| 1 | Valve outputs - output | Failure of operating voltage | 1 Bit | 1.5 alarm | CRTU |
| 2 | Pump - output | Switch pump | 1 Bit | 1.1 switch | CRTU |
| 3 | Pump - input | External pump control | 1 Bit | 1.1 switch | CWU |
| 4 | Valve outputs - output | Largest command value | 1 Byte | 5.1 percentage (0..100%) | CRTU |
| 5 | Valve outputs - input | External largest command value | 1 Byte | 5.1 percentage (0..100%) | CWU |
| 6 | Valve outputs - output | Heat requirement | 1 Bit | 1.2 boolean | CRTU |
| 7 | Valve outputs - input | External heat requirement | 1 Bit | 1.2 boolean | CWU |
| 8 | Operating mode - input | Summer / winter change-over | 1 Bit | 1.2 boolean | CWU |
| 9 | Valve outputs - input | Reset short-circuit / overload | 1 Bit | 1.15 reset | CWU |
| 10 | Valve outputs - output | Collective feedback status | 4 Bytes | 27.1 bit-combined info on/off | CTU |
| 10 | Valve outputs - output | Collective feedback status | 4 Bytes | 27.1 bit-combined info on/off | CRU |
| 11 | Energy saving mode - input | Activate / deactivate | 1 Bit | 1.3 enable | CWU |
| 12 | Service mode - input | Activate / deactivate | 2 Bit | 2.1 switch control | CWU |
| 13 | Service mode - output | Status active / inactive | 1 Bit | 1.2 boolean | CRTU |
| 14 | Manual operation - input | Disabling | 1 Bit | 1.3 enable | CWU |
| 15 | Manual operation - output | Status | 1 Bit | 1.2 boolean | CRTU |
| 20 | Valve output 1 ({{131:Name}}) - input | Command value | 1 Bit | 1.1 switch | CWU |
| 21 | Valve output 1 ({{131:Name}}) - input | Command value | 1 Byte | 5.1 percentage (0..100%) | CWU |
| 22 | Valve output 1 ({{131:Name}}) - output | Feedback valve command value | 1 Bit | 1.1 switch | CRU |
| 22 | Valve output 1 ({{131:Name}}) - output | Feedback valve command value | 1 Bit | 1.1 switch | CTU |
| 23 | Valve output 1 ({{131:Name}}) - output | Feedback valve command value | 1 Byte | 5.1 percentage (0..100%) | CRU |
| 23 | Valve output 1 ({{131:Name}}) - output | Feedback valve command value | 1 Byte | 5.1 percentage (0..100%) | CTU |
| 24 | Valve output 1 ({{131:Name}}) - input | Forced position | 1 Bit | 1.3 enable | CWU |
| 25 | Valve output 1 ({{131:Name}}) - output | Command value fault | 1 Bit | 1.15 reset | CRTU |
| 26 | Valve output 1 ({{131:Name}}) - input | Command value limit | 1 Bit | 1.2 boolean | CWU |
| 27 | Valve output 1 ({{131:Name}}) - input | Valve rinsing start / stop | 1 Bit | 1.3 enable | CWU |
| 27 | Valve output 1 ({{131:Name}}) - input | Valve rinsing start | 1 Bit | 1.3 enable | CWU |
| 28 | Valve output 1 ({{131:Name}}) - output | Valve rinsing status | 1 Bit | 1.2 boolean | CRTU |
| 29 | Valve output 1 ({{131:Name}}) - output | Signal short-circuit /overload | 1 Bit | DPT.1 | CRTU |
| 30 | Valve output 1 ({{131:Name}}) - output | Feedback combined valve status | 1 Byte | | CTU |
| 30 | Valve output 1 ({{131:Name}}) - output | Feedback combined valve status | 1 Byte | | CRU |
| 31 | Valve output 1 ({{131:Name}}) - input | Operating hours counter limit value | 2 Bytes | DPT.7 | CWU |
| 31 | Valve output 1 ({{131:Name}}) - input | Operation hours counter start value | 2 Bytes | 7.7 time (h) | CWU |
| 32 | Valve output 1 ({{131:Name}}) - input | Reset operating hours counter | 1 Bit | 1.15 reset | CWU |
| 33 | Valve output 1 ({{131:Name}}) - output | Value operating hours counter | 2 Bytes | DPT.7 | CRTU |
| 34 | Valve output 1 ({{131:Name}}) - output | Operating hours counter elapsed | 1 Bit | 1.2 boolean | CRTU |
| 70 | Valve output 2 ({{139:Name}}) - input | Command value | 1 Bit | 1.1 switch | CWU |
| 71 | Valve output 2 ({{139:Name}}) - input | Command value | 1 Byte | 5.1 percentage (0..100%) | CWU |
| 72 | Valve output 2 ({{139:Name}}) - output | Feedback valve command value | 1 Bit | 1.1 switch | CRU |
| 72 | Valve output 2 ({{139:Name}}) - output | Feedback valve command value | 1 Bit | 1.1 switch | CTU |
| 73 | Valve output 2 ({{139:Name}}) - output | Feedback valve command value | 1 Byte | 5.1 percentage (0..100%) | CRU |
| 73 | Valve output 2 ({{139:Name}}) - output | Feedback valve command value | 1 Byte | 5.1 percentage (0..100%) | CTU |
| 74 | Valve output 2 ({{139:Name}}) - input | Forced position | 1 Bit | 1.3 enable | CWU |
| 75 | Valve output 2 ({{139:Name}}) - output | Command value fault | 1 Bit | 1.15 reset | CRTU |
| 76 | Valve output 2 ({{139:Name}}) - input | Command value limit | 1 Bit | 1.2 boolean | CWU |
| 77 | Valve output 2 ({{139:Name}}) - input | Valve rinsing start / stop | 1 Bit | 1.3 enable | CWU |
| 77 | Valve output 2 ({{139:Name}}) - input | Valve rinsing start | 1 Bit | 1.3 enable | CWU |
| 78 | Valve output 2 ({{139:Name}}) - output | Valve rinsing status | 1 Bit | 1.2 boolean | CRTU |
| 79 | Valve output 2 ({{139:Name}}) - output | Signal short-circuit /overload | 1 Bit | DPT.1 | CRTU |
| 80 | Valve output 2 ({{139:Name}}) - output | Feedback combined valve status | 1 Byte | | CTU |
| 80 | Valve output 2 ({{139:Name}}) - output | Feedback combined valve status | 1 Byte | | CRU |
| 81 | Valve output 2 ({{139:Name}}) - input | Operating hours counter limit value | 2 Bytes | DPT.7 | CWU |
| 81 | Valve output 2 ({{139:Name}}) - input | Operation hours counter start value | 2 Bytes | 7.7 time (h) | CWU |
| 82 | Valve output 2 ({{139:Name}}) - input | Reset operating hours counter | 1 Bit | 1.15 reset | CWU |
| 83 | Valve output 2 ({{139:Name}}) - output | Value operating hours counter | 2 Bytes | DPT.7 | CRTU |
| 84 | Valve output 2 ({{139:Name}}) - output | Operating hours counter elapsed | 1 Bit | 1.2 boolean | CRTU |
| 120 | Valve output 3 ({{140:Name}}) - input | Command value | 1 Bit | 1.1 switch | CWU |
| 121 | Valve output 3 ({{140:Name}}) - input | Command value | 1 Byte | 5.1 percentage (0..100%) | CWU |
| 122 | Valve output 3 ({{140:Name}}) - output | Feedback valve command value | 1 Bit | 1.1 switch | CRU |
| 122 | Valve output 3 ({{140:Name}}) - output | Feedback valve command value | 1 Bit | 1.1 switch | CTU |
| 123 | Valve output 3 ({{140:Name}}) - output | Feedback valve command value | 1 Byte | 5.1 percentage (0..100%) | CRU |
| 123 | Valve output 3 ({{140:Name}}) - output | Feedback valve command value | 1 Byte | 5.1 percentage (0..100%) | CTU |
| 124 | Valve output 3 ({{140:Name}}) - input | Forced position | 1 Bit | 1.3 enable | CWU |
| 125 | Valve output 3 ({{140:Name}}) - output | Command value fault | 1 Bit | 1.15 reset | CRTU |
| 126 | Valve output 3 ({{140:Name}}) - input | Command value limit | 1 Bit | 1.2 boolean | CWU |
| 127 | Valve output 3 ({{140:Name}}) - input | Valve rinsing start / stop | 1 Bit | 1.3 enable | CWU |
| 127 | Valve output 3 ({{140:Name}}) - input | Valve rinsing start | 1 Bit | 1.3 enable | CWU |
| 128 | Valve output 3 ({{140:Name}}) - output | Valve rinsing status | 1 Bit | 1.2 boolean | CRTU |
| 129 | Valve output 3 ({{140:Name}}) - output | Signal short-circuit /overload | 1 Bit | DPT.1 | CRTU |
| 130 | Valve output 3 ({{140:Name}}) - output | Feedback combined valve status | 1 Byte | | CTU |
| 130 | Valve output 3 ({{140:Name}}) - output | Feedback combined valve status | 1 Byte | | CRU |
| 131 | Valve output 3 ({{140:Name}}) - input | Operating hours counter limit value | 2 Bytes | DPT.7 | CWU |
| 131 | Valve output 3 ({{140:Name}}) - input | Operation hours counter start value | 2 Bytes | 7.7 time (h) | CWU |
| 132 | Valve output 3 ({{140:Name}}) - input | Reset operating hours counter | 1 Bit | 1.15 reset | CWU |
| 133 | Valve output 3 ({{140:Name}}) - output | Value operating hours counter | 2 Bytes | DPT.7 | CRTU |
| 134 | Valve output 3 ({{140:Name}}) - output | Operating hours counter elapsed | 1 Bit | 1.2 boolean | CRTU |
| 170 | Valve output 4 ({{148:Name}}) - input | Command value | 1 Bit | 1.1 switch | CWU |
| 171 | Valve output 4 ({{148:Name}}) - input | Command value | 1 Byte | 5.1 percentage (0..100%) | CWU |
| 172 | Valve output 4 ({{148:Name}}) - output | Feedback valve command value | 1 Bit | 1.1 switch | CRU |
| 172 | Valve output 4 ({{148:Name}}) - output | Feedback valve command value | 1 Bit | 1.1 switch | CTU |
