SCN-RTRGx.02 Glass Room Temperature Controller Smart with Colour display SCN-RTRGx.02

MDT technologies GmbH · Order number SCN-RTRGx.02 · Temperature Controller › Glass Room temperature controller

Download .knxprod Glass Temperature Controller Smart 1.2 · 326 KB

Product

ManufacturerMDT technologies GmbH
Product nameSCN-RTRGx.02 Glass Room Temperature Controller Smart with Colour display
Order numberSCN-RTRGx.02
Product textSCN-RTRGx.02 Glass Room Temperature Controller Smart with colour display
HardwareGlas Raumtemperaturregler Smart
MediumTwisted Pair
Bus current (mA)10
Rail mountedNo
RegistrationCertified · 2022-04-19
Languagesde-DE, en-US, es-ES, fr-FR
Catalog entryM-0083_H-272-1_HP-0247-12-B13D_CI-SCN.2DRTRGx.2E02-1
FingerprintB13D
SHA-2563a49a4aec0c9084e045d89689f1f10f7774348bc7cbe7613fa8abe79191e3737
First seen2026-11-25
Markets69 markets

Application program: Glass Temperature Controller Smart 1.2

Application number$0247
Version1.2
Mask versionMV-0705 (7.5)
KNX Data SecureNo
Minimum ETS version5.0
Parameters538
Group objects261
Group objects (261)
NoNameFunctionSizeDPTFlags
0Setpoint settingPreset setpoint2 Bytes9.1 temperature (°C)CW
0Setpoint settingPreset setpoint2 Bytes9.1 temperature (°C)CRT
1ComfortPreset setpoint2 Bytes9.1 temperature (°C)CW
1Combination objectPreset setpoint8 Bytes275.100 Temperature setpoint setting for 4 HVAC ModesCW
1(Basic) Comfort setpointPreset setpoint2 Bytes9.1 temperature (°C)CW
1Combination object (Heating)Preset setpoint8 Bytes275.100 Temperature setpoint setting for 4 HVAC ModesCW
2StandbyPreset setpoint2 Bytes9.1 temperature (°C)CW
3NightPreset setpoint2 Bytes9.1 temperature (°C)CW
4Frost protectionPreset setpoint2 Bytes9.1 temperature (°C)CW
4Heating protectionPreset setpoint2 Bytes9.1 temperature (°C)CW
5Combination object (Cooling)Preset setpoint8 Bytes275.100 Temperature setpoint setting for 4 HVAC ModesCW
6Current setpointReceive setpoint2 Bytes9.1 temperature (°C)CWTU
6Current setpointSend setpoint2 Bytes9.1 temperature (°C)CRT
7Manual setpoint shiftIncrease / decrease (2Byte)2 Bytes9.2 temperature difference (K)CW
7Manual setpoint shiftIncrease / decrease (1Byte)1 Byte6.10 counter pulses (-128..127)CRT
7Manual setpoint shiftIncrease / decrease (2Byte)2 Bytes9.2 temperature difference (K)CRT
8Manual setpoint shiftIncrease / decrease (1=+ / 0=-)1 Bit1.7 stepCW
8Manual setpoint shiftIncrease / decrease (1Byte)1 Byte6.10 counter pulses (-128..127)CW
8Manual setpoint shiftIncrease / decrease (1=+ / 0=-)1 Bit1.7 stepCT
9Status setpoint shiftSend status2 Bytes9.2 temperature difference (K)CRT
9Status setpoint shiftReceive status2 Bytes9.2 temperature difference (K)CWTU
10Control value HeatingSend control value1 Byte5.1 percentage (0..100%)CRT
10Control value HeatingSend control value1 Bit1.1 switchCRT
10Control value Heating/CoolingSend control value1 Byte5.1 percentage (0..100%)CRT
10Control value Heating/CoolingSend control value1 Bit1.1 switchCRT
11Control value CoolingSend control value1 Byte5.1 percentage (0..100%)CRT
11Control value CoolingSend control value1 Bit1.1 switchCRT
12Control value Heating/CoolingReceive status1 Byte5.1 percentage (0..100%)CWTU
12Control value HeatingReceive status1 Byte5.1 percentage (0..100%)CWTU
12Control value HeatingSend status1 Byte5.1 percentage (0..100%)CRT
12Control value Heating/CoolingSend status1 Byte5.1 percentage (0..100%)CRT
13Control value CoolingReceive status1 Byte5.1 percentage (0..100%)CWTU
13Control value CoolingSend status1 Byte5.1 percentage (0..100%)CRT
14Control value additional Heating Send control value1 Bit1.1 switchCT
15Mode selectionSend mode1 Byte20.102 HVAC modeCT
