KNX Database

351-25020N SG 360-4PIR (351-) 25020N

NIKO · Order number (351-) 25020N · Presence Detector › Ceiling

Swiss Garde 360-4PIR

Download .knxprod v2.3 (1xLight On/Off, 1xLight DIM, HVAC) 2.3 · 88 KB

Product

ManufacturerNIKO
Product name351-25020N SG 360-4PIR
Order number(351-) 25020N
HardwareSwiss Garde 360 Präsenz/N
MediumTwisted Pair
Bus current (mA)15
Rail mountedNo
RegistrationRegistered · 2023-07-10
Languagesen-US
Catalog entryM-01FC_H-ZU.20002-7_HP-0002-23-6408_CI-.28351.2D.29.2025020N-0
Fingerprint6408
SHA-25650d6cdf19eec10a06d81c5f396ff994069cc9336f7ecb80cfae9cadafaae90e8
First seen2026-11-25
Markets18 markets

Application program: v2.3 (1xLight On/Off, 1xLight DIM, HVAC) 2.3

Application number$0002
Version2.3
Mask versionMV-0701 (7.1)
KNX Data SecureNo
Minimum ETS version3.0d
Parameters167
Group objects28
Group objects (28)
NoNameFunctionSizeDPTFlags
0output - lightdimming absolute1 Byte5.1 percentage (0..100%)CRT
0output - lightswitching1 Bit1.1 switchCRT
0output - lightscene1 Byte5.1 percentage (0..100%)CRT
1external switch / status - lightswitching1 Bit1.1 switchCW
2external movement - lightswitching1 Bit1.1 switchCW
3input - lightrestraint2 Bit2.1 switch controlCW
3input - lightlock1 Bit1.1 switchCW
4output - climate (HCV)switching1 Bit1.1 switchCRT
4output - climate (HCV)dimming absolute1 Byte5.1 percentage (0..100%)CRT
4output - climate (HCV)scene1 Byte5.1 percentage (0..100%)CRT
5external switch / status - climate (HCV)switching1 Bit1.1 switchCW
6external movement - lightswitching1 Bit1.1 switchCW
7input - climate (HCV)restraint2 Bit2.1 switch controlCW
7input - climate (HCV)lock1 Bit1.1 switchCW
8threshold switch brightnessswitching1 Bit1.1 switchCRT
9brightness valuebrightness value2 Bytes9.4 lux (Lux)CRT
10AD calibrationAD calibration2 Bytes8.1 pulses differenceCRT
11reserve object1 Bit
12reserve object1 Bit
13reserve object1 Bit
14reserve object1 Bit
15reserve object1 Bit
16constant lightswitch ON/OFF1 Bit1.1 switchCW
17constant lightdimming relative4 Bit3.7 dimming controlCW
18constant lightdimming absolute1 Byte5.1 percentage (0..100%)CW
20constant lightforce output1 Bit1.1 switchCW
21constant lightscene1 ByteCW
22constant lightdimming absolute1 Byte5.1 percentage (0..100%)CT
Parameters (106)
ParameterTypeDefault
release time restraintlist9 h
dummyunsignedInt 0…655350
EinschaltverzögerungunsignedInt 0…2555
operating mode of detectorlistfully automatic
LED greenlistin case of movement
follow-up timelist5 min
brightness threshold below active sensorlist300 Lux
brightness threshold above switch offlistOFF
force or lock objectlistforce object
if lock object = 0listlock (actual state)
if lock object = 1listforced ON
object type for output - lightlistswitching
object value for ONlist100%
object value for ONlistON
object value for ONlistscene 2
object value for OFFlist0%
object value for OFFlistOFF
object value for OFFlistscene 3
Sending conditions for switching objectlistON and OFF
sending conditions for external push buttonlistON and OFF
idle time after switch offlist2 s
LEDlistOFF
Helligkeitschwelle HLKunsignedInt 0…655350
number of monitoring time windowslist3
length of monitoring time window (s)unsignedInt 0…3000030
object type for output - climate (HCV)listswitching