| 173 | Valve output 4 ({{148:Name}}) - output | Feedback valve command value | 1 Byte | 5.1 percentage (0..100%) | CRU |
| 173 | Valve output 4 ({{148:Name}}) - output | Feedback valve command value | 1 Byte | 5.1 percentage (0..100%) | CTU |
| 174 | Valve output 4 ({{148:Name}}) - input | Forced position | 1 Bit | 1.3 enable | CWU |
| 175 | Valve output 4 ({{148:Name}}) - output | Command value fault | 1 Bit | 1.15 reset | CRTU |
| 176 | Valve output 4 ({{148:Name}}) - input | Command value limit | 1 Bit | 1.2 boolean | CWU |
| 177 | Valve output 4 ({{148:Name}}) - input | Valve rinsing start / stop | 1 Bit | 1.3 enable | CWU |
| 177 | Valve output 4 ({{148:Name}}) - input | Valve rinsing start | 1 Bit | 1.3 enable | CWU |
| 178 | Valve output 4 ({{148:Name}}) - output | Valve rinsing status | 1 Bit | 1.2 boolean | CRTU |
| 179 | Valve output 4 ({{148:Name}}) - output | Signal short-circuit /overload | 1 Bit | DPT.1 | CRTU |
| 180 | Valve output 4 ({{148:Name}}) - output | Feedback combined valve status | 1 Byte | | CTU |
| 180 | Valve output 4 ({{148:Name}}) - output | Feedback combined valve status | 1 Byte | | CRU |
| 181 | Valve output 4 ({{148:Name}}) - input | Operating hours counter limit value | 2 Bytes | DPT.7 | CWU |
| 181 | Valve output 4 ({{148:Name}}) - input | Operation hours counter start value | 2 Bytes | 7.7 time (h) | CWU |
| 182 | Valve output 4 ({{148:Name}}) - input | Reset operating hours counter | 1 Bit | 1.15 reset | CWU |
| 183 | Valve output 4 ({{148:Name}}) - output | Value operating hours counter | 2 Bytes | DPT.7 | CRTU |
| 184 | Valve output 4 ({{148:Name}}) - output | Operating hours counter elapsed | 1 Bit | 1.2 boolean | CRTU |
| 220 | Valve output 5 ({{149:Name}}) - input | Command value | 1 Bit | 1.1 switch | CWU |
| 221 | Valve output 5 ({{149:Name}}) - input | Command value | 1 Byte | 5.1 percentage (0..100%) | CWU |
| 222 | Valve output 5 ({{149:Name}}) - output | Feedback valve command value | 1 Bit | 1.1 switch | CRU |
| 222 | Valve output 5 ({{149:Name}}) - output | Feedback valve command value | 1 Bit | 1.1 switch | CTU |
| 223 | Valve output 5 ({{149:Name}}) - output | Feedback valve command value | 1 Byte | 5.1 percentage (0..100%) | CRU |
| 223 | Valve output 5 ({{149:Name}}) - output | Feedback valve command value | 1 Byte | 5.1 percentage (0..100%) | CTU |
| 224 | Valve output 5 ({{149:Name}}) - input | Forced position | 1 Bit | 1.3 enable | CWU |
| 225 | Valve output 5 ({{149:Name}}) - output | Command value fault | 1 Bit | 1.15 reset | CRTU |
| 226 | Valve output 5 ({{149:Name}}) - input | Command value limit | 1 Bit | 1.2 boolean | CWU |
| 227 | Valve output 5 ({{149:Name}}) - input | Valve rinsing start / stop | 1 Bit | 1.3 enable | CWU |
| 227 | Valve output 5 ({{149:Name}}) - input | Valve rinsing start | 1 Bit | 1.3 enable | CWU |
| 228 | Valve output 5 ({{149:Name}}) - output | Valve rinsing status | 1 Bit | 1.2 boolean | CRTU |
| 229 | Valve output 5 ({{149:Name}}) - output | Signal short-circuit /overload | 1 Bit | DPT.1 | CRTU |
| 230 | Valve output 5 ({{149:Name}}) - output | Feedback combined valve status | 1 Byte | | CTU |
| 230 | Valve output 5 ({{149:Name}}) - output | Feedback combined valve status | 1 Byte | | CRU |
| 231 | Valve output 5 ({{149:Name}}) - input | Operating hours counter limit value | 2 Bytes | DPT.7 | CWU |
| 231 | Valve output 5 ({{149:Name}}) - input | Operation hours counter start value | 2 Bytes | 7.7 time (h) | CWU |
| 232 | Valve output 5 ({{149:Name}}) - input | Reset operating hours counter | 1 Bit | 1.15 reset | CWU |
| 233 | Valve output 5 ({{149:Name}}) - output | Value operating hours counter | 2 Bytes | DPT.7 | CRTU |
| 234 | Valve output 5 ({{149:Name}}) - output | Operating hours counter elapsed | 1 Bit | 1.2 boolean | CRTU |
| 270 | Valve output 6 ({{152:Name}}) - input | Command value | 1 Bit | 1.1 switch | CWU |
| 271 | Valve output 6 ({{152:Name}}) - input | Command value | 1 Byte | 5.1 percentage (0..100%) | CWU |
| 272 | Valve output 6 ({{152:Name}}) - output | Feedback valve command value | 1 Bit | 1.1 switch | CRU |
| 272 | Valve output 6 ({{152:Name}}) - output | Feedback valve command value | 1 Bit | 1.1 switch | CTU |
| 273 | Valve output 6 ({{152:Name}}) - output | Feedback valve command value | 1 Byte | 5.1 percentage (0..100%) | CRU |
| 273 | Valve output 6 ({{152:Name}}) - output | Feedback valve command value | 1 Byte | 5.1 percentage (0..100%) | CTU |
| 274 | Valve output 6 ({{152:Name}}) - input | Forced position | 1 Bit | 1.3 enable | CWU |
| 275 | Valve output 6 ({{152:Name}}) - output | Command value fault | 1 Bit | 1.15 reset | CRTU |
| 276 | Valve output 6 ({{152:Name}}) - input | Command value limit | 1 Bit | 1.2 boolean | CWU |
| 277 | Valve output 6 ({{152:Name}}) - input | Valve rinsing start / stop | 1 Bit | 1.3 enable | CWU |
| 277 | Valve output 6 ({{152:Name}}) - input | Valve rinsing start | 1 Bit | 1.3 enable | CWU |
| 278 | Valve output 6 ({{152:Name}}) - output | Valve rinsing status | 1 Bit | 1.2 boolean | CRTU |
| 279 | Valve output 6 ({{152:Name}}) - output | Signal short-circuit /overload | 1 Bit | DPT.1 | CRTU |
| 280 | Valve output 6 ({{152:Name}}) - output | Feedback combined valve status | 1 Byte | | CTU |
| 280 | Valve output 6 ({{152:Name}}) - output | Feedback combined valve status | 1 Byte | | CRU |
| 281 | Valve output 6 ({{152:Name}}) - input | Operating hours counter limit value | 2 Bytes | DPT.7 | CWU |
| 281 | Valve output 6 ({{152:Name}}) - input | Operation hours counter start value | 2 Bytes | 7.7 time (h) | CWU |
| 282 | Valve output 6 ({{152:Name}}) - input | Reset operating hours counter | 1 Bit | 1.15 reset | CWU |
| 283 | Valve output 6 ({{152:Name}}) - output | Value operating hours counter | 2 Bytes | DPT.7 | CRTU |
| 284 | Valve output 6 ({{152:Name}}) - output | Operating hours counter elapsed | 1 Bit | 1.2 boolean | CRTU |
| 320 | Controller 1 ({{173:Name}}) - input | Basic setpoint | 2 Bytes | 9.1 temperature (°C) | CWU |
| 320 | Controller 1 ({{173:Name}}) - input | Setpoint active operating mode | 2 Bytes | 9.1 temperature (°C) | CWU |
| 322 | Controller 1 ({{173:Name}}) - input | Operating mode switch-over | 1 Byte | 20.102 HVAC mode | CWTU |
| 322 | Controller 1 ({{173:Name}}) - input | Comfort mode | 1 Bit | 1.1 switch | CWTU |
| 323 | Controller 1 ({{173:Name}}) - input | Standby mode | 1 Bit | 1.1 switch | CWTU |
| 324 | Controller 1 ({{173:Name}}) - input | Night operation | 1 Bit | 1.1 switch | CWTU |
| 325 | Controller 1 ({{173:Name}}) - input | Frost/ heat protection | 1 Bit | 1.1 switch | CWTU |
| 326 | Controller 1 ({{173:Name}}) - input | Operating mode forced-control | 1 Byte | 20.102 HVAC mode | CWTU |
| 327 | Controller 1 ({{173:Name}}) - input | Presence button | 1 Bit | 1.1 switch | CWTU |
| 327 | Controller 1 ({{173:Name}}) - input | Presence detector | 1 Bit | 1.1 switch | CWTU |
| 328 | Controller 1 ({{173:Name}}) - input | Windows status | 1 Bit | 1.19 window/door | CWU |
| 329 | Controller 1 ({{173:Name}}) - input | Heating / cooling change-over | 1 Bit | 1.100 heating/cooling | CWTU |
| 329 | Controller 1 ({{173:Name}}) - output | Heating / cooling change-over | 1 Bit | 1.100 heating/cooling | CTU |
| 330 | Controller 1 ({{173:Name}}) - output | Controller status | 1 Byte | | CTU |
| 330 | Controller 1 ({{173:Name}}) - output | KNX status operating mode | 1 Byte | 20.102 HVAC mode | CTU |
| 330 | Controller 1 ({{173:Name}}) - output | Controller status, Comfort mode | 1 Bit | 1.1 switch | CTU |
| 330 | Controller 1 ({{173:Name}}) - output | Controller status, Standby mode | 1 Bit | 1.1 switch | CTU |
| 330 | Controller 1 ({{173:Name}}) - output | Controller status, night mode | 1 Bit | 1.1 switch | CTU |
| 330 | Controller 1 ({{173:Name}}) - output | Controller status, frost/heat protection | 1 Bit | 1.1 switch | CTU |
| 330 | Controller 1 ({{173:Name}}) - output | Controller status, contr. disabled | 1 Bit | 1.1 switch | CTU |
| 330 | Controller 1 ({{173:Name}}) - output | Controller status, heating/cooling | 1 Bit | 1.1 switch | CTU |