15Mode selectionSelect mode1 Byte20.102 HVAC modeCW
16Comfort modeComfort extension1 Bit1.10 start/stopCW
17Comfort modeSwitch mode1 Bit1.1 switchCW
18Night modeSwitch mode1 Bit1.1 switchCW
19Frost protection modeSwitch mode1 Bit1.1 switchCW
19Heat protection modeSwitch mode1 Bit1.1 switchCW
19Frost/Heat protection modeSwitch mode1 Bit1.1 switchCW
20DPT_HVAC StatusReceive controller status1 ByteCWTU
20DPT_HVAC ModeReceive controller status1 Byte20.102 HVAC modeCWTU
20DPT_HVAC StatusSend controller status1 ByteCRT
20DPT_HVAC ModeSend controller status1 Byte20.102 HVAC modeCRT
21DPT_HVAC StatusSend controller status1 ByteCRT
21DPT_HVAC ModeSend controller status1 Byte20.102 HVAC modeCRT
21RHCC Status Send controller status2 Bytes22.101 RHCC statusCRT
21DPT_RTC combination statusSend controller status2 Bytes22.103 combined status RTCCRT
21DPT_RTSM combination statusSend controller status1 Byte21.107 combined status RTSMCRT
22Frost alarmSend alarm1 Bit1.5 alarmCRT
23Heat alarmSend alarm1 Bit1.5 alarmCRT
24Flow temperature HeatingReceive measured value2 Bytes9.1 temperature (°C)CWT
25Surface temperature CoolingReceive measured value2 Bytes9.1 temperature (°C)CWT
25Dew point alarmReceive alarm1 Bit1.5 alarmCWT
26DiagnosisStatus14 Bytes16.1 Character String (ISO 8859-1)CRT
27Window contact input0=closed / 1=open1 Bit1.19 window/doorCWTU
27Window contact input1=closed / 0=open1 Bit1.1 switchCWTU
28Lock object HeatingLock control value1 Bit1.3 enableCRWTU
29Lock object CoolingLock control value1 Bit1.3 enableCRWTU
30Dummy1 Bit
31Dummy1 Bit
32Switchover Heating/Cooling0=Cooling 1=Heating1 Bit1.100 cooling/heatingCRT
32Switchover Heating/Cooling0=Cooling 1=Heating1 Bit1.100 cooling/heatingCW
33Status Heating / Cooling0=Cooling 1=Heating1 Bit1.100 cooling/heatingCWTU
33Status Heating / Cooling0=Cooling 1=Heating1 Bit1.100 cooling/heatingCRT
34Heating requestSend request1 Bit1.1 switchCRT
35Cooling requestSend request1 Bit1.1 switchCRT
36Outdoor temperature / Reference valueReceive measured value2 Bytes9.1 temperature (°C)CW
37Reference controlReference value in percent1 Byte5.1 percentage (0..100%)CW
37Reference controlReference value in Lux2 Bytes9.4 lux (Lux)CW
38Reference controlStatus1 Bit1.11 stateCRT
39Reference controlLock1 Bit1.3 enableCW
40Dummy1 Bit
41Dummy1 Bit
42Ventilation controlLock1 Bit1.3 enableCW
43Ventilation controlOutput Level 11 Bit1.1 switchCRT
43Ventilation controlBit 01 Bit1.2 booleanCRT
44Ventilation controlOutput Level 21 Bit1.1 switchCRT
44Ventilation controlBit 11 Bit1.2 booleanCRT
44Ventilation controlOutput Level 1+21 Bit1.1 switchCRT
45Ventilation controlOutput Level 31 Bit1.1 switchCRT
45Ventilation controlBit 21 Bit1.2 booleanCRT
45Ventilation controlOutput Level 1+2+31 Bit1.1 switchCRT
46Ventilation controlOutput Level 41 Bit1.1 switchCRT
46Ventilation controlOutput Level 1+2+3+41 Bit1.1 switchCRT
47Ventilation control1Byte status ventilation level1 Byte5.10 counter pulses (0..255)CRT
47Ventilation control1Byte status ventilation level (Extension unit)1 Byte5.10 counter pulses (0..255)CWTU
48Ventilation controlControl value output1 Byte5.1 percentage (0..100%)CRT
49Ventilation controlObject Priority1 Bit1.1 switchCW
50Ventilation controlSwitch Automatic1 Bit1.1 switchCRWT
50Ventilation controlSwitch Automatic (Extension unit)1 Bit1.1 switchCT
51Ventilation controlChange ventilation levels manually (+/-)1 Bit1.7 stepCWT
52Ventilation controlManual ventilation control1 Byte5.100 fan stage (0..255)CWT
52Ventilation controlManual ventilation control (Extension unit)1 Byte5.100 fan stage (0..255)CT
53Ventilation controlStatus ventilation active1 Bit1.11 stateCRT
54Ventilation controlStatus Automatic1 Bit1.11 stateCRT
