Thermo drive actuator RS510/K23 5WG1 510-2KB23
Siemens · Order number 5WG1 510-2KB23 · Heating, Air conditioning, Ventilation › Heater › N-Devices › RCB 510/23
Download .knxprod 07 B0 A2 Thermal drive actuator 983801 0.1 · 68 KB
Product
| Manufacturer | Siemens |
|---|---|
| Product name | Thermo drive actuator RS510/K23 |
| Order number | 5WG1 510-2KB23 |
| Product text | Thermoventilaktor RS510K23 |
| Hardware | Thermoventilaktor RS510K23 |
| Medium | Twisted Pair |
| Bus current (mA) | 6 |
| Rail mounted | No |
| Registration | Registered · 2014-12-01 |
| Languages | en-US, de-DE |
| Catalog entry | M-0001_H-hp.5F00301-1_HP-9838-01-3974_CI-5WG1.20510.2D2KB23-1 |
| Fingerprint | 3974 |
| SHA-256 | c3a7f384dfc1523840186f104a40e718dda94378cf935823e62bd386cd37829d |
| First seen | 2026-11-25 |
| Markets | 59 markets |
Application program: 07 B0 A2 Thermal drive actuator 983801 0.1
| Application number | $9838 |
|---|---|
| Version | 0.1 |
| Mask version | MV-07B0 (System B) |
| KNX Data Secure | No |
| Minimum ETS version | 4.0 |
| Parameters | 53 |
| Group objects | 16 |
Group objects (16)
| No | Name | Function | Size | DPT | Flags |
|---|---|---|---|---|---|
| 1 | Status device operation | Status | 1 Bit | 1.1 switch | CRT |
| 2 | Send status values | Yes / No | 1 Bit | 1.1 switch | CW |
| 3 | A Switching actuating variable | On / Off | 1 Bit | 1.1 switch | CW |
| 4 | A Continuous actuating variable | Value | 1 Byte | 5.1 percentage (0..100%) | CW |
| 5 | A Forced position | On / Off | 1 Bit | 1.1 switch | CW |
| 6 | A Status switching | On / Off | 1 Bit | 1.1 switch | CRT |
| 7 | A Status valve position continuous | Value | 1 Byte | 5.1 percentage (0..100%) | CRT |
| 8 | A Failure status actuating variable | Failure / No Failure | 1 Bit | 1.2 boolean | CRT |
| 9 | A Accumulated output status | Status | 1 Byte | 21.1 general status | CRT |
| 10 | B Switching actuating variable | On / Off | 1 Bit | 1.1 switch | CW |
| 11 | B Continuous actuating variable | Value | 1 Byte | 5.1 percentage (0..100%) | CW |
| 12 | B Forced position | On / Off | 1 Bit | 1.1 switch | CW |
| 13 | B Status switching | On / Off | 1 Bit | 1.1 switch | CRT |
| 14 | B Status valve position continuous | Value | 1 Byte | 5.1 percentage (0..100%) | CRT |
| 15 | B Failure status actuating variable | Failure / No Failure | 1 Bit | 1.2 boolean | CRT |
| 16 | B Accumulated output status | Status | 1 Byte | 21.1 general status | CRT |
Parameters (28)
| Parameter | Type | Default |
|---|---|---|
| Cyclically send device operation [1…65535 sec] (0=disabled) | unsignedInt 0…65535 | 120 |
| Enable object to request all status values | list | No |
| Block transmission of status objects after bus power recovery for [1…60 sec] | unsignedInt 1…60 | 15 |
| Delay time between status objects in [0...10 x 0.1 sec] | unsignedInt 0…10 | 2 |
| Dummy | unsignedInt 0…255 | 0 |
| Control via | list | 8 bit object |
| Valve position when not powered | list | Closed |
| Valve closed when actuating variable is lower than or equal [0…30%] | unsignedInt 0…30 | 0 |
| internal | unsignedInt 0…255 | 0 |
| Valve fully open when actuating variable is greater than or equal [70…100%] | unsignedInt 70…100 | 100 |
| internal | unsignedInt 0…255 | 255 |
| Hysteresis [3…15%] | unsignedInt 3…15 | 9 |
| internal | unsignedInt 0…255 | 23 |
| internal | unsignedInt 0…255 | 3 |
| internal | unsignedInt 0…255 | 15 |
| PWM cycle time [5…30 min] | unsignedInt 5…30 | 9 |
| Protection of valve against blocking | list | No |
| Position of thermal drive on bus power failure | list | No change |
| Control value for thermal drive control on bus power recovery | list | As before bus voltage failure |
| Status object switching | list | Do not send |
| Forced position | list | No |
| Forced position value [0…100%] | unsignedInt 0…100 | 30 |
| internal | unsignedInt 0…255 | 77 |
| Monitoring time for actuating variable [30…65535 sec] | unsignedInt 30…65535 | 120 |
| Monitor failure of actuating variable | list | No |
| Status failure of actuating variable | list | Send on status change |
| Position of thermal drive on failure of actuating variable [0…100%] | unsignedInt 0…100 | 30 |
| Status object continuous | list | Send on status change |
Version history
| Application | App no | Fingerprint | First seen | Size | File |
|---|---|---|---|---|---|
| 07 B0 A2 Thermal drive actuator 983801 0.1 latest | $9838 | 3974 | 2026-11-25 | 68 KB | Download |
About this file
This is the official ETS product database for the Siemens Thermo drive actuator RS510/K23 (5WG1 510-2KB23), published by the manufacturer in the KNX online catalog. To use it, open ETS, go to Catalogs → Import and choose the downloaded .knxprod file. The device then appears in your catalog and can be added to a project. Older versions are kept so existing projects can be matched to the application program they were commissioned with.
More from Siemens
- Room Temperature Controller UP237KB_1 5WG1 237-2KB_1
- Valve actuator AP 562/02 5WG1 562-7AB02
- Thermal Drive Actuator N 605D41, 6 x AC 24...230 V 5WG1605-1DB41
- Thermal Drive Actuator RL 605D23, 2 x AC 24...230 V 5WG1605-4DB23
- Bus Transceiver Module UP 117/12 5WG1 117-2AB12
- Control Module Box AP 118 5WG1 118-4AB01
- Choke N 120/02 5WG1 120-1AB02
- Power supply unit N 125/02 (230V / 160mA) 5WG1 125-1AB02
- Power supply unit N 125/12 (230V / 320mA) 5WG1 125-1AB12
- Power supply unit N 125/22 (230V / 640mA) 5WG1 125-1AB22
- Decentralized Power Supply RL 125/23 5WG1 125-4AB23
- Power supply unit JB 125C33 (277V/160mA) 5WG1 125-4CB33