| 330 | Controller 1 ({{173:Name}}) - output | Controller status contr. inactive | 1 Bit | 1.1 switch | CTU |
| 330 | Controller 1 ({{173:Name}}) - output | Controller status, frost alarm | 1 Bit | 1.1 switch | CTU |
| 334 | Controller 1 ({{173:Name}}) - output | Set temperature | 2 Bytes | 9.1 temperature (°C) | CRTU |
| 336 | Controller 1 ({{173:Name}}) - output | Current setpoint shifting | 1 Byte | 6.10 counter pulses (-128..127) | CRTU |
| 337 | Controller 1 ({{173:Name}}) - input | Preset setpoint shifting | 1 Byte | 6.10 counter pulses (-128..127) | CWU |
| 338 | Controller 1 ({{173:Name}}) - output | Status signal addition | 1 Byte | | CTU |
| 338 | Controller 1 ({{173:Name}}) - output | KNX status | 2 Bytes | 22.101 RHCC status | CTU |
| 339 | Controller 1 ({{173:Name}}) - output | KNX status forced operating mode | 1 Byte | 20.102 HVAC mode | CTU |
| 340 | Controller 1 ({{173:Name}}) - input | Outdoor temperature | 2 Bytes | 9.1 temperature (°C) | CWU |
| 341 | Controller 1 ({{173:Name}}) - input | Limit of cooling setpoint temperature | 1 Bit | 1.1 switch | CWU |
| 355 | Controller 1 ({{173:Name}}) - input | Disable controller | 1 Bit | 1.3 enable | CWU |
| 356 | Controller 1 ({{173:Name}}) - input | Disable additional level | 1 Bit | 1.3 enable | CWU |
| 357 | Controller 1 ({{173:Name}}) - output | Command value for heating | 1 Byte | 5.1 percentage (0..100%) | CTU |
| 357 | Controller 1 ({{173:Name}}) - output | Command value heating (PWM) | 1 Bit | 1.1 switch | CTU |
| 357 | Controller 1 ({{173:Name}}) - output | Command value for heating | 1 Bit | 1.1 switch | CTU |
| 357 | Controller 1 ({{173:Name}}) - output | Command value heating/cooling | 1 Byte | 5.1 percentage (0..100%) | CTU |
| 357 | Controller 1 ({{173:Name}}) - output | Command value heating/cooling (PWM) | 1 Bit | 1.1 switch | CTU |
| 357 | Controller 1 ({{173:Name}}) - output | Command value heating/cooling | 1 Bit | 1.1 switch | CTU |
| 357 | Controller 1 ({{173:Name}}) - output | Command value basic heating | 1 Byte | 5.1 percentage (0..100%) | CTU |
| 357 | Controller 1 ({{173:Name}}) - output | Command value basic heating (PWM) | 1 Bit | 1.1 switch | CTU |
| 357 | Controller 1 ({{173:Name}}) - output | Command value basic heating | 1 Bit | 1.1 switch | CTU |
| 357 | Controller 1 ({{173:Name}}) - output | Command value basic level | 1 Byte | 5.1 percentage (0..100%) | CTU |
| 357 | Controller 1 ({{173:Name}}) - output | Command value basic level (PWM) | 1 Bit | 1.1 switch | CTU |
| 357 | Controller 1 ({{173:Name}}) - output | Command value basic level | 1 Bit | 1.1 switch | CTU |
| 358 | Controller 1 ({{173:Name}}) - output | Command value additional heating | 1 Byte | 5.1 percentage (0..100%) | CTU |
| 358 | Controller 1 ({{173:Name}}) - output | Command value additional heating (PWM) | 1 Bit | 1.1 switch | CTU |
| 358 | Controller 1 ({{173:Name}}) - output | Command value additional heating | 1 Bit | 1.1 switch | CTU |
| 358 | Controller 1 ({{173:Name}}) - output | Command value additional level | 1 Byte | 5.1 percentage (0..100%) | CTU |
| 358 | Controller 1 ({{173:Name}}) - output | Command value additional level (PWM) | 1 Bit | 1.1 switch | CTU |
| 358 | Controller 1 ({{173:Name}}) - output | Command value additional level | 1 Bit | 1.1 switch | CTU |
| 359 | Controller 1 ({{173:Name}}) - output | Command value cooling | 1 Byte | 5.1 percentage (0..100%) | CTU |
| 359 | Controller 1 ({{173:Name}}) - output | Command value cooling (PWM) | 1 Bit | 1.1 switch | CTU |
| 359 | Controller 1 ({{173:Name}}) - output | Command value cooling | 1 Bit | 1.1 switch | CTU |
| 359 | Controller 1 ({{173:Name}}) - output | Command value basic cooling | 1 Byte | 5.1 percentage (0..100%) | CTU |
| 359 | Controller 1 ({{173:Name}}) - output | Command value basic cooling(PWM) | 1 Bit | 1.1 switch | CTU |
| 359 | Controller 1 ({{173:Name}}) - output | Command value basic cooling | 1 Bit | 1.1 switch | CTU |
| 360 | Controller 1 ({{173:Name}}) - output | Command value additional cooling | 1 Byte | 5.1 percentage (0..100%) | CTU |
| 360 | Controller 1 ({{173:Name}}) - output | Command value additional cooling (PWM) | 1 Bit | 1.1 switch | CTU |
| 360 | Controller 1 ({{173:Name}}) - output | Command value additional cooling | 1 Bit | 1.1 switch | CTU |
| 361 | Controller 1 ({{173:Name}}) - output | PWM command value heating | 1 Byte | 5.1 percentage (0..100%) | CTU |
| 361 | Controller 1 ({{173:Name}}) - output | PWM command value heating/cooling | 1 Byte | 5.1 percentage (0..100%) | CTU |
| 361 | Controller 1 ({{173:Name}}) - output | PWM command value basic heating | 1 Byte | 5.1 percentage (0..100%) | CTU |
| 361 | Controller 1 ({{173:Name}}) - output | PWM command value basic level | 1 Byte | 5.1 percentage (0..100%) | CTU |
| 362 | Controller 1 ({{173:Name}}) - output | PWM command value additional heating | 1 Byte | 5.1 percentage (0..100%) | CTU |
| 362 | Controller 1 ({{173:Name}}) - output | PWM command value additional level | 1 Byte | 5.1 percentage (0..100%) | CTU |
| 363 | Controller 1 ({{173:Name}}) - output | PWM command value cooling | 1 Byte | 5.1 percentage (0..100%) | CTU |
| 363 | Controller 1 ({{173:Name}}) - output | PWM command value basic heating | 1 Byte | 5.1 percentage (0..100%) | CTU |
| 364 | Controller 1 ({{173:Name}}) - output | PWM command value additional cooling | 1 Byte | 5.1 percentage (0..100%) | CTU |
| 365 | Controller 1 ({{173:Name}}) - input | Command value limit | 1 Bit | 1.1 switch | CWU |
| 367 | Controller 1 ({{173:Name}}) - input | Floor temperature | 2 Bytes | 9.1 temperature (°C) | CWU |
| 371 | Controller 1 ({{173:Name}}) - output | Heating indication | 1 Bit | 1.1 switch | CTU |
| 372 | Controller 1 ({{173:Name}}) - output | Cooling indication | 1 Bit | 1.1 switch | CTU |
| 381 | Controller 1 ({{173:Name}}) - output | Actual-temperature | 2 Bytes | 9.1 temperature (°C) | CRTU |
| 382 | Controller 1 ({{173:Name}}) - input | Received temperature 1 (temperature sensor 1) | 2 Bytes | 9.1 temperature (°C) | CWTU |
| 383 | Controller 1 ({{173:Name}}) - input | Received temperature 2 (temperature sensor 2) | 2 Bytes | 9.1 temperature (°C) | CWTU |
| 391 | Controller 2 ({{1329:Name}}) - input | Basic setpoint | 2 Bytes | 9.1 temperature (°C) | CWU |
| 391 | Controller 2 ({{1329:Name}}) - input | Setpoint active operating mode | 2 Bytes | 9.1 temperature (°C) | CWU |
| 393 | Controller 2 ({{1329:Name}}) - input | Operating mode switch-over | 1 Byte | 20.102 HVAC mode | CWTU |
| 393 | Controller 2 ({{1329:Name}}) - input | Comfort mode | 1 Bit | 1.1 switch | CWTU |
| 394 | Controller 2 ({{1329:Name}}) - input | Standby mode | 1 Bit | 1.1 switch | CWTU |
| 395 | Controller 2 ({{1329:Name}}) - input | Night operation | 1 Bit | 1.1 switch | CWTU |
| 396 | Controller 2 ({{1329:Name}}) - input | Frost/ heat protection | 1 Bit | 1.1 switch | CWTU |
| 397 | Controller 2 ({{1329:Name}}) - input | Operating mode forced-control | 1 Byte | 20.102 HVAC mode | CWTU |
| 398 | Controller 2 ({{1329:Name}}) - input | Presence button | 1 Bit | 1.1 switch | CWTU |
| 398 | Controller 2 ({{1329:Name}}) - input | Presence detector | 1 Bit | 1.1 switch | CWTU |
| 399 | Controller 2 ({{1329:Name}}) - input | Windows status | 1 Bit | 1.19 window/door | CWU |
| 400 | Controller 2 ({{1329:Name}}) - input | Heating / cooling change-over | 1 Bit | 1.100 heating/cooling | CWTU |
| 400 | Controller 2 ({{1329:Name}}) - output | Heating / cooling change-over | 1 Bit | 1.100 heating/cooling | CTU |
| 401 | Controller 2 ({{1329:Name}}) - output | Controller status | 1 Byte | | CTU |
| 401 | Controller 2 ({{1329:Name}}) - output | KNX status operating mode | 1 Byte | 20.102 HVAC mode | CTU |
| 401 | Controller 2 ({{1329:Name}}) - output | Controller status, Comfort mode | 1 Bit | 1.1 switch | CTU |
| 401 | Controller 2 ({{1329:Name}}) - output | Controller status, Standby mode | 1 Bit | 1.1 switch | CTU |
| 401 | Controller 2 ({{1329:Name}}) - output | Controller status, night mode | 1 Bit | 1.1 switch | CTU |