send light value in case of change bylist100 Lux
cyclical sending of light valuelistOFF
value for switching the threshold switchlist300 Lux
hysteresislist30 Lux
send filterlistON and OFF
IR-channellistCH1
calibration brightness valuelistNO
AD Kalibrierwert 1unsignedInt 0…655350
Luxwert 1unsignedInt 0…655350
AD calibration valueunsignedInt 0…655350
Lux valueunsignedInt 0…655350
Anzahl Messungen für MittelwertbildungunsignedInt 3…3010
Offset Sensor 1unsignedInt 0…655352047
Offset Sensor 2unsignedInt 0…655352047
Offset Sensor 3unsignedInt 0…655352047
active Sensorslist4321
sensitivity 1 = min, 10 = maxlist5
triggerLevelCh_1unsignedInt 0…655351000
triggerLevelCh_2unsignedInt 0…655351000
triggerLevelCh_3unsignedInt 0…655351000
M1 pirLevelMultunsignedInt 0…25510
M2 pirExtMultunsignedInt 0…2550
M3 pirDiffMultunsignedInt 0…2550
M3 pirDiffMultunsignedInt 0…2550
L1 pirDetectLevelunsignedInt 0…25510
P1 Offset SensorunsignedInt 0…655352047
P1 trigger levelunsignedInt 0…655351000
P2 pirExtrLevelunsignedInt 0…655350
P3 pirDiffLevelunsignedInt 0…655350
nicht sichtbarlist0
###unsignedInt 0…2550
Konstant Licht Reglerlistdisabled
### Kp - mulltipliersignedInt -32768…3276740
### Kp - dividersignedInt -32768…3276710
### Ki - mulltipliersignedInt -32768…327671
### Ki - dividersignedInt -32768…32767500
### Kd - multipliersignedInt -32768…327670
### Ki - dividersignedInt -32768…327672500
### cycle time [0,1s]unsignedInt 1…32767500
### dead bandunsignedInt 1…502
Send differencelist10%
###unsignedInt 0…2551
###unsignedInt 0…25522
###unsignedInt 0…25551
preset setpointlist300 lx
###list10%
###unsignedInt 0…10
switching ON/OFF bylistobject
###listno cyclic transmission
Cycle Transmission timelistno cyclic transmission
Regler schaltet Licht auslistdisabled
switch On valuelist100%
switch On timeoutlist10 s
force output at ONlistno reaction
###unsignedInt 0…11
force output at OFFlistno reaction
relative dimming timelist8 s
Relatives Dimmen Schrittlist1%
take over setpoint afterlist5 s
write changed setpoint to flashlistdisabled
light moodslistdisabled
light mood 1list500 lx
light mood 2list500 lx
light mood 3list500 lx
light mood 4list500 lx
light mood 5list500 lx
light mood 6list500 lx
light mood 7list500 lx
light mood 8list500 lx
PID parameterliststandard
###signedInt -32768…327670
dead bandunsignedInt 1…502
cycle timeunsignedInt 1…32767500
Kp - mulltipliersignedInt -32768…3276740
Kp - dividersignedInt -32768…3276710
Ki - mulltipliersignedInt -32768…327671
Ki - dividersignedInt -32768…32767500
Kd - multipliersignedInt -32768…327670
Ki - dividersignedInt -32768…327672500
Kd - MultiplikatorsignedInt -32768…327670

Version history

ApplicationApp noFingerprintFirst seenSizeFile
v2.3 (1xLight On/Off, 1xLight DIM, HVAC) 2.3 latest$000264082026-11-2588 KBDownload

About this file

This is the official ETS product database for the NIKO 351-25020N SG 360-4PIR ((351-) 25020N), published by the manufacturer in the KNX online catalog. To use it, open ETS, go to Catalogs → Import and choose the downloaded .knxprod file. The device then appears in your catalog and can be added to a project. Older versions are kept so existing projects can be matched to the application program they were commissioned with.