54Ventilation controlStatus Automatic (Extension unit)1 Bit1.11 stateCWTU
55Ventilation controlRelative air humidity input2 Bytes9.7 humidity (%)CWTU
56Dummy1 Bit
57Dummy1 Bit
58TemperatureSend measured value2 Bytes9.1 temperature (°C)CRT
59TemperatureExternal sensor input2 Bytes9.1 temperature (°C)CWTU
60TemperatureMaximum value exceeded1 Bit1.5 alarmCRT
61TemperatureMinimum value fallen below1 Bit1.5 alarmCRT
62Buttons 1/2: {{0}}Switch On/Off1 Bit1.1 switchCT
62Buttons 1/2: {{0}}Dimming On/Off1 Bit1.1 switchCT
62Buttons 1/2: {{0}}Blinds Up/Down1 Bit1.8 up/downCT
62Button 1: {{0}}Switch1 Bit1.1 switchCT
62Button 1: {{0}}Toggle1 Bit1.1 switchCT
62Button 1 short: {{0}}Switch1 Bit1.1 switchCT
62Button 1 short: {{0}}Toggle1 Bit1.1 switchCT
62Button 1 short: {{0}}Send value1 Byte5.5 ratio (0..255)CT
62Button 1 short: {{0}}Send percent value1 Byte5.1 percentage (0..100%)CT
62Button 1 short: {{0}}Send scene1 Byte17.1 scene numberCT
62Button 1 long: {{0}}Dimming On/Off1 Bit1.1 switchCT
62Button 1: {{0}}Blinds Up/Down1 Bit1.8 up/downCT
62Button 1: {{0}}Send status1 Bit1.11 stateCT
62Button 1: {{0}}Send status1 Byte5.5 ratio (0..255)CT
62Button 1: {{0}}Send percent value1 Byte5.1 percentage (0..100%)CT
62Button 1: {{0}}Send scene1 Byte17.1 scene numberCT
63Buttons 1/2: {{0}}Dimming relative4 Bit3.7 dimming controlCT
63Buttons 1/2: {{0}}Slat adjustment / Stop1 Bit1.7 stepCT
63Button 1: {{0}}Status for toggle1 Bit1.1 switchCWTU
63Button 1 short: {{0}}Status for toggle1 Bit1.1 switchCWTU
63Button 1: {{0}}Dimming relative4 Bit3.7 dimming controlCT
63Button 1: {{0}}Slat adjustment / Stop1 Bit1.7 stepCT
63Button 1 short: {{0}}Status for display1 Bit1.1 switchCWTU
63Button 1 short: {{0}}Status for display1 Byte5.5 ratio (0..255)CWTU
63Button 1 short: {{0}}Status for display1 Byte5.1 percentage (0..100%)CWTU
64Button 1 long: {{0}}Switch1 Bit1.1 switchCT
64Button 1 long: {{0}}Toggle1 Bit1.1 switchCT
64Button 1 long: {{0}}Send value1 Byte5.5 ratio (0..255)CT
64Button 1 long: {{0}}Send percent value1 Byte5.1 percentage (0..100%)CT
64Button 1 long: {{0}}Send scene1 Byte17.1 scene numberCT
64Button 1: {{0}}Status for toggle1 Bit1.1 switchCWTU
64Button 1: {{0}}Status for change of direction1 Bit1.8 up/downCWTU
65Buttons 1/2: {{0}}Status for display1 Bit1.11 stateCWTU
65Buttons 1/2: {{0}}Status for display1 Byte5.1 percentage (0..100%)CWTU
65Button 1 long: {{0}}Status for toggle1 Bit1.11 stateCWTU
65Button 1: {{0}}Status for display1 Bit1.11 stateCWTU
65Button 1: {{0}}Status for display1 Byte5.1 percentage (0..100%)CWTU
65Button 1: {{0}}Status for display1 Byte5.5 ratio (0..255)CWTU
66Buttons 1/2: {{0}}Lock object1 Bit1.3 enableCW
66Button 1: Operating mode switchingLock object1 Bit1.3 enableCW
66Button 1: Ventilation controlLock object1 Bit1.3 enableCW
66Button 1: Control value = 0%Lock object1 Bit1.3 enableCW
66Button 1: Heating / CoolingLock object1 Bit1.3 enableCW
66Button 1: {{0}}Lock object1 Bit1.3 enableCW
67Button 2: {{0}}Switch1 Bit1.1 switchCRT
67Button 2: {{0}}Toggle1 Bit1.1 switchCRT
67Button 2 short: {{0}}Switch1 Bit1.1 switchCRT
67Button 2 short: {{0}}Toggle1 Bit1.1 switchCRT
67Button 2 short: {{0}}Send value1 Byte5.5 ratio (0..255)CRT
67Button 2 short: {{0}}Send percent value1 Byte5.1 percentage (0..100%)CRT
67Button 2 short: {{0}}Send scene1 Byte17.1 scene numberCRT
67Button 2: {{0}}Dimming On/Off1 Bit1.1 switchCRT
67Button 2: {{0}}Blinds Up/Down1 Bit1.8 up/downCRT
67Button 2: {{0}}Send status1 Bit1.11 stateCRT
67Button 2: {{0}}Send value1 Byte5.5 ratio (0..255)CRT
67Button 2: {{0}}Send percent value1 Byte5.1 percentage (0..100%)CRT
67Button 2: {{0}}Send scene1 Byte17.1 scene numberCRT