| 401 | Controller 2 ({{1329:Name}}) - output | Controller status, frost/heat protection | 1 Bit | 1.1 switch | CTU |
| 401 | Controller 2 ({{1329:Name}}) - output | Controller status, contr. disabled | 1 Bit | 1.1 switch | CTU |
| 401 | Controller 2 ({{1329:Name}}) - output | Controller status, heating/cooling | 1 Bit | 1.1 switch | CTU |
| 401 | Controller 2 ({{1329:Name}}) - output | Controller status contr. inactive | 1 Bit | 1.1 switch | CTU |
| 401 | Controller 2 ({{1329:Name}}) - output | Controller status, frost alarm | 1 Bit | 1.1 switch | CTU |
| 405 | Controller 2 ({{1329:Name}}) - output | Set temperature | 2 Bytes | 9.1 temperature (°C) | CRTU |
| 407 | Controller 2 ({{1329:Name}}) - output | Current setpoint shifting | 1 Byte | 6.10 counter pulses (-128..127) | CRTU |
| 408 | Controller 2 ({{1329:Name}}) - input | Preset setpoint shifting | 1 Byte | 6.10 counter pulses (-128..127) | CWU |
| 409 | Controller 2 ({{1329:Name}}) - output | Status signal addition | 1 Byte | | CTU |
| 409 | Controller 2 ({{1329:Name}}) - output | KNX status | 2 Bytes | 22.101 RHCC status | CTU |
| 410 | Controller 2 ({{1329:Name}}) - output | KNX status forced operating mode | 1 Byte | 20.102 HVAC mode | CTU |
| 411 | Controller 2 ({{1329:Name}}) - input | Outdoor temperature | 2 Bytes | 9.1 temperature (°C) | CWU |
| 412 | Controller 2 ({{1329:Name}}) - input | Limit of cooling setpoint temperature | 1 Bit | 1.1 switch | CWU |
| 426 | Controller 2 ({{1329:Name}}) - input | Disable controller | 1 Bit | 1.3 enable | CWU |
| 427 | Controller 2 ({{1329:Name}}) - input | Disable additional level | 1 Bit | 1.3 enable | CWU |
| 428 | Controller 2 ({{1329:Name}}) - output | Command value for heating | 1 Byte | 5.1 percentage (0..100%) | CTU |
| 428 | Controller 2 ({{1329:Name}}) - output | Command value heating (PWM) | 1 Bit | 1.1 switch | CTU |
| 428 | Controller 2 ({{1329:Name}}) - output | Command value for heating | 1 Bit | 1.1 switch | CTU |
| 428 | Controller 2 ({{1329:Name}}) - output | Command value heating/cooling | 1 Byte | 5.1 percentage (0..100%) | CTU |
| 428 | Controller 2 ({{1329:Name}}) - output | Command value heating/cooling (PWM) | 1 Bit | 1.1 switch | CTU |
| 428 | Controller 2 ({{1329:Name}}) - output | Command value heating/cooling | 1 Bit | 1.1 switch | CTU |
| 428 | Controller 2 ({{1329:Name}}) - output | Command value basic heating | 1 Byte | 5.1 percentage (0..100%) | CTU |
| 428 | Controller 2 ({{1329:Name}}) - output | Command value basic heating (PWM) | 1 Bit | 1.1 switch | CTU |
| 428 | Controller 2 ({{1329:Name}}) - output | Command value basic heating | 1 Bit | 1.1 switch | CTU |
| 428 | Controller 2 ({{1329:Name}}) - output | Command value basic level | 1 Byte | 5.1 percentage (0..100%) | CTU |
| 428 | Controller 2 ({{1329:Name}}) - output | Command value basic level (PWM) | 1 Bit | 1.1 switch | CTU |
| 428 | Controller 2 ({{1329:Name}}) - output | Command value basic level | 1 Bit | 1.1 switch | CTU |
| 429 | Controller 2 ({{1329:Name}}) - output | Command value additional heating | 1 Byte | 5.1 percentage (0..100%) | CTU |
| 429 | Controller 2 ({{1329:Name}}) - output | Command value additional heating (PWM) | 1 Bit | 1.1 switch | CTU |
| 429 | Controller 2 ({{1329:Name}}) - output | Command value additional heating | 1 Bit | 1.1 switch | CTU |
| 429 | Controller 2 ({{1329:Name}}) - output | Command value additional level | 1 Byte | 5.1 percentage (0..100%) | CTU |
| 429 | Controller 2 ({{1329:Name}}) - output | Command value additional level (PWM) | 1 Bit | 1.1 switch | CTU |
| 429 | Controller 2 ({{1329:Name}}) - output | Command value additional level | 1 Bit | 1.1 switch | CTU |
| 430 | Controller 2 ({{1329:Name}}) - output | Command value cooling | 1 Byte | 5.1 percentage (0..100%) | CTU |
| 430 | Controller 2 ({{1329:Name}}) - output | Command value cooling (PWM) | 1 Bit | 1.1 switch | CTU |
| 430 | Controller 2 ({{1329:Name}}) - output | Command value cooling | 1 Bit | 1.1 switch | CTU |
| 430 | Controller 2 ({{1329:Name}}) - output | Command value basic cooling | 1 Byte | 5.1 percentage (0..100%) | CTU |
| 430 | Controller 2 ({{1329:Name}}) - output | Command value basic cooling(PWM) | 1 Bit | 1.1 switch | CTU |
| 430 | Controller 2 ({{1329:Name}}) - output | Command value basic cooling | 1 Bit | 1.1 switch | CTU |
| 431 | Controller 2 ({{1329:Name}}) - output | Command value additional cooling | 1 Byte | 5.1 percentage (0..100%) | CTU |
| 431 | Controller 2 ({{1329:Name}}) - output | Command value additional cooling (PWM) | 1 Bit | 1.1 switch | CTU |
| 431 | Controller 2 ({{1329:Name}}) - output | Command value additional cooling | 1 Bit | 1.1 switch | CTU |
| 432 | Controller 2 ({{1329:Name}}) - output | PWM command value heating | 1 Byte | 5.1 percentage (0..100%) | CTU |
| 432 | Controller 2 ({{1329:Name}}) - output | PWM command value heating/cooling | 1 Byte | 5.1 percentage (0..100%) | CTU |
| 432 | Controller 2 ({{1329:Name}}) - output | PWM command value basic heating | 1 Byte | 5.1 percentage (0..100%) | CTU |
| 432 | Controller 2 ({{1329:Name}}) - output | PWM command value basic level | 1 Byte | 5.1 percentage (0..100%) | CTU |
| 433 | Controller 2 ({{1329:Name}}) - output | PWM command value additional heating | 1 Byte | 5.1 percentage (0..100%) | CTU |
| 433 | Controller 2 ({{1329:Name}}) - output | PWM command value additional level | 1 Byte | 5.1 percentage (0..100%) | CTU |
| 434 | Controller 2 ({{1329:Name}}) - output | PWM command value cooling | 1 Byte | 5.1 percentage (0..100%) | CTU |
| 434 | Controller 2 ({{1329:Name}}) - output | PWM command value basic heating | 1 Byte | 5.1 percentage (0..100%) | CTU |
| 435 | Controller 2 ({{1329:Name}}) - output | PWM command value additional cooling | 1 Byte | 5.1 percentage (0..100%) | CTU |
| 436 | Controller 2 ({{1329:Name}}) - input | Command value limit | 1 Bit | 1.1 switch | CWU |
| 438 | Controller 2 ({{1329:Name}}) - input | Floor temperature | 2 Bytes | 9.1 temperature (°C) | CWU |
| 442 | Controller 2 ({{1329:Name}}) - output | Heating indication | 1 Bit | 1.1 switch | CTU |
| 443 | Controller 2 ({{1329:Name}}) - output | Cooling indication | 1 Bit | 1.1 switch | CTU |
| 452 | Controller 2 ({{1329:Name}}) - output | Actual-temperature | 2 Bytes | 9.1 temperature (°C) | CRTU |
| 453 | Controller 2 ({{1329:Name}}) - input | Received temperature 1 (temperature sensor 1) | 2 Bytes | 9.1 temperature (°C) | CWTU |
| 454 | Controller 2 ({{1329:Name}}) - input | Received temperature 2 (temperature sensor 2) | 2 Bytes | 9.1 temperature (°C) | CWTU |
| 462 | Controller 3 ({{2013:Name}}) - input | Basic setpoint | 2 Bytes | 9.1 temperature (°C) | CWU |
| 462 | Controller 3 ({{2013:Name}}) - input | Setpoint active operating mode | 2 Bytes | 9.1 temperature (°C) | CWU |
| 464 | Controller 3 ({{2013:Name}}) - input | Operating mode switch-over | 1 Byte | 20.102 HVAC mode | CWTU |
| 464 | Controller 3 ({{2013:Name}}) - input | Comfort mode | 1 Bit | 1.1 switch | CWTU |
| 465 | Controller 3 ({{2013:Name}}) - input | Standby mode | 1 Bit | 1.1 switch | CWTU |
| 466 | Controller 3 ({{2013:Name}}) - input | Night operation | 1 Bit | 1.1 switch | CWTU |
| 467 | Controller 3 ({{2013:Name}}) - input | Frost/ heat protection | 1 Bit | 1.1 switch | CWTU |
| 468 | Controller 3 ({{2013:Name}}) - input | Operating mode forced-control | 1 Byte | 20.102 HVAC mode | CWTU |
| 469 | Controller 3 ({{2013:Name}}) - input | Presence button | 1 Bit | 1.1 switch | CWTU |
| 469 | Controller 3 ({{2013:Name}}) - input | Presence detector | 1 Bit | 1.1 switch | CWTU |
| 470 | Controller 3 ({{2013:Name}}) - input | Windows status | 1 Bit | 1.19 window/door | CWU |
| 471 | Controller 3 ({{2013:Name}}) - input | Heating / cooling change-over | 1 Bit | 1.100 heating/cooling | CWTU |
| 471 | Controller 3 ({{2013:Name}}) - output | Heating / cooling change-over | 1 Bit | 1.100 heating/cooling | CTU |
| 472 | Controller 3 ({{2013:Name}}) - output | Controller status | 1 Byte | | CTU |
