Presence detector P34MR, KNX, 360°, for flush mounting and flush-mounting box 350-34002
NIKO · Order number 350-34002 · KNX › Indoor
Download .knxprod KNX01-NK 0.1 · 139 KB
Product
| Manufacturer | NIKO |
|---|---|
| Product name | Presence detector P34MR, KNX, 360°, for flush mounting and flush-mounting box |
| Order number | 350-34002 |
| Hardware | 409-KNX |
| Medium | Twisted Pair |
| Bus current (mA) | 10 |
| Rail mounted | No |
| Registration | Certified · 2021-07-02 |
| Languages | en-US, de-DE, fr-FR, it-IT, nl-NL, pl-PL, sk-SK |
| Catalog entry | M-01FC_H-NK001-1_HP-0001-01-86BD_CI-350.2D34002-1 |
| Fingerprint | 86BD |
| SHA-256 | 175edcfe1217cd63dae2fcbaba6e9477ced955fc9e47e2960735adefda54efcd |
| First seen | 2026-11-25 |
| Markets | 18 markets |
Application program: KNX01-NK 0.1
| Application number | $0001 |
|---|---|
| Version | 0.1 |
| Mask version | MV-07B0 (System B) |
| KNX Data Secure | No |
| Minimum ETS version | 5.0 |
| Parameters | 141 |
| Group objects | 51 |
Group objects (51)
| No | Name | Function | Size | DPT | Flags |
|---|---|---|---|---|---|
| 1 | Secondary output | Secondary motion | 1 Bit | 1.1 switch | CRT |
| 2 | Measured lux level | Lux level | 2 Bytes | 9.4 lux (Lux) | CRT |
| 3 | External lux level | Lux level | 2 Bytes | 9.4 lux (Lux) | CW |
| 4 | External LED command | On/Off | 1 Bit | 1.1 switch | CW |
| 5 | Night Mode | On/Off | 1 Bit | 1.1 switch | CW |
| 6 | Channel 1 On/Off | On/Off | 1 Bit | 1.1 switch | CRT |
| 7 | Channel 1 Dimming steps | Dimming steps | 4 Bit | 3.7 dimming control | CRT |
| 8 | Channel 1 Dimming level | Dimming level | 1 Byte | 5.1 percentage (0..100%) | CRT |
| 9 | Channel 1 Secondary input | Secondary motion | 1 Bit | 1.1 switch | CW |
| 10 | Channel 1 Lux level | Lux value | 2 Bytes | 9.4 lux (Lux) | CW |
| 11 | Channel 1 Switch-off delay time | Switch-off delay time | 2 Bytes | 9.10 time (s) | CW |
| 12 | Channel 1 External On/Off | On/Off | 1 Bit | 1.1 switch | CW |
| 13 | Channel 1 External dimming steps | Dimming steps | 4 Bit | 3.7 dimming control | CW |
| 14 | Channel 1 External dimming level | Dimming level | 1 Byte | 5.1 percentage (0..100%) | CW |
| 15 | Channel 1 Lux level switch | On/Off | 1 Bit | 1.1 switch | CRT |
| 16 | Channel 1 Lock mode | On/Off | 1 Bit | 1.1 switch | CW |
| 17 | Channel 1 Automatic/Manual | On/Off | 1 Bit | 1.1 switch | CW |
| 18 | Channel 1 Alarm | On/Off | 1 Bit | 1.1 switch | CRT |
| 19 | Channel 2 On/Off | On/Off | 1 Bit | 1.1 switch | CRT |
| 20 | Channel 2 Dimming steps | Dimming steps | 4 Bit | 3.7 dimming control | CRT |
| 21 | Channel 2 Dimming level | Dimming level | 1 Byte | 5.1 percentage (0..100%) | CRT |
| 22 | Channel 2 Secondary input | Secondary motion | 1 Bit | 1.1 switch | CW |
| 23 | Channel 2 Lux level | Lux value | 2 Bytes | 9.4 lux (Lux) | CW |
| 24 | Channel 2 Switch-off delay time | Switch-off delay time | 2 Bytes | 9.10 time (s) | CW |
| 25 | Channel 2 External On/Off | On/Off | 1 Bit | 1.1 switch | CW |
| 26 | Channel 2 External dimming steps | Dimming steps | 4 Bit | 3.7 dimming control | CW |
| 27 | Channel 2 External dimming level | Dimming level | 1 Byte | 5.1 percentage (0..100%) | CW |
| 28 | Channel 2 Lux level switch | On/Off | 1 Bit | 1.1 switch | CRT |
| 29 | Channel 2 Lock mode | On/Off | 1 Bit | 1.1 switch | CW |