68Button 2: {{0}}Status for toggle1 Bit1.1 switchCWTU
68Button 2 short: {{0}}Status for toggle1 Bit1.1 switchCWTU
68Button 2: {{0}}Dimming relative4 Bit3.7 dimming controlCRT
68Button 2: {{0}}Slat adjustment / Stop1 Bit1.7 stepCRT
68Button 2: {{0}}Status for display1 Bit1.1 switchCWTU
68Button 2: {{0}}Status for display1 Byte5.5 ratio (0..255)CWTU
68Button 2: {{0}}Status for display1 Byte5.1 percentage (0..100%)CWTU
69Button 2 long: {{0}}Switch1 Bit1.1 switchCRT
69Button 2 long: {{0}}Toggle1 Bit1.1 switchCRT
69Button 2 long: {{0}}Send value1 Byte5.5 ratio (0..255)CRT
69Button 2 long: {{0}}Send percent value1 Byte5.1 percentage (0..100%)CRT
69Button 2 long: {{0}}Send scene1 Byte17.1 scene numberCRT
69Button 2: {{0}}Status for toggle1 Bit1.1 switchCWTU
69Button 2: {{0}}Status for change of direction1 Bit1.8 up/downCWTU
70Button 2 long: {{0}}Status for toggle1 Bit1.11 stateCWTU
70Button 2: {{0}}Status for display1 Bit1.11 stateCWTU
70Button 2: {{0}}Status for display1 Byte5.1 percentage (0..100%)CWTU
70Button 2: {{0}}Status for display1 Byte5.5 ratio (0..255)CWTU
71Button 2: Operating mode switchingLock object1 Bit1.3 enableCW
71Button 2: Ventilation controlLock object1 Bit1.3 enableCW
71Button 2: Control value = 0%Lock object1 Bit1.3 enableCW
71Button 2: Heating / CoolingLock object1 Bit1.3 enableCW
71Button 2: {{0}}Lock object1 Bit1.3 enableCW
72Buttons 3/4: Setpoint shiftLock object1 Bit1.3 enableCW
73LED 1Switch1 Bit1.1 switchCWTU
73LED 1Percent value1 Byte5.1 percentage (0..100%)CWTU
73LED 1Decimal value1 Byte5.5 ratio (0..255)CWTU
74LED 2Switch1 Bit1.1 switchCWTU
74LED 2Percent value1 Byte5.1 percentage (0..100%)CWTU
74LED 2Decimal value1 Byte5.5 ratio (0..255)CWTU
75LED 3Switch1 Bit1.1 switchCWTU
75LED 3Percent value1 Byte5.1 percentage (0..100%)CWTU
75LED 3Decimal value1 Byte5.5 ratio (0..255)CWTU
76LED 4Switch1 Bit1.1 switchCWTU
76LED 4Percent value1 Byte5.1 percentage (0..100%)CWTU
76LED 4Decimal value1 Byte5.5 ratio (0..255)CWTU
77LED 1 PrioritySwitch1 Bit1.1 switchCWTU
78LED 2 PrioritySwitch1 Bit1.1 switchCWTU
79LED 3 PrioritySwitch1 Bit1.1 switchCWTU
80LED 4 PrioritySwitch1 Bit1.1 switchCWTU
81LEDLock object1 Bit1.3 enableCWTU
82Status text 1Input14 Bytes16.0 Character String (ASCII)CWTU
83Status text 2Input14 Bytes16.0 Character String (ASCII)CWTU
84Status value 1Switch On/Off1 Bit1.1 switchCWTU
84Status value 1Percent value 0…100%1 Byte5.1 percentage (0..100%)CWTU
84Status value 1Value 0…2551 Byte5.5 ratio (0..255)CWTU
84Status value 1Value in mA2 Bytes7.12 current (mA)CWTU
84Status value 1Value in Lux2 Bytes7.13 brightness (lux)CWTU
84Status value 1Value in °C2 Bytes9.1 temperature (°C)CWTU
84Status value 1Value in Lux2 Bytes9.4 lux (Lux)CWTU
84Status value 1Value in m/s2 Bytes9.5 speed (m/s)CWTU
84Status value 1Value in %2 Bytes9.7 humidity (%)CWTU
84Status value 1Value in ppm2 Bytes9.8 parts/million (ppm)CWTU
84Status value 1Value in mA2 Bytes9.21 current (mA)CWTU
85Status value 2Switch On/Off1 Bit1.1 switchCWTU
85Status value 2Percent value 0…100%1 Byte5.1 percentage (0..100%)CWTU
85Status value 2Value 0…2551 Byte5.5 ratio (0..255)CWTU
85Status value 2Value in mA2 Bytes7.12 current (mA)CWTU
85Status value 2Value in Lux2 Bytes7.13 brightness (lux)CWTU
85Status value 2Value in °C2 Bytes9.1 temperature (°C)CWTU
85Status value 2Value in Lux2 Bytes9.4 lux (Lux)CWTU
85Status value 2Value in m/s2 Bytes9.5 speed (m/s)CWTU
85Status value 2Value in %2 Bytes9.7 humidity (%)CWTU
85Status value 2Value in ppm2 Bytes9.8 parts/million (ppm)CWTU
85Status value 2Value in mA2 Bytes9.21 current (mA)CWTU
86Status value 3Switch On/Off1 Bit1.1 switchCWTU
86Status value 3Percent value 0…100%1 Byte5.1 percentage (0..100%)CWTU