| 472 | Controller 3 ({{2013:Name}}) - output | KNX status operating mode | 1 Byte | 20.102 HVAC mode | CTU |
| 472 | Controller 3 ({{2013:Name}}) - output | Controller status, Comfort mode | 1 Bit | 1.1 switch | CTU |
| 472 | Controller 3 ({{2013:Name}}) - output | Controller status, Standby mode | 1 Bit | 1.1 switch | CTU |
| 472 | Controller 3 ({{2013:Name}}) - output | Controller status, night mode | 1 Bit | 1.1 switch | CTU |
| 472 | Controller 3 ({{2013:Name}}) - output | Controller status, frost/heat protection | 1 Bit | 1.1 switch | CTU |
| 472 | Controller 3 ({{2013:Name}}) - output | Controller status, contr. disabled | 1 Bit | 1.1 switch | CTU |
| 472 | Controller 3 ({{2013:Name}}) - output | Controller status, heating/cooling | 1 Bit | 1.1 switch | CTU |
| 472 | Controller 3 ({{2013:Name}}) - output | Controller status contr. inactive | 1 Bit | 1.1 switch | CTU |
| 472 | Controller 3 ({{2013:Name}}) - output | Controller status, frost alarm | 1 Bit | 1.1 switch | CTU |
| 476 | Controller 3 ({{2013:Name}}) - output | Set temperature | 2 Bytes | 9.1 temperature (°C) | CRTU |
| 478 | Controller 3 ({{2013:Name}}) - output | Current setpoint shifting | 1 Byte | 6.10 counter pulses (-128..127) | CRTU |
| 479 | Controller 3 ({{2013:Name}}) - input | Preset setpoint shifting | 1 Byte | 6.10 counter pulses (-128..127) | CWU |
| 480 | Controller 3 ({{2013:Name}}) - output | Status signal addition | 1 Byte | | CTU |
| 480 | Controller 3 ({{2013:Name}}) - output | KNX status | 2 Bytes | 22.101 RHCC status | CTU |
| 481 | Controller 3 ({{2013:Name}}) - output | KNX status forced operating mode | 1 Byte | 20.102 HVAC mode | CTU |
| 482 | Controller 3 ({{2013:Name}}) - input | Outdoor temperature | 2 Bytes | 9.1 temperature (°C) | CWU |
| 483 | Controller 3 ({{2013:Name}}) - input | Limit of cooling setpoint temperature | 1 Bit | 1.1 switch | CWU |
| 497 | Controller 3 ({{2013:Name}}) - input | Disable controller | 1 Bit | 1.3 enable | CWU |
| 498 | Controller 3 ({{2013:Name}}) - input | Disable additional level | 1 Bit | 1.3 enable | CWU |
| 499 | Controller 3 ({{2013:Name}}) - output | Command value for heating | 1 Byte | 5.1 percentage (0..100%) | CTU |
| 499 | Controller 3 ({{2013:Name}}) - output | Command value heating (PWM) | 1 Bit | 1.1 switch | CTU |
| 499 | Controller 3 ({{2013:Name}}) - output | Command value for heating | 1 Bit | 1.1 switch | CTU |
| 499 | Controller 3 ({{2013:Name}}) - output | Command value heating/cooling | 1 Byte | 5.1 percentage (0..100%) | CTU |
| 499 | Controller 3 ({{2013:Name}}) - output | Command value heating/cooling (PWM) | 1 Bit | 1.1 switch | CTU |
| 499 | Controller 3 ({{2013:Name}}) - output | Command value heating/cooling | 1 Bit | 1.1 switch | CTU |
| 499 | Controller 3 ({{2013:Name}}) - output | Command value basic heating | 1 Byte | 5.1 percentage (0..100%) | CTU |
| 499 | Controller 3 ({{2013:Name}}) - output | Command value basic heating (PWM) | 1 Bit | 1.1 switch | CTU |
| 499 | Controller 3 ({{2013:Name}}) - output | Command value basic heating | 1 Bit | 1.1 switch | CTU |
| 499 | Controller 3 ({{2013:Name}}) - output | Command value basic level | 1 Byte | 5.1 percentage (0..100%) | CTU |
| 499 | Controller 3 ({{2013:Name}}) - output | Command value basic level (PWM) | 1 Bit | 1.1 switch | CTU |
| 499 | Controller 3 ({{2013:Name}}) - output | Command value basic level | 1 Bit | 1.1 switch | CTU |
| 500 | Controller 3 ({{2013:Name}}) - output | Command value additional heating | 1 Byte | 5.1 percentage (0..100%) | CTU |
| 500 | Controller 3 ({{2013:Name}}) - output | Command value additional heating (PWM) | 1 Bit | 1.1 switch | CTU |
| 500 | Controller 3 ({{2013:Name}}) - output | Command value additional heating | 1 Bit | 1.1 switch | CTU |
| 500 | Controller 3 ({{2013:Name}}) - output | Command value additional level | 1 Byte | 5.1 percentage (0..100%) | CTU |
| 500 | Controller 3 ({{2013:Name}}) - output | Command value additional level (PWM) | 1 Bit | 1.1 switch | CTU |
| 500 | Controller 3 ({{2013:Name}}) - output | Command value additional level | 1 Bit | 1.1 switch | CTU |
| 501 | Controller 3 ({{2013:Name}}) - output | Command value cooling | 1 Byte | 5.1 percentage (0..100%) | CTU |
| 501 | Controller 3 ({{2013:Name}}) - output | Command value cooling (PWM) | 1 Bit | 1.1 switch | CTU |
| 501 | Controller 3 ({{2013:Name}}) - output | Command value cooling | 1 Bit | 1.1 switch | CTU |
| 501 | Controller 3 ({{2013:Name}}) - output | Command value basic cooling | 1 Byte | 5.1 percentage (0..100%) | CTU |
| 501 | Controller 3 ({{2013:Name}}) - output | Command value basic cooling(PWM) | 1 Bit | 1.1 switch | CTU |
| 501 | Controller 3 ({{2013:Name}}) - output | Command value basic cooling | 1 Bit | 1.1 switch | CTU |
| 502 | Controller 3 ({{2013:Name}}) - output | Command value additional cooling | 1 Byte | 5.1 percentage (0..100%) | CTU |
| 502 | Controller 3 ({{2013:Name}}) - output | Command value additional cooling (PWM) | 1 Bit | 1.1 switch | CTU |
| 502 | Controller 3 ({{2013:Name}}) - output | Command value additional cooling | 1 Bit | 1.1 switch | CTU |
| 503 | Controller 3 ({{2013:Name}}) - output | PWM command value heating | 1 Byte | 5.1 percentage (0..100%) | CTU |
| 503 | Controller 3 ({{2013:Name}}) - output | PWM command value heating/cooling | 1 Byte | 5.1 percentage (0..100%) | CTU |
| 503 | Controller 3 ({{2013:Name}}) - output | PWM command value basic heating | 1 Byte | 5.1 percentage (0..100%) | CTU |
| 503 | Controller 3 ({{2013:Name}}) - output | PWM command value basic level | 1 Byte | 5.1 percentage (0..100%) | CTU |
| 504 | Controller 3 ({{2013:Name}}) - output | PWM command value additional heating | 1 Byte | 5.1 percentage (0..100%) | CTU |
| 504 | Controller 3 ({{2013:Name}}) - output | PWM command value additional level | 1 Byte | 5.1 percentage (0..100%) | CTU |
| 505 | Controller 3 ({{2013:Name}}) - output | PWM command value cooling | 1 Byte | 5.1 percentage (0..100%) | CTU |
| 505 | Controller 3 ({{2013:Name}}) - output | PWM command value basic heating | 1 Byte | 5.1 percentage (0..100%) | CTU |
| 506 | Controller 3 ({{2013:Name}}) - output | PWM command value additional cooling | 1 Byte | 5.1 percentage (0..100%) | CTU |
| 507 | Controller 3 ({{2013:Name}}) - input | Command value limit | 1 Bit | 1.1 switch | CWU |
| 509 | Controller 3 ({{2013:Name}}) - input | Floor temperature | 2 Bytes | 9.1 temperature (°C) | CWU |
| 513 | Controller 3 ({{2013:Name}}) - output | Heating indication | 1 Bit | 1.1 switch | CTU |
| 514 | Controller 3 ({{2013:Name}}) - output | Cooling indication | 1 Bit | 1.1 switch | CTU |
| 523 | Controller 3 ({{2013:Name}}) - output | Actual-temperature | 2 Bytes | 9.1 temperature (°C) | CRTU |
| 524 | Controller 3 ({{2013:Name}}) - input | Received temperature 1 (temperature sensor 1) | 2 Bytes | 9.1 temperature (°C) | CWTU |
| 525 | Controller 3 ({{2013:Name}}) - input | Received temperature 2 (temperature sensor 2) | 2 Bytes | 9.1 temperature (°C) | CWTU |
| 533 | Controller 4 ({{2697:Name}}) - input | Basic setpoint | 2 Bytes | 9.1 temperature (°C) | CWU |
| 533 | Controller 4 ({{2697:Name}}) - input | Setpoint active operating mode | 2 Bytes | 9.1 temperature (°C) | CWU |
| 535 | Controller 4 ({{2697:Name}}) - input | Operating mode switch-over | 1 Byte | 20.102 HVAC mode | CWTU |
| 535 | Controller 4 ({{2697:Name}}) - input | Comfort mode | 1 Bit | 1.1 switch | CWTU |
| 536 | Controller 4 ({{2697:Name}}) - input | Standby mode | 1 Bit | 1.1 switch | CWTU |
| 537 | Controller 4 ({{2697:Name}}) - input | Night operation | 1 Bit | 1.1 switch | CWTU |
| 538 | Controller 4 ({{2697:Name}}) - input | Frost/ heat protection | 1 Bit | 1.1 switch | CWTU |
| 539 | Controller 4 ({{2697:Name}}) - input | Operating mode forced-control | 1 Byte | 20.102 HVAC mode | CWTU |
| 540 | Controller 4 ({{2697:Name}}) - input | Presence button | 1 Bit | 1.1 switch | CWTU |
| 540 | Controller 4 ({{2697:Name}}) - input | Presence detector | 1 Bit | 1.1 switch | CWTU |
| 541 | Controller 4 ({{2697:Name}}) - input | Windows status | 1 Bit | 1.19 window/door | CWU |
