.1 · 70 KB
Product
| Manufacturer | Siemens |
|---|---|
| Product name | Valve actuator AP 562/02 |
| Order number | 5WG1 562-7AB02 |
| Hardware | #Ventilstellantrieb AP 562/02 |
| Medium | Twisted Pair |
| Bus current (mA) | 9 |
| Rail mounted | No |
| Registration | Certified |
| Languages | en-US, de-DE |
| Catalog entry | M-0001_H-hp.5F00269-1-O0048_HP-510E-01-C761-O0048_CI-5WG1.20562.2D7AB02-1 |
| Fingerprint | C761 |
| SHA-256 | 06a66300baf0e114f0bf43acc055f39ba67ee908389b00613bf018896e7cacbf |
| First seen | 2026-11-25 |
| Markets | 59 markets |
Application program: 12 A1 Valve actuator 510E01 0.1
| Application number | $510E |
|---|---|
| Version | 0.1 |
| Mask version | MV-0012 (1.2) |
| KNX Data Secure | No |
| Parameters | 39 |
| Group objects | 8 |
Group objects (8)
| No | Name | Function | Size | DPT | Flags |
|---|---|---|---|---|---|
| 0 | actuating value | Drive to position | 1 Byte | CRW | |
| 1 | Forced position | Drive to forced position | 1 Bit | CRW | |
| 2 | actual valve position | indicate actual valve position | 1 Byte | CRT | |
| 3 | Maximum position | Determine maximum position | 1 Byte | CRWT | |
| 4 | Summer mode | Close valve in summer | 1 Bit | CRW | |
| 5 | Window contact | indicate state of window contact | 1 Bit | CRT | |
| 6 | Presence contact | indicate state of presence contact | 1 Bit | CRT | |
| 7 | Failure of actuating value | signal failure of actuating value | 1 Bit | CRT |
Parameters (39)
| Parameter | Type | Default |
|---|---|---|
| Characteristics of valve | list | Page |
| Valve settings | list | Standard |
| Transmission of valve position | list | No transmission |
| Cyclical transmission of valve position | list | No cyclical transmission |
| security and forced mode | list | Page |
| security settings | list | Standard |
| Monitoring of actuating value | list | No monitoring |
| Valve position in case of failure of actuating value | list | 50% |
| Transmission of object "failure of actuating value" | list | Only in case of failure of actuating value |
| Valve position at forced mode | list | 0% |
| Valve protection | list | Active |
| Transm. of object "max. actuating value" for heating system | list | Only if own actuating value is higher |
| External interface | list | Page |
| Function of external interface | list | None |
| Type of connected window contact | list | Window open - contact closed |
| Transmission of window state | list | No cyclical transmission |
| Type of connected presence contact | list | Presence = contact closed |
| Transmission of presence state | list | No cyclical transmission |
| User defined characteristics of valve | list | Page |
| Mode of operation of valve | list | Normal (closed with pushed tappet) |
| Additional pressing of rubber seal in 1/100 mm (0...100) | unsignedInt 0…100 | 20 |
| Type of valve seal | list | Valve with standard seal |
| Characteristic curve of valve | list | Typical characteristic curve |
| Maximum torque | list | Normal |
| Minimum actuating value | list | 10% |
| behaviour at minimum actuating value underflow | list | 0 % = 0 % otherwise min. actuating value |
| Maximum actuating value | list | 100% |
| Drive to new valve position | list | At change of actuating value > 5 % |
| Linear characteristic curve of valve | list | Page |
| Own characteristic curve of valve | list | Page |
| Valve position in % for 10 % volume flow (1..99) | unsignedInt 0…100 | 10 |
| Valve position in % for 20 % volume flow (1..99) | unsignedInt 0…100 | 20 |
| Valve position in % for 30 % volume flow (1..99) | unsignedInt 0…100 | 30 |
| Valve position in % for 40 % volume flow (1..99) | unsignedInt 0…100 | 40 |
| Valve position in % for 50 % volume flow (1..99) | unsignedInt 0…100 | 50 |
| Valve position in % for 60 % volume flow (1..99) | unsignedInt 0…100 | 60 |
| Valve position in % for 70 % volume flow (1..99) | unsignedInt 0…100 | 70 |
| Valve position in % for 80 % volume flow (1..99) | unsignedInt 0…100 | 80 |
| Valve position in % for 90 % volume flow (1..99) | unsignedInt 0…100 | 90 |
Version history
| Application | App no | Fingerprint | First seen | Size | File |
|---|---|---|---|---|---|
| 12 A1 Valve actuator 510E01 0.1 latest | $510E | C761 | 2026-11-25 | 70 KB | Download |
About this file
This is the official ETS product database for the Siemens Valve actuator AP 562/02 (5WG1 562-7AB02), published by the manufacturer in the KNX online catalog. To use it, open ETS, go to Catalogs → Import and choose the downloaded .knxprod file. The device then appears in your catalog and can be added to a project. Older versions are kept so existing projects can be matched to the application program they were commissioned with.
More from Siemens
- Room Temperature Controller UP237KB_1 5WG1 237-2KB_1
- Thermo drive actuator RS510/K23 5WG1 510-2KB23
- Thermal Drive Actuator N 605D41, 6 x AC 24...230 V 5WG1605-1DB41
- Thermal Drive Actuator RL 605D23, 2 x AC 24...230 V 5WG1605-4DB23
- Bus Transceiver Module UP 117/12 5WG1 117-2AB12
- Control Module Box AP 118 5WG1 118-4AB01
- Choke N 120/02 5WG1 120-1AB02
- Power supply unit N 125/02 (230V / 160mA) 5WG1 125-1AB02
- Power supply unit N 125/12 (230V / 320mA) 5WG1 125-1AB12
- Power supply unit N 125/22 (230V / 640mA) 5WG1 125-1AB22
- Decentralized Power Supply RL 125/23 5WG1 125-4AB23
- Power supply unit JB 125C33 (277V/160mA) 5WG1 125-4CB33