86Status value 3Value 0…2551 Byte5.5 ratio (0..255)CWTU
86Status value 3Value in mA2 Bytes7.12 current (mA)CWTU
86Status value 3Value in Lux2 Bytes7.13 brightness (lux)CWTU
86Status value 3Value in °C2 Bytes9.1 temperature (°C)CWTU
86Status value 3Value in Lux2 Bytes9.4 lux (Lux)CWTU
86Status value 3Value in m/s2 Bytes9.5 speed (m/s)CWTU
86Status value 3Value in %2 Bytes9.7 humidity (%)CWTU
86Status value 3Value in ppm2 Bytes9.8 parts/million (ppm)CWTU
86Status value 3Value in mA2 Bytes9.21 current (mA)CWTU
87OperatingOutput1 Bit1.11 stateCRT
88Day / NightDay = 1 / Night = 01 Bit1.1 switchCWTU
88Day / NightNight = 1 / Day = 01 Bit1.24 day/nightCWTU
89PresenceInput1 Bit1.1 switchCWTU
90Button operationOutput1 Bit1.11 stateCRT
91DisplayBrightness1 Byte5.1 percentage (0..100%)CRT
91DisplayBrightness1 Byte5.1 percentage (0..100%)CW
92LEDFlashing status1 Bit1.11 stateCT
92LEDFlashing status1 Bit1.11 stateCW
93TimeReceive current value3 Bytes10.1 time of dayCWTU
94DateReceive current value3 Bytes11.1 dateCWTU
95Time / DateReceive current value8 Bytes19.1 date timeCWTU
96Dummy1 Bit
97Dummy1 Bit
98Dummy1 Bit
99Dummy1 Bit
100Dummy1 Bit
101Dummy1 Bit
102Dummy1 Bit
103Dummy1 Bit
104Dummy1 Bit
105Dummy1 Bit
Parameters (325)
ParameterTypeDefault
Startup timeunsignedInt 2…2402
Send "Operation" cyclicallylistnot active
Value for Day/NightlistDay = 1 / Night = 0
Status for togglelistrequest
Object Day/Nightlistrequest
Objects Time/Datelistrequest
LanguagelistGerman
Reaction time on keypresslistfast
Time for long keypresslist0,4 s
Background colourlistDay = white; Night = black
Font size: function namelistbig
Font size: labelling of buttonslistsmall
Behaviour if the text is too longlisttext size is reduced
Behaviour at presencelistdisplay switched on
Adapt display brightness to ambiencelistactive
Brightness at Daylist10%
Brightness at Nightlist3%
Brightnesslistbrightness level 8
Minimum brightness for Daylist10%
Minimum brightness for Nightlist3%
Overnight shutdown in Standbylistthreshold 2 (dark)
Red partlist0%
Green partlist0%
Blue partlist0%
User-defined colourslistnot active
Colour of orientation-LEDs in Standbylistwhite
Time until StandbyunsignedInt 1…6020
Standby displaylistindividually alternating
Change Standby display afterunsignedInt 1…605
Standby display at DaylistStandby in the upper screen
Status element 1listTime (24 h)
Status element 2listnot active
Status element 3listnot active
Status element 4listnot active
Standby display at Nightlistbehaviour like Day
Line 1listone status element
Status elementlistTime (24 h)
Status element leftlistTime (24 h)
Status element rightliststatus value 1
Status element topliststatus text 1 (via object 82)
Status element bottomliststatus text 2 (via object 83)
Line 2listnot active
Action on button activation when display is OFFlistStandby is exited
Action on button activation during Standbylistfunction is not executed
Status value 1listnot active
Text for value = 0text
Text for value = 1text
Labelling "Unit"text
Labelling "Value"text
Status value 2listnot active
Status value 3listnot active
LED behaviour during StandbylistLEDs OFF
Temperature measurementlistactive
Send measured value on change of...list0,2 °C
Send measured value cyclicallylist20 min
Sensor internal/externallistinternal 100%
Calibration value for internal sensorsignedInt -50…500
Upper message valuelistnot active
Lower message valuelistnot active
Setpoint Comfort (Basic)float 7…3521
Setpoint Standbyfloat 7…3519
Setpoint Nightfloat 7…3518
Setpoint Frost protectionfloat 3…127
Maximum setpoint shiftfloat 0…103
Setpoint Comfort (Basic)float 7…3523
Setpoint Standbyfloat 7…3524