| 542 | Controller 4 ({{2697:Name}}) - input | Heating / cooling change-over | 1 Bit | 1.100 heating/cooling | CWTU |
| 542 | Controller 4 ({{2697:Name}}) - output | Heating / cooling change-over | 1 Bit | 1.100 heating/cooling | CTU |
| 543 | Controller 4 ({{2697:Name}}) - output | Controller status | 1 Byte | | CTU |
| 543 | Controller 4 ({{2697:Name}}) - output | KNX status operating mode | 1 Byte | 20.102 HVAC mode | CTU |
| 543 | Controller 4 ({{2697:Name}}) - output | Controller status, Comfort mode | 1 Bit | 1.1 switch | CTU |
| 543 | Controller 4 ({{2697:Name}}) - output | Controller status, Standby mode | 1 Bit | 1.1 switch | CTU |
| 543 | Controller 4 ({{2697:Name}}) - output | Controller status, night mode | 1 Bit | 1.1 switch | CTU |
| 543 | Controller 4 ({{2697:Name}}) - output | Controller status, frost/heat protection | 1 Bit | 1.1 switch | CTU |
| 543 | Controller 4 ({{2697:Name}}) - output | Controller status, contr. disabled | 1 Bit | 1.1 switch | CTU |
| 543 | Controller 4 ({{2697:Name}}) - output | Controller status, heating/cooling | 1 Bit | 1.1 switch | CTU |
| 543 | Controller 4 ({{2697:Name}}) - output | Controller status contr. inactive | 1 Bit | 1.1 switch | CTU |
| 543 | Controller 4 ({{2697:Name}}) - output | Controller status, frost alarm | 1 Bit | 1.1 switch | CTU |
| 547 | Controller 4 ({{2697:Name}}) - output | Set temperature | 2 Bytes | 9.1 temperature (°C) | CRTU |
| 549 | Controller 4 ({{2697:Name}}) - output | Current setpoint shifting | 1 Byte | 6.10 counter pulses (-128..127) | CRTU |
| 550 | Controller 4 ({{2697:Name}}) - input | Preset setpoint shifting | 1 Byte | 6.10 counter pulses (-128..127) | CWU |
| 551 | Controller 4 ({{2697:Name}}) - output | Status signal addition | 1 Byte | | CTU |
| 551 | Controller 4 ({{2697:Name}}) - output | KNX status | 2 Bytes | 22.101 RHCC status | CTU |
| 552 | Controller 4 ({{2697:Name}}) - output | KNX status forced operating mode | 1 Byte | 20.102 HVAC mode | CTU |
| 553 | Controller 4 ({{2697:Name}}) - input | Outdoor temperature | 2 Bytes | 9.1 temperature (°C) | CWU |
| 554 | Controller 4 ({{2697:Name}}) - input | Limit of cooling setpoint temperature | 1 Bit | 1.1 switch | CWU |
| 568 | Controller 4 ({{2697:Name}}) - input | Disable controller | 1 Bit | 1.3 enable | CWU |
| 569 | Controller 4 ({{2697:Name}}) - input | Disable additional level | 1 Bit | 1.3 enable | CWU |
| 570 | Controller 4 ({{2697:Name}}) - output | Command value for heating | 1 Byte | 5.1 percentage (0..100%) | CTU |
| 570 | Controller 4 ({{2697:Name}}) - output | Command value heating (PWM) | 1 Bit | 1.1 switch | CTU |
| 570 | Controller 4 ({{2697:Name}}) - output | Command value for heating | 1 Bit | 1.1 switch | CTU |
| 570 | Controller 4 ({{2697:Name}}) - output | Command value heating/cooling | 1 Byte | 5.1 percentage (0..100%) | CTU |
| 570 | Controller 4 ({{2697:Name}}) - output | Command value heating/cooling (PWM) | 1 Bit | 1.1 switch | CTU |
| 570 | Controller 4 ({{2697:Name}}) - output | Command value heating/cooling | 1 Bit | 1.1 switch | CTU |
| 570 | Controller 4 ({{2697:Name}}) - output | Command value basic heating | 1 Byte | 5.1 percentage (0..100%) | CTU |
| 570 | Controller 4 ({{2697:Name}}) - output | Command value basic heating (PWM) | 1 Bit | 1.1 switch | CTU |
| 570 | Controller 4 ({{2697:Name}}) - output | Command value basic heating | 1 Bit | 1.1 switch | CTU |
| 570 | Controller 4 ({{2697:Name}}) - output | Command value basic level | 1 Byte | 5.1 percentage (0..100%) | CTU |
| 570 | Controller 4 ({{2697:Name}}) - output | Command value basic level (PWM) | 1 Bit | 1.1 switch | CTU |
| 570 | Controller 4 ({{2697:Name}}) - output | Command value basic level | 1 Bit | 1.1 switch | CTU |
| 571 | Controller 4 ({{2697:Name}}) - output | Command value additional heating | 1 Byte | 5.1 percentage (0..100%) | CTU |
| 571 | Controller 4 ({{2697:Name}}) - output | Command value additional heating (PWM) | 1 Bit | 1.1 switch | CTU |
| 571 | Controller 4 ({{2697:Name}}) - output | Command value additional heating | 1 Bit | 1.1 switch | CTU |
| 571 | Controller 4 ({{2697:Name}}) - output | Command value additional level | 1 Byte | 5.1 percentage (0..100%) | CTU |
| 571 | Controller 4 ({{2697:Name}}) - output | Command value additional level (PWM) | 1 Bit | 1.1 switch | CTU |
| 571 | Controller 4 ({{2697:Name}}) - output | Command value additional level | 1 Bit | 1.1 switch | CTU |
| 572 | Controller 4 ({{2697:Name}}) - output | Command value cooling | 1 Byte | 5.1 percentage (0..100%) | CTU |
| 572 | Controller 4 ({{2697:Name}}) - output | Command value cooling (PWM) | 1 Bit | 1.1 switch | CTU |
| 572 | Controller 4 ({{2697:Name}}) - output | Command value cooling | 1 Bit | 1.1 switch | CTU |
| 572 | Controller 4 ({{2697:Name}}) - output | Command value basic cooling | 1 Byte | 5.1 percentage (0..100%) | CTU |
| 572 | Controller 4 ({{2697:Name}}) - output | Command value basic cooling(PWM) | 1 Bit | 1.1 switch | CTU |
| 572 | Controller 4 ({{2697:Name}}) - output | Command value basic cooling | 1 Bit | 1.1 switch | CTU |
| 573 | Controller 4 ({{2697:Name}}) - output | Command value additional cooling | 1 Byte | 5.1 percentage (0..100%) | CTU |
| 573 | Controller 4 ({{2697:Name}}) - output | Command value additional cooling (PWM) | 1 Bit | 1.1 switch | CTU |
| 573 | Controller 4 ({{2697:Name}}) - output | Command value additional cooling | 1 Bit | 1.1 switch | CTU |
| 574 | Controller 4 ({{2697:Name}}) - output | PWM command value heating | 1 Byte | 5.1 percentage (0..100%) | CTU |
| 574 | Controller 4 ({{2697:Name}}) - output | PWM command value heating/cooling | 1 Byte | 5.1 percentage (0..100%) | CTU |
| 574 | Controller 4 ({{2697:Name}}) - output | PWM command value basic heating | 1 Byte | 5.1 percentage (0..100%) | CTU |
| 574 | Controller 4 ({{2697:Name}}) - output | PWM command value basic level | 1 Byte | 5.1 percentage (0..100%) | CTU |
| 575 | Controller 4 ({{2697:Name}}) - output | PWM command value additional heating | 1 Byte | 5.1 percentage (0..100%) | CTU |
| 575 | Controller 4 ({{2697:Name}}) - output | PWM command value additional level | 1 Byte | 5.1 percentage (0..100%) | CTU |
| 576 | Controller 4 ({{2697:Name}}) - output | PWM command value cooling | 1 Byte | 5.1 percentage (0..100%) | CTU |
| 576 | Controller 4 ({{2697:Name}}) - output | PWM command value basic heating | 1 Byte | 5.1 percentage (0..100%) | CTU |
| 577 | Controller 4 ({{2697:Name}}) - output | PWM command value additional cooling | 1 Byte | 5.1 percentage (0..100%) | CTU |
| 578 | Controller 4 ({{2697:Name}}) - input | Command value limit | 1 Bit | 1.1 switch | CWU |
| 580 | Controller 4 ({{2697:Name}}) - input | Floor temperature | 2 Bytes | 9.1 temperature (°C) | CWU |
| 584 | Controller 4 ({{2697:Name}}) - output | Heating indication | 1 Bit | 1.1 switch | CTU |
| 585 | Controller 4 ({{2697:Name}}) - output | Cooling indication | 1 Bit | 1.1 switch | CTU |
| 594 | Controller 4 ({{2697:Name}}) - output | Actual-temperature | 2 Bytes | 9.1 temperature (°C) | CRTU |
| 595 | Controller 4 ({{2697:Name}}) - input | Received temperature 1 (temperature sensor 1) | 2 Bytes | 9.1 temperature (°C) | CWTU |
| 596 | Controller 4 ({{2697:Name}}) - input | Received temperature 2 (temperature sensor 2) | 2 Bytes | 9.1 temperature (°C) | CWTU |
| 604 | Controller 5 ({{3381:Name}}) - input | Basic setpoint | 2 Bytes | 9.1 temperature (°C) | CWU |
| 604 | Controller 5 ({{3381:Name}}) - input | Setpoint active operating mode | 2 Bytes | 9.1 temperature (°C) | CWU |
| 606 | Controller 5 ({{3381:Name}}) - input | Operating mode switch-over | 1 Byte | 20.102 HVAC mode | CWTU |
| 606 | Controller 5 ({{3381:Name}}) - input | Comfort mode | 1 Bit | 1.1 switch | CWTU |
| 607 | Controller 5 ({{3381:Name}}) - input | Standby mode | 1 Bit | 1.1 switch | CWTU |
| 608 | Controller 5 ({{3381:Name}}) - input | Night operation | 1 Bit | 1.1 switch | CWTU |
| 609 | Controller 5 ({{3381:Name}}) - input | Frost/ heat protection | 1 Bit | 1.1 switch | CWTU |
| 610 | Controller 5 ({{3381:Name}}) - input | Operating mode forced-control | 1 Byte | 20.102 HVAC mode | CWTU |
| 611 | Controller 5 ({{3381:Name}}) - input | Presence button | 1 Bit | 1.1 switch | CWTU |
| 611 | Controller 5 ({{3381:Name}}) - input | Presence detector | 1 Bit | 1.1 switch | CWTU |
| 612 | Controller 5 ({{3381:Name}}) - input | Windows status | 1 Bit | 1.19 window/door | CWU |
| 613 | Controller 5 ({{3381:Name}}) - input | Heating / cooling change-over | 1 Bit | 1.100 heating/cooling | CWTU |
| 613 | Controller 5 ({{3381:Name}}) - output | Heating / cooling change-over | 1 Bit | 1.100 heating/cooling | CTU |
| 614 | Controller 5 ({{3381:Name}}) - output | Controller status | 1 Byte | | CTU |
| 614 | Controller 5 ({{3381:Name}}) - output | KNX status operating mode | 1 Byte | 20.102 HVAC mode | CTU |
| 614 | Controller 5 ({{3381:Name}}) - output | Controller status, Comfort mode | 1 Bit | 1.1 switch | CTU |
| 614 | Controller 5 ({{3381:Name}}) - output | Controller status, Standby mode | 1 Bit | 1.1 switch | CTU |
| 614 | Controller 5 ({{3381:Name}}) - output | Controller status, night mode | 1 Bit | 1.1 switch | CTU |
| 614 | Controller 5 ({{3381:Name}}) - output | Controller status, frost/heat protection | 1 Bit | 1.1 switch | CTU |
| 614 | Controller 5 ({{3381:Name}}) - output | Controller status, contr. disabled | 1 Bit | 1.1 switch | CTU |
| 614 | Controller 5 ({{3381:Name}}) - output | Controller status, heating/cooling | 1 Bit | 1.1 switch | CTU |
| 614 | Controller 5 ({{3381:Name}}) - output | Controller status contr. inactive | 1 Bit | 1.1 switch | CTU |
| 614 | Controller 5 ({{3381:Name}}) - output | Controller status, frost alarm | 1 Bit | 1.1 switch | CTU |
| 618 | Controller 5 ({{3381:Name}}) - output | Set temperature | 2 Bytes | 9.1 temperature (°C) | CRTU |
| 620 | Controller 5 ({{3381:Name}}) - output | Current setpoint shifting | 1 Byte | 6.10 counter pulses (-128..127) | CRTU |
| 621 | Controller 5 ({{3381:Name}}) - input | Preset setpoint shifting | 1 Byte | 6.10 counter pulses (-128..127) | CWU |
| 622 | Controller 5 ({{3381:Name}}) - output | Status signal addition | 1 Byte | | CTU |
| 622 | Controller 5 ({{3381:Name}}) - output | KNX status | 2 Bytes | 22.101 RHCC status | CTU |
| 623 | Controller 5 ({{3381:Name}}) - output | KNX status forced operating mode | 1 Byte | 20.102 HVAC mode | CTU |
| 624 | Controller 5 ({{3381:Name}}) - input | Outdoor temperature | 2 Bytes | 9.1 temperature (°C) | CWU |
| 625 | Controller 5 ({{3381:Name}}) - input | Limit of cooling setpoint temperature | 1 Bit | 1.1 switch | CWU |
| 639 | Controller 5 ({{3381:Name}}) - input | Disable controller | 1 Bit | 1.3 enable | CWU |
| 640 | Controller 5 ({{3381:Name}}) - input | Disable additional level | 1 Bit | 1.3 enable | CWU |
| 641 | Controller 5 ({{3381:Name}}) - output | Command value for heating | 1 Byte | 5.1 percentage (0..100%) | CTU |
| 641 | Controller 5 ({{3381:Name}}) - output | Command value heating (PWM) | 1 Bit | 1.1 switch | CTU |
| 641 | Controller 5 ({{3381:Name}}) - output | Command value for heating | 1 Bit | 1.1 switch | CTU |
| 641 | Controller 5 ({{3381:Name}}) - output | Command value heating/cooling | 1 Byte | 5.1 percentage (0..100%) | CTU |
| 641 | Controller 5 ({{3381:Name}}) - output | Command value heating/cooling (PWM) | 1 Bit | 1.1 switch | CTU |
| 641 | Controller 5 ({{3381:Name}}) - output | Command value heating/cooling | 1 Bit | 1.1 switch | CTU |
| 641 | Controller 5 ({{3381:Name}}) - output | Command value basic heating | 1 Byte | 5.1 percentage (0..100%) | CTU |
| 641 | Controller 5 ({{3381:Name}}) - output | Command value basic heating (PWM) | 1 Bit | 1.1 switch | CTU |
| 641 | Controller 5 ({{3381:Name}}) - output | Command value basic heating | 1 Bit | 1.1 switch | CTU |
| 641 | Controller 5 ({{3381:Name}}) - output | Command value basic level | 1 Byte | 5.1 percentage (0..100%) | CTU |
| 641 | Controller 5 ({{3381:Name}}) - output | Command value basic level (PWM) | 1 Bit | 1.1 switch | CTU |
| 641 | Controller 5 ({{3381:Name}}) - output | Command value basic level | 1 Bit | 1.1 switch | CTU |
| 642 | Controller 5 ({{3381:Name}}) - output | Command value additional heating | 1 Byte | 5.1 percentage (0..100%) | CTU |
| 642 | Controller 5 ({{3381:Name}}) - output | Command value additional heating (PWM) | 1 Bit | 1.1 switch | CTU |
| 642 | Controller 5 ({{3381:Name}}) - output | Command value additional heating | 1 Bit | 1.1 switch | CTU |
| 642 | Controller 5 ({{3381:Name}}) - output | Command value additional level | 1 Byte | 5.1 percentage (0..100%) | CTU |
| 642 | Controller 5 ({{3381:Name}}) - output | Command value additional level (PWM) | 1 Bit | 1.1 switch | CTU |
| 642 | Controller 5 ({{3381:Name}}) - output | Command value additional level | 1 Bit | 1.1 switch | CTU |
| 643 | Controller 5 ({{3381:Name}}) - output | Command value cooling | 1 Byte | 5.1 percentage (0..100%) | CTU |
| 643 | Controller 5 ({{3381:Name}}) - output | Command value cooling (PWM) | 1 Bit | 1.1 switch | CTU |
| 643 | Controller 5 ({{3381:Name}}) - output | Command value cooling | 1 Bit | 1.1 switch | CTU |
| 643 | Controller 5 ({{3381:Name}}) - output | Command value basic cooling | 1 Byte | 5.1 percentage (0..100%) | CTU |
| 643 | Controller 5 ({{3381:Name}}) - output | Command value basic cooling(PWM) | 1 Bit | 1.1 switch | CTU |
| 643 | Controller 5 ({{3381:Name}}) - output | Command value basic cooling | 1 Bit | 1.1 switch | CTU |
| 644 | Controller 5 ({{3381:Name}}) - output | Command value additional cooling | 1 Byte | 5.1 percentage (0..100%) | CTU |
| 644 | Controller 5 ({{3381:Name}}) - output | Command value additional cooling (PWM) | 1 Bit | 1.1 switch | CTU |
| 644 | Controller 5 ({{3381:Name}}) - output | Command value additional cooling | 1 Bit | 1.1 switch | CTU |
| 645 | Controller 5 ({{3381:Name}}) - output | PWM command value heating | 1 Byte | 5.1 percentage (0..100%) | CTU |
| 645 | Controller 5 ({{3381:Name}}) - output | PWM command value heating/cooling | 1 Byte | 5.1 percentage (0..100%) | CTU |
| 645 | Controller 5 ({{3381:Name}}) - output | PWM command value basic heating | 1 Byte | 5.1 percentage (0..100%) | CTU |
| 645 | Controller 5 ({{3381:Name}}) - output | PWM command value basic level | 1 Byte | 5.1 percentage (0..100%) | CTU |
| 646 | Controller 5 ({{3381:Name}}) - output | PWM command value additional heating | 1 Byte | 5.1 percentage (0..100%) | CTU |
| 646 | Controller 5 ({{3381:Name}}) - output | PWM command value additional level | 1 Byte | 5.1 percentage (0..100%) | CTU |
| 647 | Controller 5 ({{3381:Name}}) - output | PWM command value cooling | 1 Byte | 5.1 percentage (0..100%) | CTU |
| 647 | Controller 5 ({{3381:Name}}) - output | PWM command value basic heating | 1 Byte | 5.1 percentage (0..100%) | CTU |
| 648 | Controller 5 ({{3381:Name}}) - output | PWM command value additional cooling | 1 Byte | 5.1 percentage (0..100%) | CTU |
| 649 | Controller 5 ({{3381:Name}}) - input | Command value limit | 1 Bit | 1.1 switch | CWU |
| 651 | Controller 5 ({{3381:Name}}) - input | Floor temperature | 2 Bytes | 9.1 temperature (°C) | CWU |
| 655 | Controller 5 ({{3381:Name}}) - output | Heating indication | 1 Bit | 1.1 switch | CTU |
| 656 | Controller 5 ({{3381:Name}}) - output | Cooling indication | 1 Bit | 1.1 switch | CTU |
| 665 | Controller 5 ({{3381:Name}}) - output | Actual-temperature | 2 Bytes | 9.1 temperature (°C) | CRTU |
| 666 | Controller 5 ({{3381:Name}}) - input | Received temperature 1 (temperature sensor 1) | 2 Bytes | 9.1 temperature (°C) | CWTU |
| 667 | Controller 5 ({{3381:Name}}) - input | Received temperature 2 (temperature sensor 2) | 2 Bytes | 9.1 temperature (°C) | CWTU |
| 675 | Controller 6 ({{4065:Name}}) - input | Basic setpoint | 2 Bytes | 9.1 temperature (°C) | CWU |
| 675 | Controller 6 ({{4065:Name}}) - input | Setpoint active operating mode | 2 Bytes | 9.1 temperature (°C) | CWU |
| 677 | Controller 6 ({{4065:Name}}) - input | Operating mode switch-over | 1 Byte | 20.102 HVAC mode | CWTU |