| 30 | Channel 2 Automatic/Manual | On/Off | 1 Bit | 1.1 switch | CW |
| 31 | Channel 2 Alarm | On/Off | 1 Bit | 1.1 switch | CRT |
| 32 | Channel 3 On/Off | On/Off | 1 Bit | 1.1 switch | CRT |
| 33 | Channel 3 Dimming steps | Dimming steps | 4 Bit | 3.7 dimming control | CRT |
| 34 | Channel 3 Dimming level | Dimming level | 1 Byte | 5.1 percentage (0..100%) | CRT |
| 35 | Channel 3 Secondary input | Secondary motion | 1 Bit | 1.1 switch | CW |
| 36 | Channel 3 Lux level | Lux value | 2 Bytes | 9.4 lux (Lux) | CW |
| 37 | Channel 3 Switch-off delay time | Switch-off delay time | 2 Bytes | 9.10 time (s) | CW |
| 38 | Channel 3 External On/Off | On/Off | 1 Bit | 1.1 switch | CW |
| 39 | Channel 3 External dimming steps | Dimming steps | 4 Bit | 3.7 dimming control | CW |
| 40 | Channel 3 External dimming level | Dimming level | 1 Byte | 5.1 percentage (0..100%) | CW |
| 41 | Channel 3 Lux level switch | On/Off | 1 Bit | 1.1 switch | CRT |
| 42 | Channel 3 Lock mode | On/Off | 1 Bit | 1.1 switch | CW |
| 43 | Channel 3 Automatic/Manual | On/Off | 1 Bit | 1.1 switch | CW |
| 44 | Channel 3 Alarm | On/Off | 1 Bit | 1.1 switch | CRT |
| 45 | HVAC On/Off | On/Off | 1 Bit | 1.1 switch | CRT |
| 46 | HVAC Secondary input | Secondary motion | 1 Bit | 1.1 switch | CW |
| 47 | HVAC Switch-off delay time | Time Value (sec.) | 2 Bytes | 9.10 time (s) | CW |
| 48 | HVAC External On/Off | On/Off | 1 Bit | 1.1 switch | CW |
| 49 | HVAC Lock | On/Off | 1 Bit | 1.1 switch | CW |
| 50 | HVAC switch-on delay time | Time Value (sec.) | 2 Bytes | 9.10 time (s) | CW |
| 51 | General_Test output | On/Off | 1 Bit | 1.1 switch | CRT |
Parameters (65)
| Parameter | Type | Default |
|---|---|---|
| Behaviour after motion has been detected | list | Switch OFF |
| Behaviour when motion is detected | list | Switch ON |
| Constant light control delay | time | 30 |
| Dimming speed | unsignedInt 1…255 | 5 |
| Dimming steps | list | 1.5625% |
| >Switch-off brightness setting | unsignedInt 0…100 | 0 |
| >Switch-on brightness setting | unsignedInt 0…100 | 100 |
| Switch-off time frame | time | 5 |
| Detection time frame | time | 5 |
| Light intensity fluctuation compensation (hysteresis) | unsignedInt 1…100 | 10 |
| Switch-off delay | time | 180 |
| Lock mode | list | Disable |
| >Lock object = 0 | list | Switch ON |
| >Lock object = 1 | list | Switch OFF |
| Activation of the lux value switch function (for day mode) | list | OFF |
| Activation of the lux value switch function (for night mode) | list | OFF |
| Amount of detected motion to disable the alarm | unsignedInt 1…255 | 1 |
| Amount of detected motion to trigger the alarm | unsignedInt 1…255 | 3 |
| Switch-off brightness setting | unsignedInt 0…100 | 0 |
| Lux level adjustment (10 - 2000 lux) | unsignedInt 10…2000 | 500 |
| Lux level adjustment (for night mode) (10 - 2000 lux) | unsignedInt 10…2000 | 300 |
| Repeat last command?every… (00:00:00=Disable) | time | 0 |
| Switch-on brightness setting | unsignedInt 0…100 | 90 |
| Switch back to Automatic | list | After motion |
| Switching/dimming mode selection via an external device | list | Disable |
| Lux level adjustment (10 - 2000 lux) | unsignedInt 10…2000 | 1000 |
| >Switch-off warning | list | Disable |
| Switch-on lux adjustment (0=Always ON, 2000 lux max) | unsignedInt 0…2000 | 500 |