Setpoint Nightfloat 7…3525
Setpoint Heating protectionfloat 24…4035
Lower limitfloat -10…10-3
Upper limitfloat -10…103
Button/Object descriptiontext
Basic functionlistswitch
Button assignment 1/2listOFF / ON
Button assignment 1/2listdarker / brighter
ValueunsignedInt 0…2550
Button assignment 1/2listUP / DOWN
Operating functionlistlong=move / short=stop/slats open/close
Displaylistfixed text
Symbol for 0%list
Symbol colour for 0%listforeground colour (black/white)
Symbol for 0% - 90%list
Symbol colour for 0% - 90%listsun orange
Symbol for > 90%list
Symbol colour for > 90%listsun orange
Symbol for 10% - 90%list
Symbol colour for 10% - 90%listsun orange
Button labelling leftlisttext entry
Button labelling rightlisttext entry
Lock objectlistnot active
Mode selectionlistComfort / Standby / Night /Frost (Heat) protection
No switchover when other operating modeunsignedInt 0…10
Ventilation controllistnot active
Control as extension unitlistnot active
Total number of levelslist4
Enable Automaticlistnot active
Subfunctionlistswitch when button is pressed
Value for pressed buttonlistON
Action for short keypress - Object 1listON
Datapoint typelist1Byte DPT 5.005 Decimal factor (0...255)
Valuelist0%
Scene numberlist1
Action for long keypress - Object 2listnot active
Valuelist100%
Value for released buttonlistOFF
Delay for released buttonlistnot active
Delay timeunsignedInt 1…30001
HVAC Status objectlistHVAC Mode (DPT 20.102)
Symbol for "Eco/Night"listEco symbol
Symbol colour for mode "Eco"listsun orange
Symbol colour for "Frost/Heat protection"listsun orange
Symbol for level 0list
Symbol for level > 0list
Symbol for Automaticlist
Symbol for Unlocked / Activelist
Symbol colour for Unlocked / Activelistforeground colour (black/white)
Symbol for Locked / Inactive (0%)list
Symbol for "Cooling"list
Symbol for "Heating"list
Cyclical sendinglistnot active
Send cyclically everyunsignedInt 1…30001
Symbol colour for "Comfort"listforeground colour (black/white)
Symbol colour for "Standby"listsun orange
Symbol colour for "Eco"listsun orange
Symbol colour for "Night"listsun orange
Symbol colour for Locked / Inactive (0%)listsun orange
Symbol colour for "Cooling"listforeground colour (black/white)
Symbol colour for "Heating"listsun orange
Symbol for "OFF"list
Symbol colour for "OFF"listforeground colour (black/white)
Symbol for "ON"list
Symbol colour for "ON"listsun orange
Symbol for 0list
Symbol colour for 0listforeground colour (black/white)
Symbol for 1 - 230list
Symbol colour for 1 - 230listsun orange
Symbol for > 230list
Symbol colour for > 230listsun orange
Symbol colour for 0%listforeground colour (black/white)
Symbol colour for Scenelistforeground colour (black/white)
Use device aslistController
Operating modelistHeating
Function button 1listmode selection (internal connection)
Function button 2listswitchover Heating/Cooling (internal connection)
Systemlist2 pipe / 1 circuit (Heating or Cooling)
PrioritylistFrost(Heat) protection/Comfort/Night/Standby
Setpoints for Standby/Nightlistdepending on setpoint Comfort (Basic)
Standby reductionlist2,0 K
Night reductionlist3,0 K
Separate objects for setpoints Comfort/Standby/Night/Frost protectionlistnot active
Setpoint shift via 1Bit/1Byte objectlist1Bit
Step widthlist0,5 K
Status setpoint shiftlistnot active
Setpoint shift applies tolistComfort
Action when shifting in Night/Standbylistno action
Delete setpoint shift after change of operating modelistnot active
Delete setpoint shift after new absolute setpointlistactive
Reset setpoints to parameterization after operating mode changelistactive
Reset basic setpoint to configured value after change of operation modelistactive
Delete setpoint shift after new basic setpointlistactive
Send setpoint changeslistactive
Send current setpoint cyclicallylistnot active
Comfort extention with timelistnot active
Comfort extention timelistnot active
Operating mode after resetlistComfort with configured setpoint
Operating mode after reprogramminglistComfort
Additional HVAC Status objectlistnot active
Send HVAC Status object cyclicallylistnot active
Lock object for control value Heatinglistnot active
Object for Heating requestlistnot active
Flow temperaturelistnot active
Limit flow temperature tounsignedInt 10…6040
Standby increaselist2,0 K
Night increaselist3,0 K
Separate objects for setpoints of Comfort/Standby/Night Heating protectionlistnot active
Lock object for control value Coolinglistnot active
Object for Cooling requestlistnot active
Limit temperature of cooling mediumlistnot active
Minimum temperature cooling mediumunsignedInt 0…6010
Switchover Heating/Coolinglistautomatically
Dead zone between Heating and Coolinglist2,0 K
Dead zone between Heating and Coolinglist0 K
Separate objects for setpoints Comfort/Standby/Night/Frost protection/Heating protectionlistnot active
Operating mode after reprogramminglistComfort (Cooling)
Alarmslistnot active
Frost alarm if value lessunsignedInt 3…107
Heat alarm if value greaterunsignedInt 25…4035
Window contactlistnot active
State of windowlist0=closed / 1=open (standard DPT)
Delay timeunsignedInt 0…2405
Action when opening the windowlistforce Frost/Heat protection
Action when closing the windowlistHVAC Modus before locking
Release timelist12 h
Control valuelistPI control continuous
Direction of controllerlistnormal
Maximum value of control valuelist100%
Heating systemlistUnderfloor Heating (4K / 150min)
Proportional rangelist4 K
Reset timelist150 min
PWM cyclelist10 min
Switching hysteresislist2,0 K
Send control value cyclicallylist5 min
Additional levellistnot active
Direction of action with rising temperaturelistnormal
Control valuelist2-step control (switching)
Distancelist2,0 K
Cooling systemlistCooling ceiling (4K / 150min)
Send outputs cyclically everylistnot active
Pause between individual levels [x100ms]unsignedInt 0…2550
Type of thresholdslistcontrol value
Minimum level for DaylistLevel 0
Maximum level for DaylistLevel 2
Minimum level for NightlistLevel 0
Maximum level for NightlistLevel 2
Maximum level for DaylistLevel 3
Maximum level for NightlistLevel 3
Maximum level for DaylistLevel 4
Maximum level for NightlistLevel 4
Threshold level 1list10%
Threshold level 2list30%
Threshold level 3list50%
Threshold level 4list70%
Output value (level 1) for Daylist10%
Output value (level 1) for Nightlist10%
Output value (level 2) for Daylist30%
Output value (level 2) for Nightlist30%
Output value (level 3) for Daylist50%
Output value (level 3) for Nightlist50%
Output value (level 4) for Daylist70%
Output value (level 4) for Nightlist70%
Hysteresislist5%
Threshold level 1list2,0 K
Threshold level 2list4,0 K
Threshold level 3list6,0 K
Threshold level 4list8,0 K
Hysteresislist0,5 K
Behaviour at locklistnot active
Behaviour when unlockinglistnot active
Level when unlockinglistLevel 0
Level at locklistLevel 0
Release time (manual => automatic)listnot active
Behaviour on resetlistautomatic mode
Sticking protectionlistnot active
Prioritylistnot active
Switch priority withlistLevel 0
Function buttons 1/2listnot active
Function buttons 3/4 (-/+)listtemperature shift
Step width of setpoint shiftfloat 0.1…10.5
Lower limitfloat 0…4519
Upper limitfloat 0…4523
Temperature shiftlist1Bit
Switchover considers status objectlistactive
Repeated sending with pressed buttonlist1 s
Repetition timelist1 s
Texttext
Symbol colour for level 0listforeground colour (black/white)
Symbol colour for level > 0listsun orange
Symbol colour for Automaticlistsun orange
Symbol for Scenelist
SymbollistHeating/Cooling
Display control valuelistnot active
Symbol colour for Heatinglistforeground colour (black/white)
Symbol colour for control value > 0% (Heating)listforeground colour (black/white)
Symbol colour for Coolinglistforeground colour (black/white)
Symbol colour for control value = 0% (Heating)listforeground colour (black/white)
Symbol colour for control value = 0% (Cooling)listforeground colour (black/white)
Symbol for Eco/Night modelistEco symbol
Symbol colour for Comfortlistforeground colour (black/white)
Symbol colour for Standbylistforeground colour (black/white)
Symbol colour for Eco/Nightlistforeground colour (black/white)
Symbol colour for Frost/Heat protectionlistforeground colour (black/white)
Labelling (Controller function)text
Symbol colour for control value > 0% (Cooling)listforeground colour (black/white)
LEDlistactive
LED reacts to:listbutton activation
Request external object cyclicallylistnot active
Datapoint typelist1Bit DPT 1.001 Switch
ON if greater thanlist50%
Selection of object numberunsignedInt 0…1000
Colour for Day (value ON)listwhite
Colour for Day (value OFF)listblack
Behaviour for Day (value ON)listpermanent
Colour for Night (value ON)listwhite
Colour for Night (value OFF)listblack
Behaviour for Night (value ON)listpermanent
Object for prioritylistnot active
Colour for Daylistwhite
Colour for Nightlistwhite
Lock object for LEDslistnot active
LED colour on button activation, only with setting "Object and button activation"listblack
Function nametext
Display status value as text under symbollistin percent (%)
Display status value as text under symbollistwithout unit
Status displaylistsetpoint temperature (big)
Synchronisation object for flashing LEDslistnot active
Send brightness via object to the buslistnot active
Labelling "Internal temperature"text
Labelling "Time"text
Behaviour on resetlistLevel 1
Behaviour of LEDs on bus power returnlistdo not request LED objects
Text for "Comfort"text
Text for "Standby"text
Text for "Eco/Night"text
Text for "Frost alarm"text
Text for "Unlocked / Active"text
Text for "Locked / Inactive"text
Text for "Cooling"text
Text for "Heating"text
Text for "OFF"text
Text for "ON"text
Text for "On"text
Reference controllistnot active
Reference variable minimumunsignedInt 10…6028
Reference variable maximumunsignedInt 10…6038
Setpoint change at maximum reference variablefloat -5…-0.5-2
Reference variable minimumlist0%
Reference variable maximumlist100%
Threshold outdoor temperaturelistnot active
Reference control released fromunsignedInt 5…3515
Reference variable minimumlist30000 Lux
Reference variable maximumlist80000 Lux
Current setpoint considers "Reference control"listnot active
Setpoint change at maximum reference variablefloat 1…1010
Position of buttonspicture
Cleaning functionlistactive
Position of LEDspicture

Version history

ApplicationApp noFingerprintFirst seenSizeFile
Glass Temperature Controller Smart 1.2 latest$0247B13D2026-11-25326 KBDownload

About this file

This is the official ETS product database for the MDT technologies GmbH SCN-RTRGx.02 Glass Room Temperature Controller Smart with Colour display (SCN-RTRGx.02), published by the manufacturer in the KNX online catalog. To use it, open ETS, go to Catalogs → Import and choose the downloaded .knxprod file. The device then appears in your catalog and can be added to a project. Older versions are kept so existing projects can be matched to the application program they were commissioned with.