| 677 | Controller 6 ({{4065:Name}}) - input | Comfort mode | 1 Bit | 1.1 switch | CWTU |
| 678 | Controller 6 ({{4065:Name}}) - input | Standby mode | 1 Bit | 1.1 switch | CWTU |
| 679 | Controller 6 ({{4065:Name}}) - input | Night operation | 1 Bit | 1.1 switch | CWTU |
| 680 | Controller 6 ({{4065:Name}}) - input | Frost/ heat protection | 1 Bit | 1.1 switch | CWTU |
| 681 | Controller 6 ({{4065:Name}}) - input | Operating mode forced-control | 1 Byte | 20.102 HVAC mode | CWTU |
| 682 | Controller 6 ({{4065:Name}}) - input | Presence button | 1 Bit | 1.1 switch | CWTU |
| 682 | Controller 6 ({{4065:Name}}) - input | Presence detector | 1 Bit | 1.1 switch | CWTU |
| 683 | Controller 6 ({{4065:Name}}) - input | Windows status | 1 Bit | 1.19 window/door | CWU |
| 684 | Controller 6 ({{4065:Name}}) - input | Heating / cooling change-over | 1 Bit | 1.100 heating/cooling | CWTU |
| 684 | Controller 6 ({{4065:Name}}) - output | Heating / cooling change-over | 1 Bit | 1.100 heating/cooling | CTU |
| 685 | Controller 6 ({{4065:Name}}) - output | Controller status | 1 Byte | | CTU |
| 685 | Controller 6 ({{4065:Name}}) - output | KNX status operating mode | 1 Byte | 20.102 HVAC mode | CTU |
| 685 | Controller 6 ({{4065:Name}}) - output | Controller status, Comfort mode | 1 Bit | 1.1 switch | CTU |
| 685 | Controller 6 ({{4065:Name}}) - output | Controller status, Standby mode | 1 Bit | 1.1 switch | CTU |
| 685 | Controller 6 ({{4065:Name}}) - output | Controller status, night mode | 1 Bit | 1.1 switch | CTU |
| 685 | Controller 6 ({{4065:Name}}) - output | Controller status, frost/heat protection | 1 Bit | 1.1 switch | CTU |
| 685 | Controller 6 ({{4065:Name}}) - output | Controller status, contr. disabled | 1 Bit | 1.1 switch | CTU |
| 685 | Controller 6 ({{4065:Name}}) - output | Controller status, heating/cooling | 1 Bit | 1.1 switch | CTU |
| 685 | Controller 6 ({{4065:Name}}) - output | Controller status contr. inactive | 1 Bit | 1.1 switch | CTU |
| 685 | Controller 6 ({{4065:Name}}) - output | Controller status, frost alarm | 1 Bit | 1.1 switch | CTU |
| 689 | Controller 6 ({{4065:Name}}) - output | Set temperature | 2 Bytes | 9.1 temperature (°C) | CRTU |
| 691 | Controller 6 ({{4065:Name}}) - output | Current setpoint shifting | 1 Byte | 6.10 counter pulses (-128..127) | CRTU |
| 692 | Controller 6 ({{4065:Name}}) - input | Preset setpoint shifting | 1 Byte | 6.10 counter pulses (-128..127) | CWU |
| 693 | Controller 6 ({{4065:Name}}) - output | Status signal addition | 1 Byte | | CTU |
| 693 | Controller 6 ({{4065:Name}}) - output | KNX status | 2 Bytes | 22.101 RHCC status | CTU |
| 694 | Controller 6 ({{4065:Name}}) - output | KNX status forced operating mode | 1 Byte | 20.102 HVAC mode | CTU |
| 695 | Controller 6 ({{4065:Name}}) - input | Outdoor temperature | 2 Bytes | 9.1 temperature (°C) | CWU |
| 696 | Controller 6 ({{4065:Name}}) - input | Limit of cooling setpoint temperature | 1 Bit | 1.1 switch | CWU |
| 710 | Controller 6 ({{4065:Name}}) - input | Disable controller | 1 Bit | 1.3 enable | CWU |
| 711 | Controller 6 ({{4065:Name}}) - input | Disable additional level | 1 Bit | 1.3 enable | CWU |
| 712 | Controller 6 ({{4065:Name}}) - output | Command value for heating | 1 Byte | 5.1 percentage (0..100%) | CTU |
| 712 | Controller 6 ({{4065:Name}}) - output | Command value heating (PWM) | 1 Bit | 1.1 switch | CTU |
| 712 | Controller 6 ({{4065:Name}}) - output | Command value for heating | 1 Bit | 1.1 switch | CTU |
| 712 | Controller 6 ({{4065:Name}}) - output | Command value heating/cooling | 1 Byte | 5.1 percentage (0..100%) | CTU |
| 712 | Controller 6 ({{4065:Name}}) - output | Command value heating/cooling (PWM) | 1 Bit | 1.1 switch | CTU |
| 712 | Controller 6 ({{4065:Name}}) - output | Command value heating/cooling | 1 Bit | 1.1 switch | CTU |
| 712 | Controller 6 ({{4065:Name}}) - output | Command value basic heating | 1 Byte | 5.1 percentage (0..100%) | CTU |
| 712 | Controller 6 ({{4065:Name}}) - output | Command value basic heating (PWM) | 1 Bit | 1.1 switch | CTU |
| 712 | Controller 6 ({{4065:Name}}) - output | Command value basic heating | 1 Bit | 1.1 switch | CTU |
| 712 | Controller 6 ({{4065:Name}}) - output | Command value basic level | 1 Byte | 5.1 percentage (0..100%) | CTU |
| 712 | Controller 6 ({{4065:Name}}) - output | Command value basic level (PWM) | 1 Bit | 1.1 switch | CTU |
| 712 | Controller 6 ({{4065:Name}}) - output | Command value basic level | 1 Bit | 1.1 switch | CTU |
| 713 | Controller 6 ({{4065:Name}}) - output | Command value additional heating | 1 Byte | 5.1 percentage (0..100%) | CTU |
| 713 | Controller 6 ({{4065:Name}}) - output | Command value additional heating (PWM) | 1 Bit | 1.1 switch | CTU |
| 713 | Controller 6 ({{4065:Name}}) - output | Command value additional heating | 1 Bit | 1.1 switch | CTU |
| 713 | Controller 6 ({{4065:Name}}) - output | Command value additional level | 1 Byte | 5.1 percentage (0..100%) | CTU |
| 713 | Controller 6 ({{4065:Name}}) - output | Command value additional level (PWM) | 1 Bit | 1.1 switch | CTU |
| 713 | Controller 6 ({{4065:Name}}) - output | Command value additional level | 1 Bit | 1.1 switch | CTU |
| 714 | Controller 6 ({{4065:Name}}) - output | Command value cooling | 1 Byte | 5.1 percentage (0..100%) | CTU |
| 714 | Controller 6 ({{4065:Name}}) - output | Command value cooling (PWM) | 1 Bit | 1.1 switch | CTU |
| 714 | Controller 6 ({{4065:Name}}) - output | Command value cooling | 1 Bit | 1.1 switch | CTU |
| 714 | Controller 6 ({{4065:Name}}) - output | Command value basic cooling | 1 Byte | 5.1 percentage (0..100%) | CTU |
| 714 | Controller 6 ({{4065:Name}}) - output | Command value basic cooling(PWM) | 1 Bit | 1.1 switch | CTU |
| 714 | Controller 6 ({{4065:Name}}) - output | Command value basic cooling | 1 Bit | 1.1 switch | CTU |
| 715 | Controller 6 ({{4065:Name}}) - output | Command value additional cooling | 1 Byte | 5.1 percentage (0..100%) | CTU |
| 715 | Controller 6 ({{4065:Name}}) - output | Command value additional cooling (PWM) | 1 Bit | 1.1 switch | CTU |
| 715 | Controller 6 ({{4065:Name}}) - output | Command value additional cooling | 1 Bit | 1.1 switch | CTU |
| 716 | Controller 6 ({{4065:Name}}) - output | PWM command value heating | 1 Byte | 5.1 percentage (0..100%) | CTU |
| 716 | Controller 6 ({{4065:Name}}) - output | PWM command value heating/cooling | 1 Byte | 5.1 percentage (0..100%) | CTU |
| 716 | Controller 6 ({{4065:Name}}) - output | PWM command value basic heating | 1 Byte | 5.1 percentage (0..100%) | CTU |
| 716 | Controller 6 ({{4065:Name}}) - output | PWM command value basic level | 1 Byte | 5.1 percentage (0..100%) | CTU |
| 717 | Controller 6 ({{4065:Name}}) - output | PWM command value additional heating | 1 Byte | 5.1 percentage (0..100%) | CTU |
| 717 | Controller 6 ({{4065:Name}}) - output | PWM command value additional level | 1 Byte | 5.1 percentage (0..100%) | CTU |
| 718 | Controller 6 ({{4065:Name}}) - output | PWM command value cooling | 1 Byte | 5.1 percentage (0..100%) | CTU |
| 718 | Controller 6 ({{4065:Name}}) - output | PWM command value basic heating | 1 Byte | 5.1 percentage (0..100%) | CTU |
| 719 | Controller 6 ({{4065:Name}}) - output | PWM command value additional cooling | 1 Byte | 5.1 percentage (0..100%) | CTU |
| 720 | Controller 6 ({{4065:Name}}) - input | Command value limit | 1 Bit | 1.1 switch | CWU |
| 722 | Controller 6 ({{4065:Name}}) - input | Floor temperature | 2 Bytes | 9.1 temperature (°C) | CWU |
| 726 | Controller 6 ({{4065:Name}}) - output | Heating indication | 1 Bit | 1.1 switch | CTU |
| 727 | Controller 6 ({{4065:Name}}) - output | Cooling indication | 1 Bit | 1.1 switch | CTU |
| 736 | Controller 6 ({{4065:Name}}) - output | Actual-temperature | 2 Bytes | 9.1 temperature (°C) | CRTU |
| 737 | Controller 6 ({{4065:Name}}) - input | Received temperature 1 (temperature sensor 1) | 2 Bytes | 9.1 temperature (°C) | CWTU |
| 738 | Controller 6 ({{4065:Name}}) - input | Received temperature 2 (temperature sensor 2) | 2 Bytes | 9.1 temperature (°C) | CWTU |