| Switch-on lux adjustment (for night mode) (0=Always ON, 2000 lux max) | unsignedInt 0…2000 | 0 |
| Switch off when below the lux level | list | OFF |
| Switching or dimming mode | list | Switch |
| >Type of dimming | list | Relative |
| >Warning brightness setting | unsignedInt 0…100 | 20 |
| >Warning brightness setting (in night mode) | unsignedInt 0…100 | 20 |
| >Warning time | time | 60 |
| Dimming speed | unsignedInt 1…100 | 5 |
| >Warning brightness setting | unsignedInt 0…100 | 10 |
| >Warning brightness setting (in night mode) | unsignedInt 0…100 | 10 |
| >Lock object=0 | list | Switch ON |
| >Lock object=1 | list | Switch OFF |
| >Warning time | time | 180 |
| Channel 1 | list | Automatic |
| Channel 2 | list | Disable |
| Channel 3 | list | Disable |
| Channel 4 (HVAC only) | list | Disable |
| >Day/night mode | list | Always day |
| >Day/night mode object value | list | Day =1 , Night =0 |
| delayTime1 | unsignedInt 0…65535 | 0 |
| Detector acting on lux value provided by an external device | list | Disable |
| Device function | list | Master |
| ETS_SetupFlag | unsignedInt 0…255 | 255 |
| LED behaviour after motion has been detected | list | OFF |
| LED behaviour when motion is detected | list | ON |
| LED behaviour when in lock mode | list | Blink |
| >Lux value sending mode | list | Lux report when change |
| >Send lux value every | time | 60 |
| Send lux value on KNX bus | list | Disable |
| >Send lux value when value varies by | unsignedInt 1…100 | 10 |
| Sensitivity adjustment | list | Maximum |
| >Switch between day and night mode | list | By next detected motion |
| Switch-off lux adjustment | unsignedInt 0…2000 | 0 |
| LED behaviour when triggered by an external device | list | Off |
| Advanced Mode | list | Disable |
| Switch-on delay | time | 0 |
| Night Mode | list | Disable |
Version history
| Application | App no | Fingerprint | First seen | Size | File |
|---|---|---|---|---|---|
| KNX01-NK 0.2 latest | $0001 | 905E | 2026-11-25 | 165 KB | Download |
| KNX01-NK 0.1 | $0001 | 86BD | 2026-11-25 | 139 KB | Download |
About this file
This is the official ETS product database for the NIKO Presence detector P34MR, KNX, 360°, for flush mounting and flush-mounting box (350-34002), published by the manufacturer in the KNX online catalog. To use it, open ETS, go to Catalogs → Import and choose the downloaded .knxprod file. The device then appears in your catalog and can be added to a project. Older versions are kept so existing projects can be matched to the application program they were commissioned with.
More from NIKO
- Mini presence detector P34MR, KNX, 360°, for flush mounting 350-34001
- Motion detector M34LR, KNX , 360°, for flush-mounting box 350-34003
- Motion detector M34HC, KNX, High ceiling, 360°, for flush-mounting box 350-34004
- Motion detector M34LR, KNX , 360°, for flush-mounting box, black 350-34013
- Motion detector M34HC, KNX, High ceiling, 360°, for flush-mounting box, black 350-34014
- Presence detector P34MR, KNX, 360°, 105mm, for flush-mounting box 350-34902
- 351-25010 SG 360 Hokuspokus/Magic (351-) 25010
- 351-25020N SG 360-4PIR (351-) 25020N
- 351-25032 SG 360-3PIR (351-) 25032
- 351-25038 SG 360-4PIR (351-) 25038
- 25240 SG 300-3PIR 25240N
- Wireless KNX Media Coupler